Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:40

Tabular Output Report in Format: HTML

Building: US+MF+CZ3B+gasfurnace+heatedbsmt+IECC_2015

Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2024-06-27 17:40:24


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1030423.49 26.42 35.04
Net Site Energy 1030423.49 26.42 35.04
Total Source Energy 2285510.71 58.60 77.73
Net Source Energy 2285510.71 58.60 77.73


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 65211.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 103912.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 54809.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 334377.15 165141.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 47281.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 239084.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 560984.95 469438.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 65211.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 103912.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 54809.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 153392.63 18429.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 120067.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 24355.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 22926.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 0.00 239084.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 0.00 65211.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 103912.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 54809.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 334377.15 165141.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 47281.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 239084.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 5.14 10.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.62
Other 11.37 5.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 19.08 15.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.62


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 3.88 7.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01
Other 8.57 4.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 14.38 12.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 560984.949 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 560984.949 100.00
     
Total On-Site and Utility Electric Sources 560984.949 100.00
Total Electricity End Uses 560984.949 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 264.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:40
RunPeriod ANNUAL
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [ft] 3891.27
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58539.52 1.00 185.02 0.00 0.00 0.00 0.4409   1.5385
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 4.4722
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 4.4722
Total 39005.22     325627.71   16363.00 0.00 2126.74 2126.74 0.4574 1083.48 2.7852
Conditioned Total 29404.35     242278.90   15481.63 0.00 2126.74 2126.74 0.6067 816.79 3.6946
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
HEATEDBSMT 7794.39 Yes Yes 1.00 HEATEDBSMT GENERAL HEATEDBSMT 0.4409 0.00 1.5385  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.6665 600.28 4.4722  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.6665 600.28 4.4722  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.6665 600.28 4.4722  
Total 39005.22             0.4574 1083.48 2.7852  
Conditioned Total 29404.35             0.6067 816.79 3.6946  
Unconditioned Total 9600.87             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 29404.35 9600.87 0.00 0.4574 1083.48 2.7852
Total 39005.22 29404.35 9600.87 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 14-JUN-18:20 01-JAN-08:19 - - - - - - - - - - 01-JAN-09:00
Heating 0.00 45.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 49.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 16.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 52.53 22.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 11.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 171.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 134.39 238.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 45.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 49.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 16.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.52 12.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 8.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 24.28 1.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 19.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 2.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 8.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 0.00 171.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 70689.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 329091.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 173581.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1058972.43 179013.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 149741.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 259167.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1776639.33 508871.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 2.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 36.01 6.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 8.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 60.42 17.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 1.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 8.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 27.15 4.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 6.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 45.55 13.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 381.27
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 474.46
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 318.48
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 367.55
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 469.71
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 317.98
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 365.88
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 496.50
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 332.19
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 389.03
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 491.98
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 330.88
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 386.67
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 463.82
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 459.54
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 567.21
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 407.14
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 402.79
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 570.30
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.46 474.46 474.46 474.46 474.46 474.46 1.00 1.00 474.46
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.48 318.48 318.48 318.48 318.48 318.48 1.00 1.00 318.48
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.55 367.55 367.55 367.55 367.55 367.55 1.00 1.00 367.55
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.71 469.71 469.71 469.71 469.71 469.71 1.00 1.00 469.71
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.98 317.98 317.98 317.98 317.98 317.98 1.00 1.00 317.98
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.88 365.88 365.88 365.88 365.88 365.88 1.00 1.00 365.88
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.50 496.50 496.50 496.50 496.50 496.50 1.00 1.00 496.50
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.19 332.19 332.19 332.19 332.19 332.19 1.00 1.00 332.19
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.03 389.03 389.03 389.03 389.03 389.03 1.00 1.00 389.03
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.98 491.98 491.98 491.98 491.98 491.98 1.00 1.00 491.98
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.88 330.88 330.88 330.88 330.88 330.88 1.00 1.00 330.88
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.67 386.67 386.67 386.67 386.67 386.67 1.00 1.00 386.67
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.21 567.21 567.21 567.21 567.21 567.21 1.00 1.00 567.21
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.79 402.79 402.79 402.79 402.79 402.79 1.00 1.00 402.79
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.54 459.54 459.54 459.54 459.54 459.54 1.00 1.00 459.54
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.30 570.30 570.30 570.30 570.30 570.30 1.00 1.00 570.30
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.14 407.14 407.14 407.14 407.14 407.14 1.00 1.00 407.14
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.82 463.82 463.82 463.82 463.82 463.82 1.00 1.00 463.82
CENTRAL SYSTEM_UNITHEATEDBSMT 381.27 381.27 381.27 381.27 381.27 381.27 1.00 1.00 381.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 474.46 1.34 0.757683
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 318.48 0.905841 0.754162
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 367.55 1.05 0.753578
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 469.71 1.32 0.758580
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 317.98 0.904596 0.754112
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 365.88 1.04 0.755366
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 496.50 1.39 0.760198
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 332.19 0.932812 0.758864
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 389.03 1.10 0.755403
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 491.98 1.37 0.762101
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 330.88 0.929524 0.758740
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 386.67 1.09 0.757762
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 567.21 1.56 0.766814
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 402.79 1.11 0.767342
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 459.54 1.27 0.764324
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 570.30 1.57 0.766948
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 407.14 1.12 0.764964
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 463.82 1.28 0.764582
DX COOLING COIL_UNITHEATEDBSMT 381.27 0.978512 0.794249
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 474.46 474.46 474.46 9452.69 1.34 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 318.48 318.48 318.48 7889.46 0.905841 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 367.55 367.55 367.55 9452.61 1.05 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 469.71 469.71 469.71 9456.06 1.32 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 317.98 317.98 317.98 7890.07 0.904596 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 365.88 365.88 365.88 9450.43 1.04 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 496.50 496.50 496.50 8876.54 1.39 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 332.19 332.19 332.19 7180.93 0.932812 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 389.03 389.03 389.03 8878.67 1.10 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 491.98 491.98 491.98 8879.65 1.37 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 330.88 330.88 330.88 7181.24 0.929524 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 386.67 386.67 386.67 8876.13 1.09 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 567.21 567.21 567.21 10954.62 1.56 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 402.79 402.79 402.79 9232.27 1.11 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 459.54 459.54 459.54 10957.53 1.27 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 570.30 570.30 570.30 10957.06 1.57 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 407.14 407.14 407.14 9232.63 1.12 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 463.82 463.82 463.82 10955.80 1.28 1.00
ACANDF_UNITHEATEDBSMT 381.27 381.27 381.27 7656.91 0.978512 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 474.46
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 318.48
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 367.55
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 469.71
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 317.98
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 365.88
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 496.50
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 332.19
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 389.03
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 491.98
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 330.88
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 386.67
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 567.21
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 402.79
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 459.54
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 570.30
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 407.14
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 463.82
SUPPLY FAN_UNITHEATEDBSMT 381.27
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 10870.59
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 9072.88
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 10870.50
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 10874.46
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 9073.59
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 10867.99
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 10208.02
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 8258.07
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 10210.47
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 10211.60
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 8258.42
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 10207.55
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 12597.82
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 10617.11
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 12601.16
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 12600.62
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 10617.52
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 12599.17
MAIN FUEL HEATING COIL_UNITHEATEDBSMT 9571.14
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 54.59 48.72 47.12 48.51 56.43 65.30 73.65 79.68 81.45 78.62 71.78 63.16


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 3891.27 13. 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 64.29 37.98 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ3B+gasfurnace+heatedbsmt+IECC_2015 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 6.1981 Rough 1.2550 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 1.5339 Rough 0.2917 5.796E-002 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5031 Smooth 0.1189 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3300 VerySmooth 0.1230 0.114 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFBASEMENTAVGWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTWALLSURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFBASEMENTAVGFLOOR N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTFLOORTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFBASEMENTUPPERWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTUPPERWALLTEMP NO 24.000 0.000 N/A N/A
4 SURFPROPOTHSDCOEFBASEMENTLOWERWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTLOWERWALLTEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 HEATEDBSMT 0.0 0.00 0.00 0.00 59.94 32.51 -3.4 1 1 1 0.00 119.89 0.00 65.10 -7.0 0.49 7.51 58539.45 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 HEATEDBSMT 7794.37 0.0 N/A 0.000 0.441 1.538 0.000 0.000 0.000 0.000 1.979 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.110 2.363 0.000 0.000 0.000 5.139 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
37 BASEMENT HARDWIRED LIGHTING INTERIORLIGHTINGHE HEATEDBSMT 7794.37 0.0 2496.919 0.320 N/A 0.000 0.600 0.200 0.200 0.000 General 171.665 2496.919
38 BASEMENT PLUG-IN LIGHTING INTERIORLIGHTINGHE HEATEDBSMT 7794.37 0.0 939.713 0.120 N/A 0.000 0.600 0.200 0.200 0.000 General 64.606 939.713


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 GAS_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
5 GAS_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 GAS_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 GAS_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
13 GAS_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 GAS_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 GAS_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
21 GAS_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 GAS_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 GAS_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
29 GAS_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 GAS_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 GAS_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
37 GAS_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 GAS_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 GAS_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
45 GAS_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 GAS_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 GAS_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
53 GAS_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 GAS_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 GAS_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
61 GAS_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 GAS_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 GAS_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
69 GAS_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 GAS_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 GAS_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
77 GAS_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 GAS_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 GAS_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
85 GAS_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 GAS_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 GAS_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
93 GAS_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 GAS_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 GAS_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
101 GAS_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 GAS_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 GAS_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
109 GAS_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 GAS_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 GAS_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
117 GAS_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 GAS_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 GAS_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
125 GAS_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 GAS_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 GAS_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
133 GAS_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 GAS_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 GAS_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
141 GAS_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 GAS_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
145 IECC_ADJ_HEATEDBSMT MISCPLUGLOAD HEATEDBSMT 7794.37 0.0 11991.491 1.538 N/A 6.244E-002 0.412 0.251 0.275 IECC_adj 6199.880 11991.491


