Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:56

Tabular Output Report in Format: HTML

Building: US+MF+CZ3C+hp+crawlspace+IECC_2015

Environment: ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904

Simulation Timestamp: 2024-06-27 17:56:16


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 592936.91 15.20 27.44
Net Site Energy 592936.91 15.20 27.44
Total Source Energy 1877831.20 48.14 86.90
Net Source Energy 1877831.20 48.14 86.90


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 14412.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 42140.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 25719.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 144305.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 592936.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 14412.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 42140.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 8414.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 144305.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 14412.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 42140.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 44251.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 25719.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 144305.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 10.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 27.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 5.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01
Other 7.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 15.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 592936.912 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 592936.912 100.00
     
Total On-Site and Utility Electric Sources 592936.912 100.00
Total Electricity End Uses 592936.912 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 477.00


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:56
RunPeriod ANNUAL
Weather File San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Latitude [deg] 32.58
Longitude [deg] -117.0
Elevation [ft] 521.68
Time Zone -8.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.6665 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.6665 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.3693 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.6665 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
CRAWLSPACE 7794.39 No Yes 1.00 CRAWLSPACE GENERAL CRAWLSPACE 0.0000 0.00 0.0000  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.6665 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.6665 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.6665 600.28 2.9092  
Total 39005.22             0.3693 1083.48 1.6118  
Conditioned Total 21609.96             0.6665 600.28 2.9092  
Unconditioned Total 17395.26             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 21609.96 17395.26 0.00 0.3693 1083.48 1.6118
Total 39005.22 21609.96 17395.26 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 02-JAN-19:20 - - - - - - - - - - - 01-JAN-08:19
Heating 12.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 14.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 47.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 180.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 262.31 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 12.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 14.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 5.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 26.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 0.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 180.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 45643.06 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 133460.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 140144.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 81453.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 457016.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1877831.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 2.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 6.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 21.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 86.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 1.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 3.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 2.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 11.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 48.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 346.01
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 198.14
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 258.56
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 323.93
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 198.14
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 258.41
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 339.99
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 189.51
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 242.03
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 318.47
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 174.72
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 222.40
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 264.94
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 265.39
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 376.36
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 223.49
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 226.06
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 371.11
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.01 346.01 346.01 346.01 346.01 346.01 1.00 1.00 346.01
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 198.14 198.14 198.14 198.14 198.14 198.14 1.00 1.00 198.14
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 258.56 258.56 258.56 258.56 258.56 258.56 1.00 1.00 258.56
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.93 323.93 323.93 323.93 323.93 323.93 1.00 1.00 323.93
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 198.14 198.14 198.14 198.14 198.14 198.14 1.00 1.00 198.14
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 258.41 258.41 258.41 258.41 258.41 258.41 1.00 1.00 258.41
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.99 339.99 339.99 339.99 339.99 339.99 1.00 1.00 339.99
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.51 189.51 189.51 189.51 189.51 189.51 1.00 1.00 189.51
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.03 242.03 242.03 242.03 242.03 242.03 1.00 1.00 242.03
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.47 318.47 318.47 318.47 318.47 318.47 1.00 1.00 318.47
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.72 174.72 174.72 174.72 174.72 174.72 1.00 1.00 174.72
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.40 222.40 222.40 222.40 222.40 222.40 1.00 1.00 222.40
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.36 376.36 376.36 376.36 376.36 376.36 1.00 1.00 376.36
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.06 226.06 226.06 226.06 226.06 226.06 1.00 1.00 226.06
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.39 265.39 265.39 265.39 265.39 265.39 1.00 1.00 265.39
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.11 371.11 371.11 371.11 371.11 371.11 1.00 1.00 371.11
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.49 223.49 223.49 223.49 223.49 223.49 1.00 1.00 223.49
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.94 264.94 264.94 264.94 264.94 264.94 1.00 1.00 264.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 346.01 1.04 0.736044
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 198.14 0.621943 0.720209
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 258.56 0.817943 0.717193
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 323.93 0.975478 0.734228
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 198.14 0.625715 0.717639
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 258.41 0.776104 0.734955
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 339.99 1.02 0.735818
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 189.51 0.592082 0.721425
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 242.03 0.762125 0.719380
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 318.47 0.959930 0.733974
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 174.72 0.551061 0.718973
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 222.40 0.670052 0.734102
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 376.36 1.12 0.738798
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 226.06 0.693778 0.727137
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 265.39 0.828781 0.721550
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 371.11 1.10 0.737468
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 223.49 0.688865 0.725988
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 264.94 0.817062 0.725846
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Supplemental Heating Coil Nominal Capacity [Btu/h] Fraction of Supply Air Flow That Goes Through the Controlling Zone
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR 346.01 346.01 346.01 12420.66 1.04 6525.99 1.00
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR 198.14 198.14 198.14 7463.31 0.621943 5373.98 1.00
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR 258.56 258.56 258.56 9815.32 0.817943 6529.39 1.00
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR 323.93 323.93 323.93 11705.74 0.975478 6528.79 1.00
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR 198.14 198.14 198.14 7508.59 0.625715 5373.96 1.00
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR 258.41 258.41 258.41 9313.25 0.776104 6526.54 1.00
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR 339.99 339.99 339.99 12214.59 1.02 5496.85 1.00
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR 189.51 189.51 189.51 7104.99 0.592082 4360.19 1.00
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR 242.03 242.03 242.03 9145.50 0.762125 5501.18 1.00
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR 318.47 318.47 318.47 11519.16 0.959930 5500.18 1.00
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR 174.72 174.72 174.72 6612.73 0.551061 4360.95 1.00
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR 222.40 222.40 222.40 8040.63 0.670052 5499.36 1.00
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR 376.36 376.36 376.36 13423.83 1.12 6649.03 1.00
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR 226.06 226.06 226.06 8325.33 0.693778 5499.48 1.00
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR 265.39 265.39 265.39 9945.37 0.828781 6653.30 1.00
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR 371.11 371.11 371.11 13252.34 1.10 6650.84 1.00
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR 223.49 223.49 223.49 8266.38 0.688865 5499.46 1.00
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR 264.94 264.94 264.94 9804.75 0.817062 6651.34 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 346.01
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 198.14
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 258.56
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 323.93
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 198.14
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 258.41
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 339.99
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 189.51
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 242.03
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 318.47
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 174.72
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 222.40
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 376.36
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 226.06
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 265.39
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 371.11
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 223.49
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 264.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Heating Capacity [Btu/h]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 346.01 13837.70
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 198.14 7923.94
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 258.56 10340.35
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 323.93 12954.49
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 198.14 7923.90
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 258.41 10334.37
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 339.99 13596.85
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 189.51 7578.72
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 242.03 9679.00
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 318.47 12736.07
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 174.72 6987.50
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 222.40 8894.26
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 376.36 15051.39
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 226.06 9040.51
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 265.39 10613.57
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 371.11 14841.28
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 223.49 8937.77
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 264.94 10595.39
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 7504.89
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 6180.07
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 7508.80
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 7508.11
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 6180.05
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 7505.52
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 6321.38
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 5014.22
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 6326.36
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 6325.21
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 5015.10
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 6324.26
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 7646.39
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 6324.40
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 7651.30
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR 7648.47
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR 6324.38
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR 7649.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.60 55.08 55.99 57.42 61.12 63.99 65.91 66.51 65.50 63.28 60.31 57.54


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 32.58 -116.98 -8.00 521.68 14. 1.1818


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 60.80 12.78 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ3C+hp+crawlspace+IECC_2015 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 6.1981 Rough 1.2550 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 2.8450 Rough 0.4584 4.910E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5031 Smooth 0.1189 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3300 VerySmooth 0.1230 0.114 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.667 2.909 0.000 0.000 0.000 0.000 3.576 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 581.408 0.484 85.201 0.000 0.600 0.200 0.200 0.000 General 39.972 581.408
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 10 0.167 0.0281 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.350 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 8 0.167 0.0513 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.2550 0.062 2.618 0.185 6.198
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1188 0.072 32.003 0.183 0.5031
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.4584 0.049 3.438 0.219 2.845


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 8 0.57415395E-12 0.13118744E-13 0.10972129E-06 -0.16121901E-12
20 7 -0.11209345E-05 0.79302418E-09 -0.25702593E-04 0.31491488E-06
21 6 0.21835020E-03 0.55842834E-06 0.16732899E-02 -0.62999473E-04
22 5 -0.11788181E-01 0.43793696E-04 -0.40973943E-01 0.36016799E-02
23 4 0.21386917 0.66464187E-03 0.43752526 -0.72376639E-01
24 3 -1.3884299 0.23440260E-02 -2.2272953 0.54574706
25 2 3.6315139 0.19014595E-02 5.4333867 -1.6855834
26 1 -4.0346078 0.26548191E-03 -6.0131296 2.1907513
27 0 1.5944472 0.16612988E-05 2.4140608  
28 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
29 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
30 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
31 1 -8.0349315 0.81344511 -1.1624309 0.21506451
32 0 8.9946927 0.48845120 2.4180636  
33 10 0.25332408E-17 -0.22101509E-14 0.15157692E-08 0.28211904E-17
34 9 -0.31506112E-08 -0.26974675E-14 -0.81843868E-03 0.20118786E-08
35 8 0.42861811E-03 0.11354105E-09 0.39097097E-01 -0.27370296E-03
36 7 -0.11368907E-01 0.51842634E-07 -0.64553953 0.74324363E-02
37 6 0.12484615 0.25047115E-05 5.3130581 -0.83937451E-01
38 5 -0.73775399 0.27964547E-04 -24.889648 0.51283867
39 4 2.5553417 0.92755650E-04 70.144414 -1.8477174
40 3 -5.2989438 0.96002462E-04 -120.51707 4.0111012
41 2 6.4233118 0.27752742E-04 123.06129 -5.1209931
42 1 -4.1707712 0.15163054E-05 -68.409714 3.5199891
43 0 1.1151582 0.34288690E-08 15.905180  
44 10 0.15157692E-08 -0.22101509E-14 0.25332408E-17 0.28211904E-17
45 9 -0.81843868E-03 -0.26974675E-14 -0.31506112E-08 0.20118786E-08
46 8 0.39097097E-01 0.11354105E-09 0.42861811E-03 -0.27370296E-03
47 7 -0.64553953 0.51842634E-07 -0.11368907E-01 0.74324363E-02
48 6 5.3130581 0.25047115E-05 0.12484615 -0.83937451E-01
49 5 -24.889648 0.27964547E-04 -0.73775399 0.51283867
50 4 70.144414 0.92755650E-04 2.5553417 -1.8477174
51 3 -120.51707 0.96002462E-04 -5.2989438 4.0111012
52 2 123.06129 0.27752742E-04 6.4233118 -5.1209931
53 1 -68.409714 0.15163054E-05 -4.1707712 3.5199891
54 0 15.905180 0.34288690E-08 1.1151582  
55 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
56 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
57 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
58 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
59 1 -19.904252 0.86481321 -19.904252 0.58144210
60 0 16.688993 0.62060609E-01 16.688993  
61 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
62 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
63 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
64 1 -11.299243 2.8799011 -8.6239668 0.15905732
65 0 15.219762 1.4410112 12.640375  
66 5 -0.24423608E-08 0.10315694E-08 -0.24423608E-08 0.46347327E-11
67 4 0.46481418E-04 0.19988510E-04 0.46481418E-04 -0.22728163E-06
68 3 -0.31887091E-01 0.95525843E-02 -0.31887091E-01 0.49135354E-03
69 2 1.3495466 0.25081638 1.3495466 -0.51058024E-01
70 1 -7.0688408 0.57876498 -7.0688408 0.58136590
71 0 6.6836766 0.93387740E-01 6.6836766  
72 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
73 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
74 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
75 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
76 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
77 1 -64.420211 0.46601667 -21.697519 0.64629334
78 0 46.121323 0.20873329E-01 15.867130  
79 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
80 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
81 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
82 2 11.651569 1.6702487 11.651569 -0.78737360E-01
83 1 -51.506798 3.1050242 -51.506798 0.66829999
84 0 45.538973 0.42297268 45.538973  
85 8 0.10972129E-06 0.13118744E-13 0.57415395E-12 -0.16121901E-12
86 7 -0.25702593E-04 0.79302418E-09 -0.11209345E-05 0.31491488E-06
87 6 0.16732899E-02 0.55842834E-06 0.21835020E-03 -0.62999473E-04
88 5 -0.40973943E-01 0.43793696E-04 -0.11788181E-01 0.36016799E-02
89 4 0.43752526 0.66464187E-03 0.21386917 -0.72376639E-01
90 3 -2.2272953 0.23440260E-02 -1.3884299 0.54574706
91 2 5.4333867 0.19014595E-02 3.6315139 -1.6855834
92 1 -6.0131296 0.26548191E-03 -4.0346078 2.1907513
93 0 2.4140608 0.16612988E-05 1.5944472  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.350 0.350 1.000 0.217    
2 INTERIOR WINDOW 13 1 VerySmooth 0.350 0.350 1.000 0.217    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.350 0.350 1.000 0.208    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
2 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
3 GLASS SpectralAverage   0.12304 0.12813 0.66165 0.66165 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 7976.07384 7976.07384 346.01691 346.01691 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 85.83021 0.00823 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 5013.84027 5013.84027 258.38980 258.38980 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4333.36894 4333.36894 187.99023 187.99023 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 82.49270 0.00823 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 3844.79251 3844.79251 198.13981 198.13981 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 5505.04636 5505.04636 238.81353 238.81353 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 88.34000 0.00823 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 5017.29062 5017.29062 258.55929 258.55929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 7466.97942 7466.97942 323.91945 323.91945 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 85.56319 0.00823 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 5016.67865 5016.67865 258.53810 258.53810 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 3990.72246 3990.72246 173.12561 173.12561 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 82.09220 0.00823 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 3844.77545 3844.77545 198.13875 198.13875 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 4963.84775 4963.84775 215.33896 215.33896 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 81.79849 0.00823 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 5014.39285 5014.39285 258.41098 258.41098 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 7837.24683 7837.24683 339.99996 339.99996 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 85.56319 0.00823 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 3969.47781 3969.47781 204.56777 204.56777 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4368.34467 4368.34467 189.50760 189.50760 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 82.09220 0.00823 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 2816.00494 2816.00494 145.12413 145.12413 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 5578.92582 5578.92582 242.03387 242.03387 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 88.20649 0.00823 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 3973.86933 3973.86933 204.79404 204.79404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 7341.08553 7341.08553 318.47454 318.47454 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 85.29620 0.00823 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 3972.85610 3972.85610 204.74192 204.74192 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4027.56902 4027.56902 174.72413 174.72413 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 82.09220 0.00823 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 2816.78080 2816.78080 145.16418 145.16418 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 5126.70701 5126.70701 222.39404 222.39404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 82.65290 0.00823 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 3972.01951 3972.01951 204.69870 204.69870 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 5760.42862 5760.42862 249.89404 249.89404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 84.49520 0.00823 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 5141.04188 5141.04188 264.93641 264.93641 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 6117.59409 6117.59409 265.40251 265.40251 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 88.34000 0.00823 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 5143.03173 5143.03173 265.04234 265.04234 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 8675.63075 8675.63075 376.35588 376.35588 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 85.56319 0.00823 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 5138.70129 5138.70129 264.80929 264.80929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5151.68415 5151.68415 223.49573 223.49573 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 82.49270 0.00823 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 3972.12955 3972.12955 204.70188 204.70188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5210.89965 5210.89965 226.05929 226.05929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 82.09220 0.00823 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 3972.14975 3972.14975 204.70294 204.70294 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 8554.52419 8554.52419 371.10165 371.10165 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 85.56319 0.00823 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 5140.53790 5140.53790 264.91522 264.91522 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 38.84000 0.00506 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2457.46 346.01691 346.01691 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 1912.66 258.38980 258.38980 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1357.68 187.99023 187.99023 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 1575.02 198.13981 198.13981 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 1778.31 238.81353 238.81353 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 1913.65 258.55929 258.55929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2306.55 323.91945 323.91945 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 1913.48 258.53810 258.53810 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1253.01 173.12561 173.12561 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 1575.02 198.13875 198.13875 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1530.20 215.33896 215.33896 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 1912.82 258.41098 258.41098 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2413.59 339.99996 339.99996 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 1611.04 204.56777 204.56777 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1362.17 189.50760 189.50760 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 1277.90 145.12413 145.12413 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 1797.80 242.03387 242.03387 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 1612.30 204.79404 204.79404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2266.42 318.47454 318.47454 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 1612.01 204.74192 204.74192 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1263.66 174.72413 174.72413 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 1278.12 145.16418 145.16418 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1589.25 222.39404 222.39404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 1611.77 204.69870 204.69870 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 2655.95 376.35588 376.35588 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 1948.72 264.80929 264.80929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1605.74 226.05929 226.05929 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 1611.80 204.70294 204.70294 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 1955.38 265.40251 265.40251 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 1949.97 265.04234 265.04234 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2620.94 371.10165 371.10165 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 1949.25 264.91522 264.91522 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1594.23 223.49573 223.49573 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 1611.80 204.70188 204.70188 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 1798.26 249.89404 249.89404 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 1949.40 264.93641 264.93641 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 346.01691
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 198.13981
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 258.55929
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 323.91945
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 198.13875
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 258.41098
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 339.99996
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 189.50760
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 242.03387
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 318.47454
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 174.72413
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 222.39404
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 264.93641
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 265.40251
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 376.35588
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 223.49573
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 226.05929
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 371.10165
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 346.01691
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 346.01691
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 346.01691
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 346.01691
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 346.01691
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 346.01691
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 198.13981
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 198.13981
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 198.13981
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 198.13981
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 198.13981
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 198.13981
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 258.55929
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 258.55929
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 258.55929
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 258.55929
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 258.55929
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 258.55929
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 323.91945
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 323.91945
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 323.91945
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 323.91945
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 323.91945
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 323.91945
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 198.13875
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 198.13875
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 198.13875
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 198.13875
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 198.13875
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 198.13875
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 258.41098
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 258.41098
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 258.41098
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 258.41098
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 258.41098
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 258.41098
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 339.99996
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 339.99996
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 339.99996
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 339.99996
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 339.99996
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 339.99996
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 189.50760
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 189.50760
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 189.50760
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 189.50760
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 189.50760
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 189.50760
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 242.03387
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 242.03387
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 242.03387
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 242.03387
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 242.03387
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 242.03387
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 318.47454
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 318.47454
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 318.47454
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 318.47454
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 318.47454
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 318.47454
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 174.72413
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 174.72413
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 174.72413
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 174.72413
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 174.72413
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 174.72413
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 222.39404
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 222.39404
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 222.39404
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 222.39404
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 222.39404
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 222.39404
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 376.35588
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 376.35588
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 376.35588
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 376.35588
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 376.35588
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 376.35588
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 226.05929
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 226.05929
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 226.05929
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 226.05929
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 226.05929
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 226.05929
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 265.40251
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 265.40251
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 265.40251
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 265.40251
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 265.40251
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 265.40251
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 371.10165
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 371.10165
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 371.10165
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 371.10165
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 371.10165
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 371.10165
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 223.49573
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 223.49573
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 223.49573
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 223.49573
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 223.49573
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 223.49573
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 264.93641
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 264.93641
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 264.93641
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 264.93641
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 264.93641
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 264.93641
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 346.01691
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 198.13981
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 258.55929
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 323.91945
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 198.13875
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 258.41098
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 339.99996
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 189.50760
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 242.03387
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 318.47454
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 174.72413
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 222.39404
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 376.35588
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 226.05929
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 265.40251
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 371.10165
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 223.49573
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 264.93641
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 346.01691
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.03505
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73604
184 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 346.01691
185 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 346.01691
186 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 346.01691
187 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 12420.65740
188 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.03505
189 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6525.99063
190 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
191 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 346.01691
192 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 346.01691
193 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 13837.70307
194 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7504.88923
195 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 198.13981
196 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.62194
197 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72021
198 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 198.13981
199 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 198.13981
200 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 198.13981
201 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7463.31279
202 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.62194
203 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5373.97564
204 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
205 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 198.13981
206 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 198.13981
207 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7923.93685
208 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6180.07197
209 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 258.55929
210 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.81794
211 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71719
212 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 258.55929
213 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 258.55929
214 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 258.55929
215 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9815.31927
216 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.81794
217 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6529.39072
218 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
219 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 258.55929
220 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 258.55929
221 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10340.34582
222 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7508.79932
223 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 323.91945
224 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.97548
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73423
226 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 323.91945
227 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 323.91945
228 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 323.91945
229 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 11705.74104
230 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.97548
231 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6528.78765
232 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
233 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 323.91945
234 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 323.91945
235 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 12954.48742
236 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7508.10580
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 198.13875
238 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.62572
239 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71764
240 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 198.13875
241 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 198.13875
242 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 198.13875
243 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 7508.58685
244 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.62572
245 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5373.95882
246 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
247 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 198.13875
248 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 198.13875
249 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7923.90167
250 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 6180.05263
251 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 258.41098
252 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.77610
253 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73495
254 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 258.41098
255 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 258.41098
256 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 258.41098
257 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 9313.24657
258 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.77610
259 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6526.53515
260 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
261 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 258.41098
262 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 258.41098
263 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10334.37373
264 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 7505.51544
265 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 339.99996
266 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.01788
267 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73582
268 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 339.99996
269 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 339.99996
270 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 339.99996
271 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 12214.59352
272 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.01788
273 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5496.85490
274 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
275 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 339.99996
276 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 339.99996
277 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 13596.84723
278 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6321.38313
279 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 189.50760
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.59208
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72142
282 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 189.50760
283 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 189.50760
284 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 189.50760
285 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 7104.98564
286 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.59208
287 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 4360.18815
288 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
289 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 189.50760
290 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 189.50760
291 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 7578.72444
292 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5014.21638
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 242.03387
294 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.76212
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71938
296 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 242.03387
297 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 242.03387
298 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 242.03387
299 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 9145.49757
300 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.76212
301 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5501.18244
302 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
303 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 242.03387
304 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 242.03387
305 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 9679.00397
306 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6326.35983
307 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 318.47454
308 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.95993
309 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73397
310 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 318.47454
311 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 318.47454
312 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 318.47454
313 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 11519.15801
314 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.95993
315 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5500.18402
316 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
317 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 318.47454
318 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 318.47454
319 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 12736.07367
320 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6325.21159
321 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 174.72413
322 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.55106
323 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71897
324 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 174.72413
325 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 174.72413
326 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 174.72413
327 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 6612.73108
328 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.55106
329 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 4360.95271
330 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
331 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 174.72413
332 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 174.72413
333 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 6987.50423
334 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 5015.09562
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 222.39404
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.67005
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73410
338 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 222.39404
339 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 222.39404
340 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 222.39404
341 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 8040.62656
342 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.67005
343 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5499.35958
344 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
345 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 222.39404
346 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 222.39404
347 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 8894.25785
348 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 6324.26350
349 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 376.35588
350 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.11865
351 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73880
352 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 376.35588
353 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 376.35588
354 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 376.35588
355 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 13423.83365
356 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.11865
357 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6649.03281
358 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
359 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 376.35588
360 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 376.35588
361 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 15051.38846
362 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7646.38774
363 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 226.05929
364 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.69378
365 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72714
366 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 226.05929
367 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 226.05929
368 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 226.05929
369 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8325.33299
370 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.69378
371 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5499.47764
372 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 226.05929
374 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 226.05929
375 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 9040.50962
376 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 6324.39926
377 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 265.40251
378 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.82878
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72155
380 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 265.40251
381 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 265.40251
382 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 265.40251
383 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9945.37167
384 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.82878
385 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6653.30020
386 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 265.40251
388 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 265.40251
389 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10613.57079
390 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7651.29522
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 371.10165
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.10436
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73747
394 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 371.10165
395 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 371.10165
396 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 371.10165
397 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 13252.34124
398 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.10436
399 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6650.84267
400 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
401 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 371.10165
402 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 371.10165
403 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 14841.28217
404 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7648.46909
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 223.49573
406 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.68887
407 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72599
408 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 223.49573
409 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 223.49573
410 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 223.49573
411 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 8266.38465
412 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.68887
413 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 5499.45771
414 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 223.49573
416 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 223.49573
417 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 8937.76686
418 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 6324.37637
419 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 264.93641
420 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.81706
421 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72585
422 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 264.93641
423 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 264.93641
424 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 264.93641
425 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 9804.74937
426 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.81706
427 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 6651.33936
428 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
429 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 264.93641
430 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 264.93641
431 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 10595.38889
432 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 7649.04026
433 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
434 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
435 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
436 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
437 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
438 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
439 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
440 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
441 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
442 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
443 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
444 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
445 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
446 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
447 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
448 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
449 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
450 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
451 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
452 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
453 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
454 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
455 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
456 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
457 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
458 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
459 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
460 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
461 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
462 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
463 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
464 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
465 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
466 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
467 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
468 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
469 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
470 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
471 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
472 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
473 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
474 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
475 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
476 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
477 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
478 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
479 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
480 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
481 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
482 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
483 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
484 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
485 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
486 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
487 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
488 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
489 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
490 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
491 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
492 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
493 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
494 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
495 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
496 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
497 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
498 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
499 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
500 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
501 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
502 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
503 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
504 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
505 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
506 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
507 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
508 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
509 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
510 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
511 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
512 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
513 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
514 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
515 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
516 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
517 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
518 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
519 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
520 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
521 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
522 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.0 3.61 12.32 12.92 12.22 12.33
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.0 3.49 11.91 12.46 12.12 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.64 12.42 13.03 12.32 12.48
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.52 12.02 12.58 12.24 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.8 3.64 12.43 13.04 12.34 12.50
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.8 3.53 12.04 12.60 12.26 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 0.9 3.62 12.34 12.93 12.23 12.35
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 0.9 3.49 11.92 12.48 12.14 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.64 12.43 13.04 12.33 12.50
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.6 3.53 12.03 12.60 12.26 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.7 3.61 12.33 12.93 12.23 12.34
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.7 3.49 11.92 12.47 12.13 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.0 3.61 12.32 12.92 12.22 12.33
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.0 3.49 11.91 12.46 12.13 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.6 3.64 12.41 13.02 12.31 12.46
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.6 3.52 12.01 12.57 12.23 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.7 3.64 12.43 13.03 12.33 12.49
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.7 3.52 12.03 12.59 12.25 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 0.9 3.62 12.34 12.94 12.24 12.35
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 0.9 3.50 11.93 12.48 12.14 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.64 12.43 13.04 12.33 12.49
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.5 3.53 12.03 12.60 12.25 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.6 3.62 12.34 12.93 12.24 12.35
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.6 3.49 11.93 12.48 12.14 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.1 3.61 12.31 12.90 12.21 12.31
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.1 3.49 11.89 12.44 12.11 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.7 3.63 12.37 12.98 12.27 12.41
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.7 3.51 11.97 12.53 12.19 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.8 3.64 12.41 13.01 12.31 12.46
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.8 3.52 12.01 12.57 12.23 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.1 3.61 12.31 12.91 12.21 12.31
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.1 3.49 11.90 12.45 12.11 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.7 3.63 12.38 12.99 12.28 12.42
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.7 3.51 11.98 12.54 12.20 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.63 12.38 12.99 12.29 12.42
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.51 11.98 12.54 12.20 -99999.


