Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:00

Tabular Output Report in Format: HTML

Building: US+MF+CZ3B+elecres+slab+IECC_2015

Environment: ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700

Simulation Timestamp: 2024-06-27 17:00:54


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 670701.10 21.49 31.04
Net Site Energy 670701.10 21.49 31.04
Total Source Energy 2124110.38 68.06 98.29
Net Source Energy 2124110.38 68.06 98.29


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 31210.83
Net Conditioned Building Area 21609.96
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 59555.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 75083.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 34465.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 135237.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 670701.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 59555.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 75083.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 17160.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 135237.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 59555.27 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 75083.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 34465.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 135237.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 14.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 31.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 9.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00
Other 9.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 21.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 10.00


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 670701.100 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 670701.100 100.00
     
Total On-Site and Utility Electric Sources 670701.100 100.00
Total Electricity End Uses 670701.100 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 390.67


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:00
RunPeriod ANNUAL
Weather File El Paso International Ap Ut TX USA TMY3 WMO#=722700
Latitude [deg] 31.77
Longitude [deg] -106.5
Elevation [ft] 3891.27
Time Zone -7.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Above Ground Wall Area [ft2] 16177.97 6115.58 1973.41 6115.58 1973.41
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94
Above Ground Window-Wall Ratio [%] 13.15 8.69 26.94 8.69 26.94


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
Total 31210.83     267088.19   16177.97 0.00 2126.74 2126.74 0.4615 866.97 2.0143
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6665 600.28 2.9092
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
Total 31210.83             0.4615 866.97 2.0143  
Conditioned Total 21609.96             0.6665 600.28 2.9092  
Unconditioned Total 9600.87             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 31210.83 21609.96 9600.87 0.00 0.4615 866.97 2.0143
Total 31210.83 21609.96 9600.87 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 05-JAN-08:30 - - - - - - - - - - - 01-JAN-09:00
Heating 61.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 2.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 168.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 272.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 61.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 2.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 1.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 1.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 3.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 16.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 3.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 168.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 188611.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 237790.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 140144.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 109153.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 428296.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 2124110.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 8.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 11.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 98.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 6.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 7.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 30.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 13.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 68.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 386.11
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 229.28
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 290.60
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 380.24
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 228.76
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 276.78
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 426.95
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 259.67
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 324.76
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 421.20
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 258.13
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 313.64
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 388.12
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 384.76
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 494.60
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 331.12
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 327.11
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 496.96
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.11 386.11 386.11 386.11 386.11 386.11 1.00 1.00 386.11
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.28 229.28 229.28 229.28 229.28 229.28 1.00 1.00 229.28
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.60 290.60 290.60 290.60 290.60 290.60 1.00 1.00 290.60
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.24 380.24 380.24 380.24 380.24 380.24 1.00 1.00 380.24
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.76 228.76 228.76 228.76 228.76 228.76 1.00 1.00 228.76
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.78 276.78 276.78 276.78 276.78 276.78 1.00 1.00 276.78
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.95 426.95 426.95 426.95 426.95 426.95 1.00 1.00 426.95
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.67 259.67 259.67 259.67 259.67 259.67 1.00 1.00 259.67
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.76 324.76 324.76 324.76 324.76 324.76 1.00 1.00 324.76
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.20 421.20 421.20 421.20 421.20 421.20 1.00 1.00 421.20
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.13 258.13 258.13 258.13 258.13 258.13 1.00 1.00 258.13
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.64 313.64 313.64 313.64 313.64 313.64 1.00 1.00 313.64
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.60 494.60 494.60 494.60 494.60 494.60 1.00 1.00 494.60
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.11 327.11 327.11 327.11 327.11 327.11 1.00 1.00 327.11
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.76 384.76 384.76 384.76 384.76 384.76 1.00 1.00 384.76
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.96 496.96 496.96 496.96 496.96 496.96 1.00 1.00 496.96
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.12 331.12 331.12 331.12 331.12 331.12 1.00 1.00 331.12
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.12 388.12 388.12 388.12 388.12 388.12 1.00 1.00 388.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 386.11 1.08 0.758794
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 229.28 0.666122 0.746139
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 290.60 0.876873 0.732680
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 380.24 1.07 0.758387
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 228.76 0.664819 0.746051
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 276.78 0.836507 0.732248
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 426.95 1.19 0.761968
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 259.67 0.734272 0.755851
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 324.76 0.965388 0.738765
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 421.20 1.17 0.761800
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 258.13 0.730399 0.755656
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 313.64 0.894531 0.753375
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 494.60 1.36 0.767163
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 327.11 0.905921 0.763923
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 384.76 1.08 0.759521
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 496.96 1.37 0.767268
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 331.12 0.920748 0.762732
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 388.12 1.08 0.762108
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 386.11 386.11 386.11 8531.68 1.08 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 229.28 229.28 229.28 7028.32 0.666122 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 290.60 290.60 290.60 8531.63 0.876873 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 380.24 380.24 380.24 8535.03 1.07 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 228.76 228.76 228.76 7028.95 0.664819 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 276.78 276.78 276.78 8529.49 0.836507 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 426.95 426.95 426.95 8078.29 1.19 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 259.67 259.67 259.67 6423.23 0.734272 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 324.76 324.76 324.76 8080.45 0.965388 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 421.20 421.20 421.20 8081.42 1.17 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 258.13 258.13 258.13 6423.53 0.730399 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 313.64 313.64 313.64 8077.90 0.894531 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 494.60 494.60 494.60 9925.03 1.36 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 327.11 327.11 327.11 8252.02 0.905921 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 384.76 384.76 384.76 9927.94 1.08 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 496.96 496.96 496.96 9927.47 1.37 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 331.12 331.12 331.12 8252.37 0.920748 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 388.12 388.12 388.12 9926.20 1.08 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 386.11
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 229.28
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 290.60
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 380.24
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 228.76
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 276.78
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 426.95
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 259.67
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 324.76
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 421.20
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 258.13
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 313.64
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 494.60
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 327.11
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 384.76
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 496.96
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 331.12
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 388.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 9811.43
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 8082.56
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 9811.38
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 9815.29
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 8083.30
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 9808.91
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 9290.04
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 7386.71
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 9292.52
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 9293.63
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 7387.06
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 9289.59
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 11413.79
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 9489.82
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 11417.13
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR 11416.59
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR 9490.22
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR 11415.13
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 54.59 48.72 47.12 48.51 56.43 65.30 73.65 79.68 81.45 78.62 71.78 63.16


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 El Paso International Ap Ut TX USA TMY3 WMO#=722700 31.77 -106.50 -7.00 3891.27 13. 1.0443


