Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:36
Tabular Output Report in Format: HTML
Building: US+MF+CZ5B+oilfurnace+unheatedbsmt+IECC_2012
Environment: ANNUAL ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-06-27 17:37:00
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Values gathered over 8760.00 hours| Total Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
| Total Site Energy | 951416.18 | 24.39 | 44.03 |
| Net Site Energy | 951416.18 | 24.39 | 44.03 |
| Total Source Energy | 1972427.78 | 50.57 | 91.27 |
| Net Source Energy | 1972427.78 | 50.57 | 91.27 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [ft2] | |
| Total Building Area | 39005.22 |
| Net Conditioned Building Area | 21609.96 |
| Unconditioned Building Area | 17395.26 |
| Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | 0.00 | 210208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 53621.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 36464.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284762.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333360.10 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 456444.83 | 210208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 284762.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333360.10 |
| Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 210208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 53621.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 17305.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 19159.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333360.10 | |
| Water Heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284762.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | Unassigned | 0.00 | 210208.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 53621.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 44251.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 36464.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284762.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 333360.10 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 3.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 4.17 | 9.73 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
| Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 21.12 | 9.73 | 0.00 | 0.00 | 0.00 | 0.00 | 13.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.43 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 1.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 2.31 | 5.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 |
| Other | 7.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 11.70 | 5.39 | 0.00 | 0.00 | 0.00 | 0.00 | 7.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.55 |
| Electricity [kBtu] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 456444.828 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 456444.828 | 100.00 |
| Total On-Site and Utility Electric Sources | 456444.828 | 100.00 |
| Total Electricity End Uses | 456444.828 | 100.00 |
| Heat [kBtu] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [gal] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 333360.10 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 333360.10 | 100.00 |
| Total Water End Uses | 333360.10 | 100.00 |
| Degrees [deltaF] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 1341.83 |
| Time Setpoint Not Met During Occupied Cooling | 0.50 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 841.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| UNHEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
General| Value | |
| Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:36 |
| RunPeriod | ANNUAL |
| Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
| Latitude [deg] | 39.72 |
| Longitude [deg] | -104.8 |
| Elevation [ft] | 5663.01 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 18953.34 | 7014.93 | 2461.74 | 7014.93 | 2461.74 |
| Above Ground Wall Area [ft2] | 16363.00 | 6175.53 | 2005.97 | 6175.53 | 2005.97 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 11.22 | 7.58 | 21.60 | 7.58 | 21.60 |
| Above Ground Window-Wall Ratio [%] | 13.00 | 8.61 | 26.51 | 8.61 | 26.51 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
| Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
| Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
| Total | |
| Gross Roof Area [ft2] | 8451.30 |
| Skylight Area [ft2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| UNHEATEDBSMT | 7794.39 | No | Yes | 58539.52 | 1.00 | 185.02 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.6665 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.6665 | 600.28 | 2.9092 |
| Total | 39005.22 | 325627.71 | 16363.00 | 2590.34 | 2126.74 | 2126.74 | 0.3693 | 1083.48 | 1.6118 | |||
| Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.6665 | 600.28 | 2.9092 | |||
| Unconditioned Total | 17395.26 | 141888.33 | 1066.39 | 2590.34 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
| UNHEATEDBSMT | 7794.39 | No | Yes | 1.00 | UNHEATEDBSMT | GENERAL | UNHEATEDBSMT | 0.0000 | 0.00 | 0.0000 | |
| BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.6665 | 600.28 | 2.9092 | |
| ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.6665 | 600.28 | 2.9092 | |
| Total | 39005.22 | 0.3693 | 1083.48 | 1.6118 | |||||||
| Conditioned Total | 21609.96 | 0.6665 | 600.28 | 2.9092 | |||||||
| Unconditioned Total | 17395.26 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| GENERAL | 39005.22 | 21609.96 | 17395.26 | 0.00 | 0.3693 | 1083.48 | 1.6118 |
| Total | 39005.22 | 21609.96 | 17395.26 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
End Uses| Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Time of Peak | 26-JUN-18:20 | 22-DEC-03:10 | - | - | - | - | 01-JAN-08:30 | - | - | - | - | - | 01-JAN-08:30 |
| Heating | 0.00 | 224.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 47.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 51.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 10.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 126.91 | 224.19 | 0.00 | 0.00 | 0.00 | 0.00 | 225.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 |
| Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Boiler | 0.00 | 224.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Cooling | General | 47.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 13.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 4.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 2.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 5.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 0.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 5.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 9.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 25.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 1.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 1.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 8.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.21 | |
| Water Heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Values gathered over 8760.00 hours| Source Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
| Heating | 0.00 | 227866.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 169820.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 140144.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 65251.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 115482.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299001.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 1445560.77 | 227866.02 | 0.00 | 0.00 | 0.00 | 0.00 | 299001.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 0.00 | 10.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 7.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 6.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 5.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 66.89 | 10.54 | 0.00 | 0.00 | 0.00 | 0.00 | 13.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 0.00 | 5.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 4.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 1.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 24.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 2.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 37.06 | 5.84 | 0.00 | 0.00 | 0.00 | 0.00 | 7.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
AirTerminal:SingleDuct:ConstantVolume:NoReheat| Design Size Maximum Air Flow Rate [ft3/min] | |
| ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 |
| ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 |
| ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 |
| ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 |
| ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 |
| ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 |
| ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 |
| ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 375.32 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 397.20 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 594.71 |
| ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 314.85 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 307.78 |
| ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 592.24 |
| Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 | 556.90 | 556.90 | 556.90 | 556.90 | 556.90 | 1.00 | 1.00 | 556.90 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 | 258.05 | 258.05 | 258.05 | 258.05 | 258.05 | 1.00 | 1.00 | 258.05 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 | 391.18 | 391.18 | 391.18 | 391.18 | 391.18 | 1.00 | 1.00 | 391.18 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 | 534.64 | 534.64 | 534.64 | 534.64 | 534.64 | 1.00 | 1.00 | 534.64 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 | 249.45 | 249.45 | 249.45 | 249.45 | 249.45 | 1.00 | 1.00 | 249.45 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 | 370.64 | 370.64 | 370.64 | 370.64 | 370.64 | 1.00 | 1.00 | 370.64 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 | 562.25 | 562.25 | 562.25 | 562.25 | 562.25 | 1.00 | 1.00 | 562.25 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 | 270.14 | 270.14 | 270.14 | 270.14 | 270.14 | 1.00 | 1.00 | 270.14 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 | 400.70 | 400.70 | 400.70 | 400.70 | 400.70 | 1.00 | 1.00 | 400.70 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 | 541.06 | 541.06 | 541.06 | 541.06 | 541.06 | 1.00 | 1.00 | 541.06 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 | 262.96 | 262.96 | 262.96 | 262.96 | 262.96 | 1.00 | 1.00 | 262.96 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 | 379.05 | 379.05 | 379.05 | 379.05 | 379.05 | 1.00 | 1.00 | 379.05 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.71 | 594.71 | 594.71 | 594.71 | 594.71 | 594.71 | 1.00 | 1.00 | 594.71 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.78 | 307.78 | 307.78 | 307.78 | 307.78 | 307.78 | 1.00 | 1.00 | 307.78 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.20 | 397.20 | 397.20 | 397.20 | 397.20 | 397.20 | 1.00 | 1.00 | 397.20 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.24 | 592.24 | 592.24 | 592.24 | 592.24 | 592.24 | 1.00 | 1.00 | 592.24 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.85 | 314.85 | 314.85 | 314.85 | 314.85 | 314.85 | 1.00 | 1.00 | 314.85 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.32 | 375.32 | 375.32 | 375.32 | 375.32 | 375.32 | 1.00 | 1.00 | 375.32 |
| Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 | 1.33 | 0.800505 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 | 0.687820 | 0.779431 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 | 0.931583 | 0.800968 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 | 1.28 | 0.800195 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 | 0.593898 | 0.800065 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 | 0.868033 | 0.800753 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 | 1.34 | 0.800980 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 | 0.649879 | 0.800520 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 | 0.958952 | 0.800290 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 | 1.29 | 0.800716 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 | 0.619072 | 0.800942 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 | 0.892419 | 0.800919 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 594.71 | 1.41 | 0.800702 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 307.78 | 0.724287 | 0.800079 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 397.20 | 0.957210 | 0.800927 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 592.24 | 1.40 | 0.800895 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 314.85 | 0.734878 | 0.800934 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 375.32 | 0.889946 | 0.800462 |
| Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 | 556.90 | 556.90 | 1.33 | 1.00 |
| ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 | 258.05 | 258.05 | 0.687820 | 1.00 |
| ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 | 391.18 | 391.18 | 0.931583 | 1.00 |
| ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 | 534.64 | 534.64 | 1.28 | 1.00 |
| ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 | 249.45 | 249.45 | 0.593898 | 1.00 |
| ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 | 370.64 | 370.64 | 0.868033 | 1.00 |
| ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 | 562.25 | 562.25 | 1.34 | 1.00 |
| ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 | 270.14 | 270.14 | 0.649879 | 1.00 |
| ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 | 400.70 | 400.70 | 0.958952 | 1.00 |
| ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 | 541.06 | 541.06 | 1.29 | 1.00 |
| ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 | 262.96 | 262.96 | 0.619072 | 1.00 |
| ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 | 379.05 | 379.05 | 0.892419 | 1.00 |
| ACANDF_UNIT1_FRONTROW_TOPFLOOR | 594.71 | 594.71 | 594.71 | 1.41 | 1.00 |
| ACANDF_UNIT2_FRONTROW_TOPFLOOR | 307.78 | 307.78 | 307.78 | 0.724287 | 1.00 |
| ACANDF_UNIT3_FRONTROW_TOPFLOOR | 397.20 | 397.20 | 397.20 | 0.957210 | 1.00 |
| ACANDF_UNIT1_BACKROW_TOPFLOOR | 592.24 | 592.24 | 592.24 | 1.40 | 1.00 |
| ACANDF_UNIT2_BACKROW_TOPFLOOR | 314.85 | 314.85 | 314.85 | 0.734878 | 1.00 |
| ACANDF_UNIT3_BACKROW_TOPFLOOR | 375.32 | 375.32 | 375.32 | 0.889946 | 1.00 |
| Design Size Rated Capacity [Btu/h] | Design Size Maximum Water Flow Rate [gal/min] | Design Size U-Factor Times Area Value [Btu/h-F] | |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 31429.34 | 3.23 | 470.58 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16325.27 | 1.68 | 236.96 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 23053.66 | 2.37 | 341.12 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 30304.51 | 3.11 | 453.17 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15890.63 | 1.63 | 230.21 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 22015.70 | 2.26 | 325.07 |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 31698.39 | 3.25 | 474.66 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 16935.96 | 1.74 | 246.40 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 23534.13 | 2.42 | 348.49 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 30627.64 | 3.14 | 458.08 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 16573.06 | 1.70 | 240.77 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 22439.92 | 2.30 | 331.57 |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 33340.45 | 3.42 | 500.02 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18838.46 | 1.93 | 275.90 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 23358.23 | 2.40 | 345.78 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 33215.37 | 3.41 | 498.09 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 19195.76 | 1.97 | 281.44 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 22252.32 | 2.28 | 328.68 |
| Design Size Maximum Flow Rate [ft3/min] | |
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 594.71 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 307.78 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 397.20 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 592.24 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 314.85 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 375.32 |
| Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
| BOILER LOOP | 5.91 | 11.83 |
| DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| Design Flow Rate [ft3/min] | |
| BOILER CIRC PUMP | 5.91 |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
| Design Size Nominal Capacity [Btu/h] | Design Size Design Water Flow Rate [gal/min] | |
| CENTRAL BOILER | 431028.79 | 44.24 |
| Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 36002.06 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_LDF | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| BGWALL_UPPER_SDR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_LDB | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| BGWALL_UPPER_SDL | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Possible Shadow Receivers | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Version| Version ID | |
| 1 | 23.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | Yes | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.200 | 0.200 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 30.67 | 34.30 | 41.36 | 48.06 | 60.73 | 67.39 | 69.22 | 65.84 | 58.05 | 48.31 | 38.71 | 32.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
| 1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 5663.01 | 12. | 0.9774 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
| 1 | Correlation | NA | 49.91 | 42.66 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | US+MF+CZ5B+oilfurnace+unheatedbsmt+IECC_2012 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | DOE-2 |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
| 1 | ThirdOrderBackwardDifference | No | No |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
| 1 | 0.220 | 1213.970 | 0.003566 |
| Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
| 1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
| 2 | CEIL_CONSOL_LAYER | 7.7625 | Rough | 1.5719 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
| 3 | FLOOR_CONSOL_LAYER | 4.5576 | Rough | 0.7710 | 5.155E-002 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
| 4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 6 | WALL_CONSOL_LAYER | 2.4438 | Rough | 0.4584 | 5.717E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
| 8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
| 10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
| 11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