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {Btu/h} Low Temperature Heating (net) Rating Capacity {Btu/h} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 14285.4 7860.6 8.31 4
2 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 14375.1 7950.3 7.36 4
3 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 8180.3 4501.1 8.16 4
4 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 8231.8 4552.6 7.36 4
5 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 10674.8 5873.8 8.37 4
6 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 10742.0 5941.0 7.36 4
7 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 13373.7 7359.0 8.29 4
8 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 13457.6 7442.9 7.36 4
9 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 8180.3 4501.1 8.16 4
10 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 8231.8 4552.6 7.36 4
11 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 10668.6 5870.7 8.37 4
12 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 10735.9 5937.6 7.36 4
13 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 14036.6 7723.7 8.30 4
14 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 14125.0 7812.1 7.36 4
15 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 7824.1 4305.3 8.10 4
16 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 7873.2 4354.4 7.36 4
17 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 9992.0 5498.1 8.33 4
18 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 10054.8 5560.9 7.36 4
19 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 13148.1 7234.8 8.27 4
20 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 13230.7 7317.4 7.36 4
21 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 7213.7 3969.2 8.38 4
22 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 7259.0 4014.6 7.36 4
23 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 9182.0 5052.5 8.30 4
24 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 9239.7 5110.2 7.36 4
25 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 15538.2 8550.1 8.35 4
26 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 15635.8 8647.7 7.36 4
27 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 9332.8 5135.4 8.30 4
28 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 9391.5 5194.1 7.36 4
29 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 10957.0 6029.0 8.39 4
30 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 11025.9 6097.9 7.36 4
31 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 15321.6 8430.7 8.34 4
32 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 15417.8 8526.9 7.36 4
33 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 9227.1 5077.1 8.30 4
34 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 9285.1 5135.1 7.36 4
35 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 10938.2 6018.8 8.39 4
36 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 11006.8 6087.7 7.36 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 12/21 12/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 08/21 08/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 38.84 0.00 DefaultMultipliers Wetbulb 3.80 {C} 14. 120 590.6 0.00 No No
2 88.34 8.90 DefaultMultipliers Wetbulb 18.40 {C} 14. 280 807.1 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 355 1232.8 0.1424 5.7719E-002 1.0 2.45 -24. ASHRAEClearSky
2 233 1106.3 0.2000 0.1216 1.0 -3.33 12.4 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000343572 0.000288685 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000080136 0.000027722 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000115 0.000000221 Pass Pass 0.019697310 0.036266589 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000047 0.000000109 Pass Pass 0.026507367 0.048992920 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000035 0.000000072 Pass Pass 0.019682135 0.036237929 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000097 0.000000192 Pass Pass 0.019685521 0.036244124 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000047 0.000000109 Pass Pass 0.026508057 0.048993983 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000035 0.000000072 Pass Pass 0.019694809 0.036261718 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000148 0.000000281 Pass Pass 0.024520740 0.045169899 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000122 0.000000253 Pass Pass 0.035847852 0.068141105 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000089 0.000000179 Pass Pass 0.024488300 0.045095484 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000142 0.000000270 Pass Pass 0.024499591 0.045135523 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000108 0.000000227 Pass Pass 0.035842313 0.068123856 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000063 0.000000137 Pass Pass 0.024502925 0.045130738 Pass Pass
15 ATTIC SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000104778 0.000091940 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000032 0.000000058 Pass Pass 0.018544988 0.032199106 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000032 0.000000058 Pass Pass 0.018535789 0.032178129 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000123 0.000000219 Pass Pass 0.018554948 0.032219386 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000065 0.000000134 Pass Pass 0.024756349 0.043203650 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000069 0.000000139 Pass Pass 0.024753884 0.043200225 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 0.000000120 0.000000214 Pass Pass 0.018549182 0.032213572 Pass Pass
22 CRAWLSPACE SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.166730592 0.098952237 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.088134952 0.047495001 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000034641 0.000196487 Pass Pass 0.100073139 0.045464460 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000029152 0.000150078 Pass Pass 0.071495433 0.052067085 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000029615 0.000121704 Pass Pass 0.082992899 0.084455150 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000032613 0.000187772 Pass Pass 0.098593982 0.044271620 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000020111 0.000125762 Pass Pass 0.067000790 0.051043299 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000050731 0.000217241 Pass Pass 0.080249348 0.085968511 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000034294 0.000195796 Pass Pass 0.085566287 0.038222849 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000028885 0.000143434 Pass Pass 0.058364462 0.044661678 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000036277 0.000151641 Pass Pass 0.070873194 0.069573608 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000032025 0.000185736 Pass Pass 0.083818508 0.037251910 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000026216 0.000135504 Pass Pass 0.054161032 0.043772245 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000037321 0.000147858 Pass Pass 0.067669085 0.071304766 Pass Pass
36 ATTIC SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.461953720 0.369076476 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000041015 0.000166492 Pass Pass 0.073852599 0.070856582 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000040026 0.000163148 Pass Pass 0.075047534 0.070486311 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000036767 0.000210083 Pass Pass 0.091541803 0.039124599 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000032444 0.000166733 Pass Pass 0.066286959 0.041791599 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000032887 0.000165598 Pass Pass 0.066072531 0.045989915 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 0.000036461 0.000210663 Pass Pass 0.091610267 0.037209853 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.116684358 0.105726482 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.036086366 0.020840874 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.012564154 0.034069820 Pass Pass 0.357657998 1.149906984 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.018780704 0.030853199 Pass Pass 0.281299093 1.038365660 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.031185405 0.048787408 Pass Pass 0.150218701 0.464052815 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000534 0.000001519 Pass Pass 0.163001642 0.261344286 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.001704121 0.005079595 Pass Pass 0.223444109 0.791153518 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000298 0.000000669 Pass Pass 0.218968893 0.337823867 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.026510607 0.042752010 Pass Pass 0.219270632 0.578533601 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.036475273 0.038813178 Pass Pass 0.195725041 0.761700424 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.039096743 0.051987795 Pass Pass 0.169894848 0.910037716 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.008059476 0.019146661 Pass Pass 0.354536210 1.627387557 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.016316329 0.031004698 Pass Pass 0.158090542 0.331638533 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.008401577 0.017218007 Pass Pass 0.460351466 0.970606493 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.292249888 0.323170757 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000000267 0.000000602 Pass Pass 0.300505481 0.690379065 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.026993610 0.038939467 Pass Pass 0.176343983 0.657079466 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.015890666 0.032731999 Pass Pass 0.250646171 0.509492577 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.008163616 0.020600829 Pass Pass 0.182606288 0.495751115 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.022410662 0.033846745 Pass Pass 0.210856665 0.673664403 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000128842 0.000748583 Pass Pass 0.407242820 1.329879777 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2966831.42 400133.79 133623.58 0.00 235642.67 3736237.85



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 8729.00 31.00 0.00 0.00 0.00
BREEZEWAY 8713.00 47.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 7409.50 1083.67 262.67 4.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 7409.50 0.00 0.00 0.00 0.00
Max 8760.00 1083.67 262.67 4.17 0.00
Average 8691.98 55.32 12.51 0.20 0.00
Sum 182531.50 1161.67 262.67 4.17 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 8668.00 92.00 0.00 0.00 0.00
BREEZEWAY 8743.67 16.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8447.67 312.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8495.67 264.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8517.50 242.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8436.50 323.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8487.83 272.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8496.00 264.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8633.00 127.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8752.67 7.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8670.50 89.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8634.67 125.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8657.33 102.67 0.00 0.00 0.00
ATTIC 7360.17 1352.83 47.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8603.00 157.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8605.83 154.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8542.00 218.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8635.17 124.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8634.33 125.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8538.67 221.33 0.00 0.00 0.00
Min 7360.17 7.33 0.00 0.00 0.00
Max 8752.67 1352.83 47.00 0.00 0.00
Average 8538.70 219.06 2.24 0.00 0.00
Sum 179312.67 4600.33 47.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11563.05 499.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11635.18 427.20 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11608.86 453.52 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11551.20 511.18 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11630.35 432.03 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11572.56 489.82 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11844.00 218.38 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12050.84 11.54 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11894.36 168.02 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11850.04 212.34 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12050.68 11.70 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11869.53 192.85 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11774.97 287.41 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11778.18 284.20 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11723.17 339.21 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11865.69 196.69 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11860.77 201.61 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11720.25 342.13 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12050.84 511.18 0.00 0.00 0.00
Average 10087.80 251.39 0.00 0.00 0.00
Sum 211843.71 5279.15 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8447.67 312.33 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8495.67 264.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8517.50 242.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8436.50 323.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8487.83 272.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8496.00 264.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8633.00 127.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8752.67 7.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8670.50 89.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8634.67 125.33 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.50 7.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8657.33 102.67 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8603.00 157.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8605.83 154.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8542.00 218.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8635.17 124.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8634.33 125.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8538.67 221.33 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8752.67 323.50 0.00 0.00 0.00
Average 7359.09 149.48 0.00 0.00 0.00
Sum 154540.83 3139.17 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.13 0.18 0.13 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.49 0.42 0.49 0.02 0.03 0.02
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.14 0.17 0.14 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.12 0.20 0.12 0.03 0.03 0.03
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.12 0.23 0.12 0.05 0.05 0.05
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.11 0.17 0.11 0.03 0.05 0.03
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.13 0.17 0.13 0.01 0.02 0.01
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.15 0.18 0.15 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.49 0.34 0.49 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.12 0.17 0.12 0.02 0.03 0.02
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.10 0.17 0.10 0.02 0.02 0.02
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.17 0.22 0.17 0.01 0.02 0.01
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.10 0.15 0.10 0.02 0.03 0.02
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.17 0.21 0.17 0.01 0.02 0.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.11 0.15 0.11 0.02 0.03 0.02
LIVING_UNIT2_BACKROW_TOPFLOOR 0.10 0.16 0.10 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.14 0.19 0.14 0.01 0.01 0.01
LIVING_UNIT1_BACKROW_TOPFLOOR 0.11 0.16 0.11 0.04 0.04 0.04
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.49 0.42 0.49 0.05 0.05 0.05
Average 0.14 0.17 0.14 0.02 0.02 0.02
Sum 3.02 3.64 3.02 0.36 0.47 0.36


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 38.84 0.00 38.84 Wetbulb [F] 590.58 120.00
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 88.34 16.02 65.12 Wetbulb [F] 807.13 280.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.08 2      
Feb 2.32 53      
Mar 2.31 43      
Apr 1.83 14      
May 0.71 12      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.12 6      
Oct 0.00 0      
Nov 0.71 12      
Dec 0.16 4      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.049 0.051 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.027 0.028 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.048 0.051 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.217 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.217 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.350 0.217 0.883                      
North Total or Average             531.68 0.350 0.217 0.883                      
Non-North Total or Average             1595.05 0.350 0.217 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 0.99 0.92 0.00 0.99 0.78 0.00 1.00 0.67 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.12 0.95 0.79 1.00 0.99 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4843 1200.55 581.41 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 523.13
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.3333 43219.92 14404.00               12960.20