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 64.29 37.98 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ3B+elecres+slab+IECC_2015 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 6.1981 Rough 1.2550 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5031 Smooth 0.1189 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3300 VerySmooth 0.1230 0.114 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 20 171 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
14 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
15 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
14 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
15 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
16 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
17 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
18 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
19 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
20 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.350 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.1188 0.072 32.003 0.183 0.5031
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
20 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
21 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
22 1 -8.3915550 0.80192706 -1.1535996 0.21114735
23 0 9.2367617 0.51139848 2.4177143  
24 10 0.25332408E-17 -0.22101509E-14 0.15157692E-08 0.28211904E-17
25 9 -0.31506112E-08 -0.26974675E-14 -0.81843868E-03 0.20118786E-08
26 8 0.42861811E-03 0.11354105E-09 0.39097097E-01 -0.27370296E-03
27 7 -0.11368907E-01 0.51842634E-07 -0.64553953 0.74324363E-02
28 6 0.12484615 0.25047115E-05 5.3130581 -0.83937451E-01
29 5 -0.73775399 0.27964547E-04 -24.889648 0.51283867
30 4 2.5553417 0.92755650E-04 70.144414 -1.8477174
31 3 -5.2989438 0.96002462E-04 -120.51707 4.0111012
32 2 6.4233118 0.27752742E-04 123.06129 -5.1209931
33 1 -4.1707712 0.15163054E-05 -68.409714 3.5199891
34 0 1.1151582 0.34288690E-08 15.905180  
35 10 0.15157692E-08 -0.22101509E-14 0.25332408E-17 0.28211904E-17
36 9 -0.81843868E-03 -0.26974675E-14 -0.31506112E-08 0.20118786E-08
37 8 0.39097097E-01 0.11354105E-09 0.42861811E-03 -0.27370296E-03
38 7 -0.64553953 0.51842634E-07 -0.11368907E-01 0.74324363E-02
39 6 5.3130581 0.25047115E-05 0.12484615 -0.83937451E-01
40 5 -24.889648 0.27964547E-04 -0.73775399 0.51283867
41 4 70.144414 0.92755650E-04 2.5553417 -1.8477174
42 3 -120.51707 0.96002462E-04 -5.2989438 4.0111012
43 2 123.06129 0.27752742E-04 6.4233118 -5.1209931
44 1 -68.409714 0.15163054E-05 -4.1707712 3.5199891
45 0 15.905180 0.34288690E-08 1.1151582  
46 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
47 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
48 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
49 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
50 1 -19.904252 0.86481321 -19.904252 0.58144210
51 0 16.688993 0.62060609E-01 16.688993  
52 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
53 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
54 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
55 1 -11.299243 2.8799011 -8.6239668 0.15905732
56 0 15.219762 1.4410112 12.640375  
57 5 -0.24423608E-08 0.10315694E-08 -0.24423608E-08 0.46347327E-11
58 4 0.46481418E-04 0.19988510E-04 0.46481418E-04 -0.22728163E-06
59 3 -0.31887091E-01 0.95525843E-02 -0.31887091E-01 0.49135354E-03
60 2 1.3495466 0.25081638 1.3495466 -0.51058024E-01
61 1 -7.0688408 0.57876498 -7.0688408 0.58136590
62 0 6.6836766 0.93387740E-01 6.6836766  
63 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
64 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
65 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
66 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
67 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
68 1 -64.420211 0.46601667 -21.697519 0.64629334
69 0 46.121323 0.20873329E-01 15.867130  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.350 0.350 1.000 0.217    
2 INTERIOR WINDOW 13 1 VerySmooth 0.350 0.350 1.000 0.217    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.350 0.350 1.000 0.208    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
2 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
3 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 BREEZEWAY Mixing/Well-Stirred
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 ATTIC Mixing/Well-Stirred
15 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
16 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 7865.44899 7865.44899 386.12283 386.12283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 96.91399 0.00687 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 6541.99025 6541.99025 137.30507 137.30507 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4670.66728 4670.66728 229.27963 229.27963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 93.20900 0.00686 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 5016.38146 5016.38146 105.28643 105.28643 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 5919.71123 5919.71123 290.59318 290.59318 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 100.58000 0.00687 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 6541.94542 6541.94542 137.30401 137.30401 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 7745.73877 7745.73877 380.23300 380.23300 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 96.91399 0.00687 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 6545.39375 6545.39375 137.37647 137.37647 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4660.07316 4660.07316 228.77116 228.77116 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 93.20900 0.00686 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 5017.02783 5017.02783 105.29999 105.29999 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 5638.18806 5638.18806 276.77963 276.77963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 100.11200 0.00687 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 6539.76747 6539.76747 137.25846 137.25846 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 8697.35502 8697.35502 426.94910 426.94910 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 96.52401 0.00687 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 6081.85189 6081.85189 127.65062 127.65062 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 5289.71682 5289.71682 259.68217 259.68217 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 4402.29939 4402.29939 92.39999 92.39999 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 6615.60190 6615.60190 324.76691 324.76691 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 100.58000 0.00687 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 6084.04331 6084.04331 127.69659 127.69659 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 8580.15094 8580.15094 421.20757 421.20757 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 6085.02419 6085.02419 127.71714 127.71714 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 5258.26094 5258.26094 258.13556 258.13556 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 91.45400 0.00686 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 4402.60794 4402.60794 92.40634 92.40634 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6389.01231 6389.01231 313.64403 313.64403 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 94.96400 0.00687 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 6081.45401 6081.45401 127.64236 127.64236 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 7906.22007 7906.22007 388.11436 388.11436 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 94.96400 0.00687 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 7957.13492 7957.13492 167.00591 167.00591 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7837.90893 7837.90893 384.76690 384.76690 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 95.74399 0.00687 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 7958.90043 7958.90043 167.04299 167.04299 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 10075.27556 10075.27556 494.59740 494.59740 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 7955.94953 7955.94953 166.98091 166.98091 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 6745.18512 6745.18512 331.12284 331.12284 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 92.62400 0.00686 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 6258.53429 6258.53429 131.35676 131.35676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 6663.47461 6663.47461 327.11860 327.11860 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 92.03900 0.00686 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 6258.17937 6258.17937 131.34914 131.34914 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 10123.51724 10123.51724 496.97028 496.97028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 96.13400 0.00687 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 7958.41848 7958.41848 167.03282 167.03282 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 22.64000 0.00281 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2545.06 386.12283 386.12283 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 2500.49 137.30507 137.30507 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1575.65 229.27963 229.27963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 2059.88 105.28643 105.28643 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2027.98 290.59318 290.59318 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 2500.48 137.30401 137.30401 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2510.45 380.23300 380.23300 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 2501.47 137.37647 137.37647 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1572.58 228.77116 228.77116 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 2060.07 105.29999 105.29999 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1940.80 276.77963 276.77963 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 2499.85 137.25846 137.25846 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2780.72 426.94910 426.94910 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 2367.61 127.65062 127.65062 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1732.87 259.68217 259.68217 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1882.54 92.39999 92.39999 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2229.15 324.76691 324.76691 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 2368.25 127.69659 127.69659 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2742.01 421.20757 421.20757 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 2368.53 127.71714 127.71714 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1723.78 258.13556 258.13556 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1882.63 92.40634 92.40634 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2094.11 313.64403 313.64403 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 2367.50 127.64236 127.64236 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3174.21 494.59740 494.59740 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 2908.86 166.98091 166.98091 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 2137.24 327.11860 327.11860 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 2418.53 131.34914 131.34914 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2522.61 384.76690 384.76690 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 2909.71 167.04299 167.04299 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3188.16 496.97028 496.97028 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 2909.57 167.03282 167.03282 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 2168.10 331.12284 331.12284 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 2418.63 131.35676 131.35676 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2532.70 388.11436 388.11436 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 2909.20 167.00591 167.00591 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 386.12283
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 229.27963
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 290.59318
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 380.23300
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 228.77116
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 276.77963
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 426.94910
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 259.68217
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 324.76691
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 421.20757
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 258.13556
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 313.64403
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 388.11436
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 384.76690
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 494.59740
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 331.12284
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 327.11860
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 496.97028
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 386.12283
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 386.12283
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 386.12283
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 386.12283
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 386.12283
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 386.12283
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 229.27963
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 229.27963
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 229.27963
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 229.27963
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 229.27963
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 229.27963
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 290.59318
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 290.59318
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 290.59318
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 290.59318
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 290.59318
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 290.59318
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 380.23300
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 380.23300
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 380.23300
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 380.23300
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 380.23300
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 380.23300
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 228.77116
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 228.77116
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 228.77116
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 228.77116
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 228.77116
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 228.77116
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 276.77963
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 276.77963
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 276.77963
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 276.77963
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 276.77963
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 276.77963
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 426.94910
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 426.94910
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 426.94910
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 426.94910
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 426.94910
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 426.94910
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 259.68217
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 259.68217
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 259.68217
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 259.68217
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 259.68217
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 259.68217
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 324.76691
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 324.76691
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 324.76691
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 324.76691
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 324.76691
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 324.76691
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 421.20757
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 421.20757
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 421.20757
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 421.20757
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 421.20757
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 421.20757
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 258.13556
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 258.13556
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 258.13556
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 258.13556
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 258.13556
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 258.13556
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 313.64403
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 313.64403
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 313.64403
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 313.64403
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 313.64403
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 313.64403
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 494.59740
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 494.59740
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 494.59740
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 494.59740
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 494.59740
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 494.59740
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 327.11860
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 327.11860
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 327.11860
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 327.11860
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 327.11860
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 327.11860
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 384.76690
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 384.76690
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 384.76690
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 384.76690
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 384.76690
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 384.76690
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 496.97028
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 496.97028
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 496.97028
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 496.97028
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 496.97028
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 496.97028
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 331.12284
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 331.12284
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 331.12284
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 331.12284
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 331.12284
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 331.12284
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 388.11436
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 388.11436
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 388.11436
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 388.11436
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 388.11436
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 388.11436
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 386.12283
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 229.27963
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 290.59318
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 380.23300
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 228.77116
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 276.77963
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 426.94910
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 259.68217
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 324.76691
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 421.20757
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 258.13556
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 313.64403
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 494.59740
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 327.11860
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 384.76690
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 496.97028
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 331.12284
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 388.11436
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 386.12283
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.08451
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75879
184 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 386.12283
185 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 386.12283
186 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 386.12283
187 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 8531.67802
188 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.08451
189 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
190 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 386.12283
191 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9811.42976
192 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 229.27963
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.66612
194 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.74614
195 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 229.27963
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 229.27963
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 229.27963
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7028.31537
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.66612
200 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
201 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 229.27963
202 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8082.56267
203 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 290.59318
204 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.87687
205 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73268
206 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 290.59318
207 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 290.59318
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 290.59318
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 8531.63384
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.87687
211 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
212 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 290.59318
213 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9811.37889
214 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 380.23300
215 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.06950
216 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75839
217 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 380.23300
218 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 380.23300
219 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 380.23300
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 8535.03195
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.06950
222 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
223 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 380.23300
224 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9815.28672
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 228.77116
226 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.66482
227 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.74605
228 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 228.77116
229 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 228.77116
230 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 228.77116
231 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7028.95229
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.66482
233 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
234 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 228.77116
235 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 8083.29513
236 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 276.77963
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.83651
238 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73225
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 276.77963
240 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 276.77963
241 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 276.77963
242 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 8529.48765
243 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.83651
244 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
245 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 276.77963
246 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 9808.91082
247 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 426.94910
248 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.19032
249 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76197
250 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 426.94910
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 426.94910
252 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 426.94910
253 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8078.29307
254 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.19032
255 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
256 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 426.94910
257 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 9290.03702
258 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 259.68217
259 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.73427
260 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75585
261 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 259.68217
262 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 259.68217
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 259.68217
264 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6423.22897
265 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.73427
266 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
267 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 259.68217
268 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7386.71328
269 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 324.76691
270 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.96539
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73877
272 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 324.76691
273 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 324.76691
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 324.76691
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8080.45255
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.96539
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
278 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 324.76691
279 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 9292.52045
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 421.20757
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.17495
282 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76180
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 421.20757
284 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 421.20757
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 421.20757
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8081.41914
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.17495
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
289 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 421.20757
290 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 9293.63201
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 258.13556
292 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.73040
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75566
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 258.13556
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 258.13556
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 258.13556
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6423.53298
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.73040
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
300 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 258.13556
301 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 7387.06295
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 313.64403
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.89453
304 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75337
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 313.64403
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 313.64403
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 313.64403
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8077.90096
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.89453
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
311 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 313.64403
312 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 9289.58613
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 494.59740
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.35943
315 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76716
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 494.59740
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 494.59740
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 494.59740
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9925.03383
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.35943
321 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
322 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 494.59740
323 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 11413.78893
324 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 327.11860
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.90592
326 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76392
327 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 327.11860
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 327.11860
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 327.11860
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8252.01559
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.90592
332 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
333 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 327.11860
334 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 9489.81791
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 384.76690
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.07802
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.75952
338 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 384.76690
339 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 384.76690
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 384.76690
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9927.94175
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.07802
343 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
344 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 384.76690
345 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 11417.13303
346 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 496.97028
347 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.36546
348 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76727
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 496.97028
350 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 496.97028
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 496.97028
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9927.46680
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.36546
354 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
355 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 496.97028
356 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 11416.58684
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 331.12284
358 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.92075
359 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76273
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 331.12284
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 331.12284
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 331.12284
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8252.36536
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.92075
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
366 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 331.12284
367 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 9490.22016
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 388.11436
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.08152
370 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76211
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 388.11436
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 388.11436
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 388.11436
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9926.20197
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.08152
376 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
377 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 388.11436
378 Coil:Heating:Electric MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 11415.13227
379 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
380 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
381 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
382 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
383 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
384 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
385 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
386 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
387 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
388 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
389 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
390 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
391 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
392 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
393 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
394 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
395 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
396 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
397 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
398 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
399 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
400 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
401 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
402 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
403 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
404 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
405 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
406 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
407 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
408 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
409 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
410 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
411 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
412 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
413 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
414 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
415 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
416 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
417 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
418 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
419 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
420 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
421 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
422 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
423 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
424 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
425 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
426 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
427 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
428 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
429 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
430 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
431 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
432 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
433 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
434 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
435 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
436 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
437 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
438 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
439 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
440 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
441 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
442 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
443 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
444 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
445 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
446 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
447 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
448 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
449 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
450 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
451 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
452 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
453 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
454 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
455 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
456 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
457 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
458 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
459 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
460 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
461 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
462 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
463 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
464 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
465 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
466 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
467 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
468 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.0 3.58 12.20 12.93 12.43 12.61
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.0 3.45 11.77 12.45 12.31 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.60 12.27 13.01 12.51 12.73
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.47 11.85 12.54 12.40 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.8 3.62 12.35 13.10 12.59 12.86
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.8 3.50 11.94 12.64 12.50 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.0 3.58 12.20 12.94 12.43 12.61
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.0 3.45 11.77 12.46 12.32 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.60 12.27 13.01 12.51 12.73
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.47 11.85 12.55 12.40 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.62 12.35 13.10 12.59 12.86
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.50 11.94 12.65 12.50 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.1 3.57 12.19 12.92 12.41 12.58
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.1 3.44 11.75 12.43 12.29 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.58 12.22 12.95 12.45 12.63
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.7 3.45 11.78 12.47 12.33 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.9 3.61 12.32 13.06 12.56 12.81
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.9 3.49 11.90 12.60 12.46 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.57 12.19 12.92 12.42 12.58
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.44 11.75 12.44 12.30 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.7 3.58 12.22 12.95 12.45 12.63
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.7 3.45 11.79 12.47 12.33 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.59 12.23 12.97 12.47 12.66
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.9 3.46 11.81 12.50 12.35 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.3 3.56 12.16 12.88 12.38 12.53
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.3 3.43 11.71 12.40 12.26 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.57 12.17 12.90 12.40 12.56
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.9 3.44 11.73 12.42 12.28 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.0 3.57 12.20 12.93 12.43 12.60
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.0 3.45 11.76 12.45 12.31 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.3 3.56 12.15 12.88 12.38 12.53
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.3 3.43 11.71 12.40 12.25 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.57 12.18 12.91 12.41 12.57
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.9 3.44 11.74 12.43 12.29 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.0 3.57 12.18 12.91 12.41 12.58
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.0 3.44 11.75 12.43 12.29 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 22.64 0.00 DefaultMultipliers Wetbulb -5.20 {C} 13. 20 433.1 0.00 No No
2 100.58 13.00 DefaultMultipliers Wetbulb 18.10 {C} 13. 280 767.8 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000002888 0.000001560 Pass Pass 0.000000000 0.000000000 Pass Pass
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.013559946 0.026205389 Pass Pass
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017767744 0.034537639 Pass Pass
4 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.013560781 0.026206943 Pass Pass
5 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.013553401 0.026192227 Pass Pass
6 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.017766554 0.034538443 Pass Pass
7 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.013565976 0.026217145 Pass Pass
8 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015247123 0.027518055 Pass Pass
9 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.021412546 0.039054233 Pass Pass
10 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015241634 0.027507625 Pass Pass
11 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015239036 0.027502818 Pass Pass
12 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.021411298 0.039051635 Pass Pass
13 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015248521 0.027520486 Pass Pass
14 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000108472 0.000094861 Pass Pass 0.000000000 0.000000000 Pass Pass
15 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.011651450 0.019764449 Pass Pass
16 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.011648893 0.019760010 Pass Pass
17 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.011653474 0.019767949 Pass Pass
18 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015023057 0.025454819 Pass Pass
19 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.015024093 0.025456599 Pass Pass
20 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.011649651 0.019761349 Pass Pass
21 BREEZEWAY SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.411010356 0.246447225 Pass Pass 0.000000000 0.000000000 Pass Pass
22 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000037107 0.000237145 Pass Pass 0.078530656 0.035764667 Pass Pass
23 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000020835 0.000123113 Pass Pass 0.057742164 0.040671804 Pass Pass
24 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000032594 0.000179050 Pass Pass 0.066204400 0.060204161 Pass Pass
25 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000024686 0.000163670 Pass Pass 0.077820516 0.036465865 Pass Pass
26 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000019777 0.000120162 Pass Pass 0.056479781 0.040415524 Pass Pass
27 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000077202 0.000265278 Pass Pass 0.065516068 0.061633987 Pass Pass
28 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000027989 0.000181593 Pass Pass 0.070923919 0.029134366 Pass Pass
29 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000027377 0.000139064 Pass Pass 0.049887687 0.035366347 Pass Pass
30 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000073769 0.000280458 Pass Pass 0.059083451 0.051393054 Pass Pass
31 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000027475 0.000179338 Pass Pass 0.070236472 0.028876240 Pass Pass
32 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000025928 0.000134154 Pass Pass 0.049359586 0.033756854 Pass Pass
33 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000058787 0.000218195 Pass Pass 0.058134461 0.052628013 Pass Pass
34 ATTIC SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.599006506 0.458400459 Pass Pass 0.000000000 0.000000000 Pass Pass
35 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000041235 0.000237212 Pass Pass 0.061592149 0.049893468 Pass Pass
36 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000040591 0.000194153 Pass Pass 0.061819677 0.049266763 Pass Pass
37 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000031524 0.000204659 Pass Pass 0.073731820 0.029065562 Pass Pass
38 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000033810 0.000172645 Pass Pass 0.056674284 0.030994063 Pass Pass
39 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000033189 0.000169636 Pass Pass 0.056105114 0.033623566 Pass Pass
40 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 0.000032297 0.000207900 Pass Pass 0.073926524 0.027965169 Pass Pass
41 BREEZEWAY RunPeriod: ANNUAL 0.263519875 0.218992200 Pass Pass 0.000000000 0.000000000 Pass Pass
42 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041668616 0.074041205 Pass Pass 0.602078799 2.693374697 Pass Pass
43 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.041667808 0.070331818 Pass Pass 0.327385365 0.660947564 Pass Pass
44 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.042079960 0.066839175 Pass Pass 0.285649238 0.881352137 Pass Pass
45 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.031495697 0.061248722 Pass Pass 0.162042389 0.310657302 Pass Pass
46 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.002451470 0.010425989 Pass Pass 0.247183641 0.689234126 Pass Pass
47 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000002240 0.000006898 Pass Pass 0.213196981 0.332332239 Pass Pass
48 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041684459 0.078825287 Pass Pass 0.462077556 2.159304099 Pass Pass
49 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041687252 0.074703999 Pass Pass 0.296151638 0.775347281 Pass Pass
50 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.041685907 0.080741670 Pass Pass 0.314379900 0.743182404 Pass Pass
51 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.043739155 0.068836772 Pass Pass 0.289777118 1.180602846 Pass Pass
52 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.022643208 0.037004662 Pass Pass 0.167050050 0.348274313 Pass Pass
53 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.013953270 0.022371770 Pass Pass 0.227033612 0.504246623 Pass Pass
54 ATTIC RunPeriod: ANNUAL 0.542026661 0.467121138 Pass Pass 0.000000000 0.000000000 Pass Pass
55 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.014605321 0.025484662 Pass Pass 0.199589411 0.486957528 Pass Pass
56 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041684145 0.075327559 Pass Pass 0.362654341 1.105294117 Pass Pass
57 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041756069 0.081240421 Pass Pass 0.318127177 0.692231178 Pass Pass
58 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.023351236 0.041034668 Pass Pass 0.192515727 0.503848464 Pass Pass
59 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.041683858 0.071895739 Pass Pass 0.251680460 0.541098231 Pass Pass
60 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.043411094 0.071545006 Pass Pass 0.212307927 0.587342306 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2862108.51 300299.25 96737.28 0.00 397190.00 3656350.04



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 6548.17 1513.17 695.67 3.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 6569.50 998.17 789.50 402.83 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 6548.17 0.00 0.00 0.00 0.00
Max 8760.00 1513.17 789.50 402.83 0.00
Average 8539.88 125.57 74.26 20.29 0.00
Sum 170797.67 2511.33 1485.17 405.83 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10856.14 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7884.00 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 7356.67 1381.67 21.67 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8715.00 45.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8727.50 32.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8727.67 32.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8714.67 45.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8727.83 32.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8726.50 33.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8747.17 12.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8751.67 8.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8751.83 8.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8747.83 12.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.83 7.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8751.33 8.67 0.00 0.00 0.00
ATTIC 6698.67 1426.00 444.67 185.83 4.83
LIVING_UNIT3_BACKROW_TOPFLOOR 8744.83 15.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8744.83 15.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8737.83 22.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8748.50 11.50 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8746.50 13.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8738.33 21.67 0.00 0.00 0.00
Min 6698.67 7.17 0.00 0.00 0.00
Max 8752.83 1426.00 444.67 185.83 4.83
Average 8567.90 159.25 23.32 9.29 0.24
Sum 171358.00 3185.00 466.33 185.83 4.83


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11982.40 79.98 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12007.92 54.46 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12002.03 60.35 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11980.77 81.61 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12006.76 55.62 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11999.69 62.69 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12041.04 21.34 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12049.28 13.11 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12048.73 13.65 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12041.90 20.48 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12051.06 11.32 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12047.98 14.40 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12035.99 26.39 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12035.99 26.39 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12024.60 37.78 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12045.30 17.08 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12041.95 20.43 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12025.09 37.29 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12051.06 81.61 0.00 0.00 0.00
Average 10823.42 32.72 0.00 0.00 0.00
Sum 216468.47 654.39 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8715.00 45.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8727.50 32.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8727.67 32.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8714.67 45.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8727.83 32.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8726.50 33.50 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8747.17 12.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8751.67 8.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8751.83 8.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8747.83 12.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.83 7.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8751.33 8.67 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8744.83 15.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8744.83 15.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8737.83 22.17 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8748.50 11.50 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8746.50 13.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8738.33 21.67 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8752.83 45.33 0.00 0.00 0.00
Average 7865.13 18.87 0.00 0.00 0.00
Sum 157302.67 377.33 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7884.00 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.18 0.18 0.18 0.01 0.01 0.01
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.15 0.19 0.15 0.02 0.02 0.02
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.12 0.14 0.12 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.15 0.17 0.15 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.12 0.18 0.12 0.03 0.03 0.03
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.13 0.15 0.13 0.02 0.03 0.02
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.21 0.23 0.21 0.01 0.01 0.01
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.17 0.24 0.17 0.02 0.02 0.02
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.15 0.16 0.15 0.02 0.02 0.02
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.17 0.21 0.17 0.02 0.03 0.02
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.14 0.22 0.14 0.03 0.02 0.03
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.16 0.18 0.16 0.02 0.03 0.02
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.15 0.18 0.15 0.03 0.03 0.03
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.17 0.20 0.17 0.01 0.01 0.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.21 0.24 0.21 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_TOPFLOOR 0.15 0.22 0.15 0.03 0.03 0.03
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.17 0.25 0.17 0.02 0.02 0.02
LIVING_UNIT1_BACKROW_TOPFLOOR 0.18 0.21 0.18 0.02 0.02 0.02
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.21 0.25 0.21 0.03 0.03 0.03
Average 0.15 0.18 0.15 0.02 0.02 0.02
Sum 2.90 3.54 2.90 0.33 0.38 0.33


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 22.64 0.00 22.64 Wetbulb [F] 433.09 20.00
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 100.58 23.40 64.58 Wetbulb [F] 767.75 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.12 6      
Feb 0.12 4      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.71 7      
Jul 1.06 16      
Aug 1.61 15      
Sep 0.00 0      
Oct 0.91 18      
Nov 0.00 0      
Dec 0.28 7      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BREEZEWAYROOF INTERIOR CEILING 0.30 0.027 0.028 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.350 0.217 0.883                      
North Total or Average             531.68 0.350 0.217 0.883                      
Non-North Total or Average             1595.05 0.350 0.217 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.96 0.00 0.99 0.93 0.00 1.00 0.95 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.00 0.94 0.85 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.85 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.99


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.3333 43219.92 14404.00               12960.20