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 GAS_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
2 GAS_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
3 GAS_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
4 GAS_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
5 GAS_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
6 GAS_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
7 GAS_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
8 GAS_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
9 GAS_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
10 GAS_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
11 GAS_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
12 GAS_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
13 GAS_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
14 GAS_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
15 GAS_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
16 GAS_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
17 GAS_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
18 GAS_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
19 GAS_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
20 GAS_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
21 GAS_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
22 GAS_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
23 GAS_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
24 GAS_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
25 GAS_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
26 GAS_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
27 GAS_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
28 GAS_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
29 GAS_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
30 GAS_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
31 GAS_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
32 GAS_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
33 GAS_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
34 GAS_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
35 GAS_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
36 GAS_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
37 GAS_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
38 GAS_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
39 GAS_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
40 GAS_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
41 GAS_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
42 GAS_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
43 GAS_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
44 GAS_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
45 GAS_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
46 GAS_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
47 GAS_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
48 GAS_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
49 GAS_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
50 GAS_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
51 GAS_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
52 GAS_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
53 GAS_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
54 GAS_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.350 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
10 BASEMENT WALL 24 3 9 0.167 0.0945 0.900 0.900 0.700 0.700 Rough
11 iz-EXTERIOR FLOOR 25 3 4 0.167 0.300 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.1188 0.072 32.003 0.183 0.5031
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
24 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
25 BSMTWALL_CONSOL_LAYER 0.2917 0.058 7.541 0.248 1.534
26 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
20 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
21 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
22 1 -8.3915550 0.80192706 -1.1535996 0.21114735
23 0 9.2367617 0.51139848 2.4177143  
24 10 0.25332408E-17 -0.22101509E-14 0.15157692E-08 0.28211904E-17
25 9 -0.31506112E-08 -0.26974675E-14 -0.81843868E-03 0.20118786E-08
26 8 0.42861811E-03 0.11354105E-09 0.39097097E-01 -0.27370296E-03
27 7 -0.11368907E-01 0.51842634E-07 -0.64553953 0.74324363E-02
28 6 0.12484615 0.25047115E-05 5.3130581 -0.83937451E-01
29 5 -0.73775399 0.27964547E-04 -24.889648 0.51283867
30 4 2.5553417 0.92755650E-04 70.144414 -1.8477174
31 3 -5.2989438 0.96002462E-04 -120.51707 4.0111012
32 2 6.4233118 0.27752742E-04 123.06129 -5.1209931
33 1 -4.1707712 0.15163054E-05 -68.409714 3.5199891
34 0 1.1151582 0.34288690E-08 15.905180  
35 10 0.15157692E-08 -0.22101509E-14 0.25332408E-17 0.28211904E-17
36 9 -0.81843868E-03 -0.26974675E-14 -0.31506112E-08 0.20118786E-08
37 8 0.39097097E-01 0.11354105E-09 0.42861811E-03 -0.27370296E-03
38 7 -0.64553953 0.51842634E-07 -0.11368907E-01 0.74324363E-02
39 6 5.3130581 0.25047115E-05 0.12484615 -0.83937451E-01
40 5 -24.889648 0.27964547E-04 -0.73775399 0.51283867
41 4 70.144414 0.92755650E-04 2.5553417 -1.8477174
42 3 -120.51707 0.96002462E-04 -5.2989438 4.0111012
43 2 123.06129 0.27752742E-04 6.4233118 -5.1209931
44 1 -68.409714 0.15163054E-05 -4.1707712 3.5199891
45 0 15.905180 0.34288690E-08 1.1151582  
46 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
47 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
48 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
49 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
50 1 -19.904252 0.86481321 -19.904252 0.58144210
51 0 16.688993 0.62060609E-01 16.688993  
52 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
53 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
54 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
55 1 -11.299243 2.8799011 -8.6239668 0.15905732
56 0 15.219762 1.4410112 12.640375  
57 5 -0.24423608E-08 0.10315694E-08 -0.24423608E-08 0.46347327E-11
58 4 0.46481418E-04 0.19988510E-04 0.46481418E-04 -0.22728163E-06
59 3 -0.31887091E-01 0.95525843E-02 -0.31887091E-01 0.49135354E-03
60 2 1.3495466 0.25081638 1.3495466 -0.51058024E-01
61 1 -7.0688408 0.57876498 -7.0688408 0.58136590
62 0 6.6836766 0.93387740E-01 6.6836766  
63 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
64 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
65 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
66 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
67 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
68 1 -64.420211 0.46601667 -21.697519 0.64629334
69 0 46.121323 0.20873329E-01 15.867130  
70 9 -0.80897332E-10 0.25083726E-14 -0.80897339E-10 0.53193778E-14
71 8 0.39289009E-06 0.32343632E-10 0.39289009E-06 -0.68074193E-10
72 7 -0.79073148E-04 0.55832398E-07 -0.79073148E-04 0.21386430E-06
73 6 0.50623992E-02 0.12454124E-04 0.50623992E-02 -0.38648400E-04
74 5 -0.13087289 0.53594127E-03 -0.13087289 0.20673172E-02
75 4 1.5051005 0.55237945E-02 1.5051005 -0.39966152E-01
76 3 -8.0002312 0.14646655E-01 -8.0002312 0.31995340
77 2 19.971617 0.92139765E-02 19.971617 -1.1487826
78 1 -22.455378 0.94314545E-03 -22.455378 1.8092119
79 0 9.1356600 0.28983972E-05 9.1356600  
80 4 0.60443234E-14 -0.40788276E-14 0.29631924E-13 -0.77798347E-16
81 3 -0.23145793E-05 0.79669069E-06 -0.11254351E-04 0.39394231E-13
82 2 0.78801895E-01 0.29587917E-01 0.49771861 -0.76025120E-05
83 1 -1.1535996 0.80192706 -8.3915550 0.21114735
84 0 2.4177143 0.51139848 9.2367617  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.350 0.350 1.000 0.217    
2 INTERIOR WINDOW 13 1 VerySmooth 0.350 0.350 1.000 0.217    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.350 0.350 1.000 0.208    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
2 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
3 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
19 VENTILATION_UNITHEATEDBSMT ALWAYS_OFF HEATEDBSMT 7794.37 0.0 60.000 0.008 N/A 6.151E-002 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 HEATEDBSMT Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 HEATEDBSMT Cooling 7766.71987 7766.71987 381.27114 381.27114 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 88.88000 0.00686 7794.38637 0.00000 59.99321 0.00000
2 HEATEDBSMT Heating 4948.56192 4948.56192 103.87859 103.87859 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 22.64000 0.00281 7794.38637 0.00000 59.99321 0.00000
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 9665.26234 9665.26234 474.47028 474.47028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 96.52401 0.00687 1200.55323 2.00000 59.99321 0.00000
4 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 6771.45987 6771.45987 142.11587 142.11587 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
5 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 6487.60239 6487.60239 318.47454 318.47454 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 93.20900 0.00686 1200.55323 2.00000 59.99321 0.00000
6 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 5185.08473 5185.08473 108.82350 108.82350 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
7 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 7487.35930 7487.35930 367.54233 367.54233 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 94.96400 0.00687 1200.55323 2.00000 59.99321 0.00000
8 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 6771.37505 6771.37505 142.11397 142.11397 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
9 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 9568.35554 9568.35554 469.70333 469.70333 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 59.99321 0.00000
10 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 6774.87399 6774.87399 142.18748 142.18748 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
11 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 6477.56425 6477.56425 317.98725 317.98725 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 93.20900 0.00686 1200.55323 2.00000 59.99321 0.00000
12 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 5185.70326 5185.70326 108.83643 108.83643 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
13 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 7453.29621 7453.29621 365.88978 365.88978 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 94.37900 0.00687 1200.55323 2.00000 59.99321 0.00000
14 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 6769.16152 6769.16152 142.06757 142.06757 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
15 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 10114.01486 10114.01486 496.50417 496.50417 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 59.99321 0.00000
16 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 6186.69811 6186.69811 129.84723 129.84723 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
17 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 6766.87169 6766.87169 332.18216 332.18216 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 92.03900 0.00686 1200.55323 2.00000 59.99321 0.00000
18 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 4465.98836 4465.98836 93.73431 93.73431 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
19 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7924.89398 7924.89398 389.02537 389.02537 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 94.96400 0.00687 1200.55323 2.00000 59.99321 0.00000
20 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 6188.86343 6188.86343 129.89257 129.89257 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
21 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 10022.00734 10022.00734 491.97028 491.97028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 59.99321 0.00000
22 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 6189.85800 6189.85800 129.91354 129.91354 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
23 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 6740.15160 6740.15160 330.86860 330.86860 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 92.03900 0.00686 1200.55323 2.00000 59.99321 0.00000
24 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 4466.29404 4466.29404 93.74067 93.74067 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
25 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 7876.76479 7876.76479 386.67368 386.67368 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 94.37900 0.00687 1200.55323 2.00000 59.99321 0.00000
26 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 6186.28451 6186.28451 129.83854 129.83854 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
27 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 9448.36583 9448.36583 463.81350 463.81350 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 94.37900 0.00687 1200.55323 2.00000 59.99321 0.00000
28 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 8296.79901 8296.79901 174.12794 174.12794 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
29 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 9361.14177 9361.14177 459.53384 459.53384 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 94.37900 0.00687 1200.55323 2.00000 59.99321 0.00000
30 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 8298.55616 8298.55616 174.16481 174.16481 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
31 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 11554.55351 11554.55351 567.20332 567.20332 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 59.99321 0.00000
32 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 8295.60621 8295.60621 174.10294 174.10294 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
33 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 8293.65608 8293.65608 407.13978 407.13978 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 92.62400 0.00686 1200.55323 2.00000 59.99321 0.00000
34 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 6548.11401 6548.11401 137.42964 137.42964 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
35 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 8205.15024 8205.15024 402.79656 402.79656 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 92.03900 0.00686 1200.55323 2.00000 59.99321 0.00000
36 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 6547.75237 6547.75237 137.42202 137.42202 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000
37 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 11617.57203 11617.57203 570.29654 570.29654 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 59.99321 0.00000
38 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 8298.07756 8298.07756 174.15485 174.15485 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 22.64000 0.00281 1200.55323 2.00000 59.99321 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 3149.35 474.47028 474.47028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2770.43 142.11587 142.11587 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 2176.03 318.47454 318.47454 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 2312.27 108.82350 108.82350 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2494.01 367.54233 367.54233 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2770.40 142.11397 142.11397 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 3114.90 469.70333 469.70333 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2771.41 142.18748 142.18748 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 2173.13 317.98725 317.98725 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 2312.45 108.83643 108.83643 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 2474.51 365.88978 365.88978 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2769.76 142.06757 142.06757 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 3272.64 496.50417 496.50417 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 2601.56 129.84723 129.84723 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 2237.45 332.18216 332.18216 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 2104.61 93.73431 93.73431 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2620.50 389.02537 389.02537 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 2602.19 129.89257 129.89257 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 3239.60 491.97028 491.97028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 2602.48 129.91354 129.91354 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 2229.73 330.86860 330.86860 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 2104.70 93.74067 93.74067 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2596.93 386.67368 386.67368 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 2601.44 129.83854 129.83854 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3682.63 567.20332 567.20332 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 3210.62 174.10294 174.10294 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 2653.22 402.79656 402.79656 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 2705.82 137.42202 137.42202 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 3026.02 459.53384 459.53384 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 3211.47 174.16481 174.16481 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3700.84 570.29654 570.29654 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 3211.33 174.15485 174.15485 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 2688.47 407.13978 407.13978 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 2705.93 137.42964 137.42964 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 3051.24 463.81350 463.81350 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 3210.96 174.12794 174.12794 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
37 CENTRAL SYSTEM_UNITHEATEDBSMT Cooling Sensible 2474.33 381.27114 381.27114 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
38 CENTRAL SYSTEM_UNITHEATEDBSMT Heating Sensible 2244.11 103.87859 103.87859 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNITHEATEDBSMT Design Size Maximum Air Flow Rate [ft3/min] 381.27114
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 474.47028
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 318.47454
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 367.54233
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 469.70333
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 317.98725
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 365.88978
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 496.50417
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 332.18216
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 389.02537
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 491.97028
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 330.86860
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 386.67368
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 463.81350
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 459.53384
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 567.20332
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 407.13978
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 402.79656
19 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 570.29654
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 474.47028
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 474.47028
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 474.47028
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 474.47028
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 474.47028
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 474.47028
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 318.47454
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 318.47454
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 318.47454
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 318.47454
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 318.47454
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 318.47454
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 367.54233
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 367.54233
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 367.54233
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 367.54233
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 367.54233
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 367.54233
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 469.70333
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 469.70333
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 469.70333
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 469.70333
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 469.70333
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 469.70333
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 317.98725
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 317.98725
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 317.98725
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 317.98725
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 317.98725
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 317.98725
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 365.88978
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 365.88978
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 365.88978
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 365.88978
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 365.88978
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 365.88978
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 496.50417
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 496.50417
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 496.50417
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 496.50417
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 496.50417
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 496.50417
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 332.18216
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 332.18216
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 332.18216
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 332.18216
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 332.18216
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 332.18216
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 389.02537
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 389.02537
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 389.02537
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 389.02537
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 389.02537
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 389.02537
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 491.97028
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 491.97028
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 491.97028
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 491.97028
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 491.97028
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 491.97028
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 330.86860
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 330.86860
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 330.86860
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 330.86860
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 330.86860
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 330.86860
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 386.67368
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 386.67368
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 386.67368
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 386.67368
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 386.67368
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 386.67368
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 567.20332
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 567.20332
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 567.20332
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 567.20332
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 567.20332
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 567.20332
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 402.79656
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 402.79656
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 402.79656
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 402.79656
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 402.79656
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 402.79656
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 459.53384
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 459.53384
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 459.53384
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 459.53384
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 459.53384
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 459.53384
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 570.29654
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 570.29654
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 570.29654
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 570.29654
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 570.29654
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 570.29654
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 407.13978
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 407.13978
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 407.13978
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 407.13978
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 407.13978
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 407.13978
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 463.81350
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 463.81350
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 463.81350
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 463.81350
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 463.81350
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 463.81350
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 381.27114
165 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 381.27114
166 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Maximum Flow Rates [ft3/min] 381.27114
167 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Heating Design Air Flow Rate [ft3/min] 381.27114
168 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Cooling Design Air Flow Rate [ft3/min] 381.27114
169 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Main Design Air Flow Rate [ft3/min] 381.27114
170 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT User Heating Air Flow Ratio [] 1.00000
171 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Calculated Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 474.47028
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 318.47454
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 367.54233
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 469.70333
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 317.98725
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 365.88978
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 496.50417
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 332.18216
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 389.02537
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 491.97028
182 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 330.86860
183 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 386.67368
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 567.20332
185 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 402.79656
186 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 459.53384
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 570.29654
188 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 407.13978
189 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 463.81350
190 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Design Supply Air Flow Rate [ft3/min] 381.27114
191 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 474.47028
192 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.33777
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75768
194 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 474.47028
195 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 474.47028
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 474.47028
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9452.69116
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.33777
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
200 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 474.47028
201 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 10870.59484
202 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 318.47454
203 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.90584
204 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75416
205 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 318.47454
206 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 318.47454
207 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 318.47454
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7889.46480
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.90584
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
211 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 318.47454
212 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9072.88455
213 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 367.54233
214 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.04756
215 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75358
216 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 367.54233
217 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 367.54233
218 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 367.54233
219 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9452.60760
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.04756
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
222 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 367.54233
223 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 10870.49873
224 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 469.70333
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.32027
226 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75858
227 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 469.70333
228 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 469.70333
229 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 469.70333
230 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9456.05549
231 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.32027
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
233 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 469.70333
234 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 10874.46381
235 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 317.98725
236 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.90460
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75411
238 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 317.98725
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 317.98725
240 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 317.98725
241 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7890.07435
242 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.90460
243 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
244 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 317.98725
245 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9073.58548
246 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 365.88978
247 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.03633
248 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75537
249 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 365.88978
250 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 365.88978
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 365.88978
252 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9450.42634
253 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.03633
254 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
255 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 365.88978
256 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 10867.99029
257 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 496.50417
258 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.38784
259 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76020
260 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 496.50417
261 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 496.50417
262 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 496.50417
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8876.53555
264 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.38784
265 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
266 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 496.50417
267 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 10208.01590
268 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 332.18216
269 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.93281
270 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75886
271 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 332.18216
272 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 332.18216
273 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 332.18216
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 7180.93434
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.93281
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
277 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 332.18216
278 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 8258.07452
279 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 389.02537
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10176
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75540
282 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 389.02537
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 389.02537
284 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 389.02537
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8878.66931
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.10176
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
288 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 389.02537
289 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 10210.46971
290 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 491.97028
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.37098
292 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76210
293 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 491.97028
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 491.97028
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 491.97028
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8879.64937
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.37098
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
299 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 491.97028
300 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 10211.59676
301 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 330.86860
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.92952
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75874
304 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 330.86860
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 330.86860
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 330.86860
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 7181.23558
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.92952
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
310 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 330.86860
311 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 8258.42094
312 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 386.67368
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.08994
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75776
315 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 386.67368
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 386.67368
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 386.67368
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8876.12799
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.08994
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
321 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 386.67368
322 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 10207.54716
323 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 567.20332
324 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.56085
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76681
326 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 567.20332
327 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 567.20332
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 567.20332
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 10954.62305
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.56085
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
332 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 567.20332
333 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 12597.81653
334 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 402.79656
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10644
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76734
337 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 402.79656
338 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 402.79656
339 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 402.79656
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9232.26930
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.10644
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
343 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 402.79656
344 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 10617.10969
345 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 459.53384
346 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.27093
347 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76432
348 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 459.53384
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 459.53384
350 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 459.53384
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 10957.53001
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.27093
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
354 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 459.53384
355 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 12601.15950
356 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 570.29654
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.56865
358 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76695
359 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 570.29654
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 570.29654
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 570.29654
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 10957.05837
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.56865
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
365 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 570.29654
366 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 12600.61713
367 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 407.13978
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.12358
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76496
370 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 407.13978
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 407.13978
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 407.13978
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9232.62565
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.12358
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
376 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 407.13978
377 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 10617.51950
378 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 463.81350
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.28166
380 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76458
381 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 463.81350
382 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 463.81350
383 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 463.81350
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 10955.79849
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.28166
386 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 463.81350
388 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 12599.16826
389 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Rated Air Flow Rate [ft3/min] 381.27114
390 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Gross Rated Total Cooling Capacity [ton] 0.97851
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Gross Rated Sensible Heat Ratio 0.79425
392 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate [ft3/min] 381.27114
393 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate During Heating Operation [ft3/min] 381.27114
394 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate During Cooling Operation [ft3/min] 381.27114
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Nominal Heating Capacity [Btu/h] 7656.90926
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Nominal Cooling Capacity [ton] 0.97851
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
398 Fan:OnOff SUPPLY FAN_UNITHEATEDBSMT Design Size Maximum Flow Rate [ft3/min] 381.27114
399 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNITHEATEDBSMT Design Size Nominal Capacity [Btu/h] 9571.13655
400 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
401 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
402 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
403 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
404 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
405 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
406 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
407 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
408 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
409 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
410 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
411 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
412 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
413 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
414 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
415 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
416 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
417 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
418 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
419 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
420 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
421 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
422 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
423 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
424 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
425 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
426 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
427 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
428 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
429 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
430 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
431 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
432 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
433 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
434 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
435 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
436 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
437 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
438 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
439 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
440 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
441 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
442 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
443 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
444 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
445 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
446 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
447 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
448 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
449 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
450 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
451 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
452 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
453 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
454 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
455 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
456 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
457 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
458 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
459 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
460 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
461 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
462 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
463 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
464 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
465 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
466 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
467 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
468 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
469 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
470 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
471 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
472 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
473 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
474 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
475 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
476 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
477 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
478 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
479 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
480 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
481 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
482 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
483 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
484 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
485 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
486 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
487 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
488 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
489 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.3 3.58 12.21 12.94 12.44 12.62
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.3 3.45 11.78 12.47 12.32 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.9 3.58 12.23 12.96 12.46 12.65
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.9 3.46 11.80 12.49 12.35 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.0 3.59 12.23 12.97 12.46 12.66
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.0 3.46 11.80 12.49 12.35 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.3 3.58 12.20 12.93 12.43 12.61
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.3 3.45 11.77 12.46 12.32 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.9 3.58 12.23 12.96 12.46 12.65
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.9 3.46 11.80 12.49 12.35 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.0 3.58 12.22 12.95 12.45 12.64
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.0 3.45 11.79 12.48 12.34 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.57 12.19 12.92 12.42 12.59
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.3 3.45 11.76 12.44 12.30 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.9 3.58 12.20 12.93 12.43 12.61
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.9 3.45 11.77 12.45 12.31 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.1 3.58 12.22 12.95 12.45 12.64
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.1 3.45 11.79 12.48 12.34 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.3 3.57 12.18 12.91 12.41 12.58
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.3 3.44 11.75 12.43 12.29 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.9 3.58 12.20 12.93 12.43 12.61
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.9 3.45 11.77 12.46 12.31 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.0 3.58 12.21 12.94 12.44 12.62
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.0 3.45 11.78 12.46 12.32 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.5 3.56 12.16 12.88 12.38 12.54
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.5 3.43 11.72 12.40 12.26 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.1 3.56 12.15 12.88 12.38 12.53
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.1 3.43 11.71 12.39 12.25 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.2 3.57 12.17 12.90 12.40 12.55
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.2 3.44 11.73 12.41 12.27 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.5 3.56 12.16 12.88 12.38 12.53
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.5 3.43 11.72 12.40 12.26 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.1 3.56 12.16 12.89 12.39 12.55
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.1 3.44 11.72 12.41 12.27 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.2 3.57 12.17 12.89 12.39 12.55
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.2 3.44 11.73 12.41 12.27 -99999.
37 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT 0.9 3.52 12.00 12.71 12.22 12.28
38 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT 0.9 3.38 11.54 12.20 12.07 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 22.64 0.00 DefaultMultipliers Wetbulb -5.20 {C} 13. 20 433.1 0.00 No No
2 100.58 13.00 DefaultMultipliers Wetbulb 18.10 {C} 13. 280 767.8 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 HEATEDBSMT SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.004200881 0.012527226 Pass Pass 0.284285211 1.232115034 Pass Pass
2 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000004279 0.000002394 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019064786 0.029038131 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023979861 0.037019098 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019066006 0.029039964 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019056465 0.029024995 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.023979736 0.037018644 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019072964 0.029050703 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020295248 0.030693297 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.027890018 0.042957750 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020288288 0.030682193 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020284946 0.030676987 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.027888786 0.042955645 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.020297090 0.030696035 Pass Pass
15 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000159464 0.000127444 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015108161 0.021419582 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015105089 0.021415028 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015110651 0.021423238 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019195031 0.027425202 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.019196263 0.027427054 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015106023 0.021416404 Pass Pass
22 HEATEDBSMT SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000009069 0.000049515 Pass Pass 0.082509578 0.131242609 Pass Pass
23 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.411008597 0.246447008 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000031199 0.000203808 Pass Pass 0.071103324 0.034018860 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000020652 0.000138134 Pass Pass 0.054118688 0.037329810 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000040344 0.000190920 Pass Pass 0.060910557 0.055176038 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000029646 0.000197211 Pass Pass 0.070504852 0.034598901 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000021124 0.000140545 Pass Pass 0.053420649 0.037056315 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000061559 0.000262312 Pass Pass 0.060418117 0.056208726 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000031248 0.000206814 Pass Pass 0.065037468 0.028832955 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000026789 0.000148934 Pass Pass 0.047578129 0.032980269 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000041851 0.000198730 Pass Pass 0.055136545 0.047489646 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000030814 0.000205036 Pass Pass 0.064471420 0.028654482 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000027145 0.000150919 Pass Pass 0.047126750 0.031991289 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000064555 0.000272451 Pass Pass 0.054347453 0.048491683 Pass Pass
36 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.599010337 0.458383142 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000031529 0.000199409 Pass Pass 0.058070899 0.046271695 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000031164 0.000161935 Pass Pass 0.058338866 0.045732360 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000034358 0.000226693 Pass Pass 0.068200827 0.028681968 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000032497 0.000173338 Pass Pass 0.053739995 0.029325768 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000037854 0.000200314 Pass Pass 0.053249573 0.031391805 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000035282 0.000231753 Pass Pass 0.068389284 0.027807101 Pass Pass
43 HEATEDBSMT RunPeriod: ANNUAL 0.032891826 0.044971934 Pass Pass 0.164103455 0.414627772 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.263515366 0.218990399 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041732891 0.086283040 Pass Pass 0.446677605 1.498248221 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041792133 0.084453617 Pass Pass 0.287587901 0.562930343 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041764995 0.088197633 Pass Pass 0.330860497 0.897255401 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041733347 0.076500118 Pass Pass 0.512644295 1.196837413 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.038448195 0.051963905 Pass Pass 0.185795269 0.448276738 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.028511901 0.041849876 Pass Pass 0.167944767 0.452131983 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041802597 0.078843182 Pass Pass 0.303365630 0.744413285 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041836604 0.079608770 Pass Pass 0.295967679 0.696844016 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041813998 0.085521485 Pass Pass 0.357286943 1.565578404 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041770859 0.073836138 Pass Pass 0.329379604 0.734203278 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041718389 0.051341261 Pass Pass 0.350003811 1.257473942 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.038638973 0.047379115 Pass Pass 0.190351900 0.678418911 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.541867319 0.467034928 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.035370905 0.050456942 Pass Pass 0.189262504 0.399743660 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041758629 0.083066074 Pass Pass 0.380158606 1.206831940 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041759827 0.083546468 Pass Pass 0.327533539 0.617456671 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.043219221 0.055633453 Pass Pass 0.299016154 0.699369441 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041823498 0.077617010 Pass Pass 0.344843292 1.211949052 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.041673243 0.079633632 Pass Pass 0.388520347 1.270273302 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2885076.05 326651.91 143856.76 0.00 567858.06 3923457.70



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 8760.00 0.00 0.00 0.00 0.00
BREEZEWAY 6548.33 1513.00 695.67 3.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 6569.17 998.17 789.67 403.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 6548.33 0.00 0.00 0.00 0.00
Max 8760.00 1513.00 789.67 403.00 0.00
Average 8550.36 119.58 70.73 19.33 0.00
Sum 179557.50 2511.17 1485.33 406.00 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 4470.17 4289.83 0.00 0.00 0.00
BREEZEWAY 7356.67 1381.67 21.67 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8734.17 25.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8739.67 20.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8738.67 21.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8734.67 25.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8741.17 18.83 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8739.33 20.67 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8752.17 7.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8759.00 1.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8754.00 6.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8752.67 7.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8754.00 6.00 0.00 0.00 0.00
ATTIC 6698.17 1426.33 444.83 185.83 4.83
LIVING_UNIT3_BACKROW_TOPFLOOR 8749.33 10.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8748.83 11.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8745.50 14.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8751.17 8.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8750.67 9.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8746.33 13.67 0.00 0.00 0.00
Min 4470.17 0.00 0.00 0.00 0.00
Max 8760.00 4289.83 444.83 185.83 4.83
Average 8379.83 348.88 22.21 8.85 0.23
Sum 175976.33 7326.50 466.50 185.83 4.83