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   12420.66 9142.15 3278.50 0.74 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7463.31 5375.15 2088.16 0.72 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9815.32 7039.48 2775.84 0.72 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11705.74 8594.69 3111.06 0.73 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7508.59 5388.46 2120.13 0.72 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   9313.25 6844.81 2468.43 0.73 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   12214.59 8987.72 3226.88 0.74 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7104.99 5125.71 1979.27 0.72 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9145.50 6579.09 2566.41 0.72 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11519.16 8454.77 3064.39 0.73 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6612.73 4754.38 1858.35 0.72 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   8040.63 5902.64 2137.98 0.73 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13423.83 9917.50 3506.33 0.74 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8325.33 6053.66 2271.68 0.73 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9945.37 7176.08 2769.29 0.72 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   13252.34 9773.18 3479.16 0.74 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   8266.38 6001.30 2265.08 0.73 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   9804.75 7116.74 2688.01 0.73 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.0 3.61 12.32 12.92 12.22 12.33
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.64 12.42 13.03 12.32 12.48
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.8 3.64 12.43 13.04 12.34 12.50
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   0.9 3.62 12.34 12.93 12.23 12.35
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.6 3.64 12.43 13.04 12.33 12.50
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.7 3.61 12.33 12.93 12.23 12.34
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.0 3.61 12.32 12.92 12.22 12.33
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.6 3.64 12.41 13.02 12.31 12.46
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.7 3.64 12.43 13.03 12.33 12.49
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   0.9 3.62 12.34 12.94 12.24 12.35
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.5 3.64 12.43 13.04 12.33 12.49
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.6 3.62 12.34 12.93 12.24 12.35
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.1 3.61 12.31 12.90 12.21 12.31
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.7 3.63 12.37 12.98 12.27 12.41
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.8 3.64 12.41 13.01 12.31 12.46
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.1 3.61 12.31 12.91 12.21 12.31
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.7 3.63 12.38 12.99 12.28 12.42
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.63 12.38 12.99 12.29 12.42
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.49 11.91 12.46 12.12  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.52 12.02 12.58 12.24  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.53 12.04 12.60 12.26  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.49 11.92 12.48 12.14  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.53 12.03 12.60 12.26  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.49 11.92 12.47 12.13  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.0 3.49 11.91 12.46 12.13  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.52 12.01 12.57 12.23  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.52 12.03 12.59 12.25  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.50 11.93 12.48 12.14  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.5 3.53 12.03 12.60 12.25  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.49 11.93 12.48 12.14  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.49 11.89 12.44 12.11  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.51 11.97 12.53 12.19  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.52 12.01 12.57 12.23  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.49 11.90 12.45 12.11  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.7 3.51 11.98 12.54 12.20  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.51 11.98 12.54 12.20  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 14285.4 7860.6 8.31 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8180.3 4501.3 8.16 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10674.9 5873.9 8.37 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 13373.6 7358.9 8.29 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8180.3 4501.2 8.16 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10668.7 5870.5 8.37 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 14036.7 7723.8 8.30 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7823.9 4305.2 8.10 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 9992.2 5498.2 8.33 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 13148.1 7234.8 8.27 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7213.6 3969.3 8.38 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 9182.0 5052.5 8.30 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 15538.3 8550.1 8.35 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 9333.0 5135.5 8.30 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 10957.0 6029.1 8.39 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 15321.4 8430.7 8.34 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 9226.9 5077.2 8.30 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 10938.2 6018.8 8.39 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 14375.2 7950.4 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8231.7 4552.7 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10742.0 5941.0 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 13457.6 7443.0 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 8231.7 4552.6 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 10735.8 5937.6 7.36 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 14125.0 7812.0 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7873.1 4354.3 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 10054.9 5561.0 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 13230.8 7317.5 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 7258.9 4014.6 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 9239.7 5110.2 7.36 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 15636.0 8647.7 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 9391.6 5194.2 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11025.8 6098.0 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 15417.7 8527.0 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 9284.9 5135.2 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 11006.9 6087.5 7.36 4
ANSI/AHRI 2023 (HSPF2) ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   13837.70 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7504.89 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   7923.94 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   6180.07 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10340.35 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   7508.80 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   12954.49 3.84
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7508.11 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   7923.90 3.84
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   6180.05 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   10334.37 3.84
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   7505.52 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   13596.85 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   6321.38 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   7578.72 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   5014.22 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   9679.00 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   6326.36 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   12736.07 3.84
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   6325.21 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   6987.50 3.84
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   5015.10 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   8894.26 3.84
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   6324.26 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   15051.39 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   7646.39 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   9040.51 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   6324.40 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   10613.57 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   7651.30 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   14841.28 3.84
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   7648.47 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   8937.77 3.84
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   6324.38 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   10595.39 3.84
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   7649.04 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 346.01 130.51 0.38 1.00 2.56 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 198.14 74.74 0.38 1.00 3.55 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 258.56 97.53 0.38 1.00 3.01 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 323.93 122.18 0.38 1.00 2.65 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 198.14 74.74 0.38 1.00 3.55 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 258.41 97.47 0.38 1.00 3.01 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 339.99 128.24 0.38 1.00 2.58 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 189.51 71.48 0.38 1.00 3.65 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 242.03 91.29 0.38 1.00 3.13 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 318.47 120.12 0.38 1.00 2.67 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 174.72 65.90 0.38 1.00 3.86 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 222.40 83.89 0.38 1.00 3.30 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 376.36 141.96 0.38 1.00 2.45 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 226.06 85.27 0.38 1.00 3.26 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 265.39 100.10 0.38 1.00 2.96 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 371.11 139.98 0.38 1.00 2.47 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 223.49 84.30 0.38 1.00 3.29 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 264.94 99.93 0.38 1.00 2.97 General SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 7976.07 7976.07 6.64 346.015 346.015 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 75.00 75.00 0.00777 85.83 0.00823 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4333.37 4333.37 3.61 187.990 187.990 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 75.00 75.00 0.00812 82.49 0.00823 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5505.05 5505.05 4.59 238.821 238.821 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 75.00 75.00 0.00781 88.34 0.00823 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 7466.98 7466.98 6.22 323.930 323.930 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 75.00 75.00 0.00781 85.56 0.00823 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3990.72 3990.72 3.32 173.126 173.126 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00818 82.09 0.00823 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4963.85 4963.85 4.13 215.338 215.338 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 75.00 75.00 0.00788 81.80 0.00823 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7837.25 7837.25 6.53 339.992 339.992 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 75.00 75.00 0.00779 85.56 0.00823 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4368.34 4368.34 3.64 189.508 189.508 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00813 82.09 0.00823 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5578.93 5578.93 4.65 242.026 242.026 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 75.00 75.00 0.00779 88.21 0.00823 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 7341.09 7341.09 6.11 318.468 318.468 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 75.00 75.00 0.00783 85.30 0.00823 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4027.57 4027.57 3.35 174.724 174.724 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00817 82.09 0.00823 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5126.71 5126.71 4.27 222.403 222.403 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 75.00 75.00 0.00785 82.65 0.00823 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5760.43 5760.43 4.80 249.898 249.898 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 75.00 75.00 0.00795 84.50 0.00823 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 6117.59 6117.59 5.10 265.395 265.395 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 75.00 75.00 0.00778 88.34 0.00823 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8675.63 8675.63 7.23 376.363 376.363 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 75.00 75.00 0.00778 85.56 0.00823 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5151.68 5151.68 4.29 223.491 223.491 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 75.00 75.00 0.00805 82.49 0.00823 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5210.90 5210.90 4.34 226.060 226.060 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 75.00 75.00 0.00806 82.09 0.00823 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8554.52 8554.52 7.13 371.109 371.109 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 75.00 75.00 0.00778 85.56 0.00823 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5013.84 5013.84 4.18 258.385 258.385 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3844.79 3844.79 3.20 198.140 198.140 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00744 38.84 0.00506 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5017.29 5017.29 4.18 258.563 258.563 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5016.68 5016.68 4.18 258.531 258.531 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3844.78 3844.78 3.20 198.139 198.139 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00744 38.84 0.00506 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5014.39 5014.39 4.18 258.413 258.413 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3969.48 3969.48 3.31 204.568 204.568 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00754 38.84 0.00506 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2816.00 2816.00 2.35 145.124 145.124 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00743 38.84 0.00506 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3973.87 3973.87 3.31 204.794 204.794 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00754 38.84 0.00506 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3972.86 3972.86 3.31 204.742 204.742 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00754 38.84 0.00506 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2816.78 2816.78 2.35 145.164 145.164 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00743 38.84 0.00506 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3972.02 3972.02 3.31 204.699 204.699 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00754 38.84 0.00506 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 5141.04 5141.04 4.28 264.940 264.940 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 5143.03 5143.03 4.28 265.042 265.042 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 5138.70 5138.70 4.28 264.819 264.819 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 3972.13 3972.13 3.31 204.702 204.702 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00745 38.84 0.00506 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 3972.15 3972.15 3.31 204.703 204.703 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00745 38.84 0.00506 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 5140.54 5140.54 4.28 264.914 264.914 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 72.00 72.00 0.00753 38.84 0.00506 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.01 346.01 258.38 258.38 346.0147 346.0147 346.0147 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.99 187.99 198.14 198.14 198.1397 198.1397 198.1397 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 238.82 238.82 258.56 258.56 258.5625 258.5625 258.5625 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.93 323.93 258.53 258.53 323.9297 323.9297 323.9297 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 173.13 173.13 198.14 198.14 198.1388 198.1388 198.1388 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 215.34 215.34 258.41 258.41 258.4132 258.4132 258.4132 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.99 339.99 204.57 204.57 339.9921 339.9921 339.9921 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.51 189.51 145.12 145.12 189.5076 189.5076 189.5076 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.03 242.03 204.79 204.79 242.0256 242.0256 242.0256 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.47 318.47 204.74 204.74 318.4682 318.4682 318.4682 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.72 174.72 145.16 145.16 174.7240 174.7240 174.7240 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.40 222.40 204.70 204.70 222.4028 222.4028 222.4028 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.36 376.36 264.82 264.82 376.3632 376.3632 376.3632 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.06 226.06 204.70 204.70 226.0599 226.0599 226.0599 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.39 265.39 265.04 265.04 265.3946 265.3946 265.3946 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.11 371.11 264.91 264.91 371.1094 371.1094 371.1094 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.49 223.49 204.70 204.70 223.4908 223.4908 223.4908 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 249.90 249.90 264.94 264.94 264.9400 264.9400 264.9400 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 12420.657 9142.153 346.014709 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 11882.90 11288.88 346.014709 77.60 60.97 0.00783388 53.60 51.04 0.00750000 85.83 0.00823127 64.38 13.0038 75.00 0.00776503 41.3468 7965.63 0.00 12418.53 9054.04
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 13837.703 13837.703 346.014709 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13837.70 8322.87 346.014709 67.69 56.27 0.00720480 90.00 65.41 0.00800000 38.84 0.00505843 38.84 13.0038 72.00 0.00752563 44.3417 5013.84 0.00 13855.89 13855.89
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 7504.889 7504.889 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7504.89 7504.89 -999. 67.69 56.27 0.00720480 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00752563 44.3417 5013.84 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 7463.313 5375.148 198.139727 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 7286.40 6617.77 198.139727 77.99 61.60 0.00814960 53.60 51.04 0.00750000 82.49 0.00822834 63.26 22.7087 75.00 0.00788424 41.9739 4128.70 0.00 7462.03 5327.90
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 7923.937 7923.937 198.139727 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7923.94 5453.41 198.139727 64.47 54.47 0.00689969 90.00 65.41 0.00800000 38.84 0.00505843 38.84 22.7087 72.00 0.00744066 43.8469 3844.79 0.00 7934.35 7934.35
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 6180.072 6180.072 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6180.07 6180.07 -999. 64.47 54.47 0.00689969 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00744066 43.8469 3844.79 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 9815.319 7039.477 258.562547 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 9352.53 8829.70 258.562547 78.71 61.45 0.00789007 53.60 51.04 0.00750000 88.34 0.00823349 65.21 17.4020 75.00 0.00781034 41.5854 5505.05 0.00 9813.64 6976.79
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 10340.346 10340.346 258.562547 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10340.35 6625.90 258.562547 66.23 55.51 0.00709650 90.00 65.41 0.00800000 38.84 0.00505843 38.84 17.4020 72.00 0.00752588 44.3432 5017.29 0.00 10353.93 10353.93
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 7508.799 7508.799 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7508.80 7508.80 -999. 66.23 55.51 0.00709650 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00752588 44.3432 5017.29 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 11705.741 8594.686 323.929714 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 11222.54 10604.18 323.929714 77.66 61.05 0.00787075 53.60 51.04 0.00750000 85.56 0.00823104 64.30 13.8904 75.00 0.00779041 41.4803 7465.27 0.00 11703.73 8514.95
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 12954.487 12954.487 323.929714 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 12954.49 7894.32 323.929714 67.39 56.12 0.00718311 90.00 65.41 0.00800000 38.84 0.00505843 38.84 13.8904 72.00 0.00752584 44.3430 5016.68 0.00 12971.51 12971.51
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 7508.106 7508.106 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7508.11 7508.11 -999. 67.39 56.12 0.00718311 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00752584 44.3430 5016.68 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 7508.587 5388.457 198.138847 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 7347.37 6637.02 198.138847 78.04 61.67 0.00818930 53.60 51.04 0.00750000 82.09 0.00822799 63.13 22.7088 75.00 0.00812581 43.2433 3944.83 0.00 7507.30 5340.76
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 7923.902 7923.902 198.138847 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7923.90 5453.39 198.138847 64.47 54.47 0.00689968 90.00 65.41 0.00800000 38.84 0.00505843 38.84 22.7088 72.00 0.00744066 43.8469 3844.78 0.00 7934.31 7934.31
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6180.053 6180.053 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6180.05 6180.05 -999. 64.47 54.47 0.00689968 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00744066 43.8469 3844.78 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 9313.247 6844.815 258.413213 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 9063.19 8461.17 258.413213 77.61 61.16 0.00795165 53.60 51.04 0.00750000 81.80 0.00822773 63.03 17.4120 75.00 0.00785943 41.8430 4943.48 0.00 9311.65 6781.94
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 10334.374 10334.374 258.413213 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10334.37 6623.01 258.413213 66.22 55.51 0.00709607 90.00 65.41 0.00800000 38.84 0.00505843 38.84 17.4120 72.00 0.00752567 44.3420 5014.39 0.00 10347.95 10347.95
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 7505.515 7505.515 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7505.52 7505.52 -999. 66.22 55.51 0.00709607 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00752567 44.3420 5014.39 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 12214.594 8987.716 339.992057 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 11701.13 11091.95 339.992057 77.59 60.99 0.00784835 53.60 51.04 0.00750000 85.56 0.00823104 64.30 13.2341 75.00 0.00776762 41.3604 7835.81 0.00 12212.50 8903.49
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 13596.847 13596.847 339.992057 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 13596.85 8205.91 339.992057 67.61 56.25 0.00720951 90.00 65.41 0.00800000 38.84 0.00505843 38.84 13.2341 72.00 0.00753761 44.4110 3969.48 0.00 13614.72 13614.72
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 6321.383 6321.383 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6321.38 6321.38 -999. 67.61 56.25 0.00720951 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753761 44.4110 3969.48 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 7104.986 5125.712 189.507617 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6942.43 6302.08 189.507617 77.88 61.56 0.00815085 53.60 51.04 0.00750000 82.09 0.00822799 63.13 23.7431 75.00 0.00807619 42.9826 4317.89 0.00 7103.77 5078.68
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 7578.724 7578.724 189.507617 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7578.72 5285.86 189.507617 64.13 54.27 0.00686774 90.00 65.41 0.00800000 38.84 0.00505843 38.84 23.7431 72.00 0.00743108 43.7907 2816.00 0.00 7588.68 7588.68
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 5014.216 5014.216 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5014.22 5014.22 -999. 64.13 54.27 0.00686774 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00743108 43.7907 2816.00 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 9145.498 6579.090 242.025553 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 8714.25 8243.30 242.025553 78.65 61.41 0.00787563 53.60 51.04 0.00750000 88.21 0.00823338 65.17 18.5910 75.00 0.00779280 41.4931 5578.88 0.00 9143.93 6520.57
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 9679.004 9679.004 242.025553 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9679.00 6304.94 242.025553 65.83 55.32 0.00707703 90.00 65.41 0.00800000 38.84 0.00505843 38.84 18.5910 72.00 0.00753801 44.4134 3973.87 0.00 9691.72 9691.72
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 6326.360 6326.360 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6326.36 6326.36 -999. 65.83 55.32 0.00707703 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753801 44.4134 3973.87 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 11519.158 8454.768 318.468231 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 11058.14 10424.33 318.468231 77.65 61.07 0.00788640 53.60 51.04 0.00750000 85.30 0.00823080 64.21 14.1286 75.00 0.00780615 41.5631 7339.82 0.00 11517.18 8376.06
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 12736.074 12736.074 318.468231 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 12736.07 7788.26 318.468231 67.31 56.10 0.00718760 90.00 65.41 0.00800000 38.84 0.00505843 38.84 14.1286 72.00 0.00753792 44.4128 3972.86 0.00 12752.81 12752.81
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 6325.212 6325.212 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6325.21 6325.21 -999. 67.31 56.10 0.00718760 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753792 44.4128 3972.86 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6612.731 4754.376 174.724030 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 6469.63 5848.08 174.724030 78.02 61.66 0.00818410 53.60 51.04 0.00750000 82.09 0.00822799 63.13 25.7520 75.00 0.00815987 43.4223 4009.73 0.00 6611.60 4711.84
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6987.504 6987.504 174.724030 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6987.50 4999.00 174.724030 63.46 53.92 0.00682016 90.00 65.41 0.00800000 38.84 0.00505843 38.84 25.7520 72.00 0.00743120 43.7913 2816.78 0.00 6996.69 6996.69
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 5015.096 5015.096 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 5015.10 5015.10 -999. 63.46 53.92 0.00682016 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00743120 43.7913 2816.78 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 8040.627 5902.643 222.402810 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 7803.00 7315.04 222.402810 77.74 61.17 0.00792531 53.60 51.04 0.00750000 82.65 0.00822848 63.32 20.2313 75.00 0.00783293 41.7036 5110.88 0.00 8039.25 5847.79
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 8894.258 8894.258 222.402810 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8894.26 5924.18 222.402810 65.29 55.04 0.00703622 90.00 65.41 0.00800000 38.84 0.00505843 38.84 20.2313 72.00 0.00753784 44.4124 3972.02 0.00 8905.95 8905.95
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 6324.264 6324.264 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6324.26 6324.26 -999. 65.29 55.04 0.00703622 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753784 44.4124 3972.02 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 13423.834 9917.502 376.363170 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 12846.93 12205.18 376.363170 77.46 60.92 0.00783194 53.60 51.04 0.00750000 85.56 0.00823104 64.30 11.9552 75.00 0.00775628 41.3008 8669.04 0.00 13421.53 9824.08
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 15051.388 15051.388 376.363170 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 15051.39 8911.77 376.363170 68.03 56.46 0.00723857 90.00 65.41 0.00800000 38.84 0.00505843 38.84 11.9552 72.00 0.00753460 44.3940 5138.70 0.00 15071.17 15071.17
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 7646.388 7646.388 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7646.39 7646.39 -999. 68.03 56.46 0.00723857 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753460 44.3940 5138.70 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 8325.333 6053.656 226.059866 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 8115.56 7424.86 226.059866 77.60 61.37 0.00809030 53.60 51.04 0.00750000 82.09 0.00822799 63.13 19.9040 75.00 0.00801430 42.6575 5178.11 0.00 8323.90 5997.68
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 9040.510 9040.510 226.059866 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 9040.51 5995.19 226.059866 65.40 54.98 0.00697719 90.00 65.41 0.00800000 38.84 0.00505843 38.84 19.9040 72.00 0.00745400 43.9246 3972.15 0.00 9052.39 9052.39
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 6324.399 6324.399 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6324.40 6324.40 -999. 65.40 54.98 0.00697719 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00745400 43.9246 3972.15 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 9945.372 7176.079 265.394596 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 9458.44 8966.71 265.394596 78.45 61.31 0.00785822 53.60 51.04 0.00750000 88.34 0.00823349 65.21 16.9540 75.00 0.00778161 41.4343 6117.59 0.00 9943.67 7110.35
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 10613.571 10613.571 265.394596 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10613.57 6758.48 265.394596 66.38 55.60 0.00711505 90.00 65.41 0.00800000 38.84 0.00505843 38.84 16.9540 72.00 0.00753491 44.3958 5143.03 0.00 10627.52 10627.52
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 7651.295 7651.295 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7651.30 7651.30 -999. 66.38 55.60 0.00711505 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753491 44.3958 5143.03 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 13252.341 9773.183 371.109418 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 12684.85 12044.87 371.109418 77.47 60.93 0.00783564 53.60 51.04 0.00750000 85.56 0.00823104 64.30 12.1245 75.00 0.00778109 41.4314 8554.52 0.00 13250.07 9680.67
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 14841.282 14841.282 371.109418 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 14841.28 8809.83 371.109418 67.98 56.43 0.00723449 90.00 65.41 0.00800000 38.84 0.00505843 38.84 12.1245 72.00 0.00753473 44.3948 5140.54 0.00 14860.79 14860.79
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 7648.469 7648.469 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7648.47 7648.47 -999. 67.98 56.43 0.00723449 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753473 44.3948 5140.54 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 8266.385 6001.300 223.490761 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 8050.74 7369.04 223.490761 77.70 61.40 0.00808899 53.60 51.04 0.00750000 82.49 0.00822834 63.26 20.1328 75.00 0.00801999 42.6874 5118.53 0.00 8264.97 5944.98
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 8937.767 8937.767 223.490761 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 8937.77 5945.33 223.490761 65.32 54.94 0.00697170 90.00 65.41 0.00800000 38.84 0.00505843 38.84 20.1328 72.00 0.00745400 43.9246 3972.13 0.00 8949.51 8949.51
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 6324.376 6324.376 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 6324.38 6324.38 -999. 65.32 54.94 0.00697170 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00745400 43.9246 3972.13 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 9804.749 7116.741 264.939954 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 9474.22 8787.70 264.939954 77.90 61.34 0.00800085 53.60 51.04 0.00750000 84.50 0.00823009 63.94 16.9831 75.00 0.00780146 41.5381 5703.11 0.00 9803.07 7049.83
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 10595.389 10595.389 264.939954 -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 10595.39 6749.65 264.939954 66.37 55.60 0.00711421 90.00 65.41 0.00800000 38.84 0.00505843 38.84 16.9831 72.00 0.00753477 44.3950 5141.04 0.00 10609.31 10609.31