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   13014.09 9875.01 3139.08 0.76 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7993.47 5964.24 2029.23 0.75 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10522.48 7709.61 2812.87 0.73 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12833.96 9733.11 3100.85 0.76 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7977.83 5951.87 2025.96 0.75 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10038.08 7350.37 2687.71 0.73 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14283.81 10883.81 3400.01 0.76 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8811.27 6660.01 2151.26 0.76 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11584.66 8558.34 3026.32 0.74 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14099.40 10740.93 3358.48 0.76 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8764.78 6623.17 2141.62 0.76 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10734.37 8087.00 2647.37 0.75 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16313.16 12514.86 3798.30 0.77 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10871.05 8304.65 2566.41 0.76 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12936.20 9825.32 3110.88 0.76 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   16385.49 12572.06 3813.43 0.77 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11048.98 8427.41 2621.57 0.76 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   12978.30 9890.87 3087.43 0.76 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.0 3.58 12.20 12.93 12.43 12.61
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.60 12.27 13.01 12.51 12.73
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.62 12.35 13.10 12.59 12.86
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.0 3.58 12.20 12.94 12.43 12.61
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.60 12.27 13.01 12.51 12.73
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.62 12.35 13.10 12.59 12.86
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.1 3.57 12.19 12.92 12.41 12.58
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.7 3.58 12.22 12.95 12.45 12.63
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.61 12.32 13.06 12.56 12.81
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.57 12.19 12.92 12.42 12.58
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.7 3.58 12.22 12.95 12.45 12.63
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.9 3.59 12.23 12.97 12.47 12.66
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.3 3.56 12.16 12.88 12.38 12.53
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.9 3.57 12.17 12.90 12.40 12.56
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.0 3.57 12.20 12.93 12.43 12.60
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.3 3.56 12.15 12.88 12.38 12.53
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.9 3.57 12.18 12.91 12.41 12.57
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.0 3.57 12.18 12.91 12.41 12.58
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.45 11.77 12.45 12.31  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.47 11.85 12.54 12.40  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.50 11.94 12.64 12.50  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.45 11.77 12.46 12.32  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.47 11.85 12.55 12.40  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.50 11.94 12.65 12.50  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.44 11.75 12.43 12.29  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.45 11.78 12.47 12.33  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.49 11.90 12.60 12.46  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.44 11.75 12.44 12.30  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.45 11.79 12.47 12.33  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.46 11.81 12.50 12.35  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.43 11.71 12.40 12.26  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.44 11.73 12.42 12.28  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.45 11.76 12.45 12.31  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.43 11.71 12.40 12.25  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.44 11.74 12.43 12.29  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.44 11.75 12.43 12.29  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   9811.43 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   8082.56 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   9811.38 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   9815.29 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   8083.30 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   9808.91 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   9290.04 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   7386.71 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   9292.52 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   9293.63 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   7387.06 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   9289.59 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   11413.79 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   9489.82 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   11417.13 1.00
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   11416.59 1.00
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   9490.22 1.00
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   11415.13 1.00


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 386.11 145.64 0.38 1.00 2.42 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 229.28 86.48 0.38 1.00 3.24 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 290.60 109.61 0.38 1.00 2.81 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 380.24 143.42 0.38 1.00 2.44 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 228.76 86.29 0.38 1.00 3.24 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 276.78 104.40 0.38 1.00 2.89 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 426.95 161.04 0.38 1.00 2.30 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 259.67 97.95 0.38 1.00 3.00 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 324.76 122.50 0.38 1.00 2.65 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 421.20 158.87 0.38 1.00 2.32 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 258.13 97.36 0.38 1.00 3.01 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 313.64 118.30 0.38 1.00 2.70 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 494.60 186.56 0.38 1.00 2.15 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 327.11 123.38 0.38 1.00 2.63 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 384.76 145.13 0.38 1.00 2.42 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 496.96 187.45 0.38 1.00 2.15 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 331.12 124.90 0.38 1.00 2.62 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 388.12 146.40 0.38 1.00 2.41 General EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7865.45 7865.45 6.55 386.114 386.114 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 75.00 75.00 0.00759 96.91 0.00687 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4670.67 4670.67 3.89 229.284 229.284 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00779 93.21 0.00686 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5919.71 5919.71 4.93 290.597 290.597 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 75.00 75.00 0.00754 100.58 0.00687 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7745.74 7745.74 6.45 380.238 380.238 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 75.00 75.00 0.00759 96.91 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4660.07 4660.07 3.88 228.764 228.764 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00780 93.21 0.00686 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5638.19 5638.19 4.70 276.778 276.778 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 75.00 75.00 0.00755 100.11 0.00687 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8697.36 8697.36 7.24 426.954 426.954 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 75.00 75.00 0.00761 96.52 0.00687 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5289.72 5289.72 4.41 259.675 259.675 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00783 91.45 0.00686 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6615.60 6615.60 5.51 324.759 324.759 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 75.00 75.00 0.00756 100.58 0.00687 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8580.15 8580.15 7.15 421.201 421.201 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00764 96.13 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5258.26 5258.26 4.38 258.131 258.131 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00783 91.45 0.00686 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6389.01 6389.01 5.32 313.638 313.638 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00771 94.96 0.00687 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7906.22 7906.22 6.59 388.117 388.117 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00767 94.96 0.00687 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7837.91 7837.91 6.53 384.763 384.763 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 75.00 75.00 0.00765 95.74 0.00687 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10075.28 10075.28 8.39 494.596 494.596 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00761 96.13 0.00687 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6745.19 6745.19 5.62 331.124 331.124 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 75.00 75.00 0.00774 92.62 0.00686 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6663.47 6663.47 5.55 327.113 327.113 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 75.00 75.00 0.00775 92.04 0.00686 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10123.52 10123.52 8.43 496.964 496.964 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 75.00 75.00 0.00761 96.13 0.00687 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6541.99 6541.99 5.45 137.305 137.305 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5016.38 5016.38 4.18 105.286 105.286 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00622 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6541.95 6541.95 5.45 137.304 137.304 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6545.39 6545.39 5.45 137.376 137.376 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5017.03 5017.03 4.18 105.300 105.300 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00622 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6539.77 6539.77 5.45 137.258 137.258 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6081.85 6081.85 5.07 127.651 127.651 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00663 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4402.30 4402.30 3.67 92.400 92.400 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00637 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 6084.04 6084.04 5.07 127.697 127.697 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00663 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6085.02 6085.02 5.07 127.717 127.717 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00663 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4402.61 4402.61 3.67 92.406 92.406 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00637 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6081.45 6081.45 5.07 127.642 127.642 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00663 22.64 0.00281 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7957.13 7957.13 6.63 167.006 167.006 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00664 22.64 0.00281 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7958.90 7958.90 6.63 167.043 167.043 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00664 22.64 0.00281 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 7955.95 7955.95 6.63 166.981 166.981 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00664 22.64 0.00281 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 6258.53 6258.53 5.21 131.357 131.357 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 6258.18 6258.18 5.21 131.349 131.349 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00645 22.64 0.00281 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 7958.42 7958.42 6.63 167.033 167.033 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 71.99 0.00664 22.64 0.00281 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.11 386.11 137.31 137.31 386.1144 386.1144 386.1144 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.28 229.28 105.29 105.29 229.2840 229.2840 229.2840 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.60 290.60 137.30 137.30 290.5972 290.5972 290.5972 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.24 380.24 137.38 137.38 380.2379 380.2379 380.2379 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.76 228.76 105.30 105.30 228.7640 228.7640 228.7640 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.78 276.78 137.26 137.26 276.7776 276.7776 276.7776 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.95 426.95 127.65 127.65 426.9540 426.9540 426.9540 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.67 259.67 92.40 92.40 259.6748 259.6748 259.6748 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.76 324.76 127.70 127.70 324.7595 324.7595 324.7595 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.20 421.20 127.72 127.72 421.2007 421.2007 421.2007 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.13 258.13 92.41 92.41 258.1306 258.1306 258.1306 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.64 313.64 127.64 127.64 313.6378 313.6378 313.6378 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.60 494.60 166.98 166.98 494.5956 494.5956 494.5956 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.11 327.11 131.35 131.35 327.1126 327.1126 327.1126 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.76 384.76 167.04 167.04 384.7632 384.7632 384.7632 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.96 496.96 167.03 167.03 496.9638 496.9638 496.9638 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.12 331.12 131.36 131.36 331.1235 331.1235 331.1235 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.12 388.12 167.01 167.01 388.1174 388.1174 388.1174 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 13014.094 9875.014 386.114444 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 11633.09 11627.86 386.114444 78.91 58.65 0.00750331 53.60 49.11 0.00750000 96.91 0.00686822 63.59 11.6533 75.00 0.00757728 35.6645 7851.44 0.00 13019.52 9242.27
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 9811.430 9811.430 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9811.43 9811.43 -999. 66.24 51.60 0.00602334 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00644741 33.6341 6541.99 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 7993.470 5964.242 229.284029 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 7320.15 7213.28 229.284029 79.92 59.16 0.00761235 53.60 49.11 0.00750000 93.21 0.00686494 62.43 19.6241 75.00 0.00774189 36.4299 4642.54 0.00 7996.81 5590.96
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 8082.563 8082.563 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8082.56 8082.56 -999. 62.31 49.17 0.00555290 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00622298 32.4744 5016.38 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 10522.477 7709.610 290.597184 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 9235.72 9235.72 290.597184 80.31 59.04 0.00744070 53.60 49.01 0.00744070 100.58 0.00687148 64.71 15.4836 75.00 0.00754499 35.5142 5919.71 0.00 10526.87 7244.88
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 9811.379 9811.379 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9811.38 9811.38 -999. 64.35 50.61 0.00588395 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00644740 33.6341 6541.95 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 12833.959 9733.113 380.237880 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 11473.04 11468.54 380.237880 78.94 58.67 0.00750289 53.60 49.11 0.00750000 96.91 0.00686822 63.59 11.8334 75.00 0.00758808 35.7147 7745.74 0.00 12839.31 9109.54
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 9815.287 9815.287 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9815.29 9815.29 -999. 66.15 51.56 0.00601725 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00644794 33.6369 6545.39 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 7977.834 5951.874 228.763974 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 7306.01 7199.18 228.763974 79.93 59.16 0.00761255 53.60 49.11 0.00750000 93.21 0.00686494 62.43 19.6687 75.00 0.00775822 36.5058 4632.42 0.00 7981.16 5579.38
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 8083.295 8083.295 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8083.30 8083.30 -999. 62.29 49.16 0.00555149 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00622312 32.4751 5017.03 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 10038.081 7350.369 276.777572 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 8836.53 8836.53 276.777572 80.43 59.07 0.00743779 53.60 49.00 0.00743779 100.11 0.00687107 64.57 16.2567 75.00 0.00754595 35.5187 5633.14 0.00 10042.27 6907.43
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 9808.911 9808.911 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9808.91 9808.91 -999. 63.97 50.40 0.00585554 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00644706 33.6324 6539.77 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 14283.811 10883.806 426.954050 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 12791.69 12730.09 426.954050 78.62 58.60 0.00753531 53.60 49.11 0.00750000 96.52 0.00686787 63.47 10.5386 75.00 0.00759579 35.7507 8684.27 0.00 14289.77 10179.77
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 9290.037 9290.037 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9290.04 9290.04 -999. 66.79 52.17 0.00622338 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00662567 34.5529 6081.85 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 8811.271 6660.010 259.674781 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8136.21 7962.49 259.674781 79.20 58.99 0.00766199 53.60 49.11 0.00750000 91.45 0.00686340 61.87 17.3274 75.00 0.00776642 36.5439 5220.48 0.00 8814.95 6233.65
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 7386.713 7386.713 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7386.71 7386.71 -999. 63.44 50.01 0.00575632 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00637418 33.2540 4402.30 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 11584.660 8558.342 324.759479 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 10160.86 10160.86 324.759479 79.90 58.93 0.00746365 53.60 49.05 0.00746365 100.58 0.00687148 64.71 13.8549 75.00 0.00755889 35.5790 6615.60 0.00 11589.49 8034.27
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 9292.520 9292.520 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9292.52 9292.52 -999. 65.16 51.30 0.00609708 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00662601 34.5546 6084.04 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 14099.404 10740.929 421.200684 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 12655.96 12563.09 421.200684 78.61 58.63 0.00755393 53.60 49.11 0.00750000 96.13 0.00686752 63.35 10.6826 75.00 0.00761517 35.8408 8568.29 0.00 14105.29 10046.17
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 9293.632 9293.632 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9293.63 9293.63 -999. 66.72 52.13 0.00621832 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00662616 34.5554 6085.02 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 8764.784 6623.166 258.130598 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8093.68 7920.50 258.130598 79.22 59.00 0.00766244 53.60 49.11 0.00750000 91.45 0.00686340 61.87 17.4311 75.00 0.00780245 36.7115 5230.03 0.00 8768.44 6199.20
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 7387.063 7387.063 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7387.06 7387.06 -999. 63.39 49.98 0.00575268 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00637425 33.2544 4402.61 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 10734.371 8087.005 313.637804 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 9715.85 9595.80 313.637804 79.22 58.89 0.00759293 53.60 49.11 0.00750000 94.96 0.00686649 62.98 14.3462 75.00 0.00756114 35.5894 6305.31 0.00 10738.85 7574.33
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 9289.586 9289.586 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9289.59 9289.59 -999. 64.91 51.17 0.00607799 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00662561 34.5526 6081.45 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 16313.159 12514.857 494.595606 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 14630.30 14547.39 494.595606 78.27 58.49 0.00754116 53.60 49.11 0.00750000 96.13 0.00686752 63.35 9.0973 75.00 0.00758942 35.7210 10071.32 0.00 16319.97 11697.40
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 11413.789 11413.789 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11413.79 11413.79 -999. 67.50 52.56 0.00629033 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00663879 34.6222 7955.95 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 10871.054 8304.649 327.112639 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 9989.46 9819.65 327.112639 78.70 58.76 0.00762648 53.60 49.11 0.00750000 92.04 0.00686391 62.06 13.7552 75.00 0.00771962 36.3265 6624.33 0.00 10875.59 7764.68
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 9489.818 9489.818 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9489.82 9489.82 -999. 65.20 51.07 0.00595088 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00645208 33.6579 6258.18 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 12936.201 9825.316 384.763246 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 11641.66 11553.99 384.763246 78.78 58.69 0.00755564 53.60 49.11 0.00750000 95.74 0.00686719 63.23 11.6942 75.00 0.00753895 35.4861 7739.29 0.00 12941.60 9192.77
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 11417.133 11417.133 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11417.13 11417.13 -999. 66.22 51.89 0.00619117 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00663915 34.6240 7958.90 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 16385.490 12572.064 496.963810 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 14694.87 14611.62 496.963810 78.27 58.49 0.00754114 53.60 49.11 0.00750000 96.13 0.00686752 63.35 9.0540 75.00 0.00760820 35.8083 10123.52 0.00 16392.33 11750.85
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 11416.587 11416.587 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11416.59 11416.59 -999. 67.52 52.57 0.00629226 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00663909 34.6237 7958.42 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 11048.978 8427.407 331.123548 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 10121.34 9957.65 331.123548 78.75 58.77 0.00762042 53.60 49.11 0.00750000 92.62 0.00686443 62.24 13.5886 75.00 0.00771764 36.3172 6710.00 0.00 11053.59 7882.14
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 9490.220 9490.220 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9490.22 9490.22 -999. 65.29 51.11 0.00595700 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00645214 33.6582 6258.53 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 12978.297 9890.871 388.117390 -999. -999.00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 11729.15 11612.10 388.117390 78.67 58.68 0.00757366 53.60 49.11 0.00750000 94.96 0.00686649 62.98 11.5931 75.00 0.00762717 35.8965 7875.65 0.00 12983.71 9251.04