| 12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
| 13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
| 14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
| 15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
| 16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
| 17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
| 18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
| 23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
| 29 | DOOR_CONST | 0.5503 | Smooth | 0.1300 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
| 32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
| 33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
| 39 | GLASS | 0.3765 | VerySmooth | 0.1318 | 0.107 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
| 1 | SURFPROPOTHSDCOEFBASEMENTAVGWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTWALLSURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 2 | SURFPROPOTHSDCOEFBASEMENTAVGFLOOR | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTFLOORTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 3 | SURFPROPOTHSDCOEFBASEMENTUPPERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTUPPERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 4 | SURFPROPOTHSDCOEFBASEMENTLOWERWALL | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCBASEMENTLOWERWALLTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
| 1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 60 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 21 | 186 | 48 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | UNHEATEDBSMT | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.51 | -3.4 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | -7.0 | 0.49 | 7.51 | 58539.45 | TARP | DOE-2 | 7794.37 | 185.05 | 185.05 | 0.00 | 15 | 0 | 0 | Yes |
| 2 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 15 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
| 1 | UNHEATEDBSMT | 7794.37 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 2 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 15 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.667 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.576 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
| 1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 581.408 | 0.484 | 85.201 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 39.972 | 581.408 |
| 36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
| 1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0631 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 3 | EXTERIOR FLOOR | 4 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 4 | INTERIOR CEILING | 6 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | ATTIC FLOOR | 7 | 2 | 12 | 0.167 | 0.0225 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
| 8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.320 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 10 | BASEMENT WALL | 24 | 3 | 4 | 0.167 | 0.534 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 11 | iz-EXTERIOR FLOOR | 25 | 3 | 9 | 0.167 | 0.0342 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
| 1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
| 2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
| 3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
| 4 | WALL_CONSOL_LAYER | 0.4584 | 0.057 | 7.541 | 0.248 | 2.444 |
| 5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
| 7 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
| 8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
| 10 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
| 11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 13 | CEIL_CONSOL_LAYER | 1.5719 | 0.062 | 2.618 | 0.185 | 7.762 |
| 14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
| 18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
| 19 | DOOR_CONST | 0.1299 | 0.072 | 32.003 | 0.183 | 0.5503 |
| 20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
| 21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
| 22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 24 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 25 | BSMTWALL_CONSOL_LAYER | 0.0010 | 10.844 | 7.541 | 0.248 | 0.2342E-04 |
| 26 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 27 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
| 28 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 29 | FLOOR_CONSOL_LAYER | 0.7707 | 0.052 | 3.438 | 0.219 | 4.558 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 11 | -0.54724946E-11 | -0.29353179E-14 | -0.58361936E-11 | 0.17617726E-15 |
| 2 | 10 | 0.24755928E-06 | 0.16971160E-13 | 0.58954555E-06 | -0.42317085E-11 |
| 3 | 9 | -0.21700660E-03 | 0.26282512E-10 | -0.34360792E-03 | 0.18634160E-06 |
| 4 | 8 | 0.10400975E-01 | 0.16063655E-07 | 0.16710006E-01 | -0.10459154E-03 |
| 5 | 7 | -0.18466841 | 0.14497582E-05 | -0.31678806 | 0.33996447E-02 |
| 6 | 6 | 1.6813335 | 0.30890211E-04 | 3.0392820 | -0.45644738E-01 |
| 7 | 5 | -8.8640021 | 0.19737274E-03 | -16.399456 | 0.32465800 |
| 8 | 4 | 28.400945 | 0.41196590E-03 | 52.185337 | -1.3315683 |
| 9 | 3 | -55.684303 | 0.27160336E-03 | -99.213599 | 3.2198962 |
| 10 | 2 | 64.740984 | 0.46773103E-04 | 110.17164 | -4.4902555 |
| 11 | 1 | -40.701741 | 0.11975386E-05 | -65.686261 | 3.3169381 |
| 12 | 0 | 10.602230 | 0.29970883E-09 | 16.204438 | |
| 13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
| 14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
| 15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
| 16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
| 17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
| 18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
| 19 | 9 | -0.61797381E-16 | 0.10275554E-15 | -0.94176193E-10 | 0.70550100E-16 |
| 20 | 8 | 0.55018702E-09 | 0.40996745E-13 | 0.10446581E-03 | -0.35964092E-09 |
| 21 | 7 | -0.45325743E-03 | 0.10183730E-08 | -0.10651944E-01 | 0.29628111E-03 |
| 22 | 6 | 0.35000963E-01 | 0.28248981E-06 | 0.18262466 | -0.23007581E-01 |
| 23 | 5 | -0.40204458 | 0.87190144E-05 | -1.3453660 | 0.27251248 |
| 24 | 4 | 1.9371679 | 0.56641591E-04 | 5.2219591 | -1.3641479 |
| 25 | 3 | -4.7809977 | 0.95620201E-04 | -11.428910 | 3.5178846 |
| 26 | 2 | 6.3416706 | 0.40914426E-04 | 14.116582 | -4.8962826 |
| 27 | 1 | -4.2976303 | 0.32019284E-05 | -9.1505965 | 3.4916880 |
| 28 | 0 | 1.1674918 | 0.10995666E-07 | 2.4144591 | |
| 29 | 12 | 0.94888791E-16 | -0.11237443E-15 | 0.21480527E-09 | -0.52606005E-16 |
| 30 | 11 | -0.44509090E-09 | -0.12338758E-15 | -0.11566016E-03 | 0.28501063E-09 |
| 31 | 10 | 0.60393314E-04 | 0.62564840E-13 | 0.62960490E-02 | -0.38672578E-04 |
| 32 | 9 | -0.20055671E-02 | 0.85912012E-10 | -0.12885789 | 0.13084700E-02 |
| 33 | 8 | 0.28697042E-01 | 0.10381403E-07 | 1.3966036 | -0.19129448E-01 |
| 34 | 7 | -0.23229993 | 0.28493476E-06 | -9.1473517 | 0.15872626 |
| 35 | 6 | 1.1750436 | 0.24973161E-05 | 38.552224 | -0.82592201 |
| 36 | 5 | -3.8729952 | 0.80040830E-05 | -107.65441 | 2.8111251 |
| 37 | 4 | 8.4143451 | 0.96510929E-05 | 200.56463 | -6.3313915 |
| 38 | 3 | -11.897084 | 0.41099356E-05 | -245.77565 | 9.3152582 |
| 39 | 2 | 10.487404 | 0.50788650E-06 | 189.69676 | -8.5734564 |
| 40 | 1 | -5.2147174 | 0.10902359E-07 | -83.415737 | 4.4633233 |
| 41 | 0 | 1.1135774 | 0.38882120E-11 | 15.905642 | |
| 42 | 12 | 0.21480527E-09 | -0.11237443E-15 | 0.94888791E-16 | -0.52606005E-16 |
| 43 | 11 | -0.11566016E-03 | -0.12338758E-15 | -0.44509090E-09 | 0.28501063E-09 |
| 44 | 10 | 0.62960490E-02 | 0.62564840E-13 | 0.60393314E-04 | -0.38672578E-04 |
| 45 | 9 | -0.12885789 | 0.85912012E-10 | -0.20055671E-02 | 0.13084700E-02 |
| 46 | 8 | 1.3966036 | 0.10381403E-07 | 0.28697042E-01 | -0.19129448E-01 |
| 47 | 7 | -9.1473517 | 0.28493476E-06 | -0.23229993 | 0.15872626 |
| 48 | 6 | 38.552224 | 0.24973161E-05 | 1.1750436 | -0.82592201 |
| 49 | 5 | -107.65441 | 0.80040830E-05 | -3.8729952 | 2.8111251 |
| 50 | 4 | 200.56463 | 0.96510929E-05 | 8.4143451 | -6.3313915 |
| 51 | 3 | -245.77565 | 0.41099356E-05 | -11.897084 | 9.3152582 |
| 52 | 2 | 189.69676 | 0.50788650E-06 | 10.487404 | -8.5734564 |
| 53 | 1 | -83.415737 | 0.10902359E-07 | -5.2147174 | 4.4633233 |
| 54 | 0 | 15.905642 | 0.38882120E-11 | 1.1135774 | |
| 55 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
| 56 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
| 57 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
| 58 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
| 59 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
| 60 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
| 61 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
| 62 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
| 63 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
| 64 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
| 65 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
| 66 | 5 | -0.47059848E-07 | 0.10808286E-07 | -0.47059848E-07 | 0.33552267E-09 |
| 67 | 4 | 0.23241354E-03 | 0.64872557E-04 | 0.23241354E-03 | -0.29116876E-05 |
| 68 | 3 | -0.69106029E-01 | 0.14208819E-01 | -0.69106029E-01 | 0.18005536E-02 |
| 69 | 2 | 1.8030591 | 0.23437818 | 1.8030591 | -0.90752678E-01 |
| 70 | 1 | -7.5310044 | 0.40520073 | -7.5310044 | 0.70046896 |
| 71 | 0 | 6.5027572 | 0.52085640E-01 | 6.5027572 | |
| 72 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
| 73 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