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12014.53 47.85 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12025.41 36.97 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12022.39 39.99 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12015.22 47.16 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12027.90 34.48 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12023.73 38.65 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12047.93 14.45 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12060.38 2.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12051.21 11.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12048.81 13.57 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12051.21 11.17 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12043.48 18.91 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12042.48 19.91 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12037.00 25.38 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12047.38 15.01 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12046.77 15.61 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12038.43 23.95 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 47.85 0.00 0.00 0.00
Average 10319.36 19.82 0.00 0.00 0.00
Sum 216706.65 416.22 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8734.17 25.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8739.67 20.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8738.67 21.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8734.67 25.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8741.17 18.83 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8739.33 20.67 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8752.17 7.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8759.00 1.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8754.00 6.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8752.67 7.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8754.00 6.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8749.33 10.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8748.83 11.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8745.50 14.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8751.17 8.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8750.67 9.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8746.33 13.67 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 25.83 0.00 0.00 0.00
Average 7497.68 10.89 0.00 0.00 0.00
Sum 157451.33 228.67 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
HEATEDBSMT 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
HEATEDBSMT 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
HEATEDBSMT 0.10 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.21 0.22 0.21 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.17 0.23 0.17 0.01 0.02 0.01
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.18 0.19 0.18 0.01 0.01 0.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.17 0.19 0.17 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.15 0.22 0.15 0.02 0.02 0.02
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.15 0.18 0.15 0.02 0.02 0.02
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.22 0.25 0.22 0.01 0.00 0.01
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.19 0.27 0.19 0.02 0.02 0.02
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.21 0.23 0.21 0.01 0.01 0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.21 0.26 0.21 0.01 0.02 0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.16 0.25 0.16 0.03 0.03 0.03
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.18 0.21 0.18 0.01 0.01 0.01
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.17 0.20 0.17 0.02 0.01 0.02
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.20 0.23 0.20 0.01 0.02 0.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.22 0.24 0.22 0.01 0.02 0.01
LIVING_UNIT2_BACKROW_TOPFLOOR 0.18 0.25 0.18 0.02 0.01 0.02
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.19 0.26 0.19 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_TOPFLOOR 0.21 0.25 0.21 0.02 0.02 0.02
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.22 0.27 0.22 0.03 0.03 0.03
Average 0.17 0.20 0.16 0.01 0.01 0.01
Sum 3.48 4.14 3.38 0.27 0.29 0.27


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 22.64 0.00 22.64 Wetbulb [F] 433.09 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 100.58 23.40 64.58 Wetbulb [F] 767.75 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.12 6      
Feb 0.12 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.71 7      
Jul 1.06 16      
Aug 1.61 15      
Sep 0.00 0      
Oct 0.91 18      
Nov 0.00 0      
Dec 0.28 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.087 0.094 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.087 0.094 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 180.00 90.00 S
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 90.00 90.00 E
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.089 0.094 839.40 839.40 0.00 90.00 N
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.089 0.094 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.027 0.028 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.350 0.217 0.883                      
North Total or Average             531.68 0.350 0.217 0.883                      
Non-North Total or Average             1595.05 0.350 0.217 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
BASEMENT HARDWIRED LIGHTING HEATEDBSMT HEATEDBSMT GENERAL 0.3203 7794.39 2496.92 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 2246.64
BASEMENT PLUG-IN LIGHTING HEATEDBSMT HEATEDBSMT GENERAL 0.1206 7794.39 939.71 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 845.52
Interior Lighting Total       0.3034 58808.69 17840.63               16052.36