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 11415.132 11415.132 -999. -999. -999.00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 11415.13 11415.13 -999. 66.27 51.91 0.00619486 122.00 72.00 0.00800000 22.64 0.00280840 22.64 -999.000 71.99 0.00663894 34.6230 7957.13 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13014.094 9875.014 386.114444 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 386.114444 0.41959121   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 16:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 Sensible 11633.09 11627.86 0.8939 0.41959121 386.114444 78.91 58.65 0.00750331 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 496.922 11136.17 96.91 0.00686822 63.59 44.99498340 11.6533 75.00 0.00758709 75.00 0.00757728 35.6645 7851.44 0.00 13019.52 9242.27 0.40302053 80.00 67.00 0.01118466 13.2 53.88 53.86 0.00881032 8.2
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9811.430 9811.430 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 386.114444 0.41959121   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9811.43 9811.43 1.0000 -0.230003E+04 -999. 66.24 51.60 0.00602334 8.2 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9811.43 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00644741 71.99 0.00644741 33.6341 6541.99 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7993.470 5964.242 229.284029 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 229.284029 0.24916333   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 7320.15 7213.28 0.9158 0.24916333 229.284029 79.92 59.16 0.00761235 11.0 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 295.084 7025.07 93.21 0.00686494 62.43 44.99498340 19.6241 75.00 0.00779484 75.00 0.00774189 36.4299 4642.54 0.00 7996.81 5590.96 0.23932327 80.00 67.00 0.01118466 13.2 53.39 53.34 0.00863797 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8082.563 8082.563 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 229.284029 0.24916333   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8082.56 8082.56 1.0000 -0.230003E+04 -999. 62.31 49.17 0.00555290 7.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8082.56 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00622298 71.99 0.00622298 32.4744 5016.38 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10522.477 7709.610 290.597184 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 290.597184 0.31579244   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 Sensible 9235.72 9235.72 0.8777 0.31579244 290.597184 80.31 59.04 0.00744070 11.0 53.60 49.01 0.00744070 7.4 -999. -999.0 -999.0 -999.0 373.993 8861.73 100.58 0.00687148 64.71 44.99498340 15.4836 75.00 0.00754499 75.00 0.00754499 35.5142 5919.71 0.00 10526.87 7244.88 0.30332103 80.00 67.00 0.01118466 13.2 52.78 52.73 0.00844355 7.9
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9811.379 9811.379 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 290.597184 0.31579244   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9811.38 9811.38 1.0000 -0.230003E+04 -999. 64.35 50.61 0.00588395 7.9 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9811.38 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00644740 71.99 0.00644740 33.6341 6541.95 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12833.959 9733.113 380.237880 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 380.237880 0.41320514   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 Sensible 11473.04 11468.54 0.8940 0.41320514 380.237880 78.94 58.67 0.00750289 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 489.359 10983.68 96.91 0.00686822 63.59 44.99498340 11.8334 75.00 0.00758808 75.00 0.00758808 35.7147 7745.74 0.00 12839.31 9109.54 0.39688666 80.00 67.00 0.01118466 13.2 53.86 53.84 0.00880394 8.2
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9815.287 9815.287 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 380.237880 0.41320514   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9815.29 9815.29 1.0000 -0.230003E+04 -999. 66.15 51.56 0.00601725 8.2 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9815.29 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00644794 71.99 0.00644794 33.6369 6545.39 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7977.834 5951.874 228.763974 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 228.763974 0.24859819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 7306.01 7199.18 0.9158 0.24859819 228.763974 79.93 59.16 0.00761255 11.0 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 294.415 7011.59 93.21 0.00686494 62.43 44.99498340 19.6687 75.00 0.00779560 75.00 0.00775822 36.5058 4632.42 0.00 7981.16 5579.38 0.23878044 80.00 67.00 0.01118466 13.2 53.38 53.34 0.00863649 8.1
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 8083.295 8083.295 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 228.763974 0.24859819   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8083.30 8083.30 1.0000 -0.230003E+04 -999. 62.29 49.16 0.00555149 7.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 8083.30 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00622312 71.99 0.00622312 32.4751 5017.03 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10038.081 7350.369 276.777572 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 276.777572 0.30077465   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 Sensible 8836.53 8836.53 0.8803 0.30077465 276.777572 80.43 59.07 0.00743779 11.0 53.60 49.00 0.00743779 7.4 -999. -999.0 -999.0 -999.0 356.208 8480.32 100.11 0.00687107 64.57 44.99498340 16.2567 75.00 0.00754781 75.00 0.00754595 35.5187 5633.14 0.00 10042.27 6907.43 0.28889632 80.00 67.00 0.01118466 13.2 52.75 52.71 0.00843572 7.8
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9808.911 9808.911 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 276.777572 0.30077465   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9808.91 9808.91 1.0000 -0.230003E+04 -999. 63.97 50.40 0.00585554 7.8 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9808.91 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00644706 71.99 0.00644706 33.6324 6539.77 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14283.811 10883.806 426.954050 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 426.954050 0.46397168   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 Sensible 12791.69 12730.09 0.8955 0.46397168 426.954050 78.62 58.60 0.00753531 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 549.482 12242.21 96.52 0.00686787 63.47 44.99498340 10.5386 75.00 0.00761394 75.00 0.00759579 35.7507 8684.27 0.00 14289.77 10179.77 0.44564830 80.00 67.00 0.01118466 13.2 53.99 53.97 0.00884828 8.3
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9290.037 9290.037 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 426.954050 0.46397168   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9290.04 9290.04 1.0000 -0.230003E+04 -999. 66.79 52.17 0.00622338 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9290.04 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00662567 71.99 0.00662567 34.5529 6081.85 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8811.271 6660.010 259.674781 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 259.674781 0.28218902   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8136.21 7962.49 0.9234 0.28218902 259.674781 79.20 58.99 0.00766199 11.0 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 334.197 7802.01 91.45 0.00686340 61.87 44.99498340 17.3274 75.00 0.00782937 75.00 0.00776642 36.5439 5220.48 0.00 8814.95 6233.65 0.27104468 80.00 67.00 0.01118466 13.2 53.81 53.76 0.00877204 8.2
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7386.713 7386.713 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 259.674781 0.28218902   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7386.71 7386.71 1.0000 -0.230003E+04 -999. 63.44 50.01 0.00575632 7.7 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7386.71 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00637418 71.99 0.00637418 33.2540 4402.30 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11584.660 8558.342 324.759479 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 324.759479 0.35291667   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 10160.86 10160.86 0.8771 0.35291667 324.759479 79.90 58.93 0.00746365 10.9 53.60 49.05 0.00746365 7.4 -999. -999.0 -999.0 -999.0 417.959 9742.90 100.58 0.00687148 64.71 44.99498340 13.8549 75.00 0.00755889 75.00 0.00755889 35.5790 6615.60 0.00 11589.49 8034.27 0.33897913 80.00 67.00 0.01118466 13.2 52.99 52.98 0.00852769 7.9
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9292.520 9292.520 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 324.759479 0.35291667   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9292.52 9292.52 1.0000 -0.230003E+04 -999. 65.16 51.30 0.00609708 8.1 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9292.52 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00662601 71.99 0.00662601 34.5546 6084.04 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14099.404 10740.929 421.200684 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 421.200684 0.45771948   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 12655.96 12563.09 0.8976 0.45771948 421.200684 78.61 58.63 0.00755393 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 542.077 12113.88 96.13 0.00686752 63.35 44.99498340 10.6826 75.00 0.00763602 75.00 0.00761517 35.8408 8568.29 0.00 14105.29 10046.17 0.43964302 80.00 67.00 0.01118466 13.2 53.98 53.96 0.00884569 8.3
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9293.632 9293.632 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 421.200684 0.45771948   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9293.63 9293.63 1.0000 -0.230003E+04 -999. 66.72 52.13 0.00621832 8.4 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9293.63 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00662616 71.99 0.00662616 34.5554 6085.02 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8764.784 6623.166 258.130598 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 258.130598 0.28051095   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8093.68 7920.50 0.9234 0.28051095 258.130598 79.22 59.00 0.00766244 11.0 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 332.209 7761.47 91.45 0.00686340 61.87 44.99498340 17.4311 75.00 0.00783112 75.00 0.00780245 36.7115 5230.03 0.00 8768.44 6199.20 0.26943289 80.00 67.00 0.01118466 13.2 53.79 53.75 0.00876894 8.2
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7387.063 7387.063 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 258.130598 0.28051095   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7387.06 7387.06 1.0000 -0.230003E+04 -999. 63.39 49.98 0.00575268 7.7 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 7387.06 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00637425 71.99 0.00637425 33.2544 4402.61 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10734.371 8087.005 313.637804 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 313.637804 0.34083072   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 9715.85 9595.80 0.9051 0.34083072 313.637804 79.22 58.89 0.00759293 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 403.646 9312.20 94.96 0.00686649 62.98 44.99498340 14.3462 75.00 0.00771460 75.00 0.00756114 35.5894 6305.31 0.00 10738.85 7574.33 0.32737049 80.00 67.00 0.01118466 13.2 53.65 53.63 0.00873581 8.2
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9289.586 9289.586 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 313.637804 0.34083072   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9289.59 9289.59 1.0000 -0.230003E+04 -999. 64.91 51.17 0.00607799 8.1 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9289.59 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00662561 71.99 0.00662561 34.5526 6081.45 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16313.159 12514.857 494.595606 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 494.595606 0.53747787   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 14630.30 14547.39 0.8968 0.53747787 494.595606 78.27 58.49 0.00754116 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 636.535 13993.76 96.13 0.00686752 63.35 44.99498340 9.0973 75.00 0.00760858 75.00 0.00758942 35.7210 10071.32 0.00 16319.97 11697.40 0.51625155 80.00 67.00 0.01118466 13.2 54.20 54.18 0.00891629 8.3
MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 11413.789 11413.789 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 494.595606 0.53747787   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11413.79 11413.79 1.0000 -0.230003E+04 -999. 67.50 52.56 0.00629033 8.5 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11413.79 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00663879 71.99 0.00663879 34.6222 7955.95 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10871.054 8304.649 327.112639 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 327.112639 0.35547385   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 Sensible 9989.46 9819.65 0.9189 0.35547385 327.112639 78.70 58.76 0.00762648 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 420.988 9568.47 92.04 0.00686391 62.06 44.99498340 13.7552 75.00 0.00774810 75.00 0.00771962 36.3265 6624.33 0.00 10875.59 7764.68 0.34143532 80.00 67.00 0.01118466 13.2 54.10 54.07 0.00887647 8.3
MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9489.818 9489.818 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 327.112639 0.35547385   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9489.82 9489.82 1.0000 -0.230003E+04 -999. 65.20 51.07 0.00595088 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9489.82 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00645208 71.99 0.00645208 33.6579 6258.18 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12936.201 9825.316 384.763246 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 384.763246 0.41812286   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 Sensible 11641.66 11553.99 0.8999 0.41812286 384.763246 78.78 58.69 0.00755564 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 495.183 11146.48 95.74 0.00686719 63.23 44.99498340 11.6942 75.00 0.00764681 75.00 0.00753895 35.4861 7739.29 0.00 12941.60 9192.77 0.40161017 80.00 67.00 0.01118466 13.2 53.93 53.90 0.00881992 8.2
MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 11417.133 11417.133 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 384.763246 0.41812286   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11417.13 11417.13 1.0000 -0.230003E+04 -999. 66.22 51.89 0.00619117 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11417.13 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00663915 71.99 0.00663915 34.6240 7958.90 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16385.490 12572.064 496.963810 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 496.963810 0.54005140   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 Sensible 14694.87 14611.62 0.8968 0.54005140 496.963810 78.27 58.49 0.00754114 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 639.583 14055.28 96.13 0.00686752 63.35 44.99498340 9.0540 75.00 0.00760820 75.00 0.00760820 35.8083 10123.52 0.00 16392.33 11750.85 0.51872345 80.00 67.00 0.01118466 13.2 54.21 54.19 0.00891786 8.3
MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 11416.587 11416.587 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 496.963810 0.54005140   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11416.59 11416.59 1.0000 -0.230003E+04 -999. 67.52 52.57 0.00629226 8.6 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11416.59 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00663909 71.99 0.00663909 34.6237 7958.42 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11048.978 8427.407 331.123548 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 331.123548 0.35983251   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 Sensible 10121.34 9957.65 0.9160 0.35983251 331.123548 78.75 58.77 0.00762042 10.9 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 426.150 9695.19 92.62 0.00686443 62.24 44.99498340 13.5886 75.00 0.00773930 75.00 0.00771764 36.3172 6710.00 0.00 11053.59 7882.14 0.34562185 80.00 67.00 0.01118466 13.2 54.03 54.01 0.00886005 8.3
MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 9490.220 9490.220 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 331.123548 0.35983251   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9490.22 9490.22 1.0000 -0.230003E+04 -999. 65.29 51.11 0.00595700 8.0 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 9490.22 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00645214 71.99 0.00645214 33.6582 6258.53 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12978.297 9890.871 388.117390 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 388.117390 0.42176781   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:30:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 11729.15 11612.10 0.9038 0.42176781 388.117390 78.67 58.68 0.00757366 10.8 53.60 49.11 0.00750000 7.4 -999. -999.0 -999.0 -999.0 499.500 11229.65 94.96 0.00686649 62.98 44.99498340 11.5931 75.00 0.00766639 75.00 0.00762717 35.8965 7875.65 0.00 12983.71 9251.04 0.40511117 80.00 67.00 0.01118466 13.2 53.99 53.98 0.00885045 8.3
MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 11415.132 11415.132 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0652 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 388.117390 0.42176781   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 11415.13 11415.13 1.0000 -0.230003E+04 -999. 66.27 51.91 0.00619486 8.3 122.00 72.00 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 11415.13 22.64 0.00280840 22.64 44.99498340 -999.000 71.99 0.00663894 71.99 0.00663894 34.6230 7957.13 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2388.50 5148.00 318.50
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1800.67 5430.00 283.67
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2110.33 5129.50 248.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2258.33 5479.83 333.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1666.33 5741.83 300.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1986.67 5400.00 261.17
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2838.00 4167.67 172.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2310.00 4260.00 118.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2682.50 4083.67 117.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2682.00 4744.67 181.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2126.50 4811.50 129.83
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2594.67 4596.33 141.33
LIVING_UNIT3_BACKROW_TOPFLOOR 2858.33 4629.17 193.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 2956.33 4255.50 176.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 2956.83 4362.83 222.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2502.50 4836.83 183.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 2605.17 4437.67 176.67
LIVING_UNIT1_BACKROW_TOPFLOOR 2874.50 4748.17 243.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3255.83 5891.83 390.67
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.106 0.000 0.270
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.094 0.000 0.270
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.106 0.000 0.269
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.106 0.000 0.269
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.093 0.000 0.269
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.106 0.000 0.269
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.047 0.000 0.270
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.034 0.000 0.270
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.047 0.000 0.270
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.047 0.000 0.270
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.034 0.000 0.270
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.047 0.000 0.270
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.106 0.000 0.269
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.107 0.000 0.270
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.106 0.000 0.270
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.094 0.000 0.270
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.094 0.000 0.270
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.106 0.000 0.270
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.004
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 9393331.97 33234825.50 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 8279501.11 32120994.64 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 9399908.31 33241401.84 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 9366559.70 33208053.23 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 8245750.18 32087243.71 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 9367937.22 33209430.75 23785081.69 3814.50 1353.17 3640.33 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 4129023.23 27971898.09 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 3008286.24 26851161.10 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 4132532.06 27975406.91 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 4116058.96 27958933.81 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 2994006.80 26836881.65 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 4115885.19 27958760.04 23785081.69 3810.33 1354.50 3643.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 9393623.20 33237880.84 23785081.69 3805.17 1356.83 3646.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 9423133.18 33267390.82 23785081.69 3805.17 1356.83 3646.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 9416590.77 33260848.40 23785081.69 3805.17 1356.83 3646.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 8273004.11 32117261.75 23785081.69 3805.17 1356.83 3646.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 8302888.38 32147146.02 23785081.69 3805.17 1356.83 3646.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 9393578.76 33237836.40 23785081.69 3805.17 1356.83 3646.00 0.00
Total Facility 0.00 0.429172E+09 0.429172E+09 0.130752E+09 0.559923E+09 0.428131E+09 3814.50 1362.50 3646.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 17.7697 62.8714 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 15.6626 60.7643 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 17.7821 62.8838 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 17.7190 62.8207 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 15.5987 60.7004 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 17.7216 62.8233 44.9950 3814.50 1353.17 3640.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 7.8110 52.9153 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 5.6909 50.7952 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 7.8176 52.9220 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 7.7865 52.8908 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 5.6639 50.7682 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 7.7861 52.8905 44.9950 3810.33 1354.50 3643.17
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 17.7702 62.8771 44.9950 3805.17 1356.83 3646.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 17.8260 62.9330 44.9950 3805.17 1356.83 3646.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 17.8137 62.9206 44.9950 3805.17 1356.83 3646.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 15.6503 60.7572 44.9950 3805.17 1356.83 3646.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 15.7068 60.8138 44.9950 3805.17 1356.83 3646.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 17.7701 62.8771 44.9950 3805.17 1356.83 3646.00
Total Facility 0.0000 811.8776 811.8776 247.3469 1059.2245 809.9097 3814.50 1362.50 3646.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23841493.53 23841493.53 23785081.69 3814.50 1353.17 3640.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23842874.86 23842874.86 23785081.69 3810.33 1354.50 3643.17 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 23844257.64 23844257.64 23785081.69 3805.17 1356.83 3646.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 45.1017 45.1017 44.9950 3814.50 1353.17 3640.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 45.1043 45.1043 44.9950 3810.33 1354.50 3643.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 45.1069 45.1069 44.9950 3805.17 1356.83 3646.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Surfaces by Class