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 7649.040 7649.040 -999. -999. -999.00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 7649.04 7649.04 -999. 66.37 55.60 0.00711421 90.00 65.41 0.00800000 38.84 0.00505843 38.84 -999.000 72.00 0.00753477 44.3950 5141.04 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12420.657 9142.153 346.014709 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 346.014709 0.42550294   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 16:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 Sensible 11882.90 11288.88 0.9567 0.42550294 346.014709 77.60 60.97 0.00783388 10.8 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 445.315 11437.58 85.83 0.00823127 64.38 44.99498340 13.0038 75.00 0.00777448 75.00 0.00776503 41.3468 7965.63 0.00 12418.53 9054.04 0.40869879 80.00 67.00 0.01118466 13.2 54.78 54.74 0.00909917 8.5
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 13837.703 13837.703 346.014709 -999. -999.00 -999.0000 1.00000 0.96877 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 346.014709 0.42550294   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13837.70 8322.87 1.0000 0.42550294 346.014709 67.69 56.27 0.00720480 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 13837.70 38.84 0.00505843 38.84 44.99498340 13.0038 72.00 0.00752563 72.00 0.00752563 44.3417 5013.84 0.00 13855.89 13855.89 0.41798417 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7504.889 7504.889 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 346.014709 0.42550294   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7504.89 7504.89 1.0000 -0.260274E+04 -999. 67.69 56.27 0.00720480 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7504.89 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00752563 72.00 0.00752563 44.3417 5013.84 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7463.313 5375.148 198.139727 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 198.139727 0.24365737   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 7286.40 6617.77 0.9763 0.24365737 198.139727 77.99 61.60 0.00814960 11.1 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 255.002 7031.40 82.49 0.00822834 63.26 44.99498340 22.7087 75.00 0.00812482 75.00 0.00788424 41.9739 4128.70 0.00 7462.03 5327.90 0.23403475 80.00 67.00 0.01118466 13.2 54.08 54.06 0.00887454 8.3
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 7923.937 7923.937 198.139727 -999. -999.00 -999.0000 1.00000 0.92323 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 198.139727 0.24365737   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7923.94 5453.41 1.0000 0.24365737 198.139727 64.47 54.47 0.00689969 8.5 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7923.94 38.84 0.00505843 38.84 44.99498340 22.7087 72.00 0.00744066 72.00 0.00744066 43.8469 3844.79 0.00 7934.35 7934.35 0.23935187 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6180.072 6180.072 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 198.139727 0.24365737   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6180.07 6180.07 1.0000 -0.260274E+04 -999. 64.47 54.47 0.00689969 8.5 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6180.07 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00744066 72.00 0.00744066 43.8469 3844.79 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9815.319 7039.477 258.562547 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 258.562547 0.31796083   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 Sensible 9352.53 8829.70 0.9529 0.31796083 258.562547 78.71 61.45 0.00789007 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 332.765 9019.77 88.34 0.00823349 65.21 44.99498340 17.4020 75.00 0.00781034 75.00 0.00781034 41.5854 5505.05 0.00 9813.64 6976.79 0.30540378 80.00 67.00 0.01118466 13.2 53.98 53.94 0.00883148 8.3
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 10340.346 10340.346 258.562547 -999. -999.00 -999.0000 1.00000 0.91608 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 258.562547 0.31796083   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10340.35 6625.90 1.0000 0.31796083 258.562547 66.23 55.51 0.00709650 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 10340.35 38.84 0.00505843 38.84 44.99498340 17.4020 72.00 0.00752588 72.00 0.00752588 44.3432 5017.29 0.00 10353.93 10353.93 0.31234236 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7508.799 7508.799 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 258.562547 0.31796083   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7508.80 7508.80 1.0000 -0.260274E+04 -999. 66.23 55.51 0.00709650 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7508.80 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00752588 72.00 0.00752588 44.3432 5017.29 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11705.741 8594.686 323.929714 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 323.929714 0.39834447   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 11222.54 10604.18 0.9587 0.39834447 323.929714 77.66 61.05 0.00787075 10.9 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 416.892 10805.65 85.56 0.00823104 64.30 44.99498340 13.8904 75.00 0.00781264 75.00 0.00779041 41.4803 7465.27 0.00 11703.73 8514.95 0.38261287 80.00 67.00 0.01118466 13.2 54.67 54.65 0.00907332 8.5
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 12954.487 12954.487 323.929714 -999. -999.00 -999.0000 1.00000 0.96233 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 323.929714 0.39834447   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 12954.49 7894.32 1.0000 0.39834447 323.929714 67.39 56.12 0.00718311 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 12954.49 38.84 0.00505843 38.84 44.99498340 13.8904 72.00 0.00752584 72.00 0.00752584 44.3430 5016.68 0.00 12971.51 12971.51 0.39130560 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7508.106 7508.106 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 323.929714 0.39834447   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7508.11 7508.11 1.0000 -0.260274E+04 -999. 67.39 56.12 0.00718311 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7508.11 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00752584 72.00 0.00752584 44.3430 5016.68 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7508.587 5388.457 198.138847 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 198.138847 0.24365629   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 7347.37 6637.02 0.9785 0.24365629 198.138847 78.04 61.67 0.00818930 11.1 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 255.001 7092.37 82.09 0.00822799 63.13 44.99498340 22.7088 75.00 0.00817572 75.00 0.00812581 43.2433 3944.83 0.00 7507.30 5340.76 0.23403371 80.00 67.00 0.01118466 13.2 54.01 53.97 0.00883945 8.3
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 7923.902 7923.902 198.138847 -999. -999.00 -999.0000 1.00000 0.91766 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 198.138847 0.24365629   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7923.90 5453.39 1.0000 0.24365629 198.138847 64.47 54.47 0.00689968 8.5 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7923.90 38.84 0.00505843 38.84 44.99498340 22.7088 72.00 0.00744066 72.00 0.00744066 43.8469 3844.78 0.00 7934.31 7934.31 0.23935081 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6180.053 6180.053 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 198.138847 0.24365629   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6180.05 6180.05 1.0000 -0.260274E+04 -999. 64.47 54.47 0.00689968 8.5 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6180.05 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00744066 72.00 0.00744066 43.8469 3844.78 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9313.247 6844.815 258.413213 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 258.413213 0.31777719   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 09:50:00 Sensible 9063.19 8461.17 0.9732 0.31777719 258.413213 77.61 61.16 0.00795165 10.9 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 332.573 8730.62 81.80 0.00822773 63.03 44.99498340 17.4120 75.00 0.00787872 75.00 0.00785943 41.8430 4943.48 0.00 9311.65 6781.94 0.30522739 80.00 67.00 0.01118466 13.2 54.71 54.69 0.00908505 8.5
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 10334.374 10334.374 258.413213 -999. -999.00 -999.0000 1.00000 0.96491 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 258.413213 0.31777719   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10334.37 6623.01 1.0000 0.31777719 258.413213 66.22 55.51 0.00709607 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 10334.37 38.84 0.00505843 38.84 44.99498340 17.4120 72.00 0.00752567 72.00 0.00752567 44.3420 5014.39 0.00 10347.95 10347.95 0.31216197 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7505.515 7505.515 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 258.413213 0.31777719   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7505.52 7505.52 1.0000 -0.260274E+04 -999. 66.22 55.51 0.00709607 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7505.52 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00752567 72.00 0.00752567 44.3420 5014.39 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 12214.594 8987.716 339.992057 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 339.992057 0.41809673   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 11701.13 11091.95 0.9580 0.41809673 339.992057 77.59 60.99 0.00784835 10.9 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 437.563 11263.56 85.56 0.00823104 64.30 44.99498340 13.2341 75.00 0.00778998 75.00 0.00776762 41.3604 7835.81 0.00 12212.50 8903.49 0.40158507 80.00 67.00 0.01118466 13.2 54.76 54.73 0.00909722 8.5
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 13596.847 13596.847 339.992057 -999. -999.00 -999.0000 1.00000 0.96797 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 339.992057 0.41809673   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 13596.85 8205.91 1.0000 0.41809673 339.992057 67.61 56.25 0.00720951 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 13596.85 38.84 0.00505843 38.84 44.99498340 13.2341 72.00 0.00753761 72.00 0.00753761 44.4110 3969.48 0.00 13614.72 13614.72 0.41070883 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6321.383 6321.383 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 339.992057 0.41809673   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6321.38 6321.38 1.0000 -0.260274E+04 -999. 67.61 56.25 0.00720951 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6321.38 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753761 72.00 0.00753761 44.4110 3969.48 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7104.986 5125.712 189.507617 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 189.507617 0.23304225   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6942.43 6302.08 0.9771 0.23304225 189.507617 77.88 61.56 0.00815085 11.1 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 243.893 6698.54 82.09 0.00822799 63.13 44.99498340 23.7431 75.00 0.00812683 75.00 0.00807619 42.9826 4317.89 0.00 7103.77 5078.68 0.22383885 80.00 67.00 0.01118466 13.2 54.16 54.12 0.00889274 8.3
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 7578.724 7578.724 189.507617 -999. -999.00 -999.0000 1.00000 0.92755 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 189.507617 0.23304225   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7578.72 5285.86 1.0000 0.23304225 189.507617 64.13 54.27 0.00686774 8.4 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7578.72 38.84 0.00505843 38.84 44.99498340 23.7431 72.00 0.00743108 72.00 0.00743108 43.7907 2816.00 0.00 7588.68 7588.68 0.22892432 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5014.216 5014.216 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 189.507617 0.23304225   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5014.22 5014.22 1.0000 -0.260274E+04 -999. 64.13 54.27 0.00686774 8.4 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 5014.22 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00743108 72.00 0.00743108 43.7907 2816.00 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9145.498 6579.090 242.025553 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 242.025553 0.29762487   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 13:50:00 Sensible 8714.25 8243.30 0.9528 0.29762487 242.025553 78.65 61.41 0.00787563 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 311.482 8402.77 88.21 0.00823338 65.17 44.99498340 18.5910 75.00 0.00779393 75.00 0.00779280 41.4931 5578.88 0.00 9143.93 6520.57 0.28587094 80.00 67.00 0.01118466 13.2 54.03 54.01 0.00885989 8.3
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 9679.004 9679.004 242.025553 -999. -999.00 -999.0000 1.00000 0.92029 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 242.025553 0.29762487   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9679.00 6304.94 1.0000 0.29762487 242.025553 65.83 55.32 0.00707703 8.8 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 9679.00 38.84 0.00505843 38.84 44.99498340 18.5910 72.00 0.00753801 72.00 0.00753801 44.4134 3973.87 0.00 9691.72 9691.72 0.29236575 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6326.360 6326.360 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 242.025553 0.29762487   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6326.36 6326.36 1.0000 -0.260274E+04 -999. 65.83 55.32 0.00707703 8.8 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6326.36 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753801 72.00 0.00753801 44.4134 3973.87 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11519.158 8454.768 318.468231 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 318.468231 0.39162835   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 Sensible 11058.14 10424.33 0.9600 0.39162835 318.468231 77.65 61.07 0.00788640 10.9 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 409.863 10648.27 85.30 0.00823080 64.21 44.99498340 14.1286 75.00 0.00782974 75.00 0.00780615 41.5631 7339.82 0.00 11517.18 8376.06 0.37616199 80.00 67.00 0.01118466 13.2 54.65 54.64 0.00906921 8.5
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 12736.074 12736.074 318.468231 -999. -999.00 -999.0000 1.00000 0.96143 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 318.468231 0.39162835   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 12736.07 7788.26 1.0000 0.39162835 318.468231 67.31 56.10 0.00718760 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 12736.07 38.84 0.00505843 38.84 44.99498340 14.1286 72.00 0.00753792 72.00 0.00753792 44.4128 3972.86 0.00 12752.81 12752.81 0.38470815 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6325.212 6325.212 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 318.468231 0.39162835   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6325.21 6325.21 1.0000 -0.260274E+04 -999. 67.31 56.10 0.00718760 9.1 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6325.21 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753792 72.00 0.00753792 44.4128 3972.86 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 6612.731 4754.376 174.724030 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 174.724030 0.21486251   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 6469.63 5848.08 0.9784 0.21486251 174.724030 78.02 61.66 0.00818410 11.1 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 224.867 6244.76 82.09 0.00822799 63.13 44.99498340 25.7520 75.00 0.00816888 75.00 0.00815987 43.4223 4009.73 0.00 6611.60 4711.84 0.20637706 80.00 67.00 0.01118466 13.2 54.00 53.98 0.00885266 8.3
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 6987.504 6987.504 174.724030 -999. -999.00 -999.0000 1.00000 0.91885 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 174.724030 0.21486251   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6987.50 4999.00 1.0000 0.21486251 174.724030 63.46 53.92 0.00682016 8.3 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6987.50 38.84 0.00505843 38.84 44.99498340 25.7520 72.00 0.00743120 72.00 0.00743120 43.7913 2816.78 0.00 6996.69 6996.69 0.21106582 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 5015.096 5015.096 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 174.724030 0.21486251   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 5015.10 5015.10 1.0000 -0.260274E+04 -999. 63.46 53.92 0.00682016 8.3 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 5015.10 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00743120 72.00 0.00743120 43.7913 2816.78 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8040.627 5902.643 222.402810 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 222.402810 0.27349429   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 10:10:00 Sensible 7803.00 7315.04 0.9704 0.27349429 222.402810 77.74 61.17 0.00792531 10.9 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 286.228 7516.77 82.65 0.00822848 63.32 44.99498340 20.2313 75.00 0.00784842 75.00 0.00783293 41.7036 5110.88 0.00 8039.25 5847.79 0.26269334 80.00 67.00 0.01118466 13.2 54.66 54.64 0.00907128 8.5
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 8894.258 8894.258 222.402810 -999. -999.00 -999.0000 1.00000 0.96188 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 222.402810 0.27349429   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8894.26 5924.18 1.0000 0.27349429 222.402810 65.29 55.04 0.00703622 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 8894.26 38.84 0.00505843 38.84 44.99498340 20.2313 72.00 0.00753784 72.00 0.00753784 44.4124 3972.02 0.00 8905.95 8905.95 0.26866157 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6324.264 6324.264 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 222.402810 0.27349429   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6324.26 6324.26 1.0000 -0.260274E+04 -999. 65.29 55.04 0.00703622 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6324.26 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753784 72.00 0.00753784 44.4124 3972.02 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13423.834 9917.502 376.363170 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 376.363170 0.46282320   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:10:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 12846.93 12205.18 0.9570 0.46282320 376.363170 77.46 60.92 0.00783194 10.8 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 484.372 12362.55 85.56 0.00823104 64.30 44.99498340 11.9552 75.00 0.00777775 75.00 0.00775628 41.3008 8669.04 0.00 13421.53 9824.08 0.44454518 80.00 67.00 0.01118466 13.2 54.85 54.83 0.00913458 8.6
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 15051.388 15051.388 376.363170 -999. -999.00 -999.0000 1.00000 0.97499 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 376.363170 0.46282320   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 15051.39 8911.77 1.0000 0.46282320 376.363170 68.03 56.46 0.00723857 9.2 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 15051.39 38.84 0.00505843 38.84 44.99498340 11.9552 72.00 0.00753460 72.00 0.00753460 44.3940 5138.70 0.00 15071.17 15071.17 0.45464497 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7646.388 7646.388 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 376.363170 0.46282320   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7646.39 7646.39 1.0000 -0.260274E+04 -999. 68.03 56.46 0.00723857 9.2 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7646.39 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753460 72.00 0.00753460 44.3940 5138.70 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8325.333 6053.656 226.059866 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 226.059866 0.27799147   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 19:00:00 Sensible 8115.56 7424.86 0.9748 0.27799147 226.059866 77.60 61.37 0.00809030 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 290.935 7824.62 82.09 0.00822799 63.13 44.99498340 19.9040 75.00 0.00805609 75.00 0.00801430 42.6575 5178.11 0.00 8323.90 5997.68 0.26701291 80.00 67.00 0.01118466 13.2 54.43 54.38 0.00897761 8.4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 9040.510 9040.510 226.059866 -999. -999.00 -999.0000 1.00000 0.94426 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 226.059866 0.27799147   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 9040.51 5995.19 1.0000 0.27799147 226.059866 65.40 54.98 0.00697719 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 9040.51 38.84 0.00505843 38.84 44.99498340 19.9040 72.00 0.00745400 72.00 0.00745400 43.9246 3972.15 0.00 9052.39 9052.39 0.27307927 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6324.399 6324.399 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 226.059866 0.27799147   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6324.40 6324.40 1.0000 -0.260274E+04 -999. 65.40 54.98 0.00697719 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6324.40 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00745400 72.00 0.00745400 43.9246 3972.15 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9945.372 7176.079 265.394596 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 265.394596 0.32636237   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 14:40:00 Sensible 9458.44 8966.71 0.9510 0.32636237 265.394596 78.45 61.31 0.00785822 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 341.558 9116.88 88.34 0.00823349 65.21 44.99498340 16.9540 75.00 0.00778161 75.00 0.00778161 41.4343 6117.59 0.00 9943.67 7110.35 0.31347352 80.00 67.00 0.01118466 13.2 54.17 54.13 0.00889491 8.3
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 10613.571 10613.571 265.394596 -999. -999.00 -999.0000 1.00000 0.92799 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 265.394596 0.32636237   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10613.57 6758.48 1.0000 0.32636237 265.394596 66.38 55.60 0.00711505 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 10613.57 38.84 0.00505843 38.84 44.99498340 16.9540 72.00 0.00753491 72.00 0.00753491 44.3958 5143.03 0.00 10627.52 10627.52 0.32059544 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7651.295 7651.295 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 265.394596 0.32636237   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7651.30 7651.30 1.0000 -0.260274E+04 -999. 66.38 55.60 0.00711505 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7651.30 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753491 72.00 0.00753491 44.3958 5143.03 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13252.341 9773.183 371.109418 -999. -999.00 -999.0000 1.00000 1.00000 0.2435 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 371.109418 0.45636253   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 17:20:00 Sensible 12684.85 12044.87 0.9572 0.45636253 371.109418 77.47 60.93 0.00783564 10.8 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 477.611 12207.24 85.56 0.00823104 64.30 44.99498340 12.1245 75.00 0.00778109 75.00 0.00778109 41.4314 8554.52 0.00 13250.07 9680.67 0.43833966 80.00 67.00 0.01118466 13.2 54.86 54.81 0.00912176 8.5
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 14841.282 14841.282 371.109418 -999. -999.00 -999.0000 1.00000 0.97383 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 371.109418 0.45636253   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 14841.28 8809.83 1.0000 0.45636253 371.109418 67.98 56.43 0.00723449 9.2 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 14841.28 38.84 0.00505843 38.84 44.99498340 12.1245 72.00 0.00753473 72.00 0.00753473 44.3948 5140.54 0.00 14860.79 14860.79 0.44829846 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7648.469 7648.469 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 371.109418 0.45636253   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7648.47 7648.47 1.0000 -0.260274E+04 -999. 67.98 56.43 0.00723449 9.2 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7648.47 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753473 72.00 0.00753473 44.3948 5140.54 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 8266.385 6001.300 223.490761 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 223.490761 0.27483218   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:20:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:40:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:50:00 Sensible 8050.74 7369.04 0.9739 0.27483218 223.490761 77.70 61.40 0.00808899 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 287.628 7763.11 82.49 0.00822834 63.26 44.99498340 20.1328 75.00 0.00805387 75.00 0.00801999 42.6874 5118.53 0.00 8264.97 5944.98 0.26397838 80.00 67.00 0.01118466 13.2 54.36 54.32 0.00895822 8.4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 8937.767 8937.767 223.490761 -999. -999.00 -999.0000 1.00000 0.94019 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 223.490761 0.27483218   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 8937.77 5945.33 1.0000 0.27483218 223.490761 65.32 54.94 0.00697170 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 8937.77 38.84 0.00505843 38.84 44.99498340 20.1328 72.00 0.00745400 72.00 0.00745400 43.9246 3972.13 0.00 8949.51 8949.51 0.26997581 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 6324.376 6324.376 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 223.490761 0.27483218   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 6324.38 6324.38 1.0000 -0.260274E+04 -999. 65.32 54.94 0.00697170 8.7 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 6324.38 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00745400 72.00 0.00745400 43.9246 3972.13 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9804.749 7116.741 264.939954 -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 264.939954 0.32580328   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 15:30:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB 8/21 18:00:00 Sensible 9474.22 8787.70 0.9663 0.32580328 264.939954 77.90 61.34 0.00800085 11.0 53.60 51.04 0.00750000 7.4 -999. -999.0 -999.0 -999.0 340.973 9133.24 84.50 0.00823009 63.94 44.99498340 16.9831 75.00 0.00795051 75.00 0.00780146 41.5381 5703.11 0.00 9803.07 7049.83 0.31293652 80.00 67.00 0.01118466 13.2 54.35 54.31 0.00895581 8.4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 10595.389 10595.389 264.939954 -999. -999.00 -999.0000 1.00000 0.93969 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 264.939954 0.32580328   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 10595.39 6749.65 1.0000 0.32580328 264.939954 66.37 55.60 0.00711421 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 10595.39 38.84 0.00505843 38.84 44.99498340 16.9831 72.00 0.00753477 72.00 0.00753477 44.3950 5141.04 0.00 10609.31 10609.31 0.32004624 70.00 60.00 0.00875166 10.4 107.76 72.17 0.00875166 15.5
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 7649.040 7649.040 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0738 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 264.939954 0.32580328   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 unknown unknown SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB 12/21 15:00:00 Sensible 7649.04 7649.04 1.0000 -0.260274E+04 -999. 66.37 55.60 0.00711421 8.9 90.00 65.41 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 7649.04 38.84 0.00505843 38.84 44.99498340 -999.000 72.00 0.00753477 72.00 0.00753477 44.3950 5141.04 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2588.50 4426.00 410.67
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1985.33 4010.83 334.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2241.33 4113.33 336.50
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2191.33 5239.50 426.83
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1734.67 5182.00 351.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1983.67 5113.50 360.67
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2839.33 3375.50 182.67
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2212.00 2654.17 13.33
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2517.50 3042.67 136.33
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2394.67 4199.33 187.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1872.33 3849.50 14.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2236.00 4035.83 157.00
LIVING_UNIT3_BACKROW_TOPFLOOR 2390.50 4448.33 230.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 2655.33 3691.83 224.17
LIVING_UNIT1_FRONTROW_TOPFLOOR 2867.00 4020.17 296.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2242.33 4351.50 184.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 2510.67 3476.50 185.17
LIVING_UNIT1_BACKROW_TOPFLOOR 2561.17 4610.67 302.00
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3364.17 5784.83 477.00
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.088 0.000 0.271
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.078 0.000 0.271
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.088 0.000 0.271
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.088 0.000 0.271
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.077 0.000 0.271
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.088 0.000 0.271
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.039 0.000 0.271
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.028 0.000 0.271
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.039 0.000 0.271
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.039 0.000 0.271
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.028 0.000 0.271
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.039 0.000 0.271
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.088 0.000 0.271
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.271
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.089 0.000 0.271
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.078 0.000 0.271
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.078 0.000 0.271
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.088 0.000 0.271
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.005
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 7765370.18 31626192.18 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 6864822.62 30725644.62 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 7779680.79 31640502.79 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 7732282.37 31593104.37 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 6819318.51 30680140.51 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 7740344.89 31601166.89 23785081.69 2170.00 3433.17 3204.83 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 3423556.09 27285767.61 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 2500665.57 26362877.08 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 3428728.34 27290939.86 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 3410870.32 27273081.84 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 2487527.32 26349738.83 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 3415607.67 27277819.19 23785081.69 2161.00 3432.17 3214.83 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 7779103.42 31642705.91 23785081.69 2153.50 3431.67 3222.83 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 7806316.99 31669919.48 23785081.69 2153.50 3431.67 3222.83 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 7790922.68 31654525.17 23785081.69 2153.50 3431.67 3222.83 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 6857661.29 30721263.78 23785081.69 2153.50 3431.67 3222.83 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 6888205.10 30751807.59 23785081.69 2153.50 3431.67 3222.83 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 7767714.77 31631317.26 23785081.69 2153.50 3431.67 3222.83 0.00
Total Facility 0.00 0.429520E+09 0.429520E+09 0.108259E+09 0.537779E+09 0.428131E+09 2170.00 3449.67 3222.83 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 14.6900 59.8283 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 12.9864 58.1247 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 14.7171 59.8553 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 14.6274 59.7657 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 12.9003 58.0386 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 14.6427 59.7809 44.9950 2170.00 3433.17 3204.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 6.4764 51.6173 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 4.7306 49.8715 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 6.4862 51.6271 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 6.4525 51.5933 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 4.7057 49.8466 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 6.4614 51.6023 44.9950 2161.00 3432.17 3214.83
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 14.7160 59.8595 44.9950 2153.50 3431.67 3222.83
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 14.7675 59.9110 44.9950 2153.50 3431.67 3222.83
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 14.7383 59.8819 44.9950 2153.50 3431.67 3222.83
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 12.9729 58.1164 44.9950 2153.50 3431.67 3222.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 13.0306 58.1742 44.9950 2153.50 3431.67 3222.83
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 14.6944 59.8380 44.9950 2153.50 3431.67 3222.83
Total Facility 0.0000 812.5361 812.5361 204.7964 1017.3324 809.9097 2170.00 3449.67 3222.83