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   16053.29 12163.30 3889.99 0.76 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10870.10 8197.81 2672.29 0.75 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12570.72 9473.02 3097.71 0.75 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15843.28 12018.39 3824.88 0.76 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10855.15 8186.00 2669.15 0.75 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12435.95 9393.69 3042.26 0.76 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16654.07 12660.40 3993.67 0.76 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11193.75 8494.53 2699.21 0.76 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13221.12 9987.28 3233.84 0.76 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   16451.74 12537.89 3913.85 0.76 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11154.29 8463.21 2691.08 0.76 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13079.23 9910.94 3168.29 0.76 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18730.20 14362.58 4367.62 0.77 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13277.22 10188.17 3089.05 0.77 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15251.21 11656.87 3594.34 0.76 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   18823.85 14436.92 4386.93 0.77 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13482.91 10313.94 3168.97 0.76 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15379.89 11759.19 3620.70 0.76 4.30    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   11742.15 9326.18 2415.96 0.79 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.3 3.58 12.21 12.94 12.44 12.62
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.9 3.58 12.23 12.96 12.46 12.65
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.0 3.59 12.23 12.97 12.46 12.66
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.3 3.58 12.20 12.93 12.43 12.61
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.9 3.58 12.23 12.96 12.46 12.65
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.0 3.58 12.22 12.95 12.45 12.64
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.3 3.57 12.19 12.92 12.42 12.59
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.9 3.58 12.20 12.93 12.43 12.61
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.1 3.58 12.22 12.95 12.45 12.64
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.3 3.57 12.18 12.91 12.41 12.58
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.9 3.58 12.20 12.93 12.43 12.61
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.0 3.58 12.21 12.94 12.44 12.62
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.5 3.56 12.16 12.88 12.38 12.54
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.1 3.56 12.15 12.88 12.38 12.53
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.2 3.57 12.17 12.90 12.40 12.55
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.5 3.56 12.16 12.88 12.38 12.53
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.1 3.56 12.16 12.89 12.39 12.55
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.2 3.57 12.17 12.89 12.39 12.55
DX COOLING COIL_UNITHEATEDBSMT   0.9 3.52 12.00 12.71 12.22 12.28
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.45 11.78 12.47 12.32  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.46 11.80 12.49 12.35  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.46 11.80 12.49 12.35  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.45 11.77 12.46 12.32  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.46 11.80 12.49 12.35  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.45 11.79 12.48 12.34  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.45 11.76 12.44 12.30  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.45 11.77 12.45 12.31  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.45 11.79 12.48 12.34  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.44 11.75 12.43 12.29  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.45 11.77 12.46 12.31  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.45 11.78 12.46 12.32  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.5 3.43 11.72 12.40 12.26  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.43 11.71 12.39 12.25  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.44 11.73 12.41 12.27  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.5 3.43 11.72 12.40 12.26  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.44 11.72 12.41 12.27  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.44 11.73 12.41 12.27  
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed 0.9 3.38 11.54 12.20 12.07  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   10870.59 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   9072.88 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   10870.50 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   10874.46 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   9073.59 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   10867.99 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   10208.02 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   8258.07 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   10210.47 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   10211.60 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   8258.42 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   10207.55 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12597.82 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   10617.11 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   12601.16 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   12600.62 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   10617.52 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   12599.17 0.80
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel   9571.14 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNITHEATEDBSMT Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 474.46 178.96 0.38 1.00 2.19 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 318.48 120.13 0.38 1.00 2.67 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 367.55 138.64 0.38 1.00 2.48 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 469.71 177.17 0.38 1.00 2.20 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 317.98 119.94 0.38 1.00 2.68 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 365.88 138.01 0.38 1.00 2.48 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 496.50 187.27 0.38 1.00 2.15 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 332.19 125.30 0.38 1.00 2.61 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 389.03 146.74 0.38 1.00 2.41 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 491.98 185.57 0.38 1.00 2.16 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 330.88 124.80 0.38 1.00 2.62 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 386.67 145.85 0.38 1.00 2.42 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 567.21 213.95 0.38 1.00 2.03 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 402.79 151.93 0.38 1.00 2.37 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 459.54 173.33 0.38 1.00 2.22 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 570.30 215.11 0.38 1.00 2.02 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 407.14 153.57 0.38 1.00 2.36 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 463.82 174.95 0.38 1.00 2.21 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 381.27 143.81 0.38 1.00 2.43 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9665.26 9665.26 8.05 474.465 474.465 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 75.00 75.00 0.00755 96.52 0.00687 59.993 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6487.60 6487.60 5.40 318.476 318.476 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00766 93.21 0.00686 59.993 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7487.36 7487.36 6.24 367.553 367.553 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00760 94.96 0.00687 59.993 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9568.36 9568.36 7.97 469.708 469.708 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00756 96.13 0.00687 59.993 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 6477.56 6477.56 5.40 317.983 317.983 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00766 93.21 0.00686 59.993 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7453.30 7453.30 6.21 365.881 365.881 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00761 94.38 0.00687 59.993 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10114.01 10114.01 8.42 496.495 496.495 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00758 96.13 0.00687 59.993 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6766.87 6766.87 5.64 332.187 332.187 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 75.00 75.00 0.00770 92.04 0.00686 59.993 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7924.89 7924.89 6.60 389.032 389.032 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00762 94.96 0.00687 59.993 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10022.01 10022.01 8.35 491.979 491.979 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00759 95.74 0.00687 59.993 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6740.15 6740.15 5.61 330.875 330.875 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 75.00 75.00 0.00770 92.04 0.00686 59.993 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7876.76 7876.76 6.56 386.670 386.670 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00763 94.38 0.00687 59.993 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 9448.37 9448.37 7.87 463.819 463.819 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00759 94.38 0.00687 59.993 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9361.14 9361.14 7.80 459.537 459.537 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00759 94.38 0.00687 59.993 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11554.55 11554.55 9.62 567.210 567.210 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00757 95.74 0.00687 59.993 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8293.66 8293.66 6.91 407.136 407.136 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 75.00 75.00 0.00764 92.62 0.00686 59.993 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8205.15 8205.15 6.83 402.792 402.792 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 75.00 75.00 0.00765 92.04 0.00686 59.993 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11617.57 11617.57 9.68 570.304 570.304 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00757 95.74 0.00687 59.993 0.00
HEATEDBSMT 7766.72 7766.72 1.00 381.269 381.269 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 75.00 75.00 0.00799 88.88 0.00686 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6771.46 6771.46 5.64 142.116 142.116 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00610 22.64 0.00281 59.993 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5185.08 5185.08 4.32 108.823 108.823 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00585 22.64 0.00281 59.993 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6771.38 6771.38 5.64 142.114 142.114 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00610 22.64 0.00281 59.993 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6774.87 6774.87 5.64 142.187 142.187 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00610 22.64 0.00281 59.993 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5185.70 5185.70 4.32 108.836 108.836 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00585 22.64 0.00281 59.993 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6769.16 6769.16 5.64 142.068 142.068 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00610 22.64 0.00281 59.993 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6186.70 6186.70 5.15 129.847 129.847 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00629 22.64 0.00281 59.993 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4465.99 4465.99 3.72 93.734 93.734 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00601 22.64 0.00281 59.993 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6188.86 6188.86 5.16 129.893 129.893 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00629 22.64 0.00281 59.993 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6189.86 6189.86 5.16 129.914 129.914 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00629 22.64 0.00281 59.993 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4466.29 4466.29 3.72 93.741 93.741 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00601 22.64 0.00281 59.993 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6186.28 6186.28 5.15 129.839 129.839 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 72.00 71.99 0.00629 22.64 0.00281 59.993 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8296.80 8296.80 6.91 174.128 174.128 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00633 22.64 0.00281 59.993 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8298.56 8298.56 6.91 174.165 174.165 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00633 22.64 0.00281 59.993 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8295.61 8295.61 6.91 174.103 174.103 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00633 22.64 0.00281 59.993 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6548.11 6548.11 5.45 137.430 137.430 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00613 22.64 0.00281 59.993 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6547.75 6547.75 5.45 137.422 137.422 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00613 22.64 0.00281 59.993 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8298.08 8298.08 6.91 174.155 174.155 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 72.00 71.99 0.00633 22.64 0.00281 59.993 0.00
HEATEDBSMT 4948.56 4948.56 0.63 103.879 103.879 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 72.00 72.00 0.00993 22.64 0.00281 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.46 474.46 142.12 142.12 474.4645 474.4645 474.4645 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.48 318.48 108.82 108.82 318.4761 318.4761 318.4761 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.55 367.55 142.11 142.11 367.5529 367.5529 367.5529 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.71 469.71 142.19 142.19 469.7077 469.7077 469.7077 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.98 317.98 108.84 108.84 317.9834 317.9834 317.9834 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.88 365.88 142.07 142.07 365.8811 365.8811 365.8811 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.50 496.50 129.85 129.85 496.4953 496.4953 496.4953 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.19 332.19 93.73 93.73 332.1870 332.1870 332.1870 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.03 389.03 129.89 129.89 389.0324 389.0324 389.0324 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.98 491.98 129.91 129.91 491.9790 491.9790 491.9790 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.88 330.88 93.74 93.74 330.8753 330.8753 330.8753 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.67 386.67 129.84 129.84 386.6700 386.6700 386.6700 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.21 567.21 174.10 174.10 567.2102 567.2102 567.2102 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.79 402.79 137.42 137.42 402.7917 402.7917 402.7917 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.54 459.54 174.16 174.16 459.5372 459.5372 459.5372 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.30 570.30 174.15 174.15 570.3037 570.3037 570.3037 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.14 407.14 137.43 137.43 407.1360 407.1360 407.1360 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.82 463.82 174.13 174.13 463.8190 463.8190 463.8190 1.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 381.27 381.27 103.88 103.88 381.2687 381.2687 381.2687 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 16053.293 12163.303 474.464506 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 14380.40 14380.40 474.464506 79.07 58.65 0.00746069 53.60 49.04 0.00746069 96.52 0.00686787 63.47 12.6444 75.00 0.00753314 35.4591 9657.44 0.00 16059.99 11384.22
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 10870.595 10870.595 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10870.59 10870.59 -999. 65.75 50.81 0.00568449 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00610080 31.8456 6771.46 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 10870.096 8197.810 318.476116 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 9939.40 9925.79 318.476116 79.78 58.96 0.00751036 53.60 49.11 0.00750000 93.21 0.00686494 62.43 18.8376 75.00 0.00761557 35.8425 6433.50 0.00 10874.63 7677.95
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 9072.885 9072.885 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9072.88 9072.88 -999. 62.70 48.83 0.00527823 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00585147 30.5555 5185.08 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 12570.724 9473.019 367.552916 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 11375.27 11375.27 367.552916 79.61 58.86 0.00748064 53.60 49.08 0.00748064 94.96 0.00686649 62.98 16.3224 75.00 0.00750580 35.3318 7474.28 0.00 12575.97 8872.43
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 10870.499 10870.499 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10870.50 10870.50 -999. 63.94 49.86 0.00556339 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00610078 31.8455 6771.38 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 15843.276 12018.392 469.707657 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 14224.08 14224.08 469.707657 79.05 58.66 0.00747286 53.60 49.06 0.00747286 96.13 0.00686752 63.35 12.7725 75.00 0.00754676 35.5224 9561.27 0.00 15849.89 11248.36
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 10874.464 10874.464 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10874.46 10874.46 -999. 65.69 50.78 0.00568077 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00610137 31.8485 6774.87 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 10855.154 8186.002 317.983352 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 9925.86 9912.40 317.983352 79.79 58.96 0.00751025 53.60 49.11 0.00750000 93.21 0.00686494 62.43 18.8668 75.00 0.00762570 35.8896 6438.98 0.00 10859.68 7666.90
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 9073.585 9073.585 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9073.59 9073.59 -999. 62.68 48.82 0.00527745 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00585161 30.5562 5185.70 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 12435.948 9393.693 365.881088 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 11288.38 11288.38 365.881088 79.53 58.84 0.00748771 53.60 49.09 0.00748771 94.38 0.00686598 62.80 16.3969 75.00 0.00750582 35.3319 7178.08 0.00 12441.14 8795.09
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 10867.990 10867.990 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10867.99 10867.99 -999. 63.90 49.84 0.00556063 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00610042 31.8436 6769.16 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 16654.074 12660.399 496.495326 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 14949.67 14949.67 496.495326 78.91 58.63 0.00749033 53.60 49.10 0.00749033 96.13 0.00686752 63.35 12.0834 75.00 0.00756152 35.5911 10098.13 0.00 16661.02 11845.13
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 10208.016 10208.016 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 10208.02 10208.02 -999. 66.03 51.25 0.00586781 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00628830 32.8128 6186.70 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 11193.748 8494.533 332.186972 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 10296.17 10229.41 332.186972 79.43 58.90 0.00754878 53.60 49.11 0.00750000 92.04 0.00686391 62.06 18.0601 75.00 0.00764790 35.9929 6695.00 0.00 11198.42 7950.23
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 8258.075 8258.075 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 8258.07 8258.07 -999. 63.08 49.27 0.00542885 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00600642 31.3552 4465.99 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 13221.121 9987.281 389.032389 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 11961.33 11958.10 389.032389 79.43 58.83 0.00750202 53.60 49.11 0.00750000 94.96 0.00686649 62.98 15.4212 75.00 0.00752535 35.4229 7873.55 0.00 13226.64 9350.84
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 10210.470 10210.470 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 10210.47 10210.47 -999. 64.38 50.38 0.00575197 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00628867 32.8147 6188.86 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 16451.736 12537.891 491.979030 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 14800.68 14800.01 491.979030 78.88 58.64 0.00750033 53.60 49.11 0.00750000 95.74 0.00686719 63.23 12.1943 75.00 0.00757642 35.6604 10005.23 0.00 16458.60 11726.82
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 10211.597 10211.597 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 10211.60 10211.60 -999. 65.97 51.22 0.00586443 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00628884 32.8156 6189.86 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 11154.289 8463.210 330.875281 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 10260.18 10193.79 330.875281 79.44 58.90 0.00754870 53.60 49.11 0.00750000 92.04 0.00686391 62.06 18.1317 75.00 0.00766690 36.0813 6686.03 0.00 11158.94 7920.93
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 8258.421 8258.421 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 8258.42 8258.42 -999. 63.05 49.25 0.00542662 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00600649 31.3555 4466.29 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 13079.234 9910.945 386.670034 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 11870.08 11855.75 386.670034 79.36 58.82 0.00750901 53.60 49.11 0.00750000 94.38 0.00686598 62.80 15.5154 75.00 0.00752608 35.4263 7560.30 0.00 13084.69 9276.12
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 10207.547 10207.547 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 10207.55 10207.55 -999. 64.34 50.36 0.00574832 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00628823 32.8124 6186.28 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 18730.202 14362.583 567.210152 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 16836.27 16836.27 567.210152 78.55 58.51 0.00749157 53.60 49.10 0.00749157 95.74 0.00686719 63.23 10.5769 75.00 0.00755516 35.5615 11548.86 0.00 18738.02 13424.53
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 12597.817 12597.817 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 12597.82 12597.82 -999. 66.77 51.70 0.00596007 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00633285 33.0449 8295.61 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 13277.224 10188.171 402.791657 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 12194.12 12138.04 402.791657 78.89 58.69 0.00753399 53.60 49.11 0.00750000 92.04 0.00686391 62.06 14.8944 75.00 0.00762407 35.8821 8166.89 0.00 13282.76 9522.66
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 10617.110 10617.110 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 10617.11 10617.11 -999. 64.64 50.28 0.00563336 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00612776 31.9844 6547.75 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 15251.208 11656.872 459.537198 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 13824.06 13824.06 459.537198 78.88 58.64 0.00749858 53.60 49.11 0.00749858 94.38 0.00686598 62.80 13.0552 75.00 0.00758188 35.6858 9337.39 0.00 15257.57 10898.84
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 12601.160 12601.160 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 12601.16 12601.16 -999. 65.55 51.07 0.00587306 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00633323 33.0469 8298.56 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 18823.846 14436.917 570.303727 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 16920.02 16920.02 570.303727 78.53 58.51 0.00749172 53.60 49.10 0.00749172 95.74 0.00686719 63.23 10.5195 75.00 0.00755499 35.5607 11598.61 0.00 18831.70 13493.97
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 12600.617 12600.617 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 12600.62 12600.62 -999. 66.80 51.72 0.00596238 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00633317 33.0466 8298.08 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 13482.910 10313.941 407.136016 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 12345.00 12295.40 407.136016 78.95 58.71 0.00752973 53.60 49.11 0.00750000 92.62 0.00686443 62.24 14.7354 75.00 0.00762314 35.8778 8255.36 0.00 13488.54 9643.09
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 10617.520 10617.520 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 10617.52 10617.52 -999. 64.72 50.32 0.00563869 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00612782 31.9847 6548.11 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 15379.894 11759.193 463.819033 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 13939.99 13939.99 463.819033 78.86 58.63 0.00749887 53.60 49.11 0.00749887 94.38 0.00686598 62.80 12.9346 75.00 0.00758561 35.7032 9436.11 0.00 15386.31 10994.44
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 12599.168 12599.168 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 12599.17 12599.17 -999. 65.61 51.10 0.00587711 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00633300 33.0457 8296.80 0.00 -999.0 -999.0
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT 11742.146 9326.185 381.268706 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 10993.66 10541.87 381.268706 78.54 58.99 0.00781195 53.60 49.11 0.00750000 88.88 0.00686114 61.04 15.7352 75.00 0.00799810 37.6201 7737.42 0.00 11747.05 8682.49
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT 9571.137 9571.137 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 9571.14 9571.14 -999. 64.23 55.49 0.00880984 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 72.00 0.00993052 51.5048 4948.56 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16053.293 12163.303 474.464506 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 474.464506 0.51560137   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 Sensible 14380.40 14380.40 0.8958 0.51560137 474.464506 79.07 58.65 0.00746069 10.8 53.60 49.04 0.00746069 7.4 -999. -999.0 -999.0 -999.0 610.627 13769.77 96.52 0.00686787 63.47 59.99331119 12.6444 75.00 0.00754649 75.00 0.00753314 35.4591 9657.44 0.00 16059.99 11384.22 0.49523901 80.00 67.00 0.01118466 13.2 53.82 53.80 0.00879283 8.2
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10870.595 10870.595 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 474.464506 0.51560137   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10870.59 10870.59 1.0000 -0.230003E+04 -999. 65.75 50.81 0.00568449 7.9 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10870.59 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00610080 71.99 0.00610080 31.8456 6771.46 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10870.096 8197.810 318.476116 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 318.476116 0.34608852   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 9939.40 9925.79 0.9144 0.34608852 318.476116 79.78 58.96 0.00751036 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 409.873 9529.53 93.21 0.00686494 62.43 59.99331119 18.8376 75.00 0.00766016 75.00 0.00761557 35.8425 6433.50 0.00 10874.63 7677.95 0.33242064 80.00 67.00 0.01118466 13.2 53.69 53.67 0.00874851 8.2
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9072.885 9072.885 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 318.476116 0.34608852   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9072.88 9072.88 1.0000 -0.230003E+04 -999. 62.70 48.83 0.00527823 7.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9072.88 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00585147 71.99 0.00585147 30.5555 5185.08 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12570.724 9473.019 367.552916 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 367.552916 0.39942036   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 11375.27 11375.27 0.9049 0.39942036 367.552916 79.61 58.86 0.00748064 10.9 53.60 49.08 0.00748064 7.4 -999. -999.0 -999.0 -999.0 473.034 10902.23 94.96 0.00686649 62.98 59.99331119 16.3224 75.00 0.00760043 75.00 0.00750580 35.3318 7474.28 0.00 12575.97 8872.43 0.38364628 80.00 67.00 0.01118466 13.2 53.66 53.64 0.00873910 8.2
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10870.499 10870.499 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 367.552916 0.39942036   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10870.50 10870.50 1.0000 -0.230003E+04 -999. 63.94 49.86 0.00556339 7.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10870.50 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00610078 71.99 0.00610078 31.8455 6771.38 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15843.276 12018.392 469.707657 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 469.707657 0.51043209   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 14224.08 14224.08 0.8978 0.51043209 469.707657 79.05 58.66 0.00747286 10.8 53.60 49.06 0.00747286 7.4 -999. -999.0 -999.0 -999.0 604.505 13619.58 96.13 0.00686752 63.35 59.99331119 12.7725 75.00 0.00756150 75.00 0.00754676 35.5224 9561.27 0.00 15849.89 11248.36 0.49027388 80.00 67.00 0.01118466 13.2 53.87 53.85 0.00880697 8.2
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10874.464 10874.464 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 469.707657 0.51043209   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10874.46 10874.46 1.0000 -0.230003E+04 -999. 65.69 50.78 0.00568077 7.9 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10874.46 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00610137 71.99 0.00610137 31.8485 6774.87 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10855.154 8186.002 317.983352 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 317.983352 0.34555304   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 9925.86 9912.40 0.9144 0.34555304 317.983352 79.79 58.96 0.00751025 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 409.239 9516.62 93.21 0.00686494 62.43 59.99331119 18.8668 75.00 0.00766032 75.00 0.00762570 35.8896 6438.98 0.00 10859.68 7666.90 0.33190630 80.00 67.00 0.01118466 13.2 53.69 53.67 0.00874771 8.2
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9073.585 9073.585 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 317.983352 0.34555304   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9073.59 9073.59 1.0000 -0.230003E+04 -999. 62.68 48.82 0.00527745 7.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9073.59 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00585161 71.99 0.00585161 30.5562 5185.70 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12435.948 9393.693 365.881088 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 365.881088 0.39760359   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 11288.38 11288.38 0.9077 0.39760359 365.881088 79.53 58.84 0.00748771 10.9 53.60 49.09 0.00748771 7.4 -999. -999.0 -999.0 -999.0 470.882 10817.50 94.38 0.00686598 62.80 59.99331119 16.3969 75.00 0.00760965 75.00 0.00750582 35.3319 7178.08 0.00 12441.14 8795.09 0.38190125 80.00 67.00 0.01118466 13.2 53.77 53.73 0.00876606 8.2
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10867.990 10867.990 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 365.881088 0.39760359   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10867.99 10867.99 1.0000 -0.230003E+04 -999. 63.90 49.84 0.00556063 7.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10867.99 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00610042 71.99 0.00610042 31.8436 6769.16 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16654.074 12660.399 496.495326 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 496.495326 0.53954230   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 14949.67 14949.67 0.8977 0.53954230 496.495326 78.91 58.63 0.00749033 10.8 53.60 49.10 0.00749033 7.4 -999. -999.0 -999.0 -999.0 638.980 14310.69 96.13 0.00686752 63.35 59.99331119 12.0834 75.00 0.00757593 75.00 0.00756152 35.5911 10098.13 0.00 16661.02 11845.13 0.51823445 80.00 67.00 0.01118466 13.2 53.97 53.93 0.00883046 8.3
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10208.016 10208.016 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 496.495326 0.53954230   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 10208.02 10208.02 1.0000 -0.230003E+04 -999. 66.03 51.25 0.00586781 8.1 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10208.02 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00628830 71.99 0.00628830 32.8128 6186.70 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11193.748 8494.533 332.186972 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 332.186972 0.36098813   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 10296.17 10229.41 0.9198 0.36098813 332.186972 79.43 58.90 0.00754878 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 427.518 9868.65 92.04 0.00686391 62.06 59.99331119 18.0601 75.00 0.00769973 75.00 0.00764790 35.9929 6695.00 0.00 11198.42 7950.23 0.34673183 80.00 67.00 0.01118466 13.2 53.89 53.86 0.00881143 8.2
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8258.075 8258.075 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 332.186972 0.36098813   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 8258.07 8258.07 1.0000 -0.230003E+04 -999. 63.08 49.27 0.00542885 7.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8258.07 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00600642 71.99 0.00600642 31.3552 4465.99 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13221.121 9987.281 389.032389 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 389.032389 0.42276214   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 11961.33 11958.10 0.9047 0.42276214 389.032389 79.43 58.83 0.00750202 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 500.677 11460.66 94.96 0.00686649 62.98 59.99331119 15.4212 75.00 0.00761789 75.00 0.00752535 35.4229 7873.55 0.00 13226.64 9350.84 0.40606623 80.00 67.00 0.01118466 13.2 53.77 53.74 0.00876666 8.2
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10210.470 10210.470 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 389.032389 0.42276214   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 10210.47 10210.47 1.0000 -0.230003E+04 -999. 64.38 50.38 0.00575197 7.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10210.47 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00628867 71.99 0.00628867 32.8147 6188.86 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16451.736 12537.891 491.979030 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 491.979030 0.53463443   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 14800.68 14800.01 0.8996 0.53463443 491.979030 78.88 58.64 0.00750033 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 633.168 14167.51 95.74 0.00686719 63.23 59.99331119 12.1943 75.00 0.00758826 75.00 0.00757642 35.6604 10005.23 0.00 16458.60 11726.82 0.51352041 80.00 67.00 0.01118466 13.2 53.99 53.98 0.00885035 8.3
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10211.597 10211.597 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 491.979030 0.53463443   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 10211.60 10211.60 1.0000 -0.230003E+04 -999. 65.97 51.22 0.00586443 8.1 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10211.60 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00628884 71.99 0.00628884 32.8156 6189.86 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11154.289 8463.210 330.875281 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 330.875281 0.35956272   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 10260.18 10193.79 0.9198 0.35956272 330.875281 79.44 58.90 0.00754870 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 425.830 9834.35 92.04 0.00686391 62.06 59.99331119 18.1317 75.00 0.00770037 75.00 0.00766690 36.0813 6686.03 0.00 11158.94 7920.93 0.34536271 80.00 67.00 0.01118466 13.2 53.88 53.86 0.00880949 8.2
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8258.421 8258.421 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 330.875281 0.35956272   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 8258.42 8258.42 1.0000 -0.230003E+04 -999. 63.05 49.25 0.00542662 7.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8258.42 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00600649 71.99 0.00600649 31.3555 4466.29 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13079.234 9910.945 386.670034 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 386.670034 0.42019497   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 11870.08 11855.75 0.9076 0.42019497 386.670034 79.36 58.82 0.00750901 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 497.637 11372.44 94.38 0.00686598 62.80 59.99331119 15.5154 75.00 0.00762711 75.00 0.00752608 35.4263 7560.30 0.00 13084.69 9276.12 0.40360044 80.00 67.00 0.01118466 13.2 53.82 53.81 0.00879408 8.2
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10207.547 10207.547 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 386.670034 0.42019497   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:00:00 Sensible 10207.55 10207.55 1.0000 -0.230003E+04 -999. 64.34 50.36 0.00574832 7.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10207.55 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00628823 71.99 0.00628823 32.8124 6186.28 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18730.202 14362.583 567.210152 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 567.210152 0.61638821   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 16836.27 16836.27 0.8989 0.61638821 567.210152 78.55 58.51 0.00749157 10.8 53.60 49.10 0.00749157 7.4 -999. -999.0 -999.0 -999.0 729.989 16106.28 95.74 0.00686719 63.23 59.99331119 10.5769 75.00 0.00756542 75.00 0.00755516 35.5615 11548.86 0.00 18738.02 13424.53 0.59204554 80.00 67.00 0.01118466 13.2 54.18 54.16 0.00891104 8.3
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 12597.817 12597.817 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 567.210152 0.61638821   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 12597.82 12597.82 1.0000 -0.230003E+04 -999. 66.77 51.70 0.00596007 8.2 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 12597.82 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00633285 71.99 0.00633285 33.0449 8295.61 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13277.224 10188.171 402.791657 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 402.791657 0.43771436   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 12194.12 12138.04 0.9184 0.43771436 402.791657 78.89 58.69 0.00753399 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 518.385 11675.73 92.04 0.00686391 62.06 59.99331119 14.8944 75.00 0.00765126 75.00 0.00762407 35.8821 8166.89 0.00 13282.76 9522.66 0.42042795 80.00 67.00 0.01118466 13.2 54.21 54.19 0.00891897 8.3
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10617.110 10617.110 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 402.791657 0.43771436   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 10617.11 10617.11 1.0000 -0.230003E+04 -999. 64.64 50.28 0.00563336 7.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10617.11 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00612776 71.99 0.00612776 31.9844 6547.75 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15251.208 11656.872 459.537198 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 459.537198 0.49937984   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 13824.06 13824.06 0.9064 0.49937984 459.537198 78.88 58.64 0.00749858 10.8 53.60 49.11 0.00749858 7.4 -999. -999.0 -999.0 -999.0 591.416 13232.64 94.38 0.00686598 62.80 59.99331119 13.0552 75.00 0.00759357 75.00 0.00758188 35.6858 9337.39 0.00 15257.57 10898.84 0.47965811 80.00 67.00 0.01118466 13.2 54.13 54.09 0.00888257 8.3
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 12601.160 12601.160 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 459.537198 0.49937984   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 12601.16 12601.16 1.0000 -0.230003E+04 -999. 65.55 51.07 0.00587306 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 12601.16 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00633323 71.99 0.00633323 33.0469 8298.56 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18823.846 14436.917 570.303727 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 570.303727 0.61975001   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 16920.02 16920.02 0.8989 0.61975001 570.303727 78.53 58.51 0.00749172 10.8 53.60 49.10 0.00749172 7.4 -999. -999.0 -999.0 -999.0 733.970 16186.05 95.74 0.00686719 63.23 59.99331119 10.5195 75.00 0.00756515 75.00 0.00755499 35.5607 11598.61 0.00 18831.70 13493.97 0.59527457 80.00 67.00 0.01118466 13.2 54.19 54.17 0.00891306 8.3
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 12600.617 12600.617 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 570.303727 0.61975001   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 12600.62 12600.62 1.0000 -0.230003E+04 -999. 66.80 51.72 0.00596238 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 12600.62 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00633317 71.99 0.00633317 33.0466 8298.08 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13482.910 10313.941 407.136016 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 407.136016 0.44243538   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 12345.00 12295.40 0.9156 0.44243538 407.136016 78.95 58.71 0.00752973 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 523.976 11821.02 92.62 0.00686443 62.24 59.99331119 14.7354 75.00 0.00764470 75.00 0.00762314 35.8778 8255.36 0.00 13488.54 9643.09 0.42496253 80.00 67.00 0.01118466 13.2 54.16 54.12 0.00889227 8.3
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 10617.520 10617.520 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 407.136016 0.44243538   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 10617.52 10617.52 1.0000 -0.230003E+04 -999. 64.72 50.32 0.00563869 7.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 10617.52 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00612782 71.99 0.00612782 31.9847 6548.11 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15379.894 11759.193 463.819033 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 463.819033 0.50403291   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 13939.99 13939.99 0.9064 0.50403291 463.819033 78.86 58.63 0.00749887 10.8 53.60 49.11 0.00749887 7.4 -999. -999.0 -999.0 -999.0 596.926 13343.06 94.38 0.00686598 62.80 59.99331119 12.9346 75.00 0.00759290 75.00 0.00758561 35.7032 9436.11 0.00 15386.31 10994.44 0.48412742 80.00 67.00 0.01118466 13.2 54.14 54.10 0.00888649 8.3
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 12599.168 12599.168 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 463.819033 0.50403291   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 11:10:00 Sensible 12599.17 12599.17 1.0000 -0.230003E+04 -999. 65.61 51.10 0.00587711 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 12599.17 22.64 0.00280840 22.64 59.99331119 -999.000 71.99 0.00633300 71.99 0.00633300 33.0457 8296.80 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT HEATEDBSMT Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11742.146 9326.185 381.268706 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0652 SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 381.268706 0.41432534   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 Sensible 10993.66 10541.87 0.9363 0.41432534 381.268706 78.54 58.99 0.00781195 11.0 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 490.686 10502.97 88.88 0.00686114 61.04 59.99331119 15.7352 75.00 0.00798950 75.00 0.00799810 37.6201 7737.42 0.00 11747.05 8682.49 0.39796262 80.00 67.00 0.01118466 13.2 55.17 55.14 0.00923384 8.7
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT HEATEDBSMT Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9571.137 9571.137 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 381.268706 0.41432534   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 04:10:00 Sensible 9571.14 9571.14 1.0000 -0.230003E+04 -999. 64.23 55.49 0.00880984 9.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9571.14 22.64 0.00280840 22.64 59.99331119 -999.000 72.00 0.00993052 72.00 0.00993052 51.5048 4948.56 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2720.50 4370.83 219.67
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2277.67 4567.83 182.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2664.50 4356.67 185.33
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2579.00 4863.00 227.67
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2110.83 4971.17 189.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2523.00 4778.00 189.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2987.50 3759.00 110.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2589.83 3680.50 76.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2947.83 3672.33 90.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2831.83 4378.67 117.33
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2385.17 4468.50 78.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2786.67 4337.17 94.67
LIVING_UNIT3_BACKROW_TOPFLOOR 2990.67 4391.00 158.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 3101.50 3999.17 146.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 3082.00 4072.33 172.83
LIVING_UNIT2_BACKROW_TOPFLOOR 2672.83 4531.50 134.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 2789.83 4067.00 133.17
LIVING_UNIT1_BACKROW_TOPFLOOR 2991.00 4484.17 187.33
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3392.83 5204.00 264.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.359
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.128 0.000 0.359
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.359
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.359
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.127 0.000 0.359
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.145 0.000 0.359
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.360
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.360
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.064 0.000 0.360
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.063 0.000 0.359
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.046 0.000 0.359
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.063 0.000 0.359
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.359
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.359
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.359
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.128 0.000 0.359
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.128 0.000 0.359
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.145 0.000 0.359
HEATEDBSMT     58539.52        
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.006
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
HEATEDBSMT     58539.52        
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 58539.52 7794.39 0.0000 0.000
Total Facility   24.79 36.00 242278.90 29404.35 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 12824824.77 44613482.80 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 11309540.96 43098198.99 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 12834763.37 44623421.41 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 12795953.10 44584611.13 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 11273273.66 43061931.70 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 12796749.54 44585407.58 31713442.25 3814.50 1353.17 3640.33 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 5628942.31 37419442.12 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 4101644.99 35892144.80 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 5633447.55 37423947.35 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 5615838.60 37406338.41 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 4088045.11 35878544.92 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 5616431.46 37406931.27 31713442.25 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 12807780.21 44600123.73 31713442.25 3805.17 1356.83 3646.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 12840898.58 44633242.10 31713442.25 3805.17 1356.83 3646.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 12832144.91 44624488.43 31713442.25 3805.17 1356.83 3646.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 11284453.76 43076797.28 31713442.25 3805.17 1356.83 3646.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 11316072.58 43108416.10 31713442.25 3805.17 1356.83 3646.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 12807220.44 44599563.95 31713442.25 3805.17 1356.83 3646.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00 31713442.25 8808.00 0.00 0.00 0.00
Total Facility 0.00 0.572229E+09 0.572229E+09 0.178408E+09 0.750637E+09 0.602555E+09 8808.00 1362.50 3646.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 24.2611 84.3967 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 21.3946 81.5302 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 24.2799 84.4155 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 24.2065 84.3421 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 21.3260 81.4616 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 24.2080 84.3436 59.9933 3814.50 1353.17 3640.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 10.6484 70.7875 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 7.7592 67.8983 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 10.6570 70.7961 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 10.6237 70.7627 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 7.7335 67.8726 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 10.6248 70.7639 59.9933 3810.33 1354.50 3643.17
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 24.2289 84.3714 59.9933 3805.17 1356.83 3646.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 24.2915 84.4341 59.9933 3805.17 1356.83 3646.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 24.2750 84.4175 59.9933 3805.17 1356.83 3646.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 21.3472 81.4897 59.9933 3805.17 1356.83 3646.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 21.4070 81.5495 59.9933 3805.17 1356.83 3646.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 24.2278 84.3704 59.9933 3805.17 1356.83 3646.00
Total Facility 0.0000 1082.5035 1082.5035 337.5000 1420.0036 1079.8796 8808.00 1362.50 3646.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 31788658.04 31788658.04 31713442.25 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 31790499.81 31790499.81 31713442.25 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 31792343.52 31792343.52 31713442.25 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNITHEATEDBSMT 0.00 0.00 0.00 31713442.25 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 60.1356 60.1356 59.9933 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 60.1391 60.1391 59.9933 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 60.1426 60.1426 59.9933 3805.17 1356.83 3646.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNITHEATEDBSMT 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2003
Defaulted Fields 1803
Fields with Defaults 6671
Autosized Fields 357
Autosizable Fields 524
Autocalculated Fields 161
Autocalculatable Fields 349