Total Outdoors
Wall 74 50
Floor 28 3
Roof 21 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1910
Defaulted Fields 1685
Fields with Defaults 6153
Autosized Fields 342
Autosizable Fields 504
Autocalculated Fields 149
Autocalculatable Fields 328



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
Electricity:Building 101263.28 6311.77 02-JAN-03:10 19306.63 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
Electricity:SpaceType:GENERAL 101263.28 6311.77 02-JAN-03:10 19306.63 01-JAN-18:10
InteriorLights:Electricity 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
General:InteriorLights:Electricity 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 10094.19 578.57 23-FEB-11:50 2512.78 26-JUL-18:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
ElectricityPurchased:Plant 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
Cogeneration:ElectricityPurchased 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
General:Cogeneration:ElectricityPurchased 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
ElectricityNet:Plant 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
Cogeneration:ElectricityNet 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
General:Cogeneration:ElectricityNet 196432.08 8268.04 24-APR-03:20 79849.76 05-JAN-08:20
Electricity:HVAC 49526.75 578.57 23-FEB-11:50 26887.92 27-DEC-07:10
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-00:10 578.57 01-JAN-00:10
General:Fans:Electricity 5025.90 0.00 23-FEB-11:50 1934.21 26-JUL-18:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 17442.29 0.00 02-JAN-16:10 24971.40 27-DEC-07:10
General:Heating:Electricity 17442.29 0.00 02-JAN-16:10 24971.40 27-DEC-07:10
Cooling:Electricity 21990.27 0.00 01-JAN-00:10 11430.64 05-JUN-17:10
General:Cooling:Electricity 21990.27 0.00 01-JAN-00:10 11430.64 05-JUN-17:10
Electricity:Plant 39607.75 0.00 01-JAN-00:10 55523.39 01-JAN-07:50
WaterSystems:Electricity 39607.75 0.00 01-JAN-00:10 55523.39 01-JAN-07:50
Water Heater:WaterSystems:Electricity 39607.75 0.00 01-JAN-00:10 55523.39 01-JAN-07:50
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:50
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 779775.61 347.69 25-SEP-04:00 291867.49 26-JUL-18:10
EnergyTransfer:Building 335489.92 0.00 23-FEB-11:50 136549.13 15-JUN-17:20
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 62732.26 0.00 02-JAN-16:10 89767.51 27-DEC-07:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 62732.26 0.00 02-JAN-16:10 89767.51 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 272757.66 0.00 01-JAN-00:10 136549.13 15-JUN-17:20
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 272757.66 0.00 01-JAN-00:10 136549.13 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 18070.73 0.00 01-JAN-10:50 8896.69 15-JUN-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4050.00 0.00 01-JAN-10:50 5371.99 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4050.00 0.00 01-JAN-10:50 5371.99 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 14020.73 0.00 01-JAN-00:10 8896.69 15-JUN-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 14020.73 0.00 01-JAN-00:10 8896.69 15-JUN-17:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12832.72 0.00 01-JAN-10:20 5216.40 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2556.15 0.00 01-JAN-10:20 3912.88 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2556.15 0.00 01-JAN-10:20 3912.88 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10276.57 0.00 01-JAN-00:10 5216.40 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10276.57 0.00 01-JAN-00:10 5216.40 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 17339.69 0.00 01-JAN-09:40 6350.35 15-JUN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3703.81 0.00 01-JAN-09:40 5411.98 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3703.81 0.00 01-JAN-09:40 5411.98 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13635.88 0.00 01-JAN-00:10 6350.35 15-JUN-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13635.88 0.00 01-JAN-00:10 6350.35 15-JUN-10:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 17325.50 0.00 01-JAN-13:50 9023.36 15-JUN-17:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5183.49 0.00 01-JAN-13:50 5468.50 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5183.49 0.00 01-JAN-13:50 5468.50 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12142.01 0.00 01-JAN-00:10 9023.36 15-JUN-17:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12142.01 0.00 01-JAN-00:10 9023.36 15-JUN-17:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12500.39 0.00 01-JAN-18:10 5330.48 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3772.11 0.00 01-JAN-18:10 4057.00 27-JAN-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3772.11 0.00 01-JAN-18:10 4057.00 27-JAN-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8728.28 0.00 01-JAN-00:10 5330.48 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8728.28 0.00 01-JAN-00:10 5330.48 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 16745.31 0.00 02-JAN-14:20 6395.65 15-JUN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4860.60 0.00 02-JAN-14:20 5494.50 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4860.60 0.00 02-JAN-14:20 5494.50 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11884.72 0.00 01-JAN-00:10 6395.65 15-JUN-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11884.72 0.00 01-JAN-00:10 6395.65 15-JUN-10:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21322.02 0.00 01-JAN-00:10 9734.88 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2471.89 0.00 01-JAN-00:10 4748.69 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2471.89 0.00 01-JAN-00:10 4748.69 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18850.13 0.00 01-JAN-00:10 9734.88 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 18850.13 0.00 01-JAN-00:10 9734.88 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 15896.42 0.00 01-JAN-00:10 5700.68 02-JUL-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1174.18 0.00 01-JAN-00:10 3223.58 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1174.18 0.00 01-JAN-00:10 3223.58 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14722.24 0.00 01-JAN-00:10 5700.68 02-JUL-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14722.24 0.00 01-JAN-00:10 5700.68 02-JUL-18:20
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 20875.67 0.00 01-JAN-00:10 7108.50 19-SEP-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2214.20 0.00 01-JAN-00:10 4756.30 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2214.20 0.00 01-JAN-00:10 4756.30 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 18661.47 0.00 01-JAN-00:10 7108.50 19-SEP-14:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 18661.47 0.00 01-JAN-00:10 7108.50 19-SEP-14:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 19453.93 0.00 01-JAN-13:30 9901.01 15-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3484.34 0.00 01-JAN-13:30 4787.75 27-DEC-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3484.34 0.00 01-JAN-13:30 4787.75 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15969.59 0.00 01-JAN-00:10 9901.01 15-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15969.59 0.00 01-JAN-00:10 9901.01 15-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14065.02 0.00 01-JAN-00:10 5846.48 14-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2116.61 0.00 01-JAN-00:10 3356.45 27-DEC-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2116.61 0.00 01-JAN-00:10 3356.45 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11948.41 0.00 01-JAN-00:10 5846.48 14-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 11948.41 0.00 01-JAN-00:10 5846.48 14-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 19025.24 0.00 01-JAN-12:20 7134.76 15-JUN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3182.16 0.00 01-JAN-12:20 4812.15 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3182.16 0.00 01-JAN-12:20 4812.15 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15843.08 0.00 01-JAN-00:10 7134.76 15-JUN-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15843.08 0.00 01-JAN-00:10 7134.76 15-JUN-10:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 22805.04 0.00 01-JAN-13:50 8600.86 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4854.26 0.00 01-JAN-13:50 6499.95 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4854.26 0.00 01-JAN-13:50 6499.95 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 17950.78 0.00 01-JAN-00:10 8600.86 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 17950.78 0.00 01-JAN-00:10 8600.86 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 23406.12 0.00 01-JAN-00:10 8476.22 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3648.79 0.00 01-JAN-00:10 6390.05 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 3648.79 0.00 01-JAN-00:10 6390.05 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19757.33 0.00 01-JAN-00:10 8476.22 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 19757.33 0.00 01-JAN-00:10 8476.22 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 24134.52 0.00 01-JAN-00:10 11187.58 15-JUN-17:20
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4059.91 0.00 01-JAN-00:10 6390.15 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4059.91 0.00 01-JAN-00:10 6390.15 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 20074.61 0.00 01-JAN-00:10 11187.58 15-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 20074.61 0.00 01-JAN-00:10 11187.58 15-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 17864.01 0.00 01-JAN-14:40 7430.32 02-JUL-18:30
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3701.92 0.00 01-JAN-14:40 4957.68 27-DEC-08:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3701.92 0.00 01-JAN-14:40 4957.68 27-DEC-08:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14162.09 0.00 01-JAN-00:10 7430.32 02-JUL-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 14162.09 0.00 01-JAN-00:10 7430.32 02-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 18391.38 0.00 01-JAN-00:10 7261.09 02-JUL-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2447.66 0.00 01-JAN-00:10 4827.01 27-DEC-07:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2447.66 0.00 01-JAN-00:10 4827.01 27-DEC-07:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15943.72 0.00 01-JAN-00:10 7261.09 02-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 15943.72 0.00 01-JAN-00:10 7261.09 02-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 23436.21 0.00 01-JAN-13:40 11375.06 15-JUN-17:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5250.17 0.00 01-JAN-13:40 6444.21 03-FEB-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5250.17 0.00 01-JAN-13:40 6444.21 03-FEB-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18186.03 0.00 01-JAN-00:10 11375.06 15-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 18186.03 0.00 01-JAN-00:10 11375.06 15-JUN-17:30
PlantLoopHeatingDemand:Facility 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
PlantLoopHeatingDemand:Plant 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
EnergyTransfer:HVAC 381661.30 0.00 23-FEB-11:50 154926.46 26-JUL-18:10
HeatingCoils:EnergyTransfer 59555.27 0.00 02-JAN-16:10 85202.42 27-DEC-07:10
CoolingCoils:EnergyTransfer 322106.03 0.00 01-JAN-00:10 154926.46 26-JUL-18:10
EnergyTransfer:Plant 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
WaterSystems:EnergyTransfer 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 62624.39 196.55 01-AUG-04:00 19549.42 05-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 4049.967 -1167.61 0.000 0.000 2986.473 2458.419 10464.601 10587.666 0.000 1335.608 0.016 0.000 -3897.70 0.000 -6747.25 -7217.08
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 2556.125 -855.81 0.000 0.000 2977.403 2458.419 10464.601 4659.119 0.000 1289.069 0.003 0.000 -1564.37 0.000 -6541.57 -6022.22
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 3703.779 -1135.56 0.000 0.000 2986.577 2458.419 10464.601 10606.842 0.000 1335.612 0.028 0.000 -3759.08 0.000 -6772.58 -7388.29
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 5183.447 -1011.16 0.000 0.000 3000.383 2458.419 10464.601 7514.941 0.000 1335.738 0.000 0.000 -4039.78 0.000 -6633.99 -7141.77
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 3772.086 -726.87 0.000 0.000 2997.997 2458.419 10464.601 1455.761 0.000 1289.308 0.000 0.000 -1671.51 0.000 -6387.96 -5650.40
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 4860.564 -989.73 0.000 0.000 3002.607 2458.419 10464.601 7433.064 0.000 1335.611 0.000 0.000 -3783.15 0.000 -6637.09 -7249.90
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 2471.867 -1569.80 0.000 0.000 2954.446 2458.419 10464.601 10450.655 0.000 1112.788 0.044 0.000 -4109.48 0.000 -5749.87 -1203.29
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 1174.164 -1226.04 0.000 0.000 2938.632 2458.419 10464.601 4597.094 0.000 1066.415 0.105 0.000 -1653.73 0.000 -5562.47 -760.84
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 2214.175 -1554.09 0.000 0.000 2954.422 2458.419 10464.601 10450.517 0.000 1112.790 0.122 0.000 -3961.02 0.000 -5777.58 -1254.82
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 3484.311 -1329.91 0.000 0.000 2971.993 2458.419 10464.601 7411.021 0.000 1112.802 0.074 0.000 -4234.90 0.000 -5645.16 -2053.48
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 2116.591 -995.04 0.000 0.000 2966.303 2458.419 10464.601 1422.868 0.000 1066.426 0.039 0.000 -1754.02 0.000 -5410.68 -1382.06
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 3182.139 -1319.38 0.000 0.000 2977.378 2458.419 10464.601 7308.472 0.000 1112.789 0.020 0.000 -3958.63 0.000 -5641.36 -2060.69
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 4854.227 -1494.90 0.000 0.000 2982.416 2458.419 10464.601 7287.315 0.000 1326.494 0.012 0.000 -3966.13 0.000 -6755.42 -701.10
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 3648.754 -1645.35 0.000 0.000 2965.208 2458.419 10464.601 10445.666 0.000 1326.493 0.103 0.000 -3944.36 0.000 -6884.71 -722.69
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 4059.877 -1671.77 0.000 0.000 2964.817 2458.419 10464.601 10438.968 0.000 1326.492 0.113 0.000 -4087.09 0.000 -6859.71 -691.75
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 3701.893 -1179.39 0.000 0.000 2973.361 2458.419 10464.601 1412.268 0.000 1280.326 148.700 0.000 -1751.83 0.000 -6525.61 -0.23
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 2447.639 -1327.76 0.000 0.000 2952.455 2458.419 10464.601 4592.569 0.000 1280.284 59.184 0.000 -1643.75 0.000 -6667.65 -0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 5250.134 -1514.49 0.000 0.000 2978.126 2458.419 10464.601 7376.097 0.000 1326.576 0.022 0.000 -4225.67 0.000 -6759.90 -682.34
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 26521.785 188271.881 0.000 0.000 0.000 -214793.67 -0.58
Total Facility 0.000 0.000 62731.739 -22714.65 0.000 0.000 53530.996 44251.534 188362.826 125450.903 0.000 48893.406 188480.466 0.000 -58006.22 0.000 -328754.23 -52183.53


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 15-JUN-17:10 0.00 0.00 0.00 -0.7 0.00 0.00 263.17 536.40 1664.02 5747.32 0.00 1576.11 0.00 0.00 0.00 0.00 0.00 -889.9
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 02-JUL-18:10 0.00 0.00 0.00 -0.4 0.00 0.00 426.76 722.08 1748.06 504.54 0.00 1315.75 499.29 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15-JUN-09:00 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 103.15 1096.02 4533.63 0.00 1256.75 0.00 0.00 0.00 0.00 0.00 -753.5
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 15-JUN-17:10 0.00 0.00 0.00 -0.8 0.00 0.00 263.17 536.40 1664.02 6135.16 0.00 1576.11 0.00 0.00 0.00 0.00 0.00 -1151.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 14-JUN-18:10 0.00 0.00 0.00 -0.4 0.00 0.00 426.77 722.08 1724.99 872.43 0.00 1439.40 144.95 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 15-JUN-09:05 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 103.15 1096.02 4441.80 0.00 1256.75 0.00 0.00 0.00 0.00 0.00 -617.2
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 15-JUN-17:19 0.00 0.00 0.00 -0.8 0.00 0.00 263.17 536.40 1664.02 5541.39 0.00 1190.67 539.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 02-JUL-18:24 0.00 0.00 0.00 -0.5 0.00 0.00 426.76 722.08 1748.06 471.10 0.00 1020.08 1313.17 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 19-SEP-13:05 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 103.15 1084.63 3406.50 0.00 844.12 1555.39 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 15-JUN-17:30 0.00 0.00 0.00 -0.8 0.00 0.00 263.17 536.40 1664.02 5867.15 0.00 1163.92 407.07 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 14-JUN-18:10 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 722.08 1724.99 868.59 0.00 1123.54 980.82 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 15-JUN-09:05 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 103.15 1096.02 4414.49 0.00 1002.82 403.22 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 02-JUL-18:13 0.00 0.00 0.00 -0.7 0.00 0.00 426.75 722.08 1748.06 1485.54 0.00 1370.93 2847.84 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 02-JUL-18:16 0.00 0.00 0.00 -0.7 0.00 0.00 426.75 722.08 1748.06 1206.52 0.00 1370.92 3003.22 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 15-JUN-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 536.40 1664.02 5509.07 0.00 1525.26 1690.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 02-JUL-18:34 0.00 0.00 0.00 -0.6 0.00 0.00 426.75 722.08 1748.06 851.09 0.00 1243.67 2438.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 02-JUL-18:13 0.00 0.00 0.00 -0.6 0.00 0.00 426.76 722.08 1748.06 493.69 0.00 1312.06 2558.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 15-JUN-17:30 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 536.40 1664.02 5832.01 0.00 1479.34 1600.76 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 15-JUN-17:19 0.00 0.00 0.00 -11.4 0.00 0.00 4737.04 9655.18 29952.39 49786.31 0.00 25041.90 58857.59 0.00 0.00 0.00 -41468.5 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5372.02 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2235.7 0.00 -3414.3 -1711.3
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 3912.90 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -906.5 0.00 -3284.2 -1711.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5412.00 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2226.2 0.00 -3414.3 -1760.8
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5468.52 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2227.5 0.00 -3414.3 -1816.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 27-JAN-08:09 0.00 0.00 4056.89 0.00 0.00 0.00 215.03 151.29 1155.86 0.00 0.00 0.00 0.00 0.00 -715.4 0.00 -3116.2 -1747.4
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 03-FEB-06:00 0.00 0.00 5494.53 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2218.3 0.00 -3414.3 -1851.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 4748.68 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -2133.5 0.00 -2680.9 -1953.6
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 3223.58 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -867.4 0.00 -2555.1 -1820.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27-DEC-07:10 0.00 0.00 4756.29 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -2132.5 0.00 -2680.9 -1962.2
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 27-DEC-08:15 0.00 0.00 4789.30 0.00 0.00 0.00 215.03 151.29 1155.86 0.00 0.00 0.00 0.00 0.00 -1652.1 0.00 -2579.2 -2080.2
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 27-DEC-08:15 0.00 0.00 3356.52 0.00 0.00 0.00 215.03 151.29 1155.86 0.00 0.00 0.00 0.00 0.00 -673.8 0.00 -2459.8 -1745.0
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 03-FEB-06:00 0.00 0.00 4812.18 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2237.4 0.00 -2804.2 -1759.9
LIVING_UNIT3_BACKROW_TOPFLOOR 03-FEB-06:00 0.00 0.00 6499.99 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2221.5 0.00 -3419.5 -2848.3
LIVING_UNIT3_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 6390.04 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -2117.6 0.00 -3275.1 -3016.7
LIVING_UNIT1_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 6390.13 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -2116.6 0.00 -3275.1 -3017.8
LIVING_UNIT2_BACKROW_TOPFLOOR 27-DEC-08:15 0.00 0.00 4957.84 0.00 0.00 0.00 215.03 151.29 1155.86 0.00 0.00 0.00 0.00 0.00 -667.2 0.00 -3024.1 -2788.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 27-DEC-07:10 0.00 0.00 4827.00 0.00 0.00 0.00 464.72 343.85 1210.75 0.00 0.00 0.00 0.00 0.00 -859.4 0.00 -3149.3 -2837.7
LIVING_UNIT1_BACKROW_TOPFLOOR 03-FEB-06:00 0.00 0.00 6444.24 0.00 0.00 0.00 526.24 385.11 1077.98 0.00 0.00 0.00 0.00 0.00 -2228.3 0.00 -3419.5 -2785.7
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 27-DEC-07:10 0.00 0.00 89767.38 0.00 0.00 0.00 8365.04 6189.22 21793.53 0.00 0.00 6990.70 0.00 0.00 -30625.9 0.00 -54601.4 -47878.6