| 74 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
| 75 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
| 76 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
| 77 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
| 78 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 | |
| 79 | 4 | 0.69987904E-07 | 0.26228811E-07 | 0.69987904E-07 | -0.89457852E-14 |
| 80 | 3 | -0.30987589E-02 | 0.10225415E-02 | -0.30987589E-02 | 0.11234143E-06 |
| 81 | 2 | 0.81559891 | 0.24124884 | 0.81559891 | -0.23762713E-02 |
| 82 | 1 | -7.9329461 | 1.4912083 | -7.9329461 | 0.29351368 |
| 83 | 0 | 9.2684202 | 0.41449462 | 9.2684202 | |
| 84 | 9 | -0.94176193E-10 | 0.10275554E-15 | -0.61797381E-16 | 0.70550100E-16 |
| 85 | 8 | 0.10446581E-03 | 0.40996745E-13 | 0.55018702E-09 | -0.35964092E-09 |
| 86 | 7 | -0.10651944E-01 | 0.10183730E-08 | -0.45325743E-03 | 0.29628111E-03 |
| 87 | 6 | 0.18262466 | 0.28248981E-06 | 0.35000963E-01 | -0.23007581E-01 |
| 88 | 5 | -1.3453660 | 0.87190144E-05 | -0.40204458 | 0.27251248 |
| 89 | 4 | 5.2219591 | 0.56641591E-04 | 1.9371679 | -1.3641479 |
| 90 | 3 | -11.428910 | 0.95620201E-04 | -4.7809977 | 3.5178846 |
| 91 | 2 | 14.116582 | 0.40914426E-04 | 6.3416706 | -4.8962826 |
| 92 | 1 | -9.1505965 | 0.32019284E-05 | -4.2976303 | 3.4916880 |
| 93 | 0 | 2.4144591 | 0.10995666E-07 | 1.1674918 |
| Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.320 | 0.320 | 1.000 | 0.335 | ||
| 2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.320 | 0.320 | 1.000 | 0.335 | ||
| 3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.320 | 0.320 | 1.000 | 0.309 | ||
| 4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
| 5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
| 2 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
| 3 | GLASS | SpectralAverage | 0.13182 | 0.24698 | 0.54906 | 0.54906 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.10671 | 1.00000 | No | |
| 4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
| 5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
| Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
| 1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| 18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 36002.1 | 0.822 | 0.6044 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
| 1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | UNHEATEDBSMT | Mixing/Well-Stirred |
| 2 | BREEZEWAY | Mixing/Well-Stirred |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 15 | ATTIC | Mixing/Well-Stirred |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
| 1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 10618.02844 | 10618.02844 | 556.90671 | 556.90671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 87.95840 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 10064.43983 | 10064.43983 | 225.67794 | 225.67794 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4920.19060 | 4920.19060 | 258.05081 | 258.05081 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 93.02000 | 0.00548 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 7688.70674 | 7688.70674 | 172.40358 | 172.40358 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 7458.33550 | 7458.33550 | 391.18639 | 391.18639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 85.56080 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 10067.21720 | 10067.21720 | 225.74150 | 225.74150 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 10193.66558 | 10193.66558 | 534.63976 | 534.63976 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 87.51439 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 10066.89292 | 10066.89292 | 225.72031 | 225.72031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 4756.06207 | 4756.06207 | 249.44912 | 249.44912 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83.29640 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 7688.33190 | 7688.33190 | 172.39511 | 172.39511 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 7066.75418 | 7066.75418 | 370.63555 | 370.63555 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 83.56280 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 10064.08218 | 10064.08218 | 225.65675 | 225.65675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 10719.89718 | 10719.89718 | 562.24569 | 562.24569 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 87.51439 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 8946.65843 | 8946.65843 | 200.61671 | 200.61671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5150.59692 | 5150.59692 | 270.14827 | 270.14827 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 84.62840 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 6562.23897 | 6562.23897 | 147.15146 | 147.15146 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7639.87297 | 7639.87297 | 400.69910 | 400.69910 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 86.22680 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 8949.28069 | 8949.28069 | 200.67540 | 200.67540 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 10315.92310 | 10315.92310 | 541.05925 | 541.05925 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 87.07041 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 8948.60890 | 8948.60890 | 200.66036 | 200.66036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 5013.67141 | 5013.67141 | 262.96607 | 262.96607 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 82.63040 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 6561.57104 | 6561.57104 | 147.13642 | 147.13642 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 7227.05956 | 7227.05956 | 379.04656 | 379.04656 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 84.22880 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 8945.99626 | 8945.99626 | 200.60167 | 200.60167 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 7156.01500 | 7156.01500 | 375.31775 | 375.31775 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 84.89480 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 11441.87989 | 11441.87989 | 256.54658 | 256.54658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 7573.22777 | 7573.22777 | 397.20334 | 397.20334 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 86.89280 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 11445.49593 | 11445.49593 | 256.63132 | 256.63132 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 11338.95149 | 11338.95149 | 594.70331 | 594.70331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 87.51439 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 11443.59701 | 11443.59701 | 256.58895 | 256.58895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 6002.89776 | 6002.89776 | 314.85166 | 314.85166 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 82.63040 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 9056.45795 | 9056.45795 | 203.07201 | 203.07201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 5868.11302 | 5868.11302 | 307.77538 | 307.77538 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83.29640 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 9058.17736 | 9058.17736 | 203.11057 | 203.11057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 11291.74008 | 11291.74008 | 592.24569 | 592.24569 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 87.07041 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 11443.75158 | 11443.75158 | 256.58895 | 256.58895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
| 1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 3219.60 | 556.90671 | 556.90671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3743.54 | 225.67794 | 225.67794 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1631.14 | 258.05081 | 258.05081 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3057.41 | 172.40358 | 172.40358 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2278.42 | 391.18639 | 391.18639 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3744.35 | 225.74150 | 225.74150 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 3091.78 | 534.63976 | 534.63976 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3744.25 | 225.72031 | 225.72031 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1471.02 | 249.44912 | 249.44912 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3057.30 | 172.39511 | 172.39511 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2142.07 | 370.63555 | 370.63555 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3743.44 | 225.65675 | 225.65675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 3243.91 | 562.24569 | 562.24569 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3420.74 | 200.61671 | 200.61671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1600.50 | 270.14827 | 270.14827 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 2732.09 | 147.15146 | 147.15146 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2338.62 | 400.69910 | 400.69910 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3421.50 | 200.67540 | 200.67540 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 3121.98 | 541.05925 | 541.05925 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3421.30 | 200.66036 | 200.66036 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1537.77 | 262.96607 | 262.96607 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 2731.90 | 147.13642 | 147.13642 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2196.13 | 379.04656 | 379.04656 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3420.55 | 200.60167 | 200.60167 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3422.86 | 594.70331 | 594.70331 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 4141.86 | 256.58895 | 256.58895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1792.48 | 307.77538 | 307.77538 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 3452.93 | 203.11057 | 203.11057 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2327.07 | 397.20334 | 397.20334 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 4142.41 | 256.63132 | 256.63132 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3404.07 | 592.24569 | 592.24569 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 4141.91 | 256.58895 | 256.58895 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1823.73 | 314.85166 | 314.85166 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 3452.43 | 203.07201 | 203.07201 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2183.31 | 375.31775 | 375.31775 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 4141.37 | 256.54658 | 256.54658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 556.90671 |