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 23860822.00 23860822.00 23785081.69 2170.00 3433.17 3204.83 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 23862211.51 23862211.51 23785081.69 2161.00 3432.17 3214.83 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 23863602.49 23863602.49 23785081.69 2153.50 3431.67 3222.83 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 45.1383 45.1383 44.9950 2170.00 3433.17 3204.83
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 45.1409 45.1409 44.9950 2161.00 3432.17 3214.83
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 45.1435 45.1435 44.9950 2153.50 3431.67 3222.83


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1940
Defaulted Fields 1825
Fields with Defaults 6415
Autosized Fields 378
Autosizable Fields 576
Autocalculated Fields 161
Autocalculatable Fields 349



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
Electricity:Building 101263.28 6311.77 02-JAN-03:10 19306.63 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
Electricity:SpaceType:GENERAL 101263.28 6311.77 02-JAN-03:10 19306.63 01-JAN-18:10
InteriorLights:Electricity 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
General:InteriorLights:Electricity 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 12960.20 290.23 01-JAN-00:10 4221.57 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5625.74 350.65 02-JAN-03:10 1072.59 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 720.01 16.12 01-JAN-00:10 234.53 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 7532.56 578.57 15-JAN-08:10 2101.78 29-SEP-15:20
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
ElectricityPurchased:Plant 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
Cogeneration:ElectricityPurchased 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
General:Cogeneration:ElectricityPurchased 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
ElectricityNet:Plant 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
Cogeneration:ElectricityNet 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
General:Cogeneration:ElectricityNet 173656.84 8268.04 17-JAN-03:40 76825.15 02-JAN-19:10
Electricity:HVAC 24095.58 578.57 15-JAN-08:10 12133.16 30-MAR-04:00
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-08:00 578.57 01-JAN-00:10
General:Fans:Electricity 2464.27 0.00 14-JAN-02:10 1523.20 29-SEP-15:20
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 12342.07 0.00 01-JAN-00:10 9328.01 29-SEP-15:10
General:Cooling:Electricity 12342.07 0.00 01-JAN-00:10 9328.01 29-SEP-15:10
Heating:Electricity 4220.95 0.00 03-JAN-14:50 10710.03 30-MAR-04:00
General:Heating:Electricity 4220.95 0.00 03-JAN-14:50 10710.03 30-MAR-04:00
Electricity:Plant 42263.68 0.00 01-JAN-00:10 55071.77 01-JAN-08:00
WaterSystems:Electricity 42263.68 0.00 01-JAN-00:10 55071.77 01-JAN-08:00
Water Heater:WaterSystems:Electricity 42263.68 0.00 01-JAN-00:10 55071.77 01-JAN-08:00
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 465905.71 536.80 06-JUL-03:00 262049.50 29-SEP-15:20
EnergyTransfer:Building 174441.22 0.00 14-JAN-02:10 123939.62 29-SEP-15:20
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 20987.61 0.00 03-JAN-14:50 61353.87 08-JAN-06:50
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 20987.61 0.00 03-JAN-14:50 61353.87 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 153453.60 0.00 01-JAN-00:10 123939.62 29-SEP-15:20
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 153453.60 0.00 01-JAN-00:10 123939.62 29-SEP-15:20
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11459.83 0.00 01-JAN-14:50 9526.07 29-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1635.50 0.00 01-JAN-14:50 4132.36 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1635.50 0.00 01-JAN-14:50 4132.36 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9824.33 0.00 01-JAN-00:10 9526.07 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9824.33 0.00 01-JAN-00:10 9526.07 29-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7593.33 0.00 01-JAN-12:20 6465.67 16-OCT-14:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 761.85 0.00 01-JAN-12:20 2934.68 30-MAR-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 761.85 0.00 01-JAN-12:20 2934.68 30-MAR-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6831.48 0.00 01-JAN-00:10 6465.67 16-OCT-14:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6831.48 0.00 01-JAN-00:10 6465.67 16-OCT-14:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10445.58 0.00 01-JAN-08:00 8160.60 16-OCT-12:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1508.92 0.00 01-JAN-08:00 4168.20 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1508.92 0.00 01-JAN-08:00 4168.20 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8936.67 0.00 01-JAN-00:10 8160.60 16-OCT-12:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8936.67 0.00 01-JAN-00:10 8160.60 16-OCT-12:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8911.39 0.00 02-JAN-14:00 7942.08 29-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2207.53 0.00 02-JAN-14:00 4372.64 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2207.53 0.00 02-JAN-14:00 4372.64 08-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6703.86 0.00 01-JAN-00:10 7942.08 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 6703.86 0.00 01-JAN-00:10 7942.08 29-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5164.56 0.00 01-JAN-19:10 4255.19 29-SEP-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1266.65 0.00 01-JAN-19:10 3148.23 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1266.65 0.00 01-JAN-19:10 3148.23 08-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3897.91 0.00 01-JAN-00:10 4255.19 29-SEP-19:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3897.91 0.00 01-JAN-00:10 4255.19 29-SEP-19:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7803.47 0.00 03-JAN-11:50 6025.28 29-SEP-13:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1997.53 0.00 03-JAN-11:50 4353.40 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1997.53 0.00 03-JAN-11:50 4353.40 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5805.94 0.00 01-JAN-00:10 6025.28 29-SEP-13:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5805.94 0.00 01-JAN-00:10 6025.28 29-SEP-13:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12801.07 0.00 01-JAN-12:00 9099.15 29-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 659.02 0.00 01-JAN-12:00 2901.51 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 659.02 0.00 01-JAN-12:00 2901.51 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12142.05 0.00 01-JAN-00:10 9099.15 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12142.05 0.00 01-JAN-00:10 9099.15 29-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9821.62 0.00 01-JAN-00:10 6083.71 16-OCT-13:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 178.46 0.00 01-JAN-00:10 1794.53 30-MAR-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 178.46 0.00 01-JAN-00:10 1794.53 30-MAR-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9643.15 0.00 01-JAN-00:10 6083.71 16-OCT-13:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 9643.15 0.00 01-JAN-00:10 6083.71 16-OCT-13:20
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12093.58 0.00 01-JAN-07:50 7787.53 16-OCT-13:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 602.12 0.00 01-JAN-07:50 2949.10 30-MAR-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 602.12 0.00 01-JAN-07:50 2949.10 30-MAR-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11491.46 0.00 01-JAN-00:10 7787.53 16-OCT-13:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11491.46 0.00 01-JAN-00:10 7787.53 16-OCT-13:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9634.67 0.00 01-JAN-15:30 7517.76 29-SEP-15:40
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1001.49 0.00 01-JAN-15:30 3160.74 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1001.49 0.00 01-JAN-15:30 3160.74 08-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8633.18 0.00 01-JAN-00:10 7517.76 29-SEP-15:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8633.18 0.00 01-JAN-00:10 7517.76 29-SEP-15:40
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6450.57 0.00 01-JAN-00:10 4325.21 29-SEP-19:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 409.00 0.00 01-JAN-00:10 2016.24 03-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 409.00 0.00 01-JAN-00:10 2016.24 03-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6041.57 0.00 01-JAN-00:10 4325.21 29-SEP-19:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6041.57 0.00 01-JAN-00:10 4325.21 29-SEP-19:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8757.84 0.00 01-JAN-08:30 5832.15 29-SEP-13:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 892.50 0.00 01-JAN-08:30 3213.43 03-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 892.50 0.00 01-JAN-08:30 3213.43 03-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7865.33 0.00 01-JAN-00:10 5832.15 29-SEP-13:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7865.33 0.00 01-JAN-00:10 5832.15 29-SEP-13:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 9985.73 0.00 03-JAN-11:50 7004.57 29-SEP-14:10
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 1658.58 0.00 03-JAN-11:50 4351.14 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 1658.58 0.00 03-JAN-11:50 4351.14 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8327.15 0.00 01-JAN-00:10 7004.57 29-SEP-14:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8327.15 0.00 01-JAN-00:10 7004.57 29-SEP-14:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 12113.97 0.00 01-JAN-08:20 8362.78 29-SEP-13:30
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 1282.40 0.00 01-JAN-08:20 4152.06 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 1282.40 0.00 01-JAN-08:20 4152.06 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10831.57 0.00 01-JAN-00:10 8362.78 29-SEP-13:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10831.57 0.00 01-JAN-00:10 8362.78 29-SEP-13:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 13095.50 0.00 01-JAN-14:40 10007.87 29-SEP-15:30
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 1422.74 0.00 01-JAN-14:40 4111.55 08-JAN-06:50
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 1422.74 0.00 01-JAN-14:40 4111.55 08-JAN-06:50
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 11672.76 0.00 01-JAN-00:10 10007.87 29-SEP-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 11672.76 0.00 01-JAN-00:10 10007.87 29-SEP-15:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 7558.41 0.00 01-JAN-18:10 5541.21 29-SEP-16:10
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1003.00 0.00 01-JAN-18:10 3132.00 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 1003.00 0.00 01-JAN-18:10 3132.00 08-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6555.41 0.00 01-JAN-00:10 5541.21 29-SEP-16:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6555.41 0.00 01-JAN-00:10 5541.21 29-SEP-16:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 9617.30 0.00 01-JAN-00:10 6570.53 29-SEP-14:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 608.32 0.00 01-JAN-00:10 2843.76 30-MAR-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 608.32 0.00 01-JAN-00:10 2843.76 30-MAR-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 9008.98 0.00 01-JAN-00:10 6570.53 29-SEP-14:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 9008.98 0.00 01-JAN-00:10 6570.53 29-SEP-14:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 11132.80 0.00 01-JAN-19:20 9044.79 29-SEP-15:40
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 1892.00 0.00 01-JAN-19:20 4360.89 08-JAN-07:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 1892.00 0.00 01-JAN-19:20 4360.89 08-JAN-07:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9240.79 0.00 01-JAN-00:10 9044.79 29-SEP-15:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9240.79 0.00 01-JAN-00:10 9044.79 29-SEP-15:40
PlantLoopHeatingDemand:Facility 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
PlantLoopHeatingDemand:Plant 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
EnergyTransfer:HVAC 219556.88 0.00 14-JAN-02:10 131596.30 29-SEP-15:30
CoolingCoils:EnergyTransfer 199323.25 0.00 01-JAN-00:10 131596.30 29-SEP-15:30
HeatingCoils:EnergyTransfer 20233.63 0.00 03-JAN-14:50 58190.24 08-JAN-06:50
EnergyTransfer:Plant 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
WaterSystems:EnergyTransfer 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 71907.61 529.12 02-AUG-03:00 17599.25 12-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 1635.444 -818.14 0.000 0.000 2982.669 2458.419 10464.601 9200.355 0.000 86.353 0.003 0.000 -4139.45 0.000 -7691.68 -5172.52
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 761.822 -568.91 0.000 0.000 2958.685 2458.419 10464.601 4053.278 0.000 83.599 0.000 0.000 -1703.19 0.000 -7570.94 -4674.82
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 1508.859 -744.22 0.000 0.000 2981.278 2458.419 10464.601 8565.765 0.000 86.341 0.005 0.000 -4064.70 0.000 -7737.94 -5325.98
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 2207.466 -558.27 0.000 0.000 2998.788 2458.419 10464.601 6262.075 0.000 87.851 0.000 0.000 -4149.59 0.000 -7561.21 -6064.66
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 1266.614 -324.61 0.000 0.000 2985.143 2458.419 10464.601 1009.146 0.000 84.750 0.000 0.000 -1707.93 0.000 -7368.32 -5294.52
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 1997.452 -483.50 0.000 0.000 3002.739 2458.419 10464.601 5559.610 0.000 86.366 0.000 0.000 -3991.25 0.000 -7578.18 -6193.84
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 658.998 -1011.15 0.000 0.000 2945.413 2458.419 10464.601 9081.105 0.000 72.957 0.076 0.000 -4317.79 0.000 -6781.03 -2440.74
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 178.459 -803.06 0.000 0.000 2917.841 2458.419 10464.601 4001.055 0.000 70.256 0.063 0.000 -1775.87 0.000 -6654.32 -2017.31
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 602.099 -956.98 0.000 0.000 2943.518 2458.419 10464.601 8460.823 0.000 72.936 0.027 0.000 -4238.15 0.000 -6815.23 -2457.60
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 1001.456 -718.94 0.000 0.000 2959.228 2458.419 10464.601 6157.463 0.000 73.661 0.050 0.000 -4333.87 0.000 -6685.74 -3462.13
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 408.985 -503.13 0.000 0.000 2939.154 2458.419 10464.601 973.424 0.000 70.721 0.009 0.000 -1786.56 0.000 -6518.53 -2968.66
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 892.466 -655.01 0.000 0.000 2961.696 2458.419 10464.601 5463.345 0.000 72.956 0.035 0.000 -4172.04 0.000 -6711.50 -3564.63
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 1658.518 -693.46 0.000 0.000 2979.002 2458.419 10464.601 5471.939 0.000 85.046 0.000 0.000 -4157.50 0.000 -7730.61 -2902.30
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 1282.354 -902.02 0.000 0.000 2965.009 2458.419 10464.601 8474.628 0.000 84.984 0.047 0.000 -4198.43 0.000 -7840.55 -2859.49
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 1422.694 -972.07 0.000 0.000 2967.378 2458.419 10464.601 9081.077 0.000 85.014 0.054 0.000 -4266.05 0.000 -7791.42 -2749.09
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 1002.969 -545.92 0.000 0.000 2959.353 2458.419 10464.601 975.152 0.000 83.399 0.000 0.000 -1775.70 0.000 -7538.90 -2073.91
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 608.302 -750.24 0.000 0.000 2942.774 2458.419 10464.601 4004.415 0.000 82.309 0.056 0.000 -1756.82 0.000 -7675.19 -2119.85
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 1891.945 -769.54 0.000 0.000 2977.892 2458.419 10464.601 6141.471 0.000 86.575 0.000 0.000 -4297.43 0.000 -7699.27 -2783.53
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 13770.485 55395.761 0.000 0.000 0.000 -69166.25 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 26407.301 202303.149 0.000 0.000 0.000 -228710.45 -1.02
Total Facility 0.000 0.000 20986.902 -12779.17 0.000 0.000 53367.561 44251.534 188362.826 102936.124 0.000 41633.859 257699.338 0.000 -60832.31 0.000 -429827.25 -65126.60