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.1144 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 386.1144 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.2840 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 229.2840 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.5972 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 290.5972 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.2379 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 380.2379 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.7640 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 228.7640 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.7776 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 276.7776 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.9540 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 426.9540 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.6748 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 259.6748 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.7595 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 324.7595 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.2007 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 421.2007 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.1306 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.1306 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.6378 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 313.6378 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.5956 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 494.5956 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.1126 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 327.1126 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.7632 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 384.7632 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.9638 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 496.9638 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.1235 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.1235 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.1174 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 388.1174 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.1144 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 386.1144 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.2840 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 229.2840 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.5972 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 290.5972 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.2379 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 380.2379 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.7640 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 228.7640 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.7776 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 276.7776 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.9540 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 426.9540 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.6748 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 259.6748 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.7595 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 324.7595 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.2007 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 421.2007 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.1306 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.1306 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.6378 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 313.6378 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.5956 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 494.5956 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.1126 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 327.1126 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.7632 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 384.7632 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.9638 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 496.9638 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.1235 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 331.1235 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.1174 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 388.1174 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 386.1144 386.1144 386.1144 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 229.2840 229.2840 229.2840 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 290.5972 290.5972 290.5972 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 380.2379 380.2379 380.2379 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 228.7640 228.7640 228.7640 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 276.7776 276.7776 276.7776 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 426.9540 426.9540 426.9540 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 259.6748 259.6748 259.6748 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 324.7595 324.7595 324.7595 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.2007 421.2007 421.2007 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.1306 258.1306 258.1306 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.6378 313.6378 313.6378 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 388.1174 388.1174 388.1174 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 384.7632 384.7632 384.7632 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 494.5956 494.5956 494.5956 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.1235 331.1235 331.1235 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 327.1126 327.1126 327.1126 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.9638 496.9638 496.9638 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.1144 386.1144 386.1144 386.1144 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.2840 229.2840 229.2840 229.2840 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.5972 290.5972 290.5972 290.5972 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.2379 380.2379 380.2379 380.2379 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.7640 228.7640 228.7640 228.7640 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.7776 276.7776 276.7776 276.7776 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.9540 426.9540 426.9540 426.9540 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.6748 259.6748 259.6748 259.6748 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.7595 324.7595 324.7595 324.7595 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.2007 421.2007 421.2007 421.2007 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.1306 258.1306 258.1306 258.1306 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.6378 313.6378 313.6378 313.6378 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.5956 494.5956 494.5956 494.5956 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.1126 327.1126 327.1126 327.1126 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.7632 384.7632 384.7632 384.7632 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.9638 496.9638 496.9638 496.9638 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.1235 331.1235 331.1235 331.1235 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.1174 388.1174 388.1174 388.1174 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 386.1144 386.1144 386.1144 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 229.2840 229.2840 229.2840 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 290.5972 290.5972 290.5972 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 380.2379 380.2379 380.2379 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 228.7640 228.7640 228.7640 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 276.7776 276.7776 276.7776 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 426.9540 426.9540 426.9540 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 259.6748 259.6748 259.6748 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 324.7595 324.7595 324.7595 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.2007 421.2007 421.2007 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.1306 258.1306 258.1306 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.6378 313.6378 313.6378 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 388.1174 388.1174 388.1174 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 384.7632 384.7632 384.7632 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 494.5956 494.5956 494.5956 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 331.1235 331.1235 331.1235 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 327.1126 327.1126 327.1126 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 496.9638 496.9638 496.9638 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 386.1144 386.1144 386.1144 386.1144 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 229.2840 229.2840 229.2840 229.2840 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 290.5972 290.5972 290.5972 290.5972 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 380.2379 380.2379 380.2379 380.2379 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 228.7640 228.7640 228.7640 228.7640 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 276.7776 276.7776 276.7776 276.7776 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 426.9540 426.9540 426.9540 426.9540 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 259.6748 259.6748 259.6748 259.6748 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 324.7595 324.7595 324.7595 324.7595 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 421.2007 421.2007 421.2007 421.2007 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 258.1306 258.1306 258.1306 258.1306 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 313.6378 313.6378 313.6378 313.6378 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 494.5956 494.5956 494.5956 494.5956 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 327.1126 327.1126 327.1126 327.1126 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 384.7632 384.7632 384.7632 384.7632 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 496.9638 496.9638 496.9638 496.9638 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 331.1235 331.1235 331.1235 331.1235 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 388.1174 388.1174 388.1174 388.1174 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Sec1.1A-General Information

Data
Weather File ANNUAL ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Total gross floor area [ft2] 31210.83
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 31210.83 21609.96 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 17442.29 24971.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 21990.27 11430.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 12960.20 4221.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 5025.90 1934.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 39607.75 55523.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 670701.10
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 670701.10


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.42
Space Heating 0.56
Space Cooling 0.70
Fans (All) 0.32
Service Water Heating 1.27
Receptacle Equipment 2.83
Miscellaneous (All) 6.29
Subtotal 6.29


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 6.60
Space Heating 8.88
Space Cooling 11.19
Fans (All) 5.14
Service Water Heating 20.16
Receptacle Equipment 44.95
Miscellaneous 3.07


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:00:54

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 88.222 1.295 477.639 17.319 17.319
February 124.167 2.588 364.733 13.983 13.983
March 200.139 4.469 336.981 12.975 12.975
April 399.839 12.743 107.547 14.421 14.421
May 602.053 22.271 7.167 22.320 22.320
June 718.667 37.205 0.000 37.205 37.205
July 744.000 42.579 0.000 42.579 42.579
August 743.833 38.220 0.000 38.220 38.220
September 666.142 31.787 1.000 31.788 31.788
October 432.304 15.679 66.472 16.253 16.253
November 197.083 5.011 332.806 13.663 13.663
December 71.722 0.928 490.111 19.332 19.332
           
Annual Sum or Average 4988.170 214.775 2184.456 280.059 280.059
Minimum of Months 71.722 0.928 0.000 12.975 12.975
Maximum of Months 744.000 42.579 490.111 42.579 42.579



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 64.917 0.400 432.708 8.043 8.043
February 117.542 1.386 326.900 6.694 6.694
March 184.833 1.942 298.167 5.768 5.768
April 397.114 7.676 67.111 8.295 8.295
May 629.467 14.666 1.667 14.669 14.669
June 720.000 27.167 0.000 27.167 27.167
July 744.000 32.360 0.000 32.360 32.360
August 744.000 29.451 0.000 29.451 29.451
September 692.892 24.747 0.000 24.747 24.747
October 463.075 11.437 25.333 11.538 11.538
November 209.514 3.138 284.181 6.943 6.943
December 51.944 0.224 446.583 9.085 9.085
           
Annual Sum or Average 5019.297 154.596 1882.650 184.761 184.761
Minimum of Months 51.944 0.224 0.000 5.768 5.768
Maximum of Months 744.000 32.360 446.583 32.360 32.360



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 55.333 0.400 462.367 11.845 11.845
February 125.922 1.791 331.917 9.515 9.515
March 221.056 3.050 288.744 8.651 8.651
April 447.706 11.229 76.500 12.176 12.176
May 635.842 20.724 4.167 20.747 20.747
June 717.417 34.985 0.000 34.985 34.985
July 744.000 40.090 0.000 40.090 40.090
August 743.833 36.017 0.000 36.017 36.017
September 671.833 29.770 1.333 29.772 29.772
October 457.250 13.753 64.417 14.185 14.185
November 211.875 3.682 308.417 9.817 9.817
December 41.278 0.244 475.153 13.491 13.491
           
Annual Sum or Average 5073.345 195.736 2013.014 241.290 241.290
Minimum of Months 41.278 0.244 0.000 8.651 8.651
Maximum of Months 744.000 40.090 475.153 40.090 40.090



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 1.667 0.006 614.319 20.765 20.765
February 53.000 0.563 468.222 14.956 14.956
March 141.472 1.983 391.858 11.827 11.827
April 376.694 10.429 117.722 12.204 12.204
May 602.664 21.576 6.833 21.619 21.619
June 718.750 37.289 0.000 37.289 37.289
July 744.000 42.268 0.000 42.268 42.268
August 743.667 36.366 0.000 36.366 36.366
September 660.092 27.289 1.333 27.292 27.292
October 373.461 10.052 83.050 10.745 10.745
November 87.722 0.990 422.889 11.867 11.867
December 0.000 0.000 642.889 23.936 23.936
           
Annual Sum or Average 4503.189 188.812 2749.117 271.134 271.134
Minimum of Months 0.000 0.000 0.000 10.745 10.745
Maximum of Months 744.000 42.268 642.889 42.268 42.268



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 684.667 11.760 11.760
February 22.583 0.068 480.139 7.897 7.897
March 66.597 0.333 391.131 5.327 5.327
April 366.561 5.738 78.514 6.427 6.427
May 630.183 14.089 1.250 14.091 14.091
June 720.000 27.359 0.000 27.359 27.359
July 744.000 32.165 0.000 32.165 32.165
August 744.000 27.738 0.000 27.738 27.738
September 689.550 20.374 0.000 20.374 20.374
October 381.095 5.908 32.622 6.049 6.049
November 27.194 0.184 415.069 5.640 5.640
December 0.000 0.000 695.444 13.544 13.544
           
Annual Sum or Average 4391.765 133.956 2778.836 178.370 178.370
Minimum of Months 0.000 0.000 0.000 5.327 5.327
Maximum of Months 744.000 32.165 695.444 32.165 32.165



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 708.056 15.082 15.082
February 33.833 0.152 471.667 9.757 9.757
March 120.161 0.799 346.675 7.027 7.027
April 423.838 8.974 79.542 9.913 9.913
May 637.603 20.016 4.000 20.037 20.037
June 717.917 34.874 0.000 34.874 34.874
July 744.000 39.579 0.000 39.579 39.579
August 743.667 34.169 0.000 34.169 34.169
September 669.014 25.548 1.417 25.551 25.551
October 412.647 8.057 72.833 8.536 8.536
November 50.972 0.368 422.258 7.692 7.692
December 0.000 0.000 715.528 17.386 17.386
           
Annual Sum or Average 4553.652 172.535 2821.975 229.602 229.602
Minimum of Months 0.000 0.000 0.000 7.027 7.027
Maximum of Months 744.000 39.579 715.528 39.579 39.579



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 178.806 3.690 371.681 15.275 15.275
February 207.208 5.661 257.667 13.319 13.319
March 303.056 9.070 216.778 14.074 14.074
April 516.362 21.044 45.361 21.784 21.784
May 699.078 33.008 0.000 33.008 33.008
June 720.000 44.530 0.000 44.530 44.530
July 744.000 49.122 0.000 49.122 49.122
August 744.000 44.375 0.000 44.375 44.375
September 688.900 37.777 0.000 37.777 37.777
October 520.503 23.078 23.000 23.280 23.280
November 281.167 9.037 250.000 15.443 15.443
December 160.833 2.872 389.583 17.384 17.384
           
Annual Sum or Average 5763.912 283.264 1554.069 329.371 329.371
Minimum of Months 160.833 2.872 0.000 13.319 13.319
Maximum of Months 744.000 49.122 389.583 49.122 49.122



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 202.125 2.749 291.428 7.129 7.129
February 232.944 4.382 180.556 7.161 7.161
March 318.750 6.058 135.161 7.620 7.620
April 570.404 15.509 22.931 15.668 15.668
May 730.600 24.562 0.000 24.562 24.562
June 720.000 33.399 0.000 33.399 33.399
July 744.000 38.004 0.000 38.004 38.004
August 744.000 34.817 0.000 34.817 34.817
September 707.189 30.233 0.000 30.233 30.233
October 603.794 19.059 2.417 19.062 19.062
November 328.219 7.461 175.694 9.647 9.647
December 180.972 2.229 304.708 8.168 8.168
           
Annual Sum or Average 6082.998 218.463 1112.894 235.470 235.470
Minimum of Months 180.972 2.229 0.000 7.129 7.129
Maximum of Months 744.000 38.004 304.708 38.004 38.004



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 174.847 2.312 345.372 10.492 10.492
February 229.061 4.835 221.583 9.869 9.869
March 332.702 7.755 169.167 10.967 10.967
April 568.403 20.036 28.583 20.416 20.416
May 712.528 31.398 0.000 31.398 31.398
June 720.000 42.119 0.000 42.119 42.119
July 744.000 46.466 0.000 46.466 46.466
August 744.000 42.020 0.000 42.020 42.020
September 694.944 35.609 0.000 35.609 35.609
October 547.617 20.959 20.500 21.110 21.110
November 304.917 7.727 231.833 12.275 12.275
December 148.250 1.781 362.139 12.170 12.170
           
Annual Sum or Average 5921.269 263.018 1379.178 294.911 294.911
Minimum of Months 148.250 1.781 0.000 9.869 9.869
Maximum of Months 744.000 46.466 362.139 46.466 46.466



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 22.611 0.118 514.833 16.719 16.719
February 105.222 1.708 345.639 12.371 12.371
March 237.278 5.009 267.389 11.284 11.284
April 497.728 18.054 50.600 18.860 18.860
May 702.344 32.293 0.000 32.293 32.293
June 720.000 44.676 0.000 44.676 44.676
July 744.000 48.839 0.000 48.839 48.839
August 744.000 42.368 0.000 42.368 42.368
September 684.092 32.758 0.000 32.758 32.758
October 467.317 15.924 29.500 16.197 16.197
November 168.722 2.604 329.250 11.404 11.404
December 2.333 0.005 557.722 20.734 20.734
           
Annual Sum or Average 5095.647 244.355 2094.933 308.503 308.503
Minimum of Months 2.333 0.005 0.000 11.284 11.284
Maximum of Months 744.000 48.839 557.722 48.839 48.839



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 7.417 0.019 531.000 8.268 8.268
February 83.333 0.777 323.611 5.809 5.809
March 203.944 2.300 210.067 4.777 4.777
April 543.336 12.519 28.389 12.713 12.713
May 730.878 23.918 0.000 23.918 23.918
June 720.000 33.611 0.000 33.611 33.611
July 744.000 37.784 0.000 37.784 37.784
August 744.000 32.873 0.000 32.873 32.873
September 703.466 25.224 0.000 25.224 25.224
October 536.486 11.541 5.972 11.557 11.557
November 129.833 1.162 284.069 4.961 4.961
December 0.000 0.000 580.250 10.717 10.717
           
Annual Sum or Average 5146.694 181.728 1963.358 212.211 212.211
Minimum of Months 0.000 0.000 0.000 4.777 4.777
Maximum of Months 744.000 37.784 580.250 37.784 37.784



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 3.500 0.006 585.528 11.989 11.989
February 97.925 1.108 334.761 7.987 7.987
March 258.247 3.700 208.611 7.560 7.560
April 558.258 17.723 29.667 18.112 18.112
May 714.014 31.675 0.000 31.675 31.675
June 720.000 43.448 0.000 43.448 43.448
July 744.000 47.424 0.000 47.424 47.424
August 744.000 41.270 0.000 41.270 41.270
September 693.764 31.864 0.000 31.864 31.864
October 513.383 14.396 24.333 14.580 14.580
November 129.925 1.538 318.178 7.416 7.416
December 0.000 0.000 627.194 15.182 15.182
           
Annual Sum or Average 5177.017 234.153 2128.272 278.507 278.507
Minimum of Months 0.000 0.000 0.000 7.416 7.416
Maximum of Months 744.000 47.424 627.194 47.424 47.424



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 138.333 2.676 426.139 20.248 20.248
February 173.667 5.022 307.172 16.836 16.836
March 268.528 8.691 268.000 16.918 16.918
April 488.711 22.875 63.667 24.277 24.277
May 677.903 37.012 3.250 37.027 37.027
June 720.000 50.747 0.000 50.747 50.747
July 744.000 55.588 0.000 55.588 55.588
August 742.167 49.284 0.000 49.284 49.284
September 672.433 40.540 3.417 40.559 40.559
October 486.219 23.683 49.700 24.269 24.269
November 246.222 8.150 302.375 18.530 18.530
December 119.583 1.825 450.583 23.471 23.471
           
Annual Sum or Average 5477.766 306.093 1874.303 377.755 377.755
Minimum of Months 119.583 1.825 0.000 16.836 16.836
Maximum of Months 744.000 55.588 450.583 55.588 55.588



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 136.167 1.750 374.528 10.474 10.474
February 180.139 3.792 250.292 9.438 9.438
March 273.306 5.819 212.181 9.500 9.500
April 527.707 17.349 41.306 17.864 17.864
May 713.500 28.612 0.000 28.612 28.612
June 720.000 39.735 0.000 39.735 39.735
July 744.000 44.647 0.000 44.647 44.647
August 744.000 39.933 0.000 39.933 39.933
September 690.353 33.157 0.000 33.157 33.157
October 532.353 19.555 20.233 19.671 19.671
November 270.056 6.460 252.983 11.366 11.366
December 120.667 1.184 396.278 12.392 12.392
           