| 2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 258.05081 |
| 3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 391.18639 |
| 4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 534.63976 |
| 5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 249.44912 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 370.63555 |
| 7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 562.24569 |
| 8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 270.14827 |
| 9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 400.69910 |
| 10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 541.05925 |
| 11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 262.96607 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 379.04656 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 375.31775 |
| 14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 397.20334 |
| 15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 594.70331 |
| 16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 314.85166 |
| 17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 307.77538 |
| 18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 592.24569 |
| 19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 556.90671 |
| 20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 556.90671 |
| 21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 556.90671 |
| 22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 556.90671 |
| 23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 556.90671 |
| 24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 556.90671 |
| 25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 258.05081 |
| 28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 258.05081 |
| 29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 258.05081 |
| 30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 258.05081 |
| 31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 258.05081 |
| 32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 258.05081 |
| 33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 391.18639 |
| 36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 391.18639 |
| 37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 391.18639 |
| 38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 391.18639 |
| 39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 391.18639 |
| 40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 391.18639 |
| 41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 534.63976 |
| 44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 534.63976 |
| 45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 534.63976 |
| 46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 534.63976 |
| 47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 534.63976 |
| 48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 534.63976 |
| 49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 249.44912 |
| 52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 249.44912 |
| 53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 249.44912 |
| 54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 249.44912 |
| 55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 249.44912 |
| 56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 249.44912 |
| 57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 370.63555 |
| 60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 370.63555 |
| 61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 370.63555 |
| 62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 370.63555 |
| 63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 370.63555 |
| 64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 370.63555 |
| 65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 562.24569 |
| 68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 562.24569 |
| 69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 562.24569 |
| 70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 562.24569 |
| 71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 562.24569 |
| 72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 562.24569 |
| 73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 270.14827 |
| 76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 270.14827 |
| 77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 270.14827 |
| 78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 270.14827 |
| 79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 270.14827 |
| 80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 270.14827 |
| 81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 400.69910 |
| 84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 400.69910 |
| 85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 400.69910 |
| 86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 400.69910 |
| 87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 400.69910 |
| 88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 400.69910 |
| 89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 541.05925 |
| 92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 541.05925 |
| 93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 541.05925 |
| 94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 541.05925 |
| 95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 541.05925 |
| 96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 541.05925 |
| 97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 262.96607 |
| 100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 262.96607 |
| 101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 262.96607 |
| 102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 262.96607 |
| 103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 262.96607 |
| 104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 262.96607 |
| 105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 379.04656 |
| 108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 379.04656 |
| 109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 379.04656 |
| 110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 379.04656 |
| 111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 379.04656 |
| 112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 379.04656 |
| 113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 594.70331 |
| 116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 594.70331 |
| 117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 594.70331 |
| 118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 594.70331 |
| 119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 594.70331 |
| 120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 594.70331 |
| 121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 307.77538 |
| 124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 307.77538 |
| 125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 307.77538 |
| 126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 307.77538 |
| 127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 307.77538 |
| 128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 307.77538 |
| 129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 397.20334 |
| 132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 397.20334 |
| 133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 397.20334 |
| 134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 397.20334 |
| 135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 397.20334 |
| 136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 397.20334 |
| 137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 592.24569 |
| 140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 592.24569 |
| 141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 592.24569 |
| 142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 592.24569 |
| 143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 592.24569 |
| 144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 592.24569 |
| 145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 314.85166 |
| 148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 314.85166 |
| 149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 314.85166 |
| 150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 314.85166 |