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-SEP-15:30 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 178.80 1147.45 6050.74 0.00 996.79 1037.10 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 16-OCT-13:05 0.00 0.00 0.00 -0.5 0.00 0.00 114.81 103.15 1084.63 2444.56 0.00 925.59 1793.25 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 16-OCT-12:20 0.00 0.00 0.00 -0.7 0.00 0.00 115.08 103.15 1090.63 4317.01 0.00 1424.50 1110.53 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-SEP-15:30 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 178.80 1147.45 5341.41 0.00 996.76 162.49 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-SEP-18:00 0.00 0.00 0.00 -0.4 0.00 0.00 426.75 722.08 1724.99 21.74 0.00 499.76 859.58 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-SEP-12:00 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 103.15 1090.63 2064.97 0.00 1418.04 1233.56 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-SEP-15:30 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 178.80 1147.45 6033.57 0.00 834.01 790.13 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 16-OCT-13:20 0.00 0.00 0.00 -0.5 0.00 0.00 115.05 103.15 1084.63 2837.99 0.00 898.40 1044.95 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 16-OCT-13:20 0.00 0.00 0.00 -0.6 0.00 0.00 115.04 103.15 1084.63 3756.09 0.00 942.01 1786.72 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 29-SEP-15:39 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 178.80 1147.45 5120.22 0.00 814.77 142.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-SEP-18:00 0.00 0.00 0.00 -0.4 0.00 0.00 426.75 722.08 1724.99 19.86 0.00 451.60 979.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-SEP-12:00 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 103.15 1090.63 2077.27 0.00 1174.84 1271.31 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-SEP-14:15 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 103.15 1091.85 1741.15 0.00 1197.29 2756.06 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-SEP-13:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 103.15 1084.63 3513.66 0.00 1319.13 2227.31 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-SEP-15:30 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 178.80 1147.45 6003.37 0.00 992.77 1570.33 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-SEP-16:15 0.00 0.00 0.00 -0.5 0.00 0.00 140.35 385.11 1350.56 405.50 0.00 841.34 2418.50 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-SEP-14:25 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 103.15 1091.85 1860.54 0.00 1128.15 2271.91 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 29-SEP-15:39 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 178.80 1147.45 5081.34 0.00 966.03 1557.00 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-SEP-15:25 0.00 0.00 0.00 -10.3 0.00 0.00 2071.63 3218.39 20654.06 49819.38 0.00 49564.21 55257.00 0.00 0.00 0.00 -56640.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 08-JAN-06:54 0.00 0.00 4133.84 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1744.4 0.00 -2811.1 -1575.4
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 30-MAR-04:00 0.00 0.00 2934.63 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -587.2 0.00 -2240.2 -1630.4
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 08-JAN-06:54 0.00 0.00 4169.69 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1743.9 0.00 -2811.1 -1611.7
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 08-JAN-06:04 0.00 0.00 4374.11 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1689.6 0.00 -2877.5 -1804.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 08-JAN-06:04 0.00 0.00 3149.58 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -687.1 0.00 -2768.8 -1690.8
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 08-JAN-06:54 0.00 0.00 4354.86 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1738.2 0.00 -2811.1 -1802.6
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 08-JAN-06:54 0.00 0.00 2902.98 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1783.6 0.00 -2320.4 -796.0
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 30-MAR-04:00 0.00 0.00 1794.49 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -604.4 0.00 -1819.2 -894.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 30-MAR-04:00 0.00 0.00 2949.04 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -1478.9 0.00 -1909.2 -1084.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 08-JAN-06:04 0.00 0.00 3162.10 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1725.8 0.00 -2368.1 -1065.3
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 03-JAN-04:00 0.00 0.00 2016.14 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -663.2 0.00 -2010.7 -865.4
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 03-JAN-04:00 0.00 0.00 3213.28 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -1625.8 0.00 -2097.9 -1012.7
LIVING_UNIT3_BACKROW_TOPFLOOR 08-JAN-06:54 0.00 0.00 4352.61 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1763.8 0.00 -2816.6 -1769.2
LIVING_UNIT3_FRONTROW_TOPFLOOR 08-JAN-06:54 0.00 0.00 4153.55 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1773.2 0.00 -2816.6 -1560.9
LIVING_UNIT1_FRONTROW_TOPFLOOR 08-JAN-06:54 0.00 0.00 4113.03 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1769.7 0.00 -2816.6 -1523.8
LIVING_UNIT2_BACKROW_TOPFLOOR 08-JAN-06:04 0.00 0.00 3133.36 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -696.8 0.00 -2774.0 -1659.6
LIVING_UNIT2_FRONTROW_TOPFLOOR 30-MAR-04:00 0.00 0.00 2843.71 0.00 0.00 0.00 526.24 165.05 831.88 0.00 0.00 0.00 0.00 0.00 -598.9 0.00 -2245.2 -1522.7
LIVING_UNIT1_BACKROW_TOPFLOOR 08-JAN-06:04 0.00 0.00 4362.37 0.00 0.00 0.00 526.24 385.11 1085.68 0.00 0.00 0.00 0.00 0.00 -1713.0 0.00 -2882.9 -1763.4
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 08-JAN-06:54 0.00 0.00 61380.68 0.00 0.00 0.00 9472.36 6931.93 19542.30 0.00 0.00 4276.41 19811.68 0.00 -25462.0 0.00 -95953.3 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.0147 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 346.0147 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 198.1397 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 198.1397 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 258.5625 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.5625 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.9297 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 323.9297 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 198.1388 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 198.1388 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 258.4132 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.4132 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.9921 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 339.9921 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.5076 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 189.5076 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.0256 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 242.0256 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.4682 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 318.4682 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.7240 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 174.7240 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.4028 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 222.4028 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.3632 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 376.3632 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.0599 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 226.0599 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.3946 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 265.3946 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.1094 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 371.1094 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.4908 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 223.4908 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.9400 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 264.9400 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.0147 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 346.0147 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 198.1397 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 198.1397 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 258.5625 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.5625 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.9297 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 323.9297 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 198.1388 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 198.1388 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 258.4132 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 258.4132 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.9921 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 339.9921 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.5076 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 189.5076 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.0256 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 242.0256 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.4682 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 318.4682 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.7240 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 174.7240 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.4028 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 222.4028 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.3632 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 376.3632 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.0599 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 226.0599 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.3946 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 265.3946 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.1094 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 371.1094 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.4908 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 223.4908 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.9400 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 264.9400 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 346.0147 346.0147 346.0147 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 198.1397 198.1397 198.1397 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.5625 258.5625 258.5625 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.9297 323.9297 323.9297 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 198.1388 198.1388 198.1388 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.4132 258.4132 258.4132 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 339.9921 339.9921 339.9921 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 189.5076 189.5076 189.5076 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 242.0256 242.0256 242.0256 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 318.4682 318.4682 318.4682 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 174.7240 174.7240 174.7240 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 222.4028 222.4028 222.4028 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 264.9400 264.9400 264.9400 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 265.3946 265.3946 265.3946 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 376.3632 376.3632 376.3632 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 223.4908 223.4908 223.4908 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 226.0599 226.0599 226.0599 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.1094 371.1094 371.1094 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.0147 346.0147 346.0147 346.0147 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 198.1397 198.1397 198.1397 198.1397 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 258.5625 258.5625 258.5625 258.5625 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.9297 323.9297 323.9297 323.9297 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 198.1388 198.1388 198.1388 198.1388 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 258.4132 258.4132 258.4132 258.4132 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.9921 339.9921 339.9921 339.9921 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.5076 189.5076 189.5076 189.5076 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.0256 242.0256 242.0256 242.0256 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.4682 318.4682 318.4682 318.4682 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.7240 174.7240 174.7240 174.7240 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.4028 222.4028 222.4028 222.4028 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.3632 376.3632 376.3632 376.3632 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.0599 226.0599 226.0599 226.0599 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.3946 265.3946 265.3946 265.3946 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.1094 371.1094 371.1094 371.1094 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.4908 223.4908 223.4908 223.4908 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.9400 264.9400 264.9400 264.9400 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 346.0147 346.0147 346.0147 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 198.1397 198.1397 198.1397 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.5625 258.5625 258.5625 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 323.9297 323.9297 323.9297 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 198.1388 198.1388 198.1388 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 258.4132 258.4132 258.4132 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 339.9921 339.9921 339.9921 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 189.5076 189.5076 189.5076 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 242.0256 242.0256 242.0256 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 318.4682 318.4682 318.4682 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 174.7240 174.7240 174.7240 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 222.4028 222.4028 222.4028 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 264.9400 264.9400 264.9400 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 265.3946 265.3946 265.3946 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 376.3632 376.3632 376.3632 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 223.4908 223.4908 223.4908 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 226.0599 226.0599 226.0599 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 371.1094 371.1094 371.1094 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 346.0147 346.0147 346.0147 346.0147 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 198.1397 198.1397 198.1397 198.1397 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 258.5625 258.5625 258.5625 258.5625 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 323.9297 323.9297 323.9297 323.9297 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 198.1388 198.1388 198.1388 198.1388 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 258.4132 258.4132 258.4132 258.4132 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 339.9921 339.9921 339.9921 339.9921 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.5076 189.5076 189.5076 189.5076 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 242.0256 242.0256 242.0256 242.0256 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 318.4682 318.4682 318.4682 318.4682 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 174.7240 174.7240 174.7240 174.7240 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 222.4028 222.4028 222.4028 222.4028 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 376.3632 376.3632 376.3632 376.3632 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 226.0599 226.0599 226.0599 226.0599 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 265.3946 265.3946 265.3946 265.3946 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 371.1094 371.1094 371.1094 371.1094 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 223.4908 223.4908 223.4908 223.4908 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 264.9400 264.9400 264.9400 264.9400 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Sec1.1A-General Information

Data
Weather File ANNUAL ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Total gross floor area [ft2] 39005.22
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 4220.95 10710.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 12342.07 9328.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 12960.20 4221.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 2464.27 1523.20 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 42263.68 55071.77 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 592936.91
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 592936.91


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.33
Space Heating 0.11
Space Cooling 0.32
Fans (All) 0.19
Service Water Heating 1.08
Receptacle Equipment 2.26
Miscellaneous (All) 4.45
Subtotal 4.45


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 7.46
Space Heating 2.43
Space Cooling 7.11
Fans (All) 4.34
Service Water Heating 24.34
Receptacle Equipment 50.85
Miscellaneous 3.47


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 17:56:16

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 276.389 6.961 234.014 10.843 10.843
February 191.194 4.932 240.500 7.406 7.406
March 183.833 5.093 317.958 9.228 9.228
April 320.000 10.174 137.208 10.988 10.988
May 320.333 8.573 109.375 9.212 9.212
June 450.319 13.532 8.833 13.560 13.560
July 585.217 20.684 0.000 20.684 20.684
August 599.994 22.152 0.000 22.152 22.152
September 486.347 17.573 9.056 17.598 17.598
October 517.097 17.950 46.222 18.242 18.242
November 296.411 8.042 169.472 9.693 9.693
December 286.564 7.850 228.292 11.064 11.064
           
Annual Sum or Average 4513.700 143.516 1500.931 160.669 160.669
Minimum of Months 183.833 4.932 0.000 7.406 7.406
Maximum of Months 599.994 22.152 317.958 22.152 22.152



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 322.331 5.650 165.722 7.677 7.677
February 206.778 3.405 166.708 4.556 4.556
March 181.764 2.910 240.857 5.272 5.272
April 334.014 5.674 53.194 5.893 5.893
May 329.117 4.170 43.944 4.352 4.352
June 498.850 8.006 0.000 8.006 8.006
July 668.236 13.710 0.000 13.710 13.710
August 678.250 15.693 0.000 15.693 15.693
September 552.803 12.809 0.000 12.809 12.809
October 556.125 14.380 14.833 14.437 14.437
November 346.069 6.240 97.250 6.847 6.847
December 332.975 6.356 166.039 7.915 7.915
           
Annual Sum or Average 5007.311 99.005 948.549 107.166 107.166
Minimum of Months 181.764 2.910 0.000 4.352 4.352
Maximum of Months 678.250 15.693 240.857 15.693 15.693



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 299.275 6.216 204.153 9.728 9.728
February 205.769 4.045 226.667 6.390 6.390
March 199.728 4.209 289.083 8.104 8.104
April 364.781 8.657 116.583 9.390 9.390
May 371.890 6.792 93.167 7.365 7.365
June 470.708 11.520 8.167 11.546 11.546
July 588.208 18.900 0.000 18.900 18.900
August 602.325 20.737 0.000 20.737 20.737
September 500.139 15.296 8.667 15.323 15.323
October 541.719 16.281 40.750 16.551 16.551
November 323.769 6.708 147.306 8.222 8.222
December 307.731 6.821 209.889 9.787 9.787
           
Annual Sum or Average 4776.043 126.180 1344.431 142.042 142.042
Minimum of Months 199.728 4.045 0.000 6.390 6.390
Maximum of Months 602.325 20.737 289.083 20.737 20.737



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 103.861 1.522 338.958 7.030 7.030
February 87.250 1.074 318.444 4.344 4.344
March 115.528 2.070 374.216 6.883 6.883
April 274.833 7.025 152.753 7.932 7.932
May 310.986 7.781 105.672 8.389 8.389
June 457.681 13.432 8.333 13.456 13.456
July 592.208 20.007 0.000 20.007 20.007
August 593.928 19.461 0.000 19.461 19.461
September 459.292 13.083 10.375 13.115 13.115
October 472.569 11.815 60.514 12.186 12.186
November 148.667 1.989 251.681 4.390 4.390
December 120.639 1.700 328.917 6.395 6.395
           
Annual Sum or Average 3737.442 100.959 1949.863 123.589 123.589
Minimum of Months 87.250 1.074 0.000 4.344 4.344
Maximum of Months 593.928 20.007 374.216 20.007 20.007



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 99.611 1.051 316.833 4.623 4.623
February 31.083 0.164 268.264 2.032 2.032
March 64.167 0.459 332.494 3.536 3.536
April 241.167 2.630 66.883 2.897 2.897
May 312.406 3.472 39.497 3.634 3.634
June 509.533 8.054 0.000 8.054 8.054
July 677.000 13.234 0.000 13.234 13.234
August 674.975 13.120 0.000 13.120 13.120
September 521.744 8.251 0.167 8.251 8.251
October 506.333 8.260 22.111 8.347 8.347
November 104.778 0.797 188.192 1.952 1.952
December 105.458 0.865 320.833 3.776 3.776
           
Annual Sum or Average 3848.256 60.355 1555.275 73.455 73.455
Minimum of Months 31.083 0.164 0.000 1.952 1.952
Maximum of Months 677.000 13.234 332.494 13.234 13.234



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 103.083 1.332 315.000 6.336 6.336
February 52.931 0.346 288.514 3.420 3.420
March 116.623 1.376 330.681 5.891 5.891
April 322.800 5.609 126.000 6.424 6.424
May 366.896 6.234 90.722 6.790 6.790
June 478.231 11.969 7.000 11.993 11.993
July 593.333 19.132 0.000 19.132 19.132
August 599.811 19.054 0.000 19.054 19.054
September 484.161 11.366 9.667 11.400 11.400
October 518.758 10.602 46.833 10.921 10.921
November 112.806 1.065 195.333 3.151 3.151
December 121.681 1.266 340.972 5.601 5.601
           
Annual Sum or Average 3871.113 89.351 1750.722 110.112 110.112
Minimum of Months 52.931 0.346 0.000 3.151 3.151
Maximum of Months 599.811 19.132 340.972 19.132 19.132



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 342.483 8.999 153.583 10.987 10.987
February 253.736 6.517 139.439 7.505 7.505
March 236.931 6.608 187.375 8.533 8.533
April 400.937 12.701 34.528 12.851 12.851
May 415.937 11.275 22.500 11.381 11.381
June 572.403 17.072 0.000 17.072 17.072
July 714.931 24.761 0.000 24.761 24.761
August 707.639 26.135 0.000 26.135 26.135
September 598.592 20.982 0.000 20.982 20.982
October 583.836 20.884 11.917 20.923 20.923
November 372.594 10.333 85.250 10.871 10.871
December 357.236 9.816 148.353 11.280 11.280
           
Annual Sum or Average 5557.254 176.083 782.944 183.281 183.281
Minimum of Months 236.931 6.517 0.000 7.505 7.505
Maximum of Months 714.931 26.135 187.375 26.135 26.135



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 422.214 8.316 83.389 8.975 8.975
February 302.097 5.410 59.606 5.618 5.618
March 263.858 4.669 107.667 5.438 5.438
April 457.517 8.695 4.333 8.719 8.719
May 475.750 7.303 0.000 7.303 7.303
June 647.908 12.154 0.000 12.154 12.154
July 740.500 18.177 0.000 18.177 18.177
August 741.583 20.043 0.000 20.043 20.043
September 687.389 16.888 0.000 16.888 16.888
October 661.131 17.868 0.000 17.868 17.868
November 446.733 9.173 15.139 9.221 9.221
December 429.589 8.989 60.736 9.331 9.331
           
Annual Sum or Average 6276.269 137.684 330.869 139.733 139.733
Minimum of Months 263.858 4.669 0.000 5.438 5.438
Maximum of Months 741.583 20.043 107.667 20.043 20.043



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 373.631 8.431 130.250 10.200 10.200
February 269.819 5.742 128.739 6.662 6.662
March 265.541 5.904 173.014 7.745 7.745
April 448.672 11.548 26.833 11.678 11.678
May 465.036 9.865 17.500 9.953 9.953
June 584.272 15.131 0.000 15.131 15.131
July 708.778 22.774 0.000 22.774 22.774
August 706.500 24.558 0.000 24.558 24.558
September 601.414 18.657 0.000 18.657 18.657
October 602.772 19.312 10.167 19.353 19.353
November 407.975 9.204 74.917 9.707 9.707
December 385.667 8.968 133.833 10.294 10.294
           
Annual Sum or Average 5820.077 160.094 695.253 166.711 166.711
Minimum of Months 265.541 5.742 0.000 6.662 6.662
Maximum of Months 708.778 24.558 173.014 24.558 24.558