Annual Sum or Average 5652.246 241.992 1547.800 276.788 276.788
Minimum of Months 120.667 1.184 0.000 9.438 9.438
Maximum of Months 744.000 44.647 396.278 44.647 44.647



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 114.750 1.452 411.750 14.256 14.256
February 177.811 4.277 274.694 12.308 12.308
March 292.558 7.426 217.514 12.735 12.735
April 543.396 22.259 40.083 22.977 22.977
May 699.792 36.354 1.333 36.358 36.358
June 720.000 49.702 0.000 49.702 49.702
July 744.000 54.412 0.000 54.412 54.412
August 742.333 48.321 0.000 48.321 48.321
September 681.203 39.576 2.333 39.589 39.589
October 513.939 22.049 46.500 22.486 22.486
November 259.386 6.892 277.208 14.373 14.373
December 100.889 0.919 440.556 16.890 16.890
           
Annual Sum or Average 5590.057 293.638 1711.972 344.407 344.407
Minimum of Months 100.889 0.919 0.000 12.308 12.308
Maximum of Months 744.000 54.412 440.556 54.412 54.412



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 26.417 0.170 544.681 23.638 23.638
February 103.833 2.185 383.750 17.554 17.554
March 224.417 6.014 308.289 15.716 15.716
April 476.750 21.128 69.500 22.639 22.639
May 679.267 36.743 3.000 36.755 36.755
June 720.000 51.080 0.000 51.080 51.080
July 744.000 55.708 0.000 55.708 55.708
August 742.167 48.303 0.000 48.303 48.303
September 667.844 37.511 3.833 37.533 37.533
October 443.314 18.360 66.292 19.113 19.113
November 156.472 3.160 372.486 16.546 16.546
December 1.167 0.005 584.806 28.848 28.848
           
Annual Sum or Average 4985.647 280.366 2336.636 373.434 373.434
Minimum of Months 1.167 0.005 0.000 15.716 15.716
Maximum of Months 744.000 55.708 584.806 55.708 55.708



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 8.056 0.039 573.194 14.002 14.002
February 86.583 1.164 369.139 9.867 9.867
March 207.639 3.261 267.444 8.204 8.204
April 508.106 15.544 46.250 16.128 16.128
May 716.272 28.274 0.000 28.274 28.274
June 720.000 39.962 0.000 39.962 39.962
July 744.000 44.651 0.000 44.651 44.651
August 744.000 38.846 0.000 38.846 38.846
September 685.539 30.010 0.000 30.010 30.010
October 475.925 13.897 27.222 14.075 14.075
November 129.278 1.548 350.833 8.852 8.852
December 0.000 0.000 619.667 17.564 17.564
           
Annual Sum or Average 5025.397 217.196 2253.750 270.435 270.435
Minimum of Months 0.000 0.000 0.000 8.204 8.204
Maximum of Months 744.000 44.651 619.667 44.651 44.651



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 6.333 0.025 621.083 18.054 18.054
February 95.722 1.494 385.097 12.215 12.215
March 237.222 4.578 251.819 10.802 10.802
April 535.944 20.567 41.333 21.314 21.314
May 700.750 36.254 1.083 36.257 36.257
June 720.000 50.205 0.000 50.205 50.205
July 744.000 54.696 0.000 54.696 54.696
August 742.333 47.562 0.000 47.562 47.562
September 679.414 36.835 2.333 36.850 36.850
October 483.319 16.636 53.000 17.153 17.153
November 131.264 1.921 371.444 11.465 11.465
December 0.000 0.000 654.778 22.313 22.313
           
Annual Sum or Average 5076.303 270.772 2381.972 338.887 338.887
Minimum of Months 0.000 0.000 0.000 10.802 10.802
Maximum of Months 744.000 54.696 654.778 54.696 54.696



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1261.71 0.00 0.00
February 993.33 0.00 0.00
March 669.74 0.00 0.00
April 136.59 0.00 0.00
May 3.84 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.09 0.00 0.00
October 45.21 0.00 0.00
November 703.92 0.00 0.00
December 1449.10 0.00 0.00
       
Annual Sum or Average 436.57 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1449.10 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 834.82 0.00 0.00
February 641.82 0.00 0.00
March 417.95 0.00 0.00
April 69.90 0.00 0.00
May 0.33 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 11.00 0.00 0.00
November 429.41 0.00 0.00
December 967.90 0.00 0.00
       
Annual Sum or Average 279.84 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 967.90 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1197.31 0.00 0.00
February 894.60 0.00 0.00
March 585.95 0.00 0.00
April 102.31 0.00 0.00
May 2.42 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.21 0.00 0.00
October 45.19 0.00 0.00
November 663.26 0.00 0.00
December 1385.82 0.00 0.00
       
Annual Sum or Average 404.77 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1385.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1660.38 0.00 0.00
February 1274.63 0.00 0.00
March 787.34 0.00 0.00
April 146.76 0.00 0.00
May 3.42 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.19 0.00 0.00
October 55.39 0.00 0.00
November 898.98 0.00 0.00
December 1914.57 0.00 0.00
       
Annual Sum or Average 559.24 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1914.57 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1287.55 0.00 0.00
February 949.04 0.00 0.00
March 546.74 0.00 0.00
April 77.99 0.00 0.00
May 0.20 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 15.35 0.00 0.00
November 617.29 0.00 0.00
December 1482.90 0.00 0.00
       
Annual Sum or Average 413.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1482.90 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1656.24 0.00 0.00
February 1167.83 0.00 0.00
March 683.92 0.00 0.00
April 106.51 0.00 0.00
May 2.30 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.32 0.00 0.00
October 52.59 0.00 0.00
November 831.11 0.00 0.00
December 1909.17 0.00 0.00
       
Annual Sum or Average 532.24 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1909.17 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 781.11 0.00 0.00
February 571.63 0.00 0.00
March 337.36 0.00 0.00
April 51.58 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 13.62 0.00 0.00
November 446.27 0.00 0.00
December 978.44 0.00 0.00
       
Annual Sum or Average 264.02 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 978.44 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 386.02 0.00 0.00
February 271.14 0.00 0.00
March 137.70 0.00 0.00
April 14.47 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.28 0.00 0.00
November 199.13 0.00 0.00
December 523.46 0.00 0.00
       
Annual Sum or Average 127.32 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 523.46 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 725.21 0.00 0.00
February 494.16 0.00 0.00
March 284.75 0.00 0.00
April 34.78 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 13.36 0.00 0.00
November 416.64 0.00 0.00
December 921.18 0.00 0.00
       
Annual Sum or Average 240.16 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 921.18 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1134.99 0.00 0.00
February 807.12 0.00 0.00
March 429.07 0.00 0.00
April 56.92 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 18.65 0.00 0.00
November 621.75 0.00 0.00
December 1417.25 0.00 0.00
       
Annual Sum or Average 372.49 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1417.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 731.45 0.00 0.00
February 494.06 0.00 0.00
March 219.61 0.00 0.00
April 17.74 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 1.39 0.00 0.00
November 348.11 0.00 0.00
December 950.35 0.00 0.00
       
Annual Sum or Average 229.58 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 950.35 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1099.78 0.00 0.00
February 698.92 0.00 0.00
March 354.25 0.00 0.00
April 36.88 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 16.87 0.00 0.00
November 557.44 0.00 0.00
December 1393.33 0.00 0.00
       
Annual Sum or Average 345.73 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1393.33 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1256.50 0.00 0.00
February 935.33 0.00 0.00
March 588.32 0.00 0.00
April 103.63 0.00 0.00
May 1.07 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.38 0.00 0.00
October 41.91 0.00 0.00
November 767.03 0.00 0.00
December 1547.82 0.00 0.00
       
Annual Sum or Average 435.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1547.82 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 784.20 0.00 0.00
February 561.90 0.00 0.00
March 330.92 0.00 0.00
April 47.89 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 10.41 0.00 0.00
November 455.71 0.00 0.00
December 1007.54 0.00 0.00
       
Annual Sum or Average 265.66 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1007.54 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1177.28 0.00 0.00
February 817.49 0.00 0.00
March 488.12 0.00 0.00
April 68.27 0.00 0.00
May 0.40 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.26 0.00 0.00
October 40.19 0.00 0.00
November 710.80 0.00 0.00
December 1468.42 0.00 0.00
       
Annual Sum or Average 396.46 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1468.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1670.55 0.00 0.00
February 1211.22 0.00 0.00
March 690.64 0.00 0.00
April 111.18 0.00 0.00
May 0.82 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.65 0.00 0.00
October 53.62 0.00 0.00
November 984.62 0.00 0.00
December 2053.17 0.00 0.00
       
Annual Sum or Average 562.66 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2053.17 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1240.04 0.00 0.00
February 855.74 0.00 0.00
March 438.97 0.00 0.00
April 53.56 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 15.79 0.00 0.00
November 670.25 0.00 0.00
December 1559.83 0.00 0.00
       
Annual Sum or Average 401.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 1559.83 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 1643.06 0.00 0.00
February 1081.73 0.00 0.00
March 567.23 0.00 0.00
April 70.37 0.00 0.00
May 0.34 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.43 0.00 0.00
October 47.09 0.00 0.00
November 898.80 0.00 0.00
December 2033.51 0.00 0.00
       
Annual Sum or Average 527.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2033.51 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.11
May 0.00 0.00 0.19
June 0.00 0.00 0.32
July 0.00 0.00 0.37
August 0.00 0.00 0.33
September 0.00 0.00 0.29
October 0.00 0.00 0.14
November 0.00 0.00 0.04
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.07
May 0.00 0.00 0.13
June 0.00 0.00 0.25
July 0.00 0.00 0.30
August 0.00 0.00 0.27
September 0.00 0.00 0.24
October 0.00 0.00 0.10
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.10
May 0.00 0.00 0.19
June 0.00 0.00 0.33
July 0.00 0.00 0.39
August 0.00 0.00 0.34
September 0.00 0.00 0.30
October 0.00 0.00 0.13
November 0.00 0.00 0.04
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.09
May 0.00 0.00 0.18
June 0.00 0.00 0.33
July 0.00 0.00 0.37
August 0.00 0.00 0.32
September 0.00 0.00 0.25
October 0.00 0.00 0.09
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.37



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.05
May 0.00 0.00 0.12
June 0.00 0.00 0.25
July 0.00 0.00 0.30
August 0.00 0.00 0.25
September 0.00 0.00 0.19
October 0.00 0.00 0.05
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.08
May 0.00 0.00 0.18
June 0.00 0.00 0.33
July 0.00 0.00 0.38
August 0.00 0.00 0.33
September 0.00 0.00 0.25
October 0.00 0.00 0.07
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.38



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.03
February 0.00 0.00 0.05
March 0.00 0.00 0.08
April 0.00 0.00 0.18
May 0.00 0.00 0.28
June 0.00 0.00 0.39
July 0.00 0.00 0.43
August 0.00 0.00 0.38
September 0.00 0.00 0.34
October 0.00 0.00 0.20
November 0.00 0.00 0.08
December 0.00 0.00 0.03
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.14
May 0.00 0.00 0.21
June 0.00 0.00 0.30
July 0.00 0.00 0.35
August 0.00 0.00 0.31
September 0.00 0.00 0.29
October 0.00 0.00 0.17
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.17
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.35



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.19
May 0.00 0.00 0.29
June 0.00 0.00 0.40
July 0.00 0.00 0.44
August 0.00 0.00 0.39
September 0.00 0.00 0.35
October 0.00 0.00 0.20
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.21
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.44



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.16
May 0.00 0.00 0.27
June 0.00 0.00 0.39
July 0.00 0.00 0.43
August 0.00 0.00 0.37
September 0.00 0.00 0.30
October 0.00 0.00 0.14
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.11
May 0.00 0.00 0.21
June 0.00 0.00 0.30
July 0.00 0.00 0.34
August 0.00 0.00 0.29
September 0.00 0.00 0.24
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.34



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.16
May 0.00 0.00 0.28
June 0.00 0.00 0.40
July 0.00 0.00 0.43
August 0.00 0.00 0.37
September 0.00 0.00 0.30
October 0.00 0.00 0.13
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.43



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.05
March 0.00 0.00 0.07
April 0.00 0.00 0.20
May 0.00 0.00 0.31
June 0.00 0.00 0.43
July 0.00 0.00 0.48
August 0.00 0.00 0.42
September 0.00 0.00 0.36
October 0.00 0.00 0.20
November 0.00 0.00 0.07
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.04
March 0.00 0.00 0.05
April 0.00 0.00 0.15
May 0.00 0.00 0.24
June 0.00 0.00 0.35
July 0.00 0.00 0.39
August 0.00 0.00 0.35
September 0.00 0.00 0.30
October 0.00 0.00 0.17
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.18
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.39



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.04
March 0.00 0.00 0.06
April 0.00 0.00 0.20
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.49
August 0.00 0.00 0.43
September 0.00 0.00 0.37
October 0.00 0.00 0.20
November 0.00 0.00 0.06
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.22
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.02
March 0.00 0.00 0.05
April 0.00 0.00 0.18
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.48
August 0.00 0.00 0.41
September 0.00 0.00 0.33
October 0.00 0.00 0.16
November 0.00 0.00 0.03
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.48



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.14
May 0.00 0.00 0.24
June 0.00 0.00 0.35
July 0.00 0.00 0.40
August 0.00 0.00 0.34
September 0.00 0.00 0.27
October 0.00 0.00 0.12
November 0.00 0.00 0.01
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.16
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.40



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.01
March 0.00 0.00 0.04
April 0.00 0.00 0.18
May 0.00 0.00 0.31
June 0.00 0.00 0.44
July 0.00 0.00 0.49
August 0.00 0.00 0.42
September 0.00 0.00 0.34
October 0.00 0.00 0.14
November 0.00 0.00 0.02
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.20
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.73 775.60
February 0.00 0.00 1038.86 698.61
March 0.00 0.00 990.73 737.62
April 0.00 0.00 908.55 654.62
May 0.00 0.00 807.06 600.88
June 0.00 0.00 723.50 521.29
July 0.00 0.00 676.97 504.02
August 0.00 0.00 672.90 500.99
September 0.00 0.00 725.64 522.83
October 0.00 0.00 809.48 602.68
November 0.00 0.00 908.62 654.67
December 0.00 0.00 994.19 740.20
         
Annual Sum or Average 0.00 0.00 857.16 7514.01
Minimum of Months 0.00 0.00 672.90 500.99
Maximum of Months 0.00 0.00 1041.73 775.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.76 775.62
February 0.00 0.00 1037.77 697.87
March 0.00 0.00 991.59 738.27
April 0.00 0.00 908.66 654.70
May 0.00 0.00 807.18 600.97
June 0.00 0.00 723.34 521.17
July 0.00 0.00 675.19 502.70
August 0.00 0.00 674.90 502.48
September 0.00 0.00 723.41 521.22
October 0.00 0.00 809.49 602.69
November 0.00 0.00 908.65 654.69
December 0.00 0.00 994.41 740.36
         
Annual Sum or Average 0.00 0.00 857.01 7512.75
Minimum of Months 0.00 0.00 674.90 502.48
Maximum of Months 0.00 0.00 1041.76 775.62



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.67 775.55
February 0.00 0.00 1037.94 697.99
March 0.00 0.00 991.59 738.27
April 0.00 0.00 908.64 654.68
May 0.00 0.00 807.32 601.07
June 0.00 0.00 723.22 521.09
July 0.00 0.00 675.21 502.71
August 0.00 0.00 674.95 502.52
September 0.00 0.00 723.20 521.08
October 0.00 0.00 809.52 602.71
November 0.00 0.00 908.84 654.83
December 0.00 0.00 994.60 740.51
         
Annual Sum or Average 0.00 0.00 857.04 7513.01
Minimum of Months 0.00 0.00 674.95 502.52
Maximum of Months 0.00 0.00 1041.67 775.55



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.98 775.78
February 0.00 0.00 1040.12 699.46
March 0.00 0.00 991.65 738.31
April 0.00 0.00 908.73 654.75
May 0.00 0.00 807.20 600.98
June 0.00 0.00 723.51 521.30
July 0.00 0.00 676.97 504.02
August 0.00 0.00 672.90 500.99
September 0.00 0.00 725.65 522.84
October 0.00 0.00 809.47 602.67
November 0.00 0.00 908.81 654.81
December 0.00 0.00 996.87 742.20
         
Annual Sum or Average 0.00 0.00 857.62 7518.11
Minimum of Months 0.00 0.00 672.90 500.99
Maximum of Months 0.00 0.00 1041.98 775.78



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.89 775.72
February 0.00 0.00 1041.75 700.55
March 0.00 0.00 991.01 737.84
April 0.00 0.00 908.73 654.75
May 0.00 0.00 807.07 600.89
June 0.00 0.00 723.42 521.23
July 0.00 0.00 676.97 504.03
August 0.00 0.00 672.89 500.99
September 0.00 0.00 725.60 522.81
October 0.00 0.00 809.49 602.69
November 0.00 0.00 908.69 654.72
December 0.00 0.00 996.75 742.11
         