| 151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 314.85166 |
| 152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 314.85166 |
| 153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 375.31775 |
| 156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 375.31775 |
| 157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 375.31775 |
| 158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 375.31775 |
| 159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 375.31775 |
| 160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 375.31775 |
| 161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 556.90671 |
| 164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 258.05081 |
| 165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 391.18639 |
| 166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 534.63976 |
| 167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 249.44912 |
| 168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 370.63555 |
| 169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 562.24569 |
| 170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 270.14827 |
| 171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 400.69910 |
| 172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 541.05925 |
| 173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 262.96607 |
| 174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 379.04656 |
| 175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 594.70331 |
| 176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 307.77538 |
| 177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 397.20334 |
| 178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 592.24569 |
| 179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 314.85166 |
| 180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 375.31775 |
| 181 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 556.90671 |
| 182 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.33193 |
| 183 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80050 |
| 184 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 556.90671 |
| 185 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 556.90671 |
| 186 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 556.90671 |
| 187 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.33193 |
| 188 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 31429.34211 |
| 189 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.22612 |
| 190 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 470.58397 |
| 191 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 192 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 556.90671 |
| 193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 258.05081 |
| 194 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.68782 |
| 195 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.77943 |
| 196 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 258.05081 |
| 197 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 258.05081 |
| 198 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 258.05081 |
| 199 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.68782 |
| 200 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 16325.27340 |
| 201 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.67573 |
| 202 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 236.95994 |
| 203 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 204 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 258.05081 |
| 205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 391.18639 |
| 206 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93158 |
| 207 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80097 |
| 208 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 391.18639 |
| 209 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 391.18639 |
| 210 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 391.18639 |
| 211 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.93158 |
| 212 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 23053.66448 |
| 213 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.36639 |
| 214 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 341.12023 |
| 215 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 216 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 391.18639 |
| 217 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 534.63976 |
| 218 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.27612 |
| 219 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80019 |
| 220 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 534.63976 |
| 221 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 534.63976 |
| 222 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 534.63976 |
| 223 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.27612 |
| 224 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 30304.50838 |
| 225 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.11065 |
| 226 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 453.16544 |
| 227 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 228 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 534.63976 |
| 229 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 249.44912 |
| 230 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.59390 |
| 231 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80006 |
| 232 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 249.44912 |
| 233 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 249.44912 |
| 234 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 249.44912 |
| 235 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.59390 |
| 236 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 15890.62865 |
| 237 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.63112 |
| 238 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 230.21077 |
| 239 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 240 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 249.44912 |
| 241 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 370.63555 |
| 242 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.86803 |
| 243 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80075 |
| 244 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 370.63555 |
| 245 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 370.63555 |
| 246 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 370.63555 |
| 247 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.86803 |
| 248 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Capacity [Btu/h] | 22015.69737 |
| 249 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.25985 |
| 250 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 325.06570 |
| 251 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 252 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 370.63555 |
| 253 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 562.24569 |
| 254 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.33894 |
| 255 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80098 |
| 256 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 562.24569 |
| 257 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 562.24569 |
| 258 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 562.24569 |
| 259 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.33894 |
| 260 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 31698.39104 |
| 261 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.25373 |
| 262 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 474.66021 |
| 263 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 264 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 562.24569 |
| 265 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 270.14827 |
| 266 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.64988 |
| 267 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80052 |
| 268 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 270.14827 |
| 269 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 270.14827 |
| 270 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 270.14827 |
| 271 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.64988 |
| 272 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 16935.95998 |
| 273 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.73843 |
| 274 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 246.39905 |
| 275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 276 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 270.14827 |
| 277 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 400.69910 |
| 278 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95895 |
| 279 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80029 |
| 280 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 400.69910 |
| 281 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 400.69910 |
| 282 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 400.69910 |
| 283 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.95895 |
| 284 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 23534.12908 |
| 285 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.41570 |
| 286 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 348.49209 |
| 287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 288 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 400.69910 |
| 289 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 541.05925 |