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 162.917 2.264 241.194 5.360 5.360
February 150.000 1.956 197.500 3.390 3.390
March 170.806 3.159 231.896 5.494 5.494
April 357.617 9.362 38.667 9.544 9.544
May 408.625 10.467 20.917 10.562 10.562
June 581.031 17.026 0.000 17.026 17.026
July 717.431 24.135 0.000 24.135 24.135
August 705.994 23.528 0.000 23.528 23.528
September 582.547 16.493 0.000 16.493 16.493
October 543.989 14.564 17.833 14.629 14.629
November 244.972 3.295 147.842 4.236 4.236
December 179.681 2.395 237.611 4.848 4.848
           
Annual Sum or Average 4805.609 128.643 1133.460 139.245 139.245
Minimum of Months 150.000 1.956 0.000 3.390 3.390
Maximum of Months 717.431 24.135 241.194 24.135 24.135



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 163.750 1.814 191.403 3.367 3.367
February 120.611 0.828 117.594 1.317 1.317
March 141.694 1.375 158.058 2.488 2.488
April 394.344 5.215 5.917 5.252 5.252
May 469.879 6.534 0.167 6.534 6.534
June 656.206 12.187 0.000 12.187 12.187
July 740.917 17.596 0.000 17.596 17.596
August 740.389 17.464 0.000 17.464 17.464
September 678.403 12.328 0.000 12.328 12.328
October 626.894 11.446 0.000 11.446 11.446
November 208.556 1.920 54.056 2.116 2.116
December 181.264 1.630 176.806 2.672 2.672
           
Annual Sum or Average 5122.907 90.336 704.000 94.767 94.767
Minimum of Months 120.611 0.828 0.000 1.317 1.317
Maximum of Months 740.917 17.596 191.403 17.596 17.596



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 146.758 2.013 206.153 4.764 4.764
February 138.306 1.043 176.000 2.371 2.371
March 174.790 2.508 205.306 4.724 4.724
April 430.967 8.473 30.083 8.631 8.631
May 463.672 9.400 16.333 9.484 9.484
June 590.458 15.637 0.000 15.637 15.637
July 711.347 22.983 0.000 22.983 22.983
August 705.028 22.925 0.000 22.925 22.925
September 590.550 14.875 0.000 14.875 14.875
October 585.847 13.653 12.833 13.711 13.711
November 205.642 2.069 108.028 2.893 2.893
December 176.833 1.998 205.375 4.204 4.204
           
Annual Sum or Average 4920.198 117.577 960.111 127.202 127.202
Minimum of Months 138.306 1.043 0.000 2.371 2.371
Maximum of Months 711.347 22.983 206.153 22.983 22.983



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 295.764 7.656 210.375 11.300 11.300
February 201.667 5.520 212.958 7.700 7.700
March 203.472 6.075 278.597 9.724 9.724
April 352.028 12.383 100.872 12.940 12.940
May 361.608 11.155 71.653 11.563 11.563
June 500.169 17.266 3.250 17.271 17.271
July 647.403 25.484 0.000 25.484 25.484
August 654.622 26.650 0.000 26.650 26.650
September 519.450 20.637 5.000 20.650 20.650
October 532.994 20.346 32.917 20.548 20.548
November 320.000 8.947 145.764 10.365 10.365
December 299.875 8.367 208.278 11.312 11.312
           
Annual Sum or Average 4889.053 170.487 1269.664 185.506 185.506
Minimum of Months 201.667 5.520 0.000 7.700 7.700
Maximum of Months 654.622 26.650 278.597 26.650 26.650



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 339.464 6.748 145.750 8.556 8.556
February 231.083 4.281 133.000 5.192 5.192
March 215.250 4.122 194.853 6.082 6.082
April 379.925 8.341 26.847 8.446 8.446
May 394.056 7.167 21.722 7.250 7.250
June 567.192 12.284 0.000 12.284 12.284
July 715.194 19.052 0.000 19.052 19.052
August 711.611 20.722 0.000 20.722 20.722
September 601.750 16.405 0.000 16.405 16.405
October 589.589 17.264 6.417 17.281 17.281
November 367.911 7.590 68.653 8.009 8.009
December 355.931 7.312 143.083 8.601 8.601
           
Annual Sum or Average 5468.956 131.288 740.325 137.881 137.881
Minimum of Months 215.250 4.122 0.000 5.192 5.192
Maximum of Months 715.194 20.722 194.853 20.722 20.722



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 320.053 6.907 182.264 10.150 10.150
February 219.661 4.627 196.250 6.656 6.656
March 221.926 5.179 252.389 8.567 8.567
April 402.772 10.885 82.139 11.356 11.356
May 416.239 9.429 56.083 9.760 9.760
June 521.169 15.265 2.667 15.269 15.269
July 649.569 23.586 0.000 23.586 23.586
August 659.900 25.149 0.000 25.149 25.149
September 533.347 18.349 3.667 18.361 18.361
October 560.328 18.666 27.917 18.848 18.848
November 350.008 7.632 123.417 8.904 8.904
December 325.933 7.352 191.917 10.029 10.029
           
Annual Sum or Average 5180.906 153.027 1118.708 166.636 166.636
Minimum of Months 219.661 4.627 0.000 6.656 6.656
Maximum of Months 659.900 25.149 252.389 25.149 25.149



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 153.528 2.456 296.583 7.472 7.472
February 136.083 2.176 271.139 4.999 4.999
March 162.944 3.877 316.519 8.003 8.003
April 324.667 10.591 110.156 11.202 11.202
May 356.994 10.874 69.306 11.256 11.256
June 504.581 17.457 2.500 17.460 17.460
July 652.750 25.392 0.000 25.392 25.392
August 652.422 25.359 0.000 25.359 25.359
September 502.681 17.951 5.333 17.966 17.966
October 501.011 15.690 44.861 15.953 15.953
November 221.722 3.534 213.375 5.575 5.575
December 160.819 2.579 293.625 6.819 6.819
           
Annual Sum or Average 4330.203 137.937 1623.397 157.456 157.456
Minimum of Months 136.083 2.176 0.000 4.999 4.999
Maximum of Months 652.750 25.392 316.519 25.392 25.392



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 131.889 1.844 243.222 4.939 4.939
February 105.361 0.936 201.639 2.385 2.385
March 139.806 1.994 238.223 4.422 4.422
April 343.411 6.478 32.036 6.610 6.610
May 387.625 6.872 20.500 6.944 6.944
June 575.378 12.472 0.000 12.472 12.472
July 717.736 18.940 0.000 18.940 18.940
August 711.667 19.388 0.000 19.388 19.388
September 586.758 13.621 0.000 13.621 13.621
October 550.122 12.447 12.425 12.479 12.479
November 182.611 2.030 137.542 2.869 2.869
December 148.542 1.670 243.225 4.101 4.101
           
Annual Sum or Average 4580.906 98.692 1128.812 109.170 109.170
Minimum of Months 105.361 0.936 0.000 2.385 2.385
Maximum of Months 717.736 19.388 243.225 19.388 19.388



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 134.194 1.999 261.625 6.462 6.462
February 122.972 1.166 242.333 3.741 3.741
March 171.625 2.949 277.833 6.744 6.744
April 385.828 9.108 85.250 9.618 9.618
May 413.008 9.207 53.833 9.523 9.523
June 525.961 15.611 2.333 15.614 15.614
July 653.278 23.750 0.000 23.750 23.750
August 660.233 24.213 0.000 24.213 24.213
September 525.756 15.924 4.667 15.939 15.939
October 544.922 14.171 32.389 14.384 14.384
November 184.583 2.172 157.139 3.869 3.869
December 152.278 1.977 267.153 5.792 5.792
           
Annual Sum or Average 4474.638 122.245 1384.556 139.650 139.650
Minimum of Months 122.972 1.166 0.000 3.741 3.741
Maximum of Months 660.233 24.213 277.833 24.213 24.213



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 444.84 0.00 0.00
February 355.53 0.00 0.00
March 502.70 0.00 0.00
April 112.28 0.00 0.00
May 84.44 0.00 0.00
June 3.99 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.54 0.00 0.00
October 38.55 0.00 0.00
November 219.58 0.00 0.00
December 397.92 0.00 0.00
       
Annual Sum or Average 179.89 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 502.70 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 226.47 0.00 0.00
February 164.48 0.00 0.00
March 283.41 0.00 0.00
April 29.44 0.00 0.00
May 23.56 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 7.28 0.00 0.00
November 79.41 0.00 0.00
December 191.20 0.00 0.00
       
Annual Sum or Average 83.73 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 283.41 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 400.37 0.00 0.00
February 337.13 0.00 0.00
March 471.22 0.00 0.00
April 100.87 0.00 0.00
May 75.19 0.00 0.00
June 3.67 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 3.86 0.00 0.00
October 35.56 0.00 0.00
November 201.15 0.00 0.00
December 367.53 0.00 0.00
       
Annual Sum or Average 165.95 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 471.22 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 660.27 0.00 0.00
February 477.77 0.00 0.00
March 594.44 0.00 0.00
April 125.79 0.00 0.00
May 80.19 0.00 0.00
June 3.31 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 4.49 0.00 0.00
October 49.70 0.00 0.00
November 327.60 0.00 0.00
December 598.78 0.00 0.00
       
Annual Sum or Average 243.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 660.27 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 426.65 0.00 0.00
February 272.72 0.00 0.00
March 378.17 0.00 0.00
April 36.19 0.00 0.00
May 20.91 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.01 0.00 0.00
October 11.32 0.00 0.00
November 156.17 0.00 0.00
December 371.66 0.00 0.00
       
Annual Sum or Average 139.39 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 426.65 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 587.93 0.00 0.00
February 444.72 0.00 0.00
March 550.78 0.00 0.00
April 112.34 0.00 0.00
May 72.85 0.00 0.00
June 3.31 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 4.86 0.00 0.00
October 42.24 0.00 0.00
November 279.40 0.00 0.00
December 545.24 0.00 0.00
       
Annual Sum or Average 219.78 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 587.93 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 218.42 0.00 0.00
February 139.15 0.00 0.00
March 224.85 0.00 0.00
April 19.89 0.00 0.00
May 13.60 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 5.03 0.00 0.00
November 69.81 0.00 0.00
December 177.74 0.00 0.00
       
Annual Sum or Average 72.37 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 224.85 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 68.02 0.00 0.00
February 29.25 0.00 0.00
March 86.75 0.00 0.00
April 3.03 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 5.97 0.00 0.00
December 40.40 0.00 0.00
       
Annual Sum or Average 19.56 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 86.75 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 192.03 0.00 0.00
February 129.38 0.00 0.00
March 212.84 0.00 0.00
April 17.12 0.00 0.00
May 11.08 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 5.24 0.00 0.00
November 65.16 0.00 0.00
December 160.70 0.00 0.00
       
Annual Sum or Average 66.11 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 212.84 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 359.30 0.00 0.00
February 205.69 0.00 0.00
March 277.90 0.00 0.00
April 24.21 0.00 0.00
May 12.15 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 8.44 0.00 0.00
November 125.90 0.00 0.00
December 307.67 0.00 0.00
       
Annual Sum or Average 110.11 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 359.30 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 176.66 0.00 0.00
February 69.77 0.00 0.00
March 129.71 0.00 0.00
April 4.80 0.00 0.00
May 0.01 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 25.72 0.00 0.00
December 130.10 0.00 0.00
       
Annual Sum or Average 44.93 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 176.66 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 310.23 0.00 0.00
February 188.55 0.00 0.00
March 259.72 0.00 0.00
April 20.84 0.00 0.00
May 10.53 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 7.47 0.00 0.00
November 108.17 0.00 0.00
December 271.52 0.00 0.00
       
Annual Sum or Average 98.06 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 310.23 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 415.44 0.00 0.00
February 312.77 0.00 0.00
March 440.98 0.00 0.00
April 76.46 0.00 0.00
May 53.68 0.00 0.00
June 0.66 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.74 0.00 0.00
October 26.50 0.00 0.00
November 188.20 0.00 0.00
December 364.50 0.00 0.00
       
Annual Sum or Average 156.45 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 440.98 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 199.95 0.00 0.00
February 129.70 0.00 0.00
March 232.76 0.00 0.00
April 13.95 0.00 0.00
May 10.79 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 2.16 0.00 0.00
November 54.56 0.00 0.00
December 157.71 0.00 0.00
       
Annual Sum or Average 66.83 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 232.76 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 366.58 0.00 0.00
February 290.89 0.00 0.00
March 406.00 0.00 0.00
April 64.26 0.00 0.00
May 42.69 0.00 0.00
June 0.61 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 1.70 0.00 0.00
October 23.72 0.00 0.00
November 168.25 0.00 0.00
December 331.05 0.00 0.00
       
Annual Sum or Average 140.99 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 406.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 596.77 0.00 0.00
February 411.35 0.00 0.00
March 505.07 0.00 0.00
April 84.20 0.00 0.00
May 50.09 0.00 0.00
June 0.45 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.13 0.00 0.00
October 35.02 0.00 0.00
November 278.20 0.00 0.00
December 540.00 0.00 0.00
       
Annual Sum or Average 208.23 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 596.77 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 365.21 0.00 0.00
February 210.84 0.00 0.00
March 294.15 0.00 0.00
April 17.58 0.00 0.00
May 9.24 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 4.23 0.00 0.00
November 113.33 0.00 0.00
December 309.17 0.00 0.00
       
Annual Sum or Average 110.34 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 365.21 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 518.42 0.00 0.00
February 371.59 0.00 0.00
March 458.15 0.00 0.00
April 69.65 0.00 0.00
May 40.78 0.00 0.00
June 0.52 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 2.06 0.00 0.00
October 28.01 0.00 0.00
November 226.47 0.00 0.00
December 477.81 0.00 0.00
       
Annual Sum or Average 182.42 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 518.42 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.10
May 0.00 0.00 0.08
June 0.00 0.00 0.14
July 0.00 0.00 0.20
August 0.00 0.00 0.22
September 0.00 0.00 0.18
October 0.00 0.00 0.17
November 0.00 0.00 0.08
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.04
March 0.00 0.00 0.03
April 0.00 0.00 0.06
May 0.00 0.00 0.04
June 0.00 0.00 0.08
July 0.00 0.00 0.14
August 0.00 0.00 0.17
September 0.00 0.00 0.14
October 0.00 0.00 0.15
November 0.00 0.00 0.06
December 0.00 0.00 0.06
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.03
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.06
February 0.00 0.00 0.04
March 0.00 0.00 0.04
April 0.00 0.00 0.09
May 0.00 0.00 0.07
June 0.00 0.00 0.12
July 0.00 0.00 0.20
August 0.00 0.00 0.22
September 0.00 0.00 0.16
October 0.00 0.00 0.16
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.07
May 0.00 0.00 0.07
June 0.00 0.00 0.14
July 0.00 0.00 0.20
August 0.00 0.00 0.19
September 0.00 0.00 0.13
October 0.00 0.00 0.11
November 0.00 0.00 0.02
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.03
June 0.00 0.00 0.09
July 0.00 0.00 0.14
August 0.00 0.00 0.14
September 0.00 0.00 0.09
October 0.00 0.00 0.08
November 0.00 0.00 0.01
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.14



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.01
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.06
May 0.00 0.00 0.06
June 0.00 0.00 0.12
July 0.00 0.00 0.19
August 0.00 0.00 0.19
September 0.00 0.00 0.11
October 0.00 0.00 0.10
November 0.00 0.00 0.01
December 0.00 0.00 0.01
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.07
March 0.00 0.00 0.06
April 0.00 0.00 0.13
May 0.00 0.00 0.11
June 0.00 0.00 0.17
July 0.00 0.00 0.24
August 0.00 0.00 0.26
September 0.00 0.00 0.21
October 0.00 0.00 0.20
November 0.00 0.00 0.10
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.06
March 0.00 0.00 0.05
April 0.00 0.00 0.09
May 0.00 0.00 0.07
June 0.00 0.00 0.13
July 0.00 0.00 0.19
August 0.00 0.00 0.21
September 0.00 0.00 0.18
October 0.00 0.00 0.18
November 0.00 0.00 0.09
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.12
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.08
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.12
May 0.00 0.00 0.10
June 0.00 0.00 0.16
July 0.00 0.00 0.24
August 0.00 0.00 0.26
September 0.00 0.00 0.20
October 0.00 0.00 0.20
November 0.00 0.00 0.09
December 0.00 0.00 0.09
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.02
March 0.00 0.00 0.03
April 0.00 0.00 0.09
May 0.00 0.00 0.10
June 0.00 0.00 0.17
July 0.00 0.00 0.24
August 0.00 0.00 0.23
September 0.00 0.00 0.17
October 0.00 0.00 0.14
November 0.00 0.00 0.03
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.01
March 0.00 0.00 0.01
April 0.00 0.00 0.05
May 0.00 0.00 0.07
June 0.00 0.00 0.13
July 0.00 0.00 0.19
August 0.00 0.00 0.18
September 0.00 0.00 0.13
October 0.00 0.00 0.12
November 0.00 0.00 0.02
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.08
May 0.00 0.00 0.09
June 0.00 0.00 0.16
July 0.00 0.00 0.23
August 0.00 0.00 0.23
September 0.00 0.00 0.15
October 0.00 0.00 0.13
November 0.00 0.00 0.02
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.06
March 0.00 0.00 0.06
April 0.00 0.00 0.12
May 0.00 0.00 0.11
June 0.00 0.00 0.17
July 0.00 0.00 0.25
August 0.00 0.00 0.26
September 0.00 0.00 0.21
October 0.00 0.00 0.19
November 0.00 0.00 0.09
December 0.00 0.00 0.08
       
Annual Sum or Average 0.00 0.00 0.14
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.05
March 0.00 0.00 0.04
April 0.00 0.00 0.09
May 0.00 0.00 0.07
June 0.00 0.00 0.13
July 0.00 0.00 0.19
August 0.00 0.00 0.21
September 0.00 0.00 0.17
October 0.00 0.00 0.17
November 0.00 0.00 0.08
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.04
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.05
March 0.00 0.00 0.05
April 0.00 0.00 0.11
May 0.00 0.00 0.09
June 0.00 0.00 0.16
July 0.00 0.00 0.25
August 0.00 0.00 0.26
September 0.00 0.00 0.19
October 0.00 0.00 0.19
November 0.00 0.00 0.08
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.13
Minimum of Months 0.00 0.00 0.05
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.02
March 0.00 0.00 0.04
April 0.00 0.00 0.10
May 0.00 0.00 0.10
June 0.00 0.00 0.17
July 0.00 0.00 0.25
August 0.00 0.00 0.25
September 0.00 0.00 0.18
October 0.00 0.00 0.15
November 0.00 0.00 0.03
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.11
Minimum of Months 0.00 0.00 0.02
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.01
March 0.00 0.00 0.02
April 0.00 0.00 0.07
May 0.00 0.00 0.07
June 0.00 0.00 0.13
July 0.00 0.00 0.19
August 0.00 0.00 0.20
September 0.00 0.00 0.14
October 0.00 0.00 0.12
November 0.00 0.00 0.02
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.02
February 0.00 0.00 0.01
March 0.00 0.00 0.03
April 0.00 0.00 0.09
May 0.00 0.00 0.09
June 0.00 0.00 0.16
July 0.00 0.00 0.24
August 0.00 0.00 0.25
September 0.00 0.00 0.17
October 0.00 0.00 0.14
November 0.00 0.00 0.02
December 0.00 0.00 0.02
       
Annual Sum or Average 0.00 0.00 0.10
Minimum of Months 0.00 0.00 0.01
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.16 723.80
February 0.00 0.00 974.26 655.17
March 0.00 0.00 959.86 714.64
April 0.00 0.00 936.67 674.88
May 0.00 0.00 901.44 671.15
June 0.00 0.00 875.65 630.91
July 0.00 0.00 857.77 638.63
August 0.00 0.00 853.08 635.14
September 0.00 0.00 871.00 627.57
October 0.00 0.00 896.13 667.20
November 0.00 0.00 926.36 667.45
December 0.00 0.00 957.17 712.64
         