Annual Sum or Average 0.00 0.00 857.65 7518.31
Minimum of Months 0.00 0.00 672.89 500.99
Maximum of Months 0.00 0.00 1041.89 775.72



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.91 775.73
February 0.00 0.00 1040.49 699.71
March 0.00 0.00 991.67 738.33
April 0.00 0.00 908.68 654.71
May 0.00 0.00 807.30 601.06
June 0.00 0.00 723.30 521.14
July 0.00 0.00 675.21 502.71
August 0.00 0.00 674.87 502.46
September 0.00 0.00 723.23 521.10
October 0.00 0.00 811.81 604.41
November 0.00 0.00 908.51 654.59
December 0.00 0.00 996.84 742.17
         
Annual Sum or Average 0.00 0.00 857.62 7518.12
Minimum of Months 0.00 0.00 674.87 502.46
Maximum of Months 0.00 0.00 1041.91 775.73



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.51 773.94
February 0.00 0.00 1040.51 699.72
March 0.00 0.00 989.72 736.87
April 0.00 0.00 906.65 653.25
May 0.00 0.00 807.30 601.06
June 0.00 0.00 723.32 521.16
July 0.00 0.00 675.19 502.69
August 0.00 0.00 674.90 502.48
September 0.00 0.00 723.41 521.22
October 0.00 0.00 809.39 602.61
November 0.00 0.00 908.56 654.63
December 0.00 0.00 994.53 740.45
         
Annual Sum or Average 0.00 0.00 856.71 7510.10
Minimum of Months 0.00 0.00 674.90 502.48
Maximum of Months 0.00 0.00 1040.51 773.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.42 773.88
February 0.00 0.00 1038.18 698.16
March 0.00 0.00 989.80 736.94
April 0.00 0.00 906.52 653.16
May 0.00 0.00 807.15 600.94
June 0.00 0.00 723.18 521.06
July 0.00 0.00 676.97 504.02
August 0.00 0.00 672.88 500.98
September 0.00 0.00 725.59 522.79
October 0.00 0.00 807.52 601.22
November 0.00 0.00 908.52 654.59
December 0.00 0.00 992.15 738.68
         
Annual Sum or Average 0.00 0.00 856.29 7506.43
Minimum of Months 0.00 0.00 672.88 500.98
Maximum of Months 0.00 0.00 1039.42 773.88



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.41 773.87
February 0.00 0.00 1040.13 699.46
March 0.00 0.00 989.64 736.82
April 0.00 0.00 906.45 653.11
May 0.00 0.00 807.32 601.07
June 0.00 0.00 723.36 521.19
July 0.00 0.00 675.12 502.65
August 0.00 0.00 672.92 501.01
September 0.00 0.00 725.68 522.86
October 0.00 0.00 809.68 602.83
November 0.00 0.00 906.41 653.08
December 0.00 0.00 994.21 740.21
         
Annual Sum or Average 0.00 0.00 856.49 7508.14
Minimum of Months 0.00 0.00 672.92 501.01
Maximum of Months 0.00 0.00 1040.13 773.87



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.73 775.60
February 0.00 0.00 1040.52 699.73
March 0.00 0.00 989.67 736.84
April 0.00 0.00 908.54 654.61
May 0.00 0.00 807.16 600.95
June 0.00 0.00 723.11 521.01
July 0.00 0.00 675.12 502.65
August 0.00 0.00 672.86 500.96
September 0.00 0.00 725.73 522.90
October 0.00 0.00 809.64 602.80
November 0.00 0.00 908.61 654.67
December 0.00 0.00 995.88 741.46
         
Annual Sum or Average 0.00 0.00 857.17 7514.16
Minimum of Months 0.00 0.00 672.86 500.96
Maximum of Months 0.00 0.00 1041.73 775.60



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.82 775.66
February 0.00 0.00 1040.30 699.58
March 0.00 0.00 989.73 736.88
April 0.00 0.00 908.58 654.64
May 0.00 0.00 807.14 600.93
June 0.00 0.00 721.89 520.13
July 0.00 0.00 676.30 503.52
August 0.00 0.00 672.88 500.98
September 0.00 0.00 725.81 522.95
October 0.00 0.00 807.55 601.25
November 0.00 0.00 908.87 654.85
December 0.00 0.00 996.98 742.28
         
Annual Sum or Average 0.00 0.00 857.12 7513.66
Minimum of Months 0.00 0.00 672.88 500.98
Maximum of Months 0.00 0.00 1041.82 775.66



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.96 775.77
February 0.00 0.00 1040.25 699.54
March 0.00 0.00 989.67 736.84
April 0.00 0.00 908.57 654.64
May 0.00 0.00 805.15 599.46
June 0.00 0.00 723.68 521.42
July 0.00 0.00 676.94 504.00
August 0.00 0.00 672.93 501.01
September 0.00 0.00 725.60 522.80
October 0.00 0.00 807.51 601.21
November 0.00 0.00 909.67 655.42
December 0.00 0.00 995.74 741.36
         
Annual Sum or Average 0.00 0.00 857.09 7513.47
Minimum of Months 0.00 0.00 672.93 501.01
Maximum of Months 0.00 0.00 1041.96 775.77



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.53 773.96
February 0.00 0.00 1040.16 699.49
March 0.00 0.00 991.48 738.19
April 0.00 0.00 906.51 653.15
May 0.00 0.00 807.21 600.99
June 0.00 0.00 723.30 521.15
July 0.00 0.00 675.26 502.75
August 0.00 0.00 674.87 502.46
September 0.00 0.00 723.24 521.11
October 0.00 0.00 809.53 602.72
November 0.00 0.00 908.70 654.73
December 0.00 0.00 994.62 740.52
         
Annual Sum or Average 0.00 0.00 856.84 7511.21
Minimum of Months 0.00 0.00 674.87 502.46
Maximum of Months 0.00 0.00 1040.16 773.96



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.55 773.97
February 0.00 0.00 1039.95 699.34
March 0.00 0.00 989.64 736.81
April 0.00 0.00 908.59 654.65
May 0.00 0.00 806.76 600.66
June 0.00 0.00 721.68 519.98
July 0.00 0.00 677.06 504.09
August 0.00 0.00 672.86 500.96
September 0.00 0.00 725.72 522.89
October 0.00 0.00 807.60 601.28
November 0.00 0.00 908.60 654.66
December 0.00 0.00 994.22 740.22
         
Annual Sum or Average 0.00 0.00 856.64 7509.51
Minimum of Months 0.00 0.00 672.86 500.96
Maximum of Months 0.00 0.00 1039.95 773.97



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1039.53 773.96
February 0.00 0.00 1040.10 699.44
March 0.00 0.00 989.63 736.81
April 0.00 0.00 908.42 654.53
May 0.00 0.00 807.31 601.06
June 0.00 0.00 723.28 521.13
July 0.00 0.00 675.08 502.62
August 0.00 0.00 672.89 500.98
September 0.00 0.00 725.66 522.85
October 0.00 0.00 809.62 602.79
November 0.00 0.00 908.36 654.48
December 0.00 0.00 994.48 740.42
         
Annual Sum or Average 0.00 0.00 856.82 7511.06
Minimum of Months 0.00 0.00 672.89 500.98
Maximum of Months 0.00 0.00 1040.10 773.96



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.76 775.62
February 0.00 0.00 1040.32 699.59
March 0.00 0.00 989.78 736.92
April 0.00 0.00 908.56 654.63
May 0.00 0.00 807.09 600.90
June 0.00 0.00 723.31 521.15
July 0.00 0.00 675.19 502.69
August 0.00 0.00 674.90 502.48
September 0.00 0.00 723.44 521.25
October 0.00 0.00 809.69 602.84
November 0.00 0.00 908.98 654.93
December 0.00 0.00 996.81 742.16
         
Annual Sum or Average 0.00 0.00 857.29 7515.15
Minimum of Months 0.00 0.00 674.90 502.48
Maximum of Months 0.00 0.00 1041.76 775.62



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.88 775.71
February 0.00 0.00 1040.41 699.65
March 0.00 0.00 989.85 736.97
April 0.00 0.00 908.53 654.60
May 0.00 0.00 807.31 601.07
June 0.00 0.00 723.34 521.17
July 0.00 0.00 675.11 502.64
August 0.00 0.00 672.92 501.00
September 0.00 0.00 725.70 522.87
October 0.00 0.00 809.59 602.76
November 0.00 0.00 908.68 654.72
December 0.00 0.00 996.57 741.97
         
Annual Sum or Average 0.00 0.00 857.28 7515.14
Minimum of Months 0.00 0.00 672.92 501.00
Maximum of Months 0.00 0.00 1041.88 775.71



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1041.98 775.78
February 0.00 0.00 1040.29 699.57
March 0.00 0.00 991.48 738.18
April 0.00 0.00 906.49 653.14
May 0.00 0.00 807.14 600.93
June 0.00 0.00 723.31 521.15
July 0.00 0.00 675.19 502.69
August 0.00 0.00 674.90 502.48
September 0.00 0.00 723.42 521.23
October 0.00 0.00 809.51 602.70
November 0.00 0.00 908.86 654.84
December 0.00 0.00 997.03 742.32
         
Annual Sum or Average 0.00 0.00 857.27 7515.03
Minimum of Months 0.00 0.00 674.90 502.48
Maximum of Months 0.00 0.00 1041.98 775.78



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 7.93 994.09
February 15.63 706.90
March 26.86 527.68
April 74.79 104.15
May 126.46 3.03
June 207.73 0.00
July 213.95 0.00
August 201.19 0.00
September 169.86 0.07
October 87.27 35.62
November 30.27 536.73
December 5.69 1141.73
     
Annual Sum or Average 1167.61 4050.00
Minimum of Months 5.69 0.00
Maximum of Months 213.95 1141.73



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.47 647.64
February 8.58 449.73
March 11.88 324.24
April 46.16 52.48
May 84.80 0.26
June 156.61 0.00
July 165.97 0.00
August 158.95 0.00
September 134.95 0.00
October 64.67 8.54
November 19.39 322.38
December 1.39 750.88
     
Annual Sum or Average 855.81 2556.15
Minimum of Months 1.39 0.00
Maximum of Months 165.97 750.88



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.55 930.51
February 11.47 627.97
March 19.41 455.38
April 70.26 76.95
May 125.38 1.88
June 210.70 0.00
July 217.07 0.00
August 203.55 0.00
September 169.59 0.16
October 80.51 35.12
November 23.50 498.84
December 1.57 1077.01
     
Annual Sum or Average 1135.56 3703.81
Minimum of Months 1.57 0.00
Maximum of Months 217.07 1077.01



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.04 1307.08
February 3.29 906.31
March 11.68 619.80
April 60.73 111.81
May 122.42 2.69
June 208.73 0.00
July 212.49 0.00
August 190.12 0.00
September 142.41 0.14
October 53.57 43.61
November 5.69 684.86
December 0.00 1507.18
     
Annual Sum or Average 1011.16 5183.49
Minimum of Months 0.00 0.00
Maximum of Months 212.49 1507.18



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 998.77
February 0.41 664.94
March 2.00 424.11
April 34.06 58.55
May 81.15 0.15
June 157.87 0.00
July 164.69 0.00
August 147.82 0.00
September 106.76 0.00
October 31.04 11.91
November 1.07 463.39
December 0.00 1150.30
     
Annual Sum or Average 726.87 3772.11
Minimum of Months 0.00 0.00
Maximum of Months 164.69 1150.30



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 1284.61
February 0.93 818.13
March 4.94 530.46
April 55.57 79.95
May 121.24 1.78
June 211.46 0.00
July 215.29 0.00
August 192.19 0.00
September 141.57 0.24
October 44.36 40.79
November 2.18 623.84
December 0.00 1480.79
     
Annual Sum or Average 989.73 4860.60
Minimum of Months 0.00 0.00
Maximum of Months 215.29 1480.79



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 22.82 621.12
February 34.68 410.56
March 55.32 268.26
April 125.06 39.69
May 189.79 0.00
June 249.23 0.00
July 250.77 0.00
August 235.48 0.00
September 203.62 0.00
October 130.16 10.83
November 55.11 343.41
December 17.75 778.03
     
Annual Sum or Average 1569.79 2471.89
Minimum of Months 17.75 0.00
Maximum of Months 250.77 778.03



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 17.23 302.36
February 27.41 191.83
March 37.52 107.86
April 93.81 10.97
May 143.22 0.00
June 190.38 0.00
July 195.56 0.00
August 187.06 0.00
September 164.55 0.00
October 108.87 0.22
November 46.41 150.94
December 14.01 410.01
     
Annual Sum or Average 1226.03 1174.18
Minimum of Months 14.01 0.00
Maximum of Months 195.56 410.01



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 14.94 567.87
February 31.40 349.50
March 50.17 222.97
April 127.11 26.35
May 192.94 0.00
June 253.45 0.00
July 254.86 0.00
August 238.81 0.00
September 204.23 0.00
October 124.75 10.46
November 49.85 315.72
December 11.57 721.32
     
Annual Sum or Average 1554.08 2214.20
Minimum of Months 11.57 0.00
Maximum of Months 254.86 721.32



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.69 901.71
February 10.15 579.18
March 29.99 340.88
April 106.43 43.76
May 185.51 0.00
June 250.55 0.00
July 249.36 0.00
August 223.25 0.00
September 172.56 0.00
October 86.30 14.82
November 15.09 478.03
December 0.03 1125.96
     
Annual Sum or Average 1329.91 3484.34
Minimum of Months 0.03 0.00
Maximum of Months 250.55 1125.96



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.11 572.75
February 4.72 349.43
March 13.98 171.96
April 74.83 13.44
May 139.16 0.00
June 191.98 0.00
July 194.33 0.00
August 174.66 0.00
September 132.43 0.00
October 62.10 1.09
November 6.73 263.79
December 0.00 744.15
     
Annual Sum or Average 995.04 2116.61
Minimum of Months 0.00 0.00
Maximum of Months 194.33 744.15



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.03 859.73
February 6.67 493.49
March 22.39 276.93
April 107.36 27.90
May 188.48 0.00
June 254.46 0.00
July 253.06 0.00
August 226.26 0.00
September 172.62 0.00
October 79.02 13.19
November 9.00 421.71
December 0.00 1089.21
     
Annual Sum or Average 1319.37 3182.16
Minimum of Months 0.00 0.00
Maximum of Months 254.46 1089.21



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.15 1284.86
February 8.83 764.04
March 27.12 443.57
April 121.73 53.25
May 210.44 0.27
June 286.92 0.00
July 285.26 0.00
August 255.84 0.00
September 197.01 1.08
October 90.53 36.82
November 11.07 680.18
December 0.00 1590.19
     
Annual Sum or Average 1494.90 4854.26
Minimum of Months 0.00 0.00
Maximum of Months 286.92 1590.19



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 8.82 920.24
February 25.99 577.17
March 44.89 381.55
April 133.26 51.64
May 212.29 0.31
June 285.20 0.00
July 285.03 0.00
August 262.20 0.00
September 215.88 0.96
October 124.58 31.42
November 41.66 537.69
December 5.56 1147.81
     
Annual Sum or Average 1645.34 3648.79
Minimum of Months 5.56 0.00
Maximum of Months 285.20 1147.81



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 16.16 995.50
February 30.05 669.33
March 51.89 466.11
April 133.86 79.46
May 210.40 0.85
June 281.56 0.00
July 281.47 0.00
August 259.23 0.00
September 216.06 1.05
October 131.52 33.21
November 48.59 588.10
December 10.99 1226.30
     
Annual Sum or Average 1671.77 4059.91
Minimum of Months 10.99 0.00
Maximum of Months 281.56 1226.30



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.23 970.92
February 6.95 605.18
March 19.48 343.70
April 91.70 40.59
May 162.27 0.00
June 225.04 0.00
July 227.06 0.00
August 204.83 0.00
September 157.82 0.00
October 75.06 12.37
November 8.94 507.86
December 0.00 1221.31
     
Annual Sum or Average 1179.39 3701.92
Minimum of Months 0.00 0.00
Maximum of Months 227.06 1221.31



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 10.64 613.64
February 22.97 397.15
March 34.98 258.95
April 102.57 36.27
May 163.94 0.00
June 223.07 0.00
July 226.54 0.00
August 211.11 0.00
September 176.84 0.00
October 109.08 8.15
November 38.87 345.10
December 7.17 788.41
     
Annual Sum or Average 1327.76 2447.66
Minimum of Months 7.17 0.00
Maximum of Months 226.54 788.41



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:00:54

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.99 1323.90
February 12.82 866.99
March 35.50 547.33
April 123.08 85.27
May 208.59 0.65
June 283.38 0.00
July 281.89 0.00
August 253.05 0.00
September 197.57 1.27
October 99.40 42.49
November 18.19 755.14
December 0.03 1627.13
     
Annual Sum or Average 1514.49 5250.17