| 290 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.28572 |
| 291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80072 |
| 292 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 541.05925 |
| 293 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 541.05925 |
| 294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 541.05925 |
| 295 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.28572 |
| 296 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 30627.64146 |
| 297 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.14383 |
| 298 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 458.08029 |
| 299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 300 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 541.05925 |
| 301 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 262.96607 |
| 302 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.61907 |
| 303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80094 |
| 304 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 262.96607 |
| 305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 262.96607 |
| 306 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 262.96607 |
| 307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.61907 |
| 308 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 16573.06058 |
| 309 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.70117 |
| 310 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 240.76807 |
| 311 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 312 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 262.96607 |
| 313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 379.04656 |
| 314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.89242 |
| 315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80092 |
| 316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 379.04656 |
| 317 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 379.04656 |
| 318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 379.04656 |
| 319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.89242 |
| 320 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Capacity [Btu/h] | 22439.91921 |
| 321 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.30339 |
| 322 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 331.57266 |
| 323 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 324 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 379.04656 |
| 325 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 594.70331 |
| 326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.41327 |
| 327 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80070 |
| 328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 594.70331 |
| 329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 594.70331 |
| 330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 594.70331 |
| 331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.41327 |
| 332 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 33340.45070 |
| 333 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.42229 |
| 334 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 500.01585 |
| 335 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 336 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 594.70331 |
| 337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 307.77538 |
| 338 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.72429 |
| 339 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80008 |
| 340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 307.77538 |
| 341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 307.77538 |
| 342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 307.77538 |
| 343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.72429 |
| 344 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 18838.45720 |
| 345 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.93371 |
| 346 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 275.90234 |
| 347 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 348 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 307.77538 |
| 349 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 397.20334 |
| 350 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95721 |
| 351 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80093 |
| 352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 397.20334 |
| 353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 397.20334 |
| 354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 397.20334 |
| 355 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.95721 |
| 356 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 23358.22694 |
| 357 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.39765 |
| 358 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 345.77702 |
| 359 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 360 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 397.20334 |
| 361 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 592.24569 |
| 362 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.40253 |
| 363 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80089 |
| 364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 592.24569 |
| 365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 592.24569 |
| 366 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 592.24569 |
| 367 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.40253 |
| 368 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 33215.37095 |
| 369 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 3.40945 |
| 370 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 498.08502 |
| 371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 372 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 592.24569 |
| 373 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 314.85166 |
| 374 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.73488 |
| 375 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80093 |
| 376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 314.85166 |
| 377 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 314.85166 |
| 378 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 314.85166 |
| 379 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.73488 |
| 380 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 19195.75692 |
| 381 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 1.97039 |
| 382 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 281.43731 |
| 383 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 384 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 314.85166 |
| 385 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 375.31775 |
| 386 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.88995 |
| 387 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80046 |
| 388 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 375.31775 |
| 389 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 375.31775 |
| 390 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 375.31775 |
| 391 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.88995 |
| 392 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Capacity [Btu/h] | 22252.31527 |
| 393 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Water Flow Rate [gal/min] | 2.28413 |
| 394 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size U-Factor Times Area Value [Btu/h-F] | 328.67553 |
| 395 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 396 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 375.31775 |
| 397 | PlantLoop | BOILER LOOP | Maximum Loop Flow Rate [ft3/min] | 5.91324 |
| 398 | PlantLoop | BOILER LOOP | Plant Loop Volume [ft3] | 11.82967 |
| 399 | Pump:VariableSpeed | BOILER CIRC PUMP | Design Flow Rate [ft3/min] | 5.91324 |
| 400 | Boiler:HotWater | CENTRAL BOILER | Design Size Nominal Capacity [Btu/h] | 0.431029E+06 |
| 401 | Boiler:HotWater | CENTRAL BOILER | Design Size Design Water Flow Rate [gal/min] | 44.24372 |
| 402 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 403 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 404 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 405 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 406 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 407 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 408 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 409 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 410 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 411 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 412 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 413 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 414 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 415 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 416 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 417 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 418 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 419 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 420 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 421 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 422 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 423 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 424 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 425 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 426 