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
Electricity:Building 113983.31 9003.32 02-JAN-03:10 21540.76 01-JAN-20:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
Electricity:SpaceType:GENERAL 113983.31 9003.32 02-JAN-03:10 21540.76 01-JAN-20:10
InteriorLights:Electricity 16052.36 359.48 01-JAN-00:10 5228.79 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 16052.36 359.48 01-JAN-00:10 5228.79 01-JAN-19:10
General:InteriorLights:Electricity 16052.36 359.48 01-JAN-00:10 5228.79 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 16052.36 359.48 01-JAN-00:10 5228.79 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5005.20 389.91 02-JAN-03:10 945.50 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:HEATEDBSMT 23889.75 1946.92 01-JAN-09:10 4521.72 01-JAN-20:10
InteriorLights:Electricity:Zone:HEATEDBSMT 3092.16 69.25 01-JAN-00:10 1007.22 01-JAN-19:10
General:InteriorLights:Electricity:Zone:HEATEDBSMT 3092.16 69.25 01-JAN-00:10 1007.22 01-JAN-19:10
InteriorEquipment:Electricity 97930.96 8367.37 02-JAN-04:10 16311.97 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 97930.96 8367.37 02-JAN-04:10 16311.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:10 291.20 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 1138.84 5.81 02-JAN-03:10 291.20 01-JAN-11:10
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity 44924.98 3925.09 01-JAN-09:10 7591.70 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 44924.98 3925.09 01-JAN-09:10 7591.70 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 35164.90 3072.35 01-JAN-09:10 5942.38 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 35164.90 3072.35 01-JAN-09:10 5942.38 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:HEATEDBSMT 20797.59 1817.08 01-JAN-09:10 3514.51 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:HEATEDBSMT 20797.59 1817.08 01-JAN-09:10 3514.51 01-JAN-20:10
Fans:Electricity 13847.72 814.29 04-JAN-01:20 3316.25 26-JUL-18:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
ElectricityPurchased:Plant 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
Cogeneration:ElectricityPurchased 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
General:Cogeneration:ElectricityPurchased 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
ElectricityNet:Plant 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
Cogeneration:ElectricityNet 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
General:Cogeneration:ElectricityNet 164298.88 10738.30 02-NOV-12:10 39360.42 14-JUN-18:10
Electricity:HVAC 44281.26 814.29 04-JAN-01:20 17879.37 14-JUN-18:10
Ventilation:Fans:Electricity 7133.15 814.29 30-MAR-08:10 814.29 01-JAN-00:10
General:Fans:Electricity 6714.58 0.00 04-JAN-01:20 2501.97 26-JUL-18:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 30433.54 0.00 01-JAN-00:10 14603.22 14-JUN-17:30
General:Cooling:Electricity 30433.54 0.00 01-JAN-00:10 14603.22 14-JUN-17:30
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4694.39 2752.05 16-MAR-03:10 238628.34 01-JAN-08:10
NaturalGas:Building 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
NaturalGas:SpaceType:GENERAL 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
InteriorEquipment:NaturalGas 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas 792.69 403.80 02-JAN-03:10 20254.25 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:SpaceType:GENERAL 792.69 403.80 02-JAN-03:10 20254.25 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas 674.43 651.88 01-JAN-02:10 27685.38 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:SpaceType:GENERAL 674.43 651.88 01-JAN-02:10 27685.38 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas 184.30 1609.08 01-JAN-09:10 3112.21 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:SpaceType:GENERAL 184.30 1609.08 01-JAN-09:10 3112.21 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:HVAC 652.12 0.00 01-JAN-13:20 115281.12 27-DEC-05:00
Heating:NaturalGas 652.12 0.00 01-JAN-13:20 115281.12 27-DEC-05:00
General:Heating:NaturalGas 652.12 0.00 01-JAN-13:20 115281.12 27-DEC-05:00
NaturalGas:Plant 2390.85 0.00 01-JAN-00:10 170932.61 01-JAN-08:10
WaterSystems:NaturalGas 2390.85 0.00 01-JAN-00:10 170932.61 01-JAN-08:10
Water Heater:WaterSystems:NaturalGas 2390.85 0.00 01-JAN-00:10 170932.61 01-JAN-08:10


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1006989.76 407.92 07-OCT-03:00 371679.77 26-JUL-18:10
EnergyTransfer:Building 441130.08 0.00 04-JAN-01:20 175296.15 14-JUN-18:10
EnergyTransfer:Zone:HEATEDBSMT 18475.62 0.00 01-JAN-00:10 8085.19 06-AUG-19:10
Heating:EnergyTransfer 55272.47 0.00 01-JAN-13:20 97692.99 27-DEC-05:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 3195.44 0.00 01-JAN-00:10 4691.63 02-FEB-05:00
General:Heating:EnergyTransfer 55272.47 0.00 01-JAN-13:20 97692.99 27-DEC-05:00
General:Heating:EnergyTransfer:Zone:HEATEDBSMT 3195.44 0.00 01-JAN-00:10 4691.63 02-FEB-05:00
Cooling:EnergyTransfer 385857.61 0.00 01-JAN-00:10 175296.15 14-JUN-18:10
Cooling:EnergyTransfer:Zone:HEATEDBSMT 15280.17 0.00 01-JAN-00:10 8085.19 06-AUG-19:10
General:Cooling:EnergyTransfer 385857.61 0.00 01-JAN-00:10 175296.15 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:HEATEDBSMT 15280.17 0.00 01-JAN-00:10 8085.19 06-AUG-19:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 24164.59 0.00 01-JAN-10:10 11005.79 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3287.31 0.00 01-JAN-10:10 5589.51 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3287.31 0.00 01-JAN-10:10 5589.51 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20877.29 0.00 01-JAN-00:10 11005.79 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 20877.29 0.00 01-JAN-00:10 11005.79 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 19018.39 0.00 01-JAN-00:10 7203.36 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1946.04 0.00 01-JAN-00:10 4123.12 27-DEC-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1946.04 0.00 01-JAN-00:10 4123.12 27-DEC-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17072.35 0.00 01-JAN-00:10 7203.36 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 17072.35 0.00 01-JAN-00:10 7203.36 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23452.35 0.00 01-JAN-09:20 8162.91 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2965.27 0.00 01-JAN-09:20 5635.92 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2965.27 0.00 01-JAN-09:20 5635.92 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20487.08 0.00 01-JAN-00:10 8162.91 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 20487.08 0.00 01-JAN-00:10 8162.91 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 22348.63 0.00 01-JAN-12:50 11183.30 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4062.27 0.00 01-JAN-12:50 5707.29 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4062.27 0.00 01-JAN-12:50 5707.29 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18286.35 0.00 01-JAN-00:10 11183.30 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18286.35 0.00 01-JAN-00:10 11183.30 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 17246.46 0.00 01-JAN-00:10 7376.32 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2673.84 0.00 01-JAN-00:10 4216.24 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2673.84 0.00 01-JAN-00:10 4216.24 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14572.62 0.00 01-JAN-00:10 7376.32 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14572.62 0.00 01-JAN-00:10 7376.32 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 21660.98 0.00 01-JAN-10:20 8333.76 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3690.09 0.00 01-JAN-10:20 5765.46 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3690.09 0.00 01-JAN-10:20 5765.46 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 17970.89 0.00 01-JAN-00:10 8333.76 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 17970.89 0.00 01-JAN-00:10 8333.76 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 26288.22 0.00 01-JAN-00:10 11283.14 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2089.74 0.00 01-JAN-00:10 4923.52 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2089.74 0.00 01-JAN-00:10 4923.52 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24198.47 0.00 01-JAN-00:10 11283.14 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24198.47 0.00 01-JAN-00:10 11283.14 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 21234.82 0.00 01-JAN-00:10 7251.21 05-JUN-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 903.97 0.00 01-JAN-00:10 3362.64 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 903.97 0.00 01-JAN-00:10 3362.64 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20330.85 0.00 01-JAN-00:10 7251.21 05-JUN-19:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 20330.85 0.00 01-JAN-00:10 7251.21 05-JUN-19:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 25905.35 0.00 01-JAN-00:10 8433.15 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1860.62 0.00 01-JAN-00:10 4922.38 27-DEC-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1860.62 0.00 01-JAN-00:10 4922.38 27-DEC-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24044.73 0.00 01-JAN-00:10 8433.15 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24044.73 0.00 01-JAN-00:10 8433.15 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23719.96 0.00 01-JAN-00:10 11441.70 15-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2810.55 0.00 01-JAN-00:10 4956.73 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2810.55 0.00 01-JAN-00:10 4956.73 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20909.42 0.00 01-JAN-00:10 11441.70 15-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 20909.42 0.00 01-JAN-00:10 11441.70 15-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18422.19 0.00 01-JAN-00:10 7413.59 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1491.69 0.00 01-JAN-00:10 3430.27 27-DEC-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1491.69 0.00 01-JAN-00:10 3430.27 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16930.51 0.00 01-JAN-00:10 7413.59 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 16930.51 0.00 01-JAN-00:10 7413.59 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23254.13 0.00 01-JAN-00:10 8574.17 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2508.31 0.00 01-JAN-00:10 5021.09 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2508.31 0.00 01-JAN-00:10 5021.09 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20745.82 0.00 01-JAN-00:10 8574.17 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 20745.82 0.00 01-JAN-00:10 8574.17 14-JUN-18:10
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 26820.28 0.00 01-JAN-11:50 10240.24 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4353.98 0.00 01-JAN-11:50 6968.78 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4353.98 0.00 01-JAN-11:50 6968.78 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 22466.30 0.00 01-JAN-00:10 10240.24 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 22466.30 0.00 01-JAN-00:10 10240.24 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 27977.77 0.00 01-JAN-00:10 10132.15 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3439.91 0.00 01-JAN-00:10 6810.94 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3439.91 0.00 01-JAN-00:10 6810.94 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 24537.86 0.00 01-JAN-00:10 10132.15 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 24537.86 0.00 01-JAN-00:10 10132.15 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 28681.46 0.00 01-JAN-00:10 12797.43 05-JUN-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3828.47 0.00 01-JAN-00:10 6797.28 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 3828.47 0.00 01-JAN-00:10 6797.28 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24852.99 0.00 01-JAN-00:10 12797.43 05-JUN-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24852.99 0.00 01-JAN-00:10 12797.43 05-JUN-17:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 21880.25 0.00 01-JAN-00:10 9055.00 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3158.07 0.00 01-JAN-00:10 5259.80 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3158.07 0.00 01-JAN-00:10 5259.80 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 18722.18 0.00 01-JAN-00:10 9055.00 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 18722.18 0.00 01-JAN-00:10 9055.00 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 23093.37 0.00 01-JAN-00:10 8895.69 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2245.58 0.00 01-JAN-00:10 5202.17 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2245.58 0.00 01-JAN-00:10 5202.17 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20847.79 0.00 01-JAN-00:10 8895.69 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 20847.79 0.00 01-JAN-00:10 8895.69 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 27485.26 0.00 01-JAN-00:10 13009.46 15-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4761.32 0.00 01-JAN-00:10 6863.92 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4761.32 0.00 01-JAN-00:10 6863.92 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 22723.94 0.00 01-JAN-00:10 13009.46 15-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 22723.94 0.00 01-JAN-00:10 13009.46 15-JUN-17:30
PlantLoopHeatingDemand:Facility 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
PlantLoopHeatingDemand:Plant 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
EnergyTransfer:HVAC 503072.41 0.00 04-JAN-01:20 197462.18 26-JUL-18:10
HeatingCoils:EnergyTransfer 52169.53 0.00 01-JAN-13:20 92224.89 27-DEC-05:00
CoolingCoils:EnergyTransfer 450902.88 0.00 01-JAN-00:10 197462.18 26-JUL-18:10
EnergyTransfer:Plant 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
WaterSystems:EnergyTransfer 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 62787.27 196.57 01-AUG-04:00 19592.73 05-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 3287.277 -1738.61 0.000 0.000 2962.114 2458.419 14573.293 10521.024 0.000 1791.635 0.006 0.000 -4024.63 0.000 -9224.92 -1466.92
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 1946.015 -1421.75 0.000 0.000 2949.029 2458.419 14573.293 4628.540 0.000 1728.290 0.037 0.000 -1621.36 0.000 -8971.13 -618.70
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 2965.241 -1706.12 0.000 0.000 2960.962 2458.419 14573.293 10540.206 0.000 1791.636 0.007 0.000 -3890.45 0.000 -9267.35 -1644.85
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 4062.237 -1522.85 0.000 0.000 2973.213 2458.419 14573.293 7445.688 0.000 1791.635 0.118 0.000 -4180.13 0.000 -9098.49 -1739.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 2673.813 -1213.58 0.000 0.000 2965.235 2458.419 14573.293 1427.031 0.000 1728.290 0.162 0.000 -1740.47 0.000 -8795.79 -717.14
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 3690.060 -1496.58 0.000 0.000 2975.954 2458.419 14573.293 7366.161 0.000 1791.637 0.099 0.000 -3928.59 0.000 -9097.78 -1858.23
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 2089.723 -2015.20 0.000 0.000 2942.477 2458.419 14573.293 10435.948 0.000 1488.440 2133.589 0.000 -4158.36 0.000 -7765.01 -0.23
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 903.960 -1693.11 0.000 0.000 2925.486 2458.419 14573.293 4588.521 0.000 1425.322 2646.607 0.000 -1676.46 0.000 -7514.22 -0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 1860.599 -2002.39 0.000 0.000 2941.501 2458.419 14573.293 10439.843 0.000 1488.441 2099.003 0.000 -4014.50 0.000 -7801.80 -0.08
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 2810.524 -1741.29 0.000 0.000 2954.541 2458.419 14573.293 7389.835 0.000 1488.440 1197.575 0.000 -4304.10 0.000 -7659.06 -0.16
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 1491.673 -1409.94 0.000 0.000 2943.350 2458.419 14573.293 1412.562 0.000 1425.322 1786.687 0.000 -1792.94 0.000 -7367.78 -0.09
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 2508.289 -1727.67 0.000 0.000 2958.663 2458.419 14573.293 7291.425 0.000 1488.442 1165.381 0.000 -4037.30 0.000 -7660.73 -0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 4353.944 -1870.95 0.000 0.000 2970.429 2458.419 14573.293 7281.256 0.000 1779.404 2221.892 0.000 -4016.60 0.000 -9155.67 -0.19
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 3439.880 -2043.46 0.000 0.000 2956.535 2458.419 14573.293 10443.093 0.000 1779.404 2168.012 0.000 -3977.65 0.000 -9303.07 -0.02
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 3828.440 -2069.70 0.000 0.000 2956.927 2458.419 14573.293 10433.333 0.000 1779.401 2206.894 0.000 -4116.01 0.000 -9267.67 -0.13
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 3158.045 -1559.15 0.000 0.000 2958.764 2458.419 14573.293 1406.621 0.000 1716.509 3087.982 0.000 -1776.83 0.000 -8860.55 -0.04
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 2245.557 -1736.16 0.000 0.000 2943.628 2458.419 14573.293 4587.961 0.000 1716.508 2993.884 0.000 -1658.13 0.000 -9013.26 -0.25
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 4761.280 -1892.40 0.000 0.000 2966.864 2458.419 14573.293 7365.991 0.000 1779.401 2245.664 0.000 -4268.22 0.000 -9158.70 -0.33
HEATEDBSMT 0.000 0.000 3195.439 -1272.49 0.000 0.000 0.000 10557.914 48750.612 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -47223.84
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 26380.017 188587.447 0.000 0.000 0.000 -214967.46 -0.05
Total Facility 0.000 0.000 55271.997 -32133.39 0.000 0.000 53205.674 54809.448 311069.882 125005.039 0.000 56358.174 214541.045 0.000 -59182.72 0.000 -369950.48 -55270.75