Annual Sum or Average 0.00 0.00 914.78 8019.17
Minimum of Months 0.00 0.00 853.08 627.57
Maximum of Months 0.00 0.00 974.26 723.80



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 971.98 723.67
February 0.00 0.00 971.98 653.64
March 0.00 0.00 961.91 716.17
April 0.00 0.00 934.02 672.97
May 0.00 0.00 903.50 672.68
June 0.00 0.00 873.58 629.42
July 0.00 0.00 857.58 638.50
August 0.00 0.00 853.09 635.15
September 0.00 0.00 870.86 627.46
October 0.00 0.00 894.08 665.67
November 0.00 0.00 926.51 667.56
December 0.00 0.00 957.28 712.72
         
Annual Sum or Average 0.00 0.00 914.37 8015.60
Minimum of Months 0.00 0.00 853.09 627.46
Maximum of Months 0.00 0.00 971.98 723.67



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.07 723.73
February 0.00 0.00 974.18 655.12
March 0.00 0.00 960.07 714.80
April 0.00 0.00 934.20 673.10
May 0.00 0.00 903.35 672.57
June 0.00 0.00 873.70 629.51
July 0.00 0.00 857.57 638.48
August 0.00 0.00 855.16 636.69
September 0.00 0.00 868.79 625.97
October 0.00 0.00 896.35 667.35
November 0.00 0.00 926.38 667.47
December 0.00 0.00 957.28 712.72
         
Annual Sum or Average 0.00 0.00 914.59 8017.51
Minimum of Months 0.00 0.00 855.16 625.97
Maximum of Months 0.00 0.00 974.18 723.73



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.38 723.97
February 0.00 0.00 976.86 656.92
March 0.00 0.00 960.05 714.79
April 0.00 0.00 936.42 674.70
May 0.00 0.00 903.65 672.79
June 0.00 0.00 873.80 629.58
July 0.00 0.00 857.43 638.38
August 0.00 0.00 854.99 636.56
September 0.00 0.00 869.07 626.17
October 0.00 0.00 896.37 667.37
November 0.00 0.00 928.82 669.23
December 0.00 0.00 957.30 712.74
         
Annual Sum or Average 0.00 0.00 915.24 8023.21
Minimum of Months 0.00 0.00 854.99 626.17
Maximum of Months 0.00 0.00 976.86 723.97



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.26 723.88
February 0.00 0.00 977.08 657.06
March 0.00 0.00 959.77 714.58
April 0.00 0.00 936.19 674.53
May 0.00 0.00 903.28 672.52
June 0.00 0.00 873.64 629.47
July 0.00 0.00 857.44 638.39
August 0.00 0.00 855.15 636.68
September 0.00 0.00 868.76 625.95
October 0.00 0.00 896.20 667.25
November 0.00 0.00 926.65 667.66
December 0.00 0.00 959.74 714.55
         
Annual Sum or Average 0.00 0.00 915.16 8022.51
Minimum of Months 0.00 0.00 855.15 625.95
Maximum of Months 0.00 0.00 977.08 723.88



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.44 724.01
February 0.00 0.00 976.91 656.95
March 0.00 0.00 960.20 714.89
April 0.00 0.00 936.36 674.66
May 0.00 0.00 901.07 670.87
June 0.00 0.00 873.61 629.44
July 0.00 0.00 859.66 640.04
August 0.00 0.00 853.00 635.09
September 0.00 0.00 870.93 627.52
October 0.00 0.00 896.14 667.20
November 0.00 0.00 926.56 667.60
December 0.00 0.00 959.78 714.58
         
Annual Sum or Average 0.00 0.00 915.20 8022.85
Minimum of Months 0.00 0.00 853.00 627.52
Maximum of Months 0.00 0.00 976.91 724.01



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 969.88 722.11
February 0.00 0.00 974.23 655.15
March 0.00 0.00 959.70 714.53
April 0.00 0.00 934.41 673.25
May 0.00 0.00 903.32 672.55
June 0.00 0.00 873.28 629.21
July 0.00 0.00 857.98 638.79
August 0.00 0.00 852.90 635.01
September 0.00 0.00 870.88 627.48
October 0.00 0.00 893.98 665.60
November 0.00 0.00 926.29 667.40
December 0.00 0.00 957.15 712.62
         
Annual Sum or Average 0.00 0.00 914.16 8013.69
Minimum of Months 0.00 0.00 852.90 627.48
Maximum of Months 0.00 0.00 974.23 722.11



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 969.97 722.17
February 0.00 0.00 971.93 653.60
March 0.00 0.00 959.92 714.69
April 0.00 0.00 934.11 673.04
May 0.00 0.00 901.47 671.17
June 0.00 0.00 873.73 629.53
July 0.00 0.00 857.67 638.56
August 0.00 0.00 852.91 635.02
September 0.00 0.00 868.82 625.99
October 0.00 0.00 896.11 667.18
November 0.00 0.00 925.14 666.57
December 0.00 0.00 956.10 711.84
         
Annual Sum or Average 0.00 0.00 913.66 8009.36
Minimum of Months 0.00 0.00 852.91 625.99
Maximum of Months 0.00 0.00 971.93 722.17



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 969.81 722.05
February 0.00 0.00 974.33 655.21
March 0.00 0.00 959.86 714.64
April 0.00 0.00 934.00 672.96
May 0.00 0.00 901.37 671.09
June 0.00 0.00 873.60 629.44
July 0.00 0.00 857.72 638.60
August 0.00 0.00 855.18 636.70
September 0.00 0.00 868.67 625.89
October 0.00 0.00 893.93 665.56
November 0.00 0.00 926.23 667.36
December 0.00 0.00 957.14 712.62
         
Annual Sum or Average 0.00 0.00 913.98 8012.11
Minimum of Months 0.00 0.00 855.18 625.89
Maximum of Months 0.00 0.00 974.33 722.05



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.26 723.87
February 0.00 0.00 974.08 655.05
March 0.00 0.00 959.75 714.56
April 0.00 0.00 936.57 674.81
May 0.00 0.00 901.14 670.93
June 0.00 0.00 873.52 629.38
July 0.00 0.00 857.38 638.35
August 0.00 0.00 855.12 636.66
September 0.00 0.00 868.68 625.90
October 0.00 0.00 896.14 667.20
November 0.00 0.00 926.38 667.47
December 0.00 0.00 957.38 712.80
         
Annual Sum or Average 0.00 0.00 914.53 8016.97
Minimum of Months 0.00 0.00 855.12 625.90
Maximum of Months 0.00 0.00 974.08 723.87



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.33 723.93
February 0.00 0.00 974.28 655.18
March 0.00 0.00 959.93 714.69
April 0.00 0.00 933.85 672.85
May 0.00 0.00 901.50 671.19
June 0.00 0.00 873.56 629.41
July 0.00 0.00 857.68 638.56
August 0.00 0.00 852.89 635.00
September 0.00 0.00 868.96 626.09
October 0.00 0.00 895.81 666.96
November 0.00 0.00 926.46 667.52
December 0.00 0.00 957.16 712.63
         
Annual Sum or Average 0.00 0.00 914.19 8014.03
Minimum of Months 0.00 0.00 852.89 626.09
Maximum of Months 0.00 0.00 974.28 723.93



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.28 723.89
February 0.00 0.00 974.30 655.19
March 0.00 0.00 959.95 714.71
April 0.00 0.00 934.05 672.99
May 0.00 0.00 901.03 670.84
June 0.00 0.00 873.58 629.43
July 0.00 0.00 857.65 638.55
August 0.00 0.00 855.14 636.67
September 0.00 0.00 868.64 625.86
October 0.00 0.00 896.03 667.12
November 0.00 0.00 926.29 667.40
December 0.00 0.00 957.27 712.72
         
Annual Sum or Average 0.00 0.00 914.35 8015.38
Minimum of Months 0.00 0.00 855.14 625.86
Maximum of Months 0.00 0.00 974.30 723.89



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.11 723.76
February 0.00 0.00 974.21 655.13
March 0.00 0.00 960.09 714.81
April 0.00 0.00 934.20 673.10
May 0.00 0.00 903.32 672.55
June 0.00 0.00 873.77 629.56
July 0.00 0.00 857.55 638.47
August 0.00 0.00 855.17 636.70
September 0.00 0.00 868.78 625.96
October 0.00 0.00 896.31 667.32
November 0.00 0.00 926.31 667.42
December 0.00 0.00 957.09 712.58
         
Annual Sum or Average 0.00 0.00 914.58 8017.37
Minimum of Months 0.00 0.00 855.17 625.96
Maximum of Months 0.00 0.00 974.21 723.76



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 969.92 722.13
February 0.00 0.00 974.27 655.17
March 0.00 0.00 959.77 714.57
April 0.00 0.00 934.42 673.26
May 0.00 0.00 903.36 672.58
June 0.00 0.00 873.50 629.37
July 0.00 0.00 857.68 638.56
August 0.00 0.00 852.91 635.01
September 0.00 0.00 870.93 627.52
October 0.00 0.00 894.02 665.62
November 0.00 0.00 926.18 667.32
December 0.00 0.00 957.18 712.65
         
Annual Sum or Average 0.00 0.00 914.17 8013.77
Minimum of Months 0.00 0.00 852.91 627.52
Maximum of Months 0.00 0.00 974.27 722.13



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.06 723.73
February 0.00 0.00 972.00 653.65
March 0.00 0.00 959.80 714.60
April 0.00 0.00 936.05 674.43
May 0.00 0.00 901.48 671.18
June 0.00 0.00 873.56 629.41
July 0.00 0.00 857.92 638.75
August 0.00 0.00 855.14 636.67
September 0.00 0.00 868.82 625.99
October 0.00 0.00 896.18 667.23
November 0.00 0.00 926.54 667.58
December 0.00 0.00 957.02 712.53
         
Annual Sum or Average 0.00 0.00 914.39 8015.75
Minimum of Months 0.00 0.00 855.14 625.99
Maximum of Months 0.00 0.00 972.06 723.73



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.25 723.87
February 0.00 0.00 974.33 655.21
March 0.00 0.00 961.91 716.17
April 0.00 0.00 934.21 673.11
May 0.00 0.00 903.35 672.57
June 0.00 0.00 873.76 629.55
July 0.00 0.00 857.53 638.45
August 0.00 0.00 855.17 636.70
September 0.00 0.00 868.78 625.97
October 0.00 0.00 896.37 667.37
November 0.00 0.00 926.47 667.53
December 0.00 0.00 957.70 713.03
         
Annual Sum or Average 0.00 0.00 914.82 8019.53
Minimum of Months 0.00 0.00 855.17 625.97
Maximum of Months 0.00 0.00 974.33 723.87



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.39 723.97
February 0.00 0.00 974.34 655.22
March 0.00 0.00 959.93 714.69
April 0.00 0.00 936.16 674.51
May 0.00 0.00 901.29 671.03
June 0.00 0.00 873.66 629.48
July 0.00 0.00 857.69 638.58
August 0.00 0.00 855.16 636.69
September 0.00 0.00 868.68 625.89
October 0.00 0.00 896.12 667.18
November 0.00 0.00 926.42 667.50
December 0.00 0.00 957.45 712.84
         
Annual Sum or Average 0.00 0.00 914.60 8017.59
Minimum of Months 0.00 0.00 855.16 625.89
Maximum of Months 0.00 0.00 974.34 723.97



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 972.33 723.93
February 0.00 0.00 974.38 655.25
March 0.00 0.00 959.96 714.72
April 0.00 0.00 936.16 674.51
May 0.00 0.00 901.33 671.07
June 0.00 0.00 873.52 629.38
July 0.00 0.00 857.74 638.61
August 0.00 0.00 855.14 636.67
September 0.00 0.00 868.81 625.99
October 0.00 0.00 896.22 667.26
November 0.00 0.00 926.67 667.68
December 0.00 0.00 959.49 714.37
         
Annual Sum or Average 0.00 0.00 914.81 8019.44
Minimum of Months 0.00 0.00 855.14 625.99
Maximum of Months 0.00 0.00 974.38 723.93



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 42.53 344.45
February 30.09 247.54
March 30.03 388.39
April 59.38 83.67
May 49.40 65.05
June 75.06 2.97
July 111.03 0.00
August 118.34 0.00
September 98.00 2.64
October 105.92 29.70
November 48.72 163.85
December 49.65 307.24
     
Annual Sum or Average 818.15 1635.50
Minimum of Months 30.03 0.00
Maximum of Months 118.34 388.39



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 35.61 175.53
February 21.26 114.54
March 17.17 219.07
April 32.80 21.96
May 23.47 18.16
June 43.26 0.00
July 71.92 0.00
August 82.67 0.00
September 71.98 0.00
October 87.75 5.62
November 38.94 59.29
December 42.06 147.68
     
Annual Sum or Average 568.91 761.85
Minimum of Months 17.17 0.00
Maximum of Months 87.75 219.07



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 39.61 310.08
February 25.72 234.72
March 25.64 364.14
April 51.93 75.18
May 39.93 57.94
June 65.13 2.73
July 104.30 0.00
August 114.60 0.00
September 88.25 2.87
October 101.02 27.40
November 42.54 150.10
December 45.55 283.76
     
Annual Sum or Average 744.22 1508.92
Minimum of Months 25.64 0.00
Maximum of Months 114.60 364.14



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 8.96 510.39
February 6.25 332.46
March 11.77 459.01
April 40.31 93.73
May 44.92 61.78
June 75.09 2.47
July 107.80 0.00
August 102.79 0.00
September 71.22 3.34
October 67.00 38.27
November 11.53 244.24
December 10.65 461.84
     
Annual Sum or Average 558.28 2207.53
Minimum of Months 6.25 0.00
Maximum of Months 107.80 510.39



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 6.25 329.85
February 0.95 189.78
March 2.52 292.07
April 14.52 26.98
May 19.35 16.12
June 43.61 0.00
July 69.06 0.00
August 66.91 0.00
September 44.14 0.00
October 47.08 8.73
November 4.60 116.47
December 5.62 286.65
     
Annual Sum or Average 324.61 1266.65
Minimum of Months 0.95 0.00
Maximum of Months 69.06 329.85



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 7.72 454.82
February 2.06 309.56
March 7.67 425.49
April 31.39 83.72
May 35.08 56.14
June 65.13 2.47
July 100.99 0.00
August 98.78 0.00
September 60.62 3.62
October 59.91 32.54
November 6.25 208.43
December 7.91 420.75
     
Annual Sum or Average 483.50 1997.53
Minimum of Months 2.06 0.00
Maximum of Months 100.99 454.82



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 54.83 169.41
February 39.61 96.95
March 38.98 173.98
April 74.40 14.85
May 65.26 10.49
June 95.66 0.00
July 134.92 0.00
August 141.68 0.00
September 118.07 0.00
October 123.52 3.88
November 62.42 52.14
December 61.82 137.33
     
Annual Sum or Average 1011.16 659.02
Minimum of Months 38.98 0.00
Maximum of Months 141.68 173.98



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 52.40 52.89
February 33.65 20.38
March 27.70 67.21
April 50.81 2.26
May 41.80 0.00
June 67.33 0.00
July 98.34 0.00
August 108.73 0.00
September 96.41 0.00
October 109.64 0.00
November 57.22 4.46
December 59.03 31.24
     
Annual Sum or Average 803.06 178.46
Minimum of Months 27.70 0.00
Maximum of Months 109.64 67.21



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 53.74 149.01
February 36.40 90.15
March 36.12 164.75
April 69.93 12.78
May 58.65 8.55
June 87.20 0.00
July 128.84 0.00
August 138.99 0.00
September 109.18 0.00
October 120.28 4.04
November 58.15 48.66
December 59.51 124.17
     
Annual Sum or Average 956.98 602.12
Minimum of Months 36.12 0.00
Maximum of Months 138.99 164.75



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 13.15 278.08
February 11.22 143.22
March 17.88 214.88
April 53.94 18.07
May 60.73 9.37
June 96.18 0.00
July 132.13 0.00
August 126.34 0.00
September 90.66 0.00
October 82.96 6.51
November 18.80 93.92
December 14.96 237.44
     
Annual Sum or Average 718.95 1001.49
Minimum of Months 11.22 0.00
Maximum of Months 132.13 278.08



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 10.77 136.83
February 4.65 48.59
March 7.59 100.37
April 29.42 3.58
May 37.43 0.01
June 68.32 0.00
July 95.83 0.00
August 93.17 0.00
September 67.75 0.00
October 66.57 0.00
November 11.02 19.20
December 10.59 100.42
     
Annual Sum or Average 503.13 409.00
Minimum of Months 4.65 0.00
Maximum of Months 95.83 136.83



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 11.68 240.36
February 5.95 131.33
March 14.04 200.94
April 48.30 15.55
May 53.96 8.12
June 87.65 0.00
July 125.92 0.00
August 123.45 0.00
September 81.29 0.00
October 78.31 5.76
November 11.90 80.75
December 12.56 209.69
     
Annual Sum or Average 655.01 892.50
Minimum of Months 5.95 0.00
Maximum of Months 125.92 240.36



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 11.88 401.21
February 6.78 258.68
March 16.97 354.07
April 53.15 51.93
May 53.77 31.44
June 88.69 0.39
July 131.81 0.00
August 132.75 0.00
September 89.19 1.53
October 83.02 21.59
November 12.78 168.97
December 12.65 368.77
     
Annual Sum or Average 693.47 1658.58
Minimum of Months 6.78 0.00
Maximum of Months 132.75 401.21



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 43.38 284.00
February 28.93 202.54
March 31.26 313.85
April 65.25 47.91
May 55.73 32.91
June 87.44 0.46
July 132.34 0.00
August 140.79 0.00
September 106.20 1.27
October 114.80 18.28
November 47.64 125.57
December 48.26 255.62
     
Annual Sum or Average 902.03 1282.40
Minimum of Months 28.93 0.00
Maximum of Months 140.79 313.85



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 46.22 321.75
February 33.29 217.78
March 35.62 340.78
April 72.29 56.99
May 64.57 41.36
June 96.78 0.49
July 138.73 0.00
August 143.99 0.00
September 115.48 1.29
October 119.26 20.42
November 53.59 140.44
December 52.27 281.44
     
Annual Sum or Average 972.08 1422.74
Minimum of Months 33.29 0.00
Maximum of Months 143.99 340.78



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 10.86 282.48
February 5.26 146.73
March 11.18 227.29
April 36.85 13.11
May 39.21 7.12
June 69.12 0.00
July 101.82 0.00
August 102.82 0.00
September 74.89 0.00
October 71.66 3.26
November 11.59 84.52
December 10.66 238.48
     
Annual Sum or Average 545.92 1003.00
Minimum of Months 5.26 0.00
Maximum of Months 102.82 282.48



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 41.53 155.04
February 26.09 90.33
March 24.06 179.99
April 48.21 10.41
May 40.83 8.32
June 67.68 0.00
July 102.13 0.00
August 110.84 0.00
September 92.09 0.00
October 103.55 1.67
November 46.26 40.75
December 46.98 121.82
     
Annual Sum or Average 750.25 608.32
Minimum of Months 24.06 0.00
Maximum of Months 110.84 179.99



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 17:56:16

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 14.26 461.44
February 12.51 286.26
March 22.12 390.13
April 61.17 62.75
May 62.89 38.60
June 98.05 0.34
July 138.25 0.00
August 136.09 0.00
September 98.91 1.59
October 89.15 26.97
November 20.19 207.41
December 15.96 416.52
     
Annual Sum or Average 769.55 1892.00
Minimum of Months 12.51 0.00
Maximum of Months 138.25 461.44