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 15-JUN-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 536.40 2763.36 5580.65 0.00 2055.66 0.00 0.00 0.00 0.00 0.00 -186.8
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 722.08 2673.33 513.75 0.00 1932.88 935.21 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.7 0.00 0.00 426.77 722.08 2673.33 1242.03 0.00 2023.83 1075.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15-JUN-17:24 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 536.40 2763.36 6017.83 0.00 2055.65 0.00 0.00 0.00 0.00 0.00 -452.8
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 722.08 2673.33 870.86 0.00 1932.88 751.10 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.7 0.00 0.00 426.77 722.08 2673.33 1597.12 0.00 2023.83 891.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 15-JUN-17:24 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 536.40 2763.36 5556.65 0.00 1594.83 568.99 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 05-JUN-18:00 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 722.08 2673.33 384.34 0.00 1414.31 1630.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 02-JUL-18:13 0.00 0.00 0.00 -0.7 0.00 0.00 426.75 722.08 2705.30 1239.45 0.00 1466.48 1875.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15-JUN-17:30 0.00 0.00 0.00 -1.0 0.00 0.00 263.17 536.40 2763.36 5882.40 0.00 1558.76 438.55 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 722.08 2673.33 871.03 0.00 1502.99 1218.16 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.7 0.00 0.00 426.77 722.08 2673.33 1596.23 0.00 1593.81 1562.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 02-JUL-18:16 0.00 0.00 0.00 -0.9 0.00 0.00 426.75 722.08 2705.30 1493.63 0.00 1841.58 3063.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 02-JUL-18:13 0.00 0.00 0.00 -0.8 0.00 0.00 426.75 722.08 2705.30 1214.19 0.00 1841.58 3224.09 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 05-JUN-17:15 0.00 0.00 0.00 -1.1 0.00 0.00 263.17 536.40 2763.36 5298.97 0.00 2232.94 1703.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 14-JUN-18:15 0.00 0.00 0.00 -0.8 0.00 0.00 426.77 722.08 2673.33 860.07 0.00 1927.90 2445.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUL-18:13 0.00 0.00 0.00 -0.7 0.00 0.00 426.75 722.08 2705.30 496.36 0.00 1761.45 2785.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 15-JUN-17:34 0.00 0.00 0.00 -1.1 0.00 0.00 263.17 536.40 2763.36 5848.55 0.00 1988.10 1610.20 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 06-AUG-19:10 0.00 0.00 0.00 -0.7 0.00 0.00 0.00 3436.63 7958.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -3310.0
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 14-JUN-18:15 0.00 0.00 0.00 -14.6 0.00 0.00 7681.78 16098.38 55830.48 32024.02 0.00 33272.50 54588.14 0.00 0.00 0.00 -24192.9 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5589.52 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2241.7 0.00 -4582.7 -1113.4
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 27-DEC-04:00 0.00 0.00 4123.65 0.00 0.00 0.00 526.24 165.05 1040.85 0.00 0.00 0.00 0.00 0.00 -832.7 0.00 -4078.3 -944.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5635.93 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2232.1 0.00 -4582.7 -1169.4
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5707.30 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2233.0 0.00 -4582.7 -1239.9
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 4216.24 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -902.4 0.00 -4405.6 -1256.5
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5765.47 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2223.1 0.00 -4582.7 -1307.9
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 4923.50 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -2129.6 0.00 -3587.3 -1702.7
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 3362.63 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -866.5 0.00 -3416.2 -1576.0
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27-DEC-06:00 0.00 0.00 4922.37 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2131.4 0.00 -3596.9 -1542.4
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 4956.72 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -2128.4 0.00 -3587.3 -1737.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 27-DEC-08:15 0.00 0.00 3432.34 0.00 0.00 0.00 215.03 151.29 1628.02 0.00 0.00 0.00 0.00 0.00 -673.3 0.00 -3288.6 -1464.8
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 03-FEB-06:00 0.00 0.00 5021.11 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2237.0 0.00 -3752.1 -1380.3
LIVING_UNIT3_BACKROW_TOPFLOOR 03-FEB-06:00 0.00 0.00 6968.78 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2219.4 0.00 -4589.7 -2508.1
LIVING_UNIT3_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 6810.92 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -2112.4 0.00 -4396.1 -2798.5
LIVING_UNIT1_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 6797.25 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -2111.4 0.00 -4396.1 -2785.9
LIVING_UNIT2_BACKROW_TOPFLOOR 03-FEB-06:00 0.00 0.00 5259.81 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -901.5 0.00 -4412.3 -2294.4
LIVING_UNIT2_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 5202.16 0.00 0.00 0.00 464.72 343.85 1687.52 0.00 0.00 0.00 0.00 0.00 -857.7 0.00 -4224.8 -2615.7
LIVING_UNIT1_BACKROW_TOPFLOOR 03-FEB-06:00 0.00 0.00 6863.93 0.00 0.00 0.00 526.24 385.11 1436.97 0.00 0.00 0.00 0.00 0.00 -2227.0 0.00 -4589.7 -2395.6
HEATEDBSMT 02-FEB-04:00 0.00 0.00 4691.47 0.00 0.00 0.00 0.00 708.81 4317.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -9718.0
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-DEC-04:04 0.00 0.00 97701.07 0.00 0.00 0.00 9472.36 3679.63 23052.93 0.00 0.00 6482.08 0.00 0.00 -29508.9 0.00 -70920.7 -39958.5



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.4645 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 474.4645 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.4761 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 318.4761 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.5529 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 367.5529 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.7077 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 469.7077 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.9834 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 317.9834 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.8811 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 365.8811 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.4953 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 496.4953 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.1870 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 332.1870 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.0324 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 389.0324 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.9790 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 491.9790 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.8753 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 330.8753 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.6700 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 386.6700 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.2102 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 567.2102 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.7917 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 402.7917 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.5372 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 459.5372 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.3037 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 570.3037 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.1360 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 407.1360 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.8190 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 463.8190 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNITHEATEDBSMT 381.2687 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 381.2687 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.4645 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 474.4645 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.4761 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 318.4761 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.5529 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 367.5529 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.7077 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 469.7077 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.9834 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 317.9834 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.8811 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 365.8811 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.4953 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 496.4953 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.1870 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 332.1870 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.0324 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 389.0324 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.9790 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 491.9790 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.8753 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 330.8753 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.6700 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 386.6700 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.2102 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 567.2102 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.7917 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 402.7917 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.5372 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 459.5372 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.3037 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 570.3037 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.1360 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 407.1360 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.8190 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 463.8190 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNITHEATEDBSMT 381.2687 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 381.2687 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.0000 0.000000 7794.39 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.3864 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 474.4645 474.4645 474.4645 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 318.4761 318.4761 318.4761 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 367.5529 367.5529 367.5529 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 469.7077 469.7077 469.7077 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 317.9834 317.9834 317.9834 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 365.8811 365.8811 365.8811 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.4953 496.4953 496.4953 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 332.1870 332.1870 332.1870 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 389.0324 389.0324 389.0324 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 491.9790 491.9790 491.9790 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 330.8753 330.8753 330.8753 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 386.6700 386.6700 386.6700 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 463.8190 463.8190 463.8190 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 459.5372 459.5372 459.5372 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 567.2102 567.2102 567.2102 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 407.1360 407.1360 407.1360 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 402.7917 402.7917 402.7917 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 570.3037 570.3037 570.3037 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 381.2687 381.2687 381.2687 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.4645 474.4645 474.4645 474.4645 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.4761 318.4761 318.4761 318.4761 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.5529 367.5529 367.5529 367.5529 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.7077 469.7077 469.7077 469.7077 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.9834 317.9834 317.9834 317.9834 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.8811 365.8811 365.8811 365.8811 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.4953 496.4953 496.4953 496.4953 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.1870 332.1870 332.1870 332.1870 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.0324 389.0324 389.0324 389.0324 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.9790 491.9790 491.9790 491.9790 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.8753 330.8753 330.8753 330.8753 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.6700 386.6700 386.6700 386.6700 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.2102 567.2102 567.2102 567.2102 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.7917 402.7917 402.7917 402.7917 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.5372 459.5372 459.5372 459.5372 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.3037 570.3037 570.3037 570.3037 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.1360 407.1360 407.1360 407.1360 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.8190 463.8190 463.8190 463.8190 0.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 381.2687 381.2687 381.2687 381.2687 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 474.4645 474.4645 474.4645 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 318.4761 318.4761 318.4761 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 367.5529 367.5529 367.5529 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 469.7077 469.7077 469.7077 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 317.9834 317.9834 317.9834 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 365.8811 365.8811 365.8811 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.4953 496.4953 496.4953 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 332.1870 332.1870 332.1870 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 389.0324 389.0324 389.0324 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 491.9790 491.9790 491.9790 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 330.8753 330.8753 330.8753 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 386.6700 386.6700 386.6700 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 463.8190 463.8190 463.8190 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 459.5372 459.5372 459.5372 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 567.2102 567.2102 567.2102 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 407.1360 407.1360 407.1360 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 402.7917 402.7917 402.7917 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 570.3037 570.3037 570.3037 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 381.2687 381.2687 381.2687 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 474.4645 474.4645 474.4645 474.4645 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 318.4761 318.4761 318.4761 318.4761 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 367.5529 367.5529 367.5529 367.5529 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 469.7077 469.7077 469.7077 469.7077 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 317.9834 317.9834 317.9834 317.9834 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 365.8811 365.8811 365.8811 365.8811 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 496.4953 496.4953 496.4953 496.4953 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 332.1870 332.1870 332.1870 332.1870 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 389.0324 389.0324 389.0324 389.0324 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 491.9790 491.9790 491.9790 491.9790 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 330.8753 330.8753 330.8753 330.8753 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 386.6700 386.6700 386.6700 386.6700 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 567.2102 567.2102 567.2102 567.2102 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 402.7917 402.7917 402.7917 402.7917 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 459.5372 459.5372 459.5372 459.5372 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 570.3037 570.3037 570.3037 570.3037 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 407.1360 407.1360 407.1360 407.1360 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 463.8190 463.8190 463.8190 463.8190 0.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 381.2687 381.2687 381.2687 381.2687 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Sec1.1A-General Information

Data
Weather File ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [ft2] 39005.22
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 29404.35 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 652.12 115281.12 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 30433.54 14603.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 16052.36 5228.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_dryer 1138.84 291.20 792.69 20254.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_range 0.00 0.00 674.43 27685.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_mels 44924.98 7591.70 184.30 3112.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 35164.90 5942.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 7133.15 814.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 6714.58 2501.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 2390.85 170932.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 334377.15 560984.95
Natural Gas 165141.93 469438.54
Additional 0.00 0.00
Total 499519.07 1030423.49


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.41
Space Heating 0.00
Space Cooling 0.78
Fans (All) 0.36
Service Water Heating 0.00
Receptacle Equipment 2.51
Miscellaneous (All) 4.21
Subtotal 4.21


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.49
Service Water Heating 1.80
Miscellaneous (All) 3.52
Subtotal 3.52


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 5.32
Space Heating 6.33
Space Cooling 10.08
Fans (All) 4.59
Service Water Heating 23.20
Receptacle Equipment 48.48
Miscellaneous 2.00


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:40:24

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 165.528 3.589 394.611 17.913 17.913
February 205.139 5.805 285.142 15.862 15.862
March 296.500 9.423 254.867 16.527 16.527
April 494.880 21.658 62.667 22.927 22.927
May 693.467 37.251 0.333 37.251 37.251
June 720.000 49.518 0.000 49.518 49.518
July 744.000 55.265 0.000 55.265 55.265
August 744.000 49.470 0.000 49.470 49.470
September 689.284 41.648 0.000 41.648 41.648
October 536.567 26.575 19.972 26.736 26.736
November 270.861 9.294 261.000 17.162 17.162
December 147.028 2.796 400.167 20.433 20.433
           
Annual Sum or Average 5707.253 312.291 1678.758 370.711 370.711
Minimum of Months 147.028 2.796 0.000 15.862 15.862
Maximum of Months 744.000 55.265 400.167 55.265 55.265



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 186.889 2.658 333.972 9.673 9.673
February 222.078 4.617 225.328 9.482 9.482
March 308.736 6.660 190.528 9.838 9.838
April 523.962 16.498 38.975 16.975 16.975
May 722.500 29.631 0.000 29.631 29.631
June 720.000 39.545 0.000 39.545 39.545
July 744.000 45.234 0.000 45.234 45.234
August 744.000 40.914 0.000 40.914 40.914
September 703.042 34.886 0.000 34.886 34.886
October 607.089 22.884 1.833 22.890 22.890
November 306.167 7.703 203.358 11.282 11.282
December 164.333 2.120 343.403 11.149 11.149
           
Annual Sum or Average 5952.796 253.352 1337.397 281.499 281.499
Minimum of Months 164.333 2.120 0.000 9.482 9.482
Maximum of Months 744.000 45.234 343.403 45.234 45.234



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 162.931 2.221 367.306 12.541 12.541
February 215.411 4.950 252.889 11.843 11.843
March 321.218 8.072 209.967 12.860 12.860
April 539.853 20.944 43.333 21.668 21.668
May 704.889 36.633 0.000 36.633 36.633
June 720.000 48.605 0.000 48.605 48.605
July 744.000 54.221 0.000 54.221 54.221
August 744.000 48.563 0.000 48.563 48.563
September 693.472 40.711 0.333 40.711 40.711
October 559.931 25.189 18.917 25.312 25.312
November 291.161 8.055 240.653 13.733 13.733
December 140.542 1.707 377.117 14.571 14.571
           
Annual Sum or Average 5837.408 299.872 1510.514 341.261 341.261
Minimum of Months 140.542 1.707 0.000 11.843 11.843
Maximum of Months 744.000 54.221 377.117 54.221 54.221



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 52.333 0.413 498.472 18.345 18.345
February 122.444 2.435 351.000 14.732 14.732
March 243.056 5.973 291.639 14.040 14.040
April 480.536 19.084 67.143 20.400 20.400
May 695.389 36.674 0.000 36.674 36.674
June 720.000 49.782 0.000 49.782 49.782
July 744.000 55.130 0.000 55.130 55.130
August 744.000 47.722 0.000 47.722 47.722
September 687.529 37.130 0.000 37.130 37.130
October 507.344 20.247 22.250 20.436 20.436
November 185.931 3.747 318.917 13.302 13.302
December 21.583 0.103 517.472 22.237 22.237
           
Annual Sum or Average 5204.146 278.441 2066.893 349.928 349.928
Minimum of Months 21.583 0.103 0.000 13.302 13.302
Maximum of Months 744.000 55.130 517.472 55.130 55.130



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 23.306 0.146 486.833 10.073 10.073
February 118.722 1.461 319.639 8.185 8.185
March 230.583 3.389 241.681 7.345 7.345
April 506.103 13.919 42.467 14.421 14.421
May 723.417 29.027 0.000 29.027 29.027
June 720.000 39.752 0.000 39.752 39.752
July 744.000 45.033 0.000 45.033 45.033
August 744.000 39.103 0.000 39.103 39.103
September 701.467 30.261 0.000 30.261 30.261
October 580.103 16.245 2.500 16.255 16.255
November 178.833 2.143 270.436 6.921 6.921
December 9.000 0.034 515.994 12.751 12.751
           
Annual Sum or Average 5279.534 220.513 1879.550 259.128 259.128
Minimum of Months 9.000 0.034 0.000 6.921 6.921
Maximum of Months 744.000 45.033 515.994 45.033 45.033



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 15.583 0.090 528.778 13.328 13.328
February 122.333 1.658 341.628 10.149 10.149
March 262.463 4.407 240.147 9.769 9.769
April 527.075 18.342 44.167 19.073 19.073
May 705.639 36.172 0.000 36.172 36.172
June 720.000 48.954 0.000 48.954 48.954
July 744.000 54.185 0.000 54.185 54.185
August 744.000 47.000 0.000 47.000 47.000
September 692.625 36.470 1.000 36.471 36.471
October 545.519 18.855 20.167 18.995 18.995
November 174.222 2.383 290.778 8.985 8.985
December 2.250 0.003 554.514 16.732 16.732
           
Annual Sum or Average 5255.710 268.520 2021.178 319.814 319.814
Minimum of Months 2.250 0.003 0.000 8.985 8.985
Maximum of Months 744.000 54.185 554.514 54.185 54.185



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 224.639 5.834 322.264 16.123 16.123
February 273.681 8.577 212.706 15.411 15.411
March 359.564 13.183 167.431 17.322 17.322
April 573.006 27.845 31.833 28.387 28.387
May 726.339 42.360 0.000 42.360 42.360
June 720.000 54.184 0.000 54.184 54.184
July 744.000 59.876 0.000 59.876 59.876
August 744.000 54.159 0.000 54.159 54.159
September 698.982 46.249 0.000 46.249 46.249
October 596.883 30.313 9.667 30.377 30.377
November 326.814 12.351 204.819 17.859 17.859
December 203.250 4.729 340.097 18.452 18.452
           
Annual Sum or Average 6191.158 359.659 1288.817 400.758 400.758
Minimum of Months 203.250 4.729 0.000 15.411 15.411
Maximum of Months 744.000 59.876 340.097 59.876 59.876



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 273.556 5.402 223.861 9.112 9.112
February 316.594 7.784 124.806 10.221 10.221
March 408.297 10.630 78.047 11.840 11.840
April 624.894 22.741 9.833 22.832 22.832
May 737.444 34.111 0.000 34.111 34.111
June 720.000 43.204 0.000 43.204 43.204
July 744.000 48.894 0.000 48.894 48.894
August 744.000 44.756 0.000 44.756 44.756
September 712.556 38.925 0.000 38.925 38.925
October 673.819 26.926 0.000 26.926 26.926
November 383.856 11.249 123.811 12.979 12.979
December 251.889 4.540 259.056 10.237 10.237
           
Annual Sum or Average 6590.906 299.160 819.414 314.036 314.036
Minimum of Months 251.889 4.540 0.000 9.112 9.112
Maximum of Months 744.000 48.894 259.056 48.894 48.894



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 239.778 4.578 289.696 11.962 11.962
February 299.226 8.011 177.681 12.596 12.596
March 401.737 12.326 131.722 15.083 15.083
April 606.947 27.711 19.667 28.004 28.004
May 730.833 41.759 0.000 41.759 41.759
June 720.000 53.213 0.000 53.213 53.213
July 744.000 58.725 0.000 58.725 58.725
August 744.000 53.155 0.000 53.155 53.155
September 702.542 45.238 0.000 45.238 45.238
October 612.944 28.898 9.333 28.949 28.949
November 347.714 11.356 187.917 15.327 15.327
December 208.375 3.658 314.458 13.706 13.706
           
Annual Sum or Average 6358.096 348.629 1130.474 377.718 377.718
Minimum of Months 208.375 3.658 0.000 11.962 11.962
Maximum of Months 744.000 58.725 314.458 58.725 58.725



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 95.917 0.906 429.750 14.978 14.978
February 170.611 3.646 271.639 12.784 12.784
March 304.722 8.750 204.642 13.750 13.750
April 562.804 24.906 34.542 25.478 25.478
May 727.411 41.769 0.000 41.769 41.769
June 720.000 54.468 0.000 54.468 54.468
July 744.000 59.722 0.000 59.722 59.722
August 744.000 52.270 0.000 52.270 52.270
September 697.195 41.335 0.000 41.335 41.335
October 564.944 23.145 12.111 23.235 23.235
November 242.056 5.305 263.611 12.565 12.565
December 58.667 0.390 457.917 19.046 19.046
           
Annual Sum or Average 5632.327 316.613 1674.211 371.401 371.401
Minimum of Months 58.667 0.390 0.000 12.565 12.565
Maximum of Months 744.000 59.722 457.917 59.722 59.722



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 61.833 0.455 368.472 6.877 6.877
February 180.167 2.746 204.722 6.780 6.780
March 325.556 6.030 120.211 7.762 7.762
April 612.689 19.693 11.583 19.793 19.793
May 738.194 33.469 0.000 33.469 33.469
June 720.000 43.423 0.000 43.423 43.423
July 744.000 48.678 0.000 48.678 48.678
August 744.000 42.803 0.000 42.803 42.803
September 711.800 33.896 0.000 33.896 33.896
October 653.725 19.433 0.000 19.433 19.433
November 247.389 3.748 194.025 6.558 6.558
December 37.111 0.234 423.639 9.591 9.591
           
Annual Sum or Average 5776.464 254.608 1322.652 279.063 279.063
Minimum of Months 37.111 0.234 0.000 6.558 6.558
Maximum of Months 744.000 48.678 423.639 48.678 48.678



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 35.778 0.280 436.917 10.563 10.563
February 174.628 3.024 244.089 9.056 9.056
March 347.310 7.626 156.500 10.874 10.874
April 603.086 24.826 19.917 25.124 25.124
May 731.056 41.225 0.000 41.225 41.225
June 720.000 53.504 0.000 53.504 53.504
July 744.000 58.593 0.000 58.593 58.593
August 744.000 51.395 0.000 51.395 51.395
September 701.681 40.588 0.000 40.588 40.588
October 598.669 21.825 10.500 21.891 21.891
November 234.333 3.985 227.583 8.971 8.971
December 21.083 0.089 489.583 14.175 14.175
           
Annual Sum or Average 5655.624 306.960 1585.089 345.960 345.960
Minimum of Months 21.083 0.089 0.000 8.971 8.971
Maximum of Months 744.000 58.593 489.583 58.593 58.593



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 168.000 4.114 397.167 21.369 21.369
February 216.583 7.102 275.389 18.702 18.702
March 309.806 11.945 237.306 19.742 19.742
April 528.558 28.882 53.161 30.137 30.137
May 702.936 45.468 1.000 45.471 45.471
June 720.000 60.579 0.000 60.579 60.579
July 744.000 66.663 0.000 66.663 66.663
August 744.000 59.274 0.000 59.274 59.274
September 687.525 48.947 1.639 48.954 48.954
October 525.372 29.768 29.622 30.158 30.158
November 273.528 10.748 271.444 20.675 20.675
December 148.750 3.011 411.306 24.825 24.825
           
Annual Sum or Average 5769.058 376.501 1678.033 446.551 446.551
Minimum of Months 148.750 3.011 0.000 18.702 18.702
Maximum of Months 744.000 66.663 411.306 66.663 66.663



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 190.778 3.354 334.417 12.076 12.076
February 238.972 6.136 217.306 11.863 11.863
March 330.039 9.284 173.664 12.772 12.772
April 570.881 23.704 33.000 24.157 24.157
May 728.756 37.400 0.000 37.400 37.400
June 720.000 49.858 0.000 49.858 49.858
July 744.000 55.989 0.000 55.989 55.989
August 744.000 50.197 0.000 50.197 50.197
September 700.147 41.877 0.000 41.877 41.877
October 589.969 26.087 9.833 26.138 26.138
November 311.731 9.340 213.000 14.100 14.100
December 165.000 2.540 356.528 14.302 14.302
           
Annual Sum or Average 6034.272 315.766 1337.747 350.731 350.731
Minimum of Months 165.000 2.540 0.000 11.863 11.863
Maximum of Months 744.000 55.989 356.528 55.989 55.989



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 159.333 2.758 377.431 15.733 15.733
February 226.489 6.390 245.428 14.589 14.589
March 335.361 10.787 188.139 16.090 16.090
April 570.067 28.633 34.042 29.328 29.328
May 715.708 45.191 0.167 45.191 45.191
June 720.000 60.022 0.000 60.022 60.022
July 744.000 65.991 0.000 65.991 65.991
August 744.000 58.753 0.000 58.753 58.753
September 693.392 48.366 1.417 48.372 48.372
October 551.644 28.409 27.667 28.708 28.708
November 290.317 9.570 250.233 17.010 17.010
December 134.333 1.993 397.722 18.666 18.666
           
Annual Sum or Average 5884.644 366.862 1522.244 418.453 418.453
Minimum of Months 134.333 1.993 0.000 14.589 14.589
Maximum of Months 744.000 65.991 397.722 65.991 65.991



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 65.556 0.743 494.028 22.828 22.828
February 142.167 3.743 330.806 18.208 18.208
March 273.139 9.065 263.792 17.997 17.997
April 518.799 27.133 55.856 28.453 28.453
May 704.633 45.220 0.500 45.221 45.221
June 720.000 60.928 0.000 60.928 60.928
July 744.000 66.801 0.000 66.801 66.801
August 744.000 58.320 0.000 58.320 58.320
September 685.153 45.948 2.000 45.956 45.956
October 492.711 24.412 34.850 24.878 24.878
November 206.806 5.311 325.861 17.647 17.647
December 36.083 0.200 520.111 28.131 28.131
           
Annual Sum or Average 5333.046 347.824 2027.803 435.370 435.370
Minimum of Months 36.083 0.200 0.000 17.647 17.647
Maximum of Months 744.000 66.801 520.111 66.801 66.801



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 34.778 0.328 477.083 13.192 13.192
February 146.278 2.749 297.983 10.921 10.921
March 278.681 6.324 214.444 10.732 10.732
April 559.522 21.837 35.167 22.328 22.328
May 729.967 37.041 0.000 37.041 37.041
June 720.000 50.066 0.000 50.066 50.066
July 744.000 55.994 0.000 55.994 55.994
August 744.000 49.114 0.000 49.114 49.114
September 698.233 38.732 0.000 38.732 38.732
October 555.736 20.342 12.811 20.417 20.417
November 204.500 3.664 277.653 10.230 10.230
December 18.583 0.077 516.944 17.173 17.173
           
Annual Sum or Average 5434.278 286.266 1832.086 335.939 335.939
Minimum of Months 18.583 0.077 0.000 10.230 10.230
Maximum of Months 744.000 55.994 516.944 55.994 55.994



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 24.667 0.237 527.306 17.478 17.478
February 143.058 3.032 320.367 13.432 13.432
March 295.058 7.697 214.917 13.711 13.711
April 565.611 26.866 35.222 27.577 27.577
May 716.556 44.985 0.000 44.985 44.985
June 720.000 60.393 0.000 60.393 60.393
July 744.000 66.148 0.000 66.148 66.148
August 744.000 57.876 0.000 57.876 57.876
September 692.861 45.519 1.417 45.526 45.526
October 535.697 22.908 30.000 23.244 23.244
November 199.417 3.947 304.944 12.949 12.949
December 7.583 0.025 553.972 22.201 22.201
           
Annual Sum or Average 5388.508 339.635 1988.144 405.522 405.522
Minimum of Months 7.583 0.025 0.000 12.949 12.949
Maximum of Months 744.000 66.148 553.972 66.148 66.148



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 440.000 17.421 17.421
February 0.000 0.000 349.306 12.305 12.305
March 2.139 0.013 321.622 8.955 8.955
April 82.486 2.469 60.358 3.579 3.579
May 704.500 30.239 0.000 30.239 30.239
June 720.000 44.730 0.000 44.730 44.730
July 744.000 48.040 0.000 48.040 48.040
August 744.000 47.768 0.000 47.768 47.768
September 720.000 43.291 0.000 43.291 43.291
October 715.444 34.413 0.000 34.413 34.413
November 94.389 3.410 108.356 4.911 4.911
December 0.000 0.000 417.889 15.083 15.083
           
Annual Sum or Average 4526.958 254.372 1697.531 310.734 310.734
Minimum of Months 0.000 0.000 0.000 3.579 3.579
Maximum of Months 744.000 48.040 440.000 48.040 48.040



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1016.87 0.00 0.00
February 790.47 0.00 0.00
March 504.32 0.00 0.00
April 93.09 0.00 0.00
May 0.04 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 11.38 0.00 0.00
November 577.19 0.00 0.00
December 1252.14 0.00 0.00
       
Annual Sum or Average 352.24 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1252.14 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 619.19 0.00 0.00
February 475.38 0.00 0.00
March 280.54 0.00 0.00
April 43.50 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.52 0.00 0.00
November 326.46 0.00 0.00
December 797.04 0.00 0.00
       
Annual Sum or Average 211.03 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 797.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 945.70 0.00 0.00
February 699.37 0.00 0.00
March 438.76 0.00 0.00
April 68.53 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.01 0.00 0.00
October 11.32 0.00 0.00
November 537.66 0.00 0.00
December 1178.81 0.00 0.00
       
Annual Sum or Average 322.14 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1178.81 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1286.35 0.00 0.00
February 976.68 0.00 0.00
March 578.68 0.00 0.00
April 97.53 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 13.51 0.00 0.00
November 708.28 0.00 0.00
December 1587.81 0.00 0.00
       
Annual Sum or Average 435.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1587.81 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 877.75 0.00 0.00
February 658.21 0.00 0.00
March 349.80 0.00 0.00
April 45.87 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.87 0.00 0.00
November 436.60 0.00 0.00
December 1124.38 0.00 0.00
       
Annual Sum or Average 289.98 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1124.38 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1218.43 0.00 0.00
February 865.27 0.00 0.00
March 493.54 0.00 0.00
April 69.49 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.05 0.00 0.00
October 12.89 0.00 0.00
November 627.87 0.00 0.00
December 1539.75 0.00 0.00
       
Annual Sum or Average 400.97 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1539.75 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 655.46 0.00 0.00
February 482.04 0.00 0.00
March 263.68 0.00 0.00
April 35.67 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 4.08 0.00 0.00
November 362.62 0.00 0.00
December 874.25 0.00 0.00
       
Annual Sum or Average 222.38 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 874.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 285.82 0.00 0.00
February 207.82 0.00 0.00
March 93.21 0.00 0.00
April 7.27 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 137.70 0.00 0.00
December 438.89 0.00 0.00
       
Annual Sum or Average 97.32 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 438.89 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 600.49 0.00 0.00
February 412.82 0.00 0.00
March 224.25 0.00 0.00
April 24.60 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 4.15 0.00 0.00
November 333.66 0.00 0.00
December 817.19 0.00 0.00
       
Annual Sum or Average 200.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 817.19 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 905.09 0.00 0.00
February 650.67 0.00 0.00
March 321.51 0.00 0.00
April 38.04 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 5.76 0.00 0.00
November 482.50 0.00 0.00
December 1199.86 0.00 0.00
       
Annual Sum or Average 299.27 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1199.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 496.70 0.00 0.00
February 345.39 0.00 0.00
March 133.96 0.00 0.00
April 8.04 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 224.53 0.00 0.00
December 723.68 0.00 0.00
       
Annual Sum or Average 160.64 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 723.68 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 841.10 0.00 0.00
February 546.25 0.00 0.00
March 265.75 0.00 0.00
April 25.19 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 5.40 0.00 0.00
November 421.48 0.00 0.00
December 1152.23 0.00 0.00
       
Annual Sum or Average 270.94 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1152.23 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1187.53 0.00 0.00
February 883.87 0.00 0.00
March 536.65 0.00 0.00
April 89.29 0.00 0.00
May 0.18 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.47 0.00 0.00
October 26.86 0.00 0.00
November 705.93 0.00 0.00
December 1501.31 0.00 0.00
       
Annual Sum or Average 409.44 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1501.31 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 712.40 0.00 0.00
February 517.86 0.00 0.00
March 284.92 0.00 0.00
April 38.25 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 4.12 0.00 0.00
November 401.79 0.00 0.00
December 960.72 0.00 0.00
       
Annual Sum or Average 242.54 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 960.72 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1102.49 0.00 0.00
February 771.31 0.00 0.00
March 450.64 0.00 0.00
April 61.03 0.00 0.00
May 0.01 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.57 0.00 0.00
October 25.45 0.00 0.00
November 653.19 0.00 0.00
December 1416.66 0.00 0.00
       
Annual Sum or Average 372.31 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1416.66 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1511.98 0.00 0.00
February 1096.42 0.00 0.00
March 611.51 0.00 0.00
April 93.45 0.00 0.00
May 0.08 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.57 0.00 0.00
October 31.90 0.00 0.00
November 872.72 0.00 0.00
December 1912.25 0.00 0.00
       
Annual Sum or Average 509.04 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1912.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1039.52 0.00 0.00
February 731.14 0.00 0.00
March 356.23 0.00 0.00
April 40.99 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 6.03 0.00 0.00
November 548.26 0.00 0.00
December 1381.51 0.00 0.00
       
Annual Sum or Average 340.91 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1381.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1451.24 0.00 0.00
February 969.16 0.00 0.00
March 506.17 0.00 0.00
April 61.84 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.65 0.00 0.00
October 28.29 0.00 0.00
November 782.96 0.00 0.00
December 1866.57 0.00 0.00
       
Annual Sum or Average 471.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1866.57 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1246.71 0.00 0.00
February 974.91 0.00 0.00
March 639.90 0.00 0.00
April 82.04 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 111.01 0.00 0.00
December 1079.40 0.00 0.00
       
Annual Sum or Average 342.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1246.71 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.06
March 0.00 0.00 0.08
April 0.00 0.00 0.19
May 0.00 0.00 0.32
June 0.00 0.00 0.43
July 0.00 0.00 0.49
August 0.00 0.00 0.43
September 0.00 0.00 0.38
October 0.00 0.00 0.24
November 0.00 0.00 0.08
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.06
April 0.00 0.00 0.15
May 0.00 0.00 0.26
June 0.00 0.00 0.36
July 0.00 0.00 0.41
August 0.00 0.00 0.37
September 0.00 0.00 0.33
October 0.00 0.00 0.21
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.19
May 0.00 0.00 0.32
June 0.00 0.00 0.44
July 0.00 0.00 0.50
August 0.00 0.00 0.44
September 0.00 0.00 0.39
October 0.00 0.00 0.23
November 0.00 0.00 0.07
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.50



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.05
April 0.00 0.00 0.17
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.49
August 0.00 0.00 0.41
September 0.00 0.00 0.34
October 0.00 0.00 0.18
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.12
May 0.00 0.00 0.25
June 0.00 0.00 0.36
July 0.00 0.00 0.41
August 0.00 0.00 0.35
September 0.00 0.00 0.28
October 0.00 0.00 0.15
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.41



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.16
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.49
August 0.00 0.00 0.42
September 0.00 0.00 0.34
October 0.00 0.00 0.17
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.08
March 0.00 0.00 0.11
April 0.00 0.00 0.24
May 0.00 0.00 0.36
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.47
September 0.00 0.00 0.42
October 0.00 0.00 0.27
November 0.00 0.00 0.11
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.05
February 0.00 0.00 0.08
March 0.00 0.00 0.09
April 0.00 0.00 0.20
May 0.00 0.00 0.29
June 0.00 0.00 0.38
July 0.00 0.00 0.44
August 0.00 0.00 0.40
September 0.00 0.00 0.36
October 0.00 0.00 0.24
November 0.00 0.00 0.10
December 0.00 0.00 0.04
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.08
March 0.00 0.00 0.11
April 0.00 0.00 0.25
May 0.00 0.00 0.37
June 0.00 0.00 0.48
July 0.00 0.00 0.53
August 0.00 0.00 0.48
September 0.00 0.00 0.43
October 0.00 0.00 0.26
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.26
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.07
April 0.00 0.00 0.22
May 0.00 0.00 0.35
June 0.00 0.00 0.47
July 0.00 0.00 0.52
August 0.00 0.00 0.45
September 0.00 0.00 0.37
October 0.00 0.00 0.20
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.52



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.17
May 0.00 0.00 0.29
June 0.00 0.00 0.39
July 0.00 0.00 0.44
August 0.00 0.00 0.38
September 0.00 0.00 0.31
October 0.00 0.00 0.17
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.19
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.03
March 0.00 0.00 0.07
April 0.00 0.00 0.22
May 0.00 0.00 0.36
June 0.00 0.00 0.48
July 0.00 0.00 0.53
August 0.00 0.00 0.46
September 0.00 0.00 0.38
October 0.00 0.00 0.19
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.53



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.04
February 0.00 0.00 0.07
March 0.00 0.00 0.10
April 0.00 0.00 0.25
May 0.00 0.00 0.38
June 0.00 0.00 0.52
July 0.00 0.00 0.57
August 0.00 0.00 0.51
September 0.00 0.00 0.44
October 0.00 0.00 0.26
November 0.00 0.00 0.10
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.57



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.06
March 0.00 0.00 0.08
April 0.00 0.00 0.21
May 0.00 0.00 0.31
June 0.00 0.00 0.43
July 0.00 0.00 0.49
August 0.00 0.00 0.43
September 0.00 0.00 0.38
October 0.00 0.00 0.23
November 0.00 0.00 0.08
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.23
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.06
March 0.00 0.00 0.09
April 0.00 0.00 0.25
May 0.00 0.00 0.38
June 0.00 0.00 0.53
July 0.00 0.00 0.58
August 0.00 0.00 0.51
September 0.00 0.00 0.44
October 0.00 0.00 0.25
November 0.00 0.00 0.09
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.27
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.03
March 0.00 0.00 0.08
April 0.00 0.00 0.23
May 0.00 0.00 0.38
June 0.00 0.00 0.52
July 0.00 0.00 0.58
August 0.00 0.00 0.50
September 0.00 0.00 0.41
October 0.00 0.00 0.21
November 0.00 0.00 0.05
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.03
March 0.00 0.00 0.05
April 0.00 0.00 0.19
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.49
August 0.00 0.00 0.43
September 0.00 0.00 0.35
October 0.00 0.00 0.18
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.03
March 0.00 0.00 0.06
April 0.00 0.00 0.23
May 0.00 0.00 0.38
June 0.00 0.00 0.53
July 0.00 0.00 0.58
August 0.00 0.00 0.50
September 0.00 0.00 0.41
October 0.00 0.00 0.20
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.25
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.58



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.25
June 0.00 0.00 0.37
July 0.00 0.00 0.39
August 0.00 0.00 0.39
September 0.00 0.00 0.37
October 0.00 0.00 0.29
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1405.96 1046.77
February 0.00 0.00 1401.01 942.15
March 0.00 0.00 1351.52 1006.24
April 0.00 0.00 1261.56 908.97
May 0.00 0.00 1156.89 861.33
June 0.00 0.00 1070.84 771.55
July 0.00 0.00 1024.72 762.94
August 0.00 0.00 1022.90 761.58
September 0.00 0.00 1074.15 773.94
October 0.00 0.00 1160.39 863.94
November 0.00 0.00 1270.38 915.33
December 0.00 0.00 1360.17 1012.68
         
Annual Sum or Average 0.00 0.00 1212.32 10627.41
Minimum of Months 0.00 0.00 1022.90 761.58
Maximum of Months 0.00 0.00 1405.96 1046.77



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.00 1045.32
February 0.00 0.00 1400.75 941.97
March 0.00 0.00 1349.49 1004.73
April 0.00 0.00 1258.28 906.60
May 0.00 0.00 1156.85 861.31
June 0.00 0.00 1072.51 772.76
July 0.00 0.00 1024.67 762.89
August 0.00 0.00 1022.85 761.54
September 0.00 0.00 1072.51 772.76
October 0.00 0.00 1160.19 863.79
November 0.00 0.00 1266.89 912.80
December 0.00 0.00 1358.35 1011.33
         
Annual Sum or Average 0.00 0.00 1211.22 10617.81
Minimum of Months 0.00 0.00 1022.85 761.54
Maximum of Months 0.00 0.00 1404.00 1045.32



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.16 1045.43
February 0.00 0.00 1400.83 942.03
March 0.00 0.00 1349.58 1004.80
April 0.00 0.00 1259.69 907.62
May 0.00 0.00 1156.86 861.32
June 0.00 0.00 1072.42 772.69
July 0.00 0.00 1024.51 762.77
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1073.69 773.60
October 0.00 0.00 1160.89 864.31
November 0.00 0.00 1267.08 912.95
December 0.00 0.00 1359.94 1012.52
         
Annual Sum or Average 0.00 0.00 1211.65 10621.61
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1404.16 1045.43



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1410.93 1050.48
February 0.00 0.00 1404.76 944.67
March 0.00 0.00 1354.70 1008.62
April 0.00 0.00 1261.68 909.06
May 0.00 0.00 1155.26 860.12
June 0.00 0.00 1072.46 772.72
July 0.00 0.00 1024.44 762.73
August 0.00 0.00 1022.92 761.59
September 0.00 0.00 1074.25 774.01
October 0.00 0.00 1161.95 865.10
November 0.00 0.00 1272.31 916.71
December 0.00 0.00 1365.19 1016.42
         
Annual Sum or Average 0.00 0.00 1214.00 10642.21
Minimum of Months 0.00 0.00 1022.92 761.59
Maximum of Months 0.00 0.00 1410.93 1050.48



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1411.01 1050.53
February 0.00 0.00 1406.75 946.00
March 0.00 0.00 1351.40 1006.15
April 0.00 0.00 1261.49 908.92
May 0.00 0.00 1155.24 860.10
June 0.00 0.00 1072.38 772.66
July 0.00 0.00 1024.44 762.72
August 0.00 0.00 1022.96 761.62
September 0.00 0.00 1074.25 774.01
October 0.00 0.00 1158.72 862.70
November 0.00 0.00 1272.22 916.65
December 0.00 0.00 1365.38 1016.56
         
Annual Sum or Average 0.00 0.00 1213.60 10638.63
Minimum of Months 0.00 0.00 1022.96 761.62
Maximum of Months 0.00 0.00 1411.01 1050.53



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1412.98 1052.01
February 0.00 0.00 1406.45 945.81
March 0.00 0.00 1351.19 1006.00
April 0.00 0.00 1260.03 907.86
May 0.00 0.00 1155.18 860.07
June 0.00 0.00 1072.47 772.73
July 0.00 0.00 1024.60 762.84
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1074.19 773.96
October 0.00 0.00 1160.27 863.86
November 0.00 0.00 1272.27 916.69
December 0.00 0.00 1368.69 1019.03
         
Annual Sum or Average 0.00 0.00 1214.03 10642.41
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1412.98 1052.01



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1402.36 1044.10
February 0.00 0.00 1398.93 940.75
March 0.00 0.00 1347.99 1003.61
April 0.00 0.00 1258.22 906.56
May 0.00 0.00 1156.76 861.24
June 0.00 0.00 1072.51 772.75
July 0.00 0.00 1024.66 762.89
August 0.00 0.00 1022.86 761.55
September 0.00 0.00 1072.52 772.76
October 0.00 0.00 1160.36 863.92
November 0.00 0.00 1266.88 912.80
December 0.00 0.00 1356.60 1010.03
         
Annual Sum or Average 0.00 0.00 1210.67 10612.96
Minimum of Months 0.00 0.00 1022.86 761.55
Maximum of Months 0.00 0.00 1402.36 1044.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1399.08 1041.65
February 0.00 0.00 1397.00 939.45
March 0.00 0.00 1344.56 1001.06
April 0.00 0.00 1256.43 905.27
May 0.00 0.00 1156.82 861.29
June 0.00 0.00 1070.82 771.54
July 0.00 0.00 1024.71 762.93
August 0.00 0.00 1022.88 761.56
September 0.00 0.00 1074.22 773.99
October 0.00 0.00 1156.89 861.34
November 0.00 0.00 1265.11 911.53
December 0.00 0.00 1353.27 1007.54
         
Annual Sum or Average 0.00 0.00 1209.09 10599.15
Minimum of Months 0.00 0.00 1022.88 761.56
Maximum of Months 0.00 0.00 1399.08 1041.65



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1402.42 1044.14
February 0.00 0.00 1397.09 939.51
March 0.00 0.00 1346.27 1002.33
April 0.00 0.00 1256.36 905.22
May 0.00 0.00 1156.71 861.20
June 0.00 0.00 1072.43 772.70
July 0.00 0.00 1023.18 761.79
August 0.00 0.00 1024.52 762.79
September 0.00 0.00 1072.43 772.70
October 0.00 0.00 1160.16 863.77
November 0.00 0.00 1265.20 911.59
December 0.00 0.00 1356.68 1010.08
         
Annual Sum or Average 0.00 0.00 1210.08 10607.82
Minimum of Months 0.00 0.00 1023.18 761.79
Maximum of Months 0.00 0.00 1402.42 1044.14



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1407.51 1047.93
February 0.00 0.00 1402.89 943.41
March 0.00 0.00 1351.11 1005.94
April 0.00 0.00 1258.11 906.48
May 0.00 0.00 1155.24 860.11
June 0.00 0.00 1072.50 772.75
July 0.00 0.00 1024.63 762.86
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1074.20 773.97
October 0.00 0.00 1160.22 863.81
November 0.00 0.00 1268.83 914.21
December 0.00 0.00 1365.04 1016.31
         
Annual Sum or Average 0.00 0.00 1212.54 10629.35
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1407.51 1047.93



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1407.61 1048.01
February 0.00 0.00 1401.09 942.20
March 0.00 0.00 1348.05 1003.66
April 0.00 0.00 1258.17 906.52
May 0.00 0.00 1155.21 860.08
June 0.00 0.00 1072.42 772.69
July 0.00 0.00 1024.51 762.77
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1072.72 772.90
October 0.00 0.00 1158.59 862.60
November 0.00 0.00 1268.74 914.14
December 0.00 0.00 1363.45 1015.13
         
Annual Sum or Average 0.00 0.00 1211.73 10622.29
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1407.61 1048.01



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1411.02 1050.54
February 0.00 0.00 1401.12 942.22
March 0.00 0.00 1347.86 1003.52
April 0.00 0.00 1257.95 906.36
May 0.00 0.00 1155.24 860.11
June 0.00 0.00 1072.47 772.73
July 0.00 0.00 1024.57 762.82
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1074.21 773.98
October 0.00 0.00 1158.57 862.59
November 0.00 0.00 1270.31 915.28
December 0.00 0.00 1365.21 1016.44
         
Annual Sum or Average 0.00 0.00 1212.40 10628.16
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1411.02 1050.54



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1405.96 1046.78
February 0.00 0.00 1401.00 942.14
March 0.00 0.00 1351.16 1005.98
April 0.00 0.00 1259.97 907.82
May 0.00 0.00 1155.85 860.56
June 0.00 0.00 1071.87 772.29
July 0.00 0.00 1024.63 762.87
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1074.18 773.96
October 0.00 0.00 1161.98 865.13
November 0.00 0.00 1268.80 914.19
December 0.00 0.00 1360.05 1012.60
         
Annual Sum or Average 0.00 0.00 1212.14 10625.87
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1405.96 1046.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1404.00 1045.32
February 0.00 0.00 1398.91 940.73
March 0.00 0.00 1349.68 1004.88
April 0.00 0.00 1258.20 906.55
May 0.00 0.00 1155.29 860.15
June 0.00 0.00 1072.39 772.67
July 0.00 0.00 1024.53 762.79
August 0.00 0.00 1022.87 761.56
September 0.00 0.00 1074.22 773.99
October 0.00 0.00 1158.61 862.62
November 0.00 0.00 1268.60 914.04
December 0.00 0.00 1358.37 1011.34
         
Annual Sum or Average 0.00 0.00 1211.09 10616.63
Minimum of Months 0.00 0.00 1022.87 761.56
Maximum of Months 0.00 0.00 1404.00 1045.32



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1405.85 1046.69
February 0.00 0.00 1400.80 942.01
March 0.00 0.00 1347.89 1003.54
April 0.00 0.00 1259.51 907.49
May 0.00 0.00 1155.55 860.34
June 0.00 0.00 1072.42 772.69
July 0.00 0.00 1024.51 762.77
August 0.00 0.00 1022.89 761.57
September 0.00 0.00 1073.84 773.72
October 0.00 0.00 1160.83 864.27
November 0.00 0.00 1268.54 913.99
December 0.00 0.00 1360.02 1012.57
         
Annual Sum or Average 0.00 0.00 1211.66 10621.66
Minimum of Months 0.00 0.00 1022.89 761.57
Maximum of Months 0.00 0.00 1405.85 1046.69



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1409.31 1049.27
February 0.00 0.00 1406.34 945.73
March 0.00 0.00 1351.36 1006.13
April 0.00 0.00 1259.95 907.80
May 0.00 0.00 1156.77 861.25
June 0.00 0.00 1072.49 772.74
July 0.00 0.00 1024.66 762.89
August 0.00 0.00 1022.86 761.55
September 0.00 0.00 1072.51 772.76
October 0.00 0.00 1163.64 866.36
November 0.00 0.00 1272.28 916.69
December 0.00 0.00 1365.29 1016.49
         
Annual Sum or Average 0.00 0.00 1213.71 10639.66
Minimum of Months 0.00 0.00 1022.86 761.55
Maximum of Months 0.00 0.00 1409.31 1049.27



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1411.02 1050.54
February 0.00 0.00 1404.84 944.72
March 0.00 0.00 1349.95 1005.07
April 0.00 0.00 1258.16 906.52
May 0.00 0.00 1156.75 861.23
June 0.00 0.00 1072.51 772.75
July 0.00 0.00 1024.66 762.89
August 0.00 0.00 1022.86 761.55
September 0.00 0.00 1072.53 772.77
October 0.00 0.00 1160.40 863.95
November 0.00 0.00 1271.19 915.91
December 0.00 0.00 1366.25 1017.21
         
Annual Sum or Average 0.00 0.00 1213.19 10635.11
Minimum of Months 0.00 0.00 1022.86 761.55
Maximum of Months 0.00 0.00 1411.02 1050.54



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1412.75 1051.83
February 0.00 0.00 1404.85 944.73
March 0.00 0.00 1349.91 1005.04
April 0.00 0.00 1258.16 906.52
May 0.00 0.00 1156.86 861.32
June 0.00 0.00 1072.49 772.74
July 0.00 0.00 1024.64 762.88
August 0.00 0.00 1022.83 761.53
September 0.00 0.00 1072.51 772.75
October 0.00 0.00 1162.04 865.17
November 0.00 0.00 1272.21 916.64
December 0.00 0.00 1367.13 1017.87
         
Annual Sum or Average 0.00 0.00 1213.64 10639.02
Minimum of Months 0.00 0.00 1022.83 761.53
Maximum of Months 0.00 0.00 1412.75 1051.83



Table of Contents

Report: HEATING AND COOLING LOADS

For: HEATEDBSMT

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 987.70
February 0.00 697.62
March 0.03 506.96
April 5.52 62.90
May 142.24 0.00
June 223.86 0.00
July 243.82 0.00
August 244.67 0.00
September 224.99 0.00
October 177.95 0.00
November 9.42 85.11
December 0.00 855.15
     
Annual Sum or Average 1272.50 3195.44
Minimum of Months 0.00 0.00
Maximum of Months 244.67 987.70



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.35 805.99
February 35.68 565.91
March 57.65 399.74
April 129.46 71.41
May 216.72 0.03
June 280.21 0.00
July 281.47 0.00
August 263.73 0.00
September 225.33 0.00
October 151.58 9.02
November 57.05 442.74
December 17.37 992.48
     
Annual Sum or Average 1738.61 3287.31
Minimum of Months 17.37 0.00
Maximum of Months 281.47 992.48



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 16.65 484.96
February 28.71 336.29
March 41.02 219.72
April 99.66 32.97
May 174.34 0.00
June 226.97 0.00
July 231.67 0.00
August 220.06 0.00
September 189.82 0.00
October 131.74 0.41
November 47.84 247.44
December 13.26 624.25
     
Annual Sum or Average 1421.75 1946.04
Minimum of Months 13.26 0.00
Maximum of Months 231.67 624.25



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 13.81 739.34
February 30.68 493.85
March 49.70 343.02
April 127.36 51.85
May 218.32 0.00
June 283.48 0.00
July 284.80 0.00
August 266.27 0.00
September 225.25 0.01
October 145.96 8.85
November 49.90 406.78
December 10.59 921.58
     
Annual Sum or Average 1706.12 2965.27
Minimum of Months 10.59 0.00
Maximum of Months 284.80 921.58



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.47 1018.95
February 14.56 698.78
March 35.89 458.38
April 112.93 74.76
May 212.51 0.00
June 281.31 0.00
July 279.99 0.00
August 252.21 0.00
September 196.52 0.00
October 111.72 10.70
November 22.13 542.95
December 0.61 1257.74
     
Annual Sum or Average 1522.84 4062.27
Minimum of Months 0.61 0.00
Maximum of Months 281.31 1257.74



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.89 687.41
February 8.88 465.59
March 20.54 273.95
April 83.25 34.77
May 170.38 0.00
June 228.33 0.00
July 230.36 0.00
August 208.39 0.00
September 160.05 0.00
October 89.53 0.68
November 12.76 330.89
December 0.21 880.56
     
Annual Sum or Average 1213.57 2673.84
Minimum of Months 0.21 0.00
Maximum of Months 230.36 880.56



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.53 952.35
February 9.90 610.86
March 26.37 385.76
April 109.77 52.57
May 213.98 0.00
June 284.30 0.00
July 282.96 0.00
August 254.44 0.00
September 195.91 0.04
October 104.36 10.07
November 14.02 474.93
December 0.02 1203.51
     
Annual Sum or Average 1496.57 3690.09
Minimum of Months 0.02 0.00
Maximum of Months 284.30 1203.51



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 36.41 523.14
February 52.85 347.50
March 80.91 210.45
April 166.74 27.55
May 245.98 0.00
June 305.78 0.00
July 307.68 0.00
August 289.74 0.00
September 251.06 0.00
October 172.68 3.26
November 75.90 280.09
December 29.46 697.77
     
Annual Sum or Average 2015.19 2089.74
Minimum of Months 29.46 0.00
Maximum of Months 307.68 697.77



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 34.05 225.47
February 48.62 148.07
March 65.85 73.53
April 137.77 5.55
May 200.17 0.00
June 246.76 0.00
July 252.38 0.00
August 241.39 0.00
September 212.56 0.00
October 154.82 0.00
November 70.10 105.12
December 28.65 346.22
     
Annual Sum or Average 1693.11 903.97
Minimum of Months 28.65 0.00
Maximum of Months 252.38 346.22



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 28.73 472.30
February 50.07 293.27
March 76.64 176.38
April 169.75 18.72
May 249.09 0.00
June 310.03 0.00
July 311.79 0.00
August 293.11 0.00
September 251.76 0.00
October 167.64 3.27
November 70.84 253.96
December 22.94 642.73
     
Annual Sum or Average 2002.39 1860.62
Minimum of Months 22.94 0.00
Maximum of Months 311.79 642.73



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 5.43 721.92
February 21.87 468.76
March 52.75 256.45
April 147.69 29.37
May 241.70 0.00
June 307.11 0.00
July 306.27 0.00
August 277.44 0.00
September 219.73 0.00
October 127.61 4.59
November 31.35 372.44
December 2.34 957.03
     
Annual Sum or Average 1741.29 2810.55
Minimum of Months 2.34 0.00
Maximum of Months 307.11 957.03



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.77 391.74
February 16.73 246.04
March 36.76 105.65
April 118.18 6.14
May 196.09 0.00
June 248.37 0.00
July 251.13 0.00
August 228.88 0.00
September 180.15 0.00
October 107.07 0.00
November 22.37 171.37
December 1.44 570.75
     
Annual Sum or Average 1409.93 1491.69
Minimum of Months 1.44 0.00
Maximum of Months 251.13 570.75



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 1.69 661.33
February 18.25 387.94
March 46.19 208.96
April 149.99 19.17
May 244.61 0.00
June 311.05 0.00
July 310.00 0.00
August 280.48 0.00
September 219.95 0.00
October 121.28 4.25
November 23.63 320.71
December 0.54 905.96
     
Annual Sum or Average 1727.66 2508.31
Minimum of Months 0.54 0.00
Maximum of Months 311.05 905.96



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 1.40 1139.36
February 17.91 687.25
March 45.55 397.39
April 158.53 46.98
May 260.17 0.00
June 343.31 0.00
July 342.39 0.00
August 310.06 0.00
September 243.16 0.49
October 125.38 22.21
November 22.94 594.87
December 0.15 1465.43
     
Annual Sum or Average 1870.94 4353.98
Minimum of Months 0.15 0.00
Maximum of Months 343.31 1465.43



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 16.69 865.14
February 38.51 546.68
March 64.67 353.62
April 170.06 46.34
May 262.00 0.01
June 341.58 0.00
July 342.15 0.00
August 316.40 0.00
September 262.01 0.43
October 159.84 19.97
November 57.53 496.04
December 12.01 1111.67
     
Annual Sum or Average 2043.46 3439.91
Minimum of Months 12.01 0.00
Maximum of Months 342.15 1111.67



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 25.01 943.07
February 42.67 633.99
March 71.57 426.18
April 169.75 68.63
May 259.82 0.14
June 337.90 0.00
July 338.56 0.00
August 313.38 0.00
September 261.98 0.36
October 166.39 21.33
November 64.45 542.53
December 18.22 1192.25
     
Annual Sum or Average 2069.70 3828.47
Minimum of Months 18.22 0.00
Maximum of Months 338.56 1192.25



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 1.96 817.87
February 16.40 519.58
March 37.69 280.27
April 128.55 31.21
May 212.49 0.00
June 281.39 0.00
July 284.24 0.00
August 259.23 0.00
September 204.34 0.00
October 110.92 4.74
November 21.47 417.45
December 0.46 1086.95
     
Annual Sum or Average 1559.14 3158.07
Minimum of Months 0.46 0.00
Maximum of Months 284.24 1086.95



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 20.41 560.19
February 37.00 367.80
March 55.60 224.04
April 139.69 29.11
May 214.13 0.00
June 279.41 0.00
July 283.71 0.00
August 265.49 0.00
September 223.41 0.00
October 145.75 3.24
November 56.16 305.75
December 15.40 755.45
     
Annual Sum or Average 1736.16 2245.58
Minimum of Months 15.40 0.00
Maximum of Months 283.71 755.45



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:40:24

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 4.40 1201.12
February 22.11 786.71
March 53.82 485.79
April 158.81 71.84
May 258.04 0.06
June 339.73 0.00
July 338.99 0.00
August 307.22 0.00
September 243.43 0.44
October 133.67 25.34
November 31.01 670.93
December 1.17 1519.10
     
Annual Sum or Average 1892.40 4761.32
Minimum of Months 1.17 0.00