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 427 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 428 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 429 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 430 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 431 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 432 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 433 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 434 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 435 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 436 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 437 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 438 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 439 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 440 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 441 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 442 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 443 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 444 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 445 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 446 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 447 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 448 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 449 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 450 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 451 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 452 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 453 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 454 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 455 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 456 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 457 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 458 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 459 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 460 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 461 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 462 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 463 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 464 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 465 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 466 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 467 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 468 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 469 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 470 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 471 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 472 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 473 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 474 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 475 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 476 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 477 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 478 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 479 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 480 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 481 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 482 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 483 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 484 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 485 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 486 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 487 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 488 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 489 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 490 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 36002.05920 |
| 491 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | 3.32 | 11.34 | 12.02 | 11.55 | 11.59 |
| 2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | 3.19 | 10.89 | 11.52 | 11.39 | -99999. |
| 3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.39 | 11.58 | 12.27 | 11.80 | 11.96 |
| 4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.27 | 11.16 | 11.81 | 11.68 | -99999. |
| 5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 |
| 6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.19 | 10.88 | 11.51 | 11.38 | -99999. |
| 7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.32 | 11.34 | 12.01 | 11.54 | 11.58 |
| 8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.19 | 10.89 | 11.52 | 11.39 | -99999. |
| 9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 |
| 10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.19 | 10.88 | 11.51 | 11.38 | -99999. |
| 11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.31 | 11.30 | 11.96 | 11.50 | 11.51 |
| 12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.18 | 10.84 | 11.46 | 11.33 | -99999. |
| 13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 |
| 14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.19 | 10.88 | 11.51 | 11.38 | -99999. |
| 15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.33 | 11.36 | 12.03 | 11.56 | 11.61 |
| 16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.20 | 10.91 | 11.54 | 11.41 | -99999. |
| 17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.32 | 11.34 | 12.02 | 11.55 | 11.59 |
| 18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.19 | 10.90 | 11.52 | 11.39 | -99999. |
| 19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 |
| 20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.19 | 10.88 | 11.50 | 11.37 | -99999. |
| 21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 |
| 22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.18 | 10.85 | 11.48 | 11.35 | -99999. |
| 23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 |
| 24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.18 | 10.85 | 11.48 | 11.35 | -99999. |
| 25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 |
| 26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.3 | 3.19 | 10.88 | 11.50 | 11.37 | -99999. |
| 27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.7 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 |
| 28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.7 | 3.18 | 10.85 | 11.48 | 11.35 | -99999. |
| 29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.33 | 11.36 | 12.03 | 11.57 | 11.61 |
| 30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.20 | 10.91 | 11.54 | 11.41 | -99999. |
| 31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.32 | 11.32 | 11.99 | 11.53 | 11.55 |
| 32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.19 | 10.87 | 11.49 | 11.36 | -99999. |
| 33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.7 | 3.31 | 11.29 | 11.96 | 11.49 | 11.50 |
| 34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.7 | 3.17 | 10.83 | 11.45 | 11.32 | -99999. |
| 35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.32 | 11.32 | 11.99 | 11.53 | 11.56 |
| 36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.8 | 3.19 | 10.87 | 11.50 | 11.37 | -99999. |
| Component Type | Name | Nominal Total Capacity {Btu/h} | |
| 1 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 32793.79 |
| 2 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 16082.70 |
| 3 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 23542.80 |
| 4 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 31551.04 |
| 5 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15598.54 |
| 6 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 22394.42 |
| 7 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 33087.87 |
| 8 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 16761.14 |
| 9 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 24072.24 |
| 10 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 31904.96 |
| 11 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 16357.33 |
| 12 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 22862.00 |
| 13 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 34898.28 |
| 14 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 18874.74 |
| 15 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 23877.55 |
| 16 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 34760.36 |
| 17 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 19271.15 |
| 18 | Coil:Heating:Water | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 22654.28 |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 2 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | No | SizingPeriod:DesignDay | ||
| 2 | No | SizingPeriod:DesignDay | ||
| 3 | No |
| NumberofWarmupDays | |
| 1 | 7 |
| 2 | 6 |
| 3 | 6 |
| Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
| 1 | -0.2 | 0.00 | DefaultMultipliers | Wetbulb | -17.90 | {C} | 12. | 180 | 492.2 | 0.00 | No | No |
| 2 | 93.02 | 14.80 | DefaultMultipliers | Wetbulb | 15.00 | {C} | 12. | 30 | 708.7 | 0.00 | No | No |
| DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
| 1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
| 2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | UNHEATEDBSMT | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000669848 | 0.000490027 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 2 | BREEZEWAY | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000807056 | 0.000218274 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 3 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000003119 | 0.000004971 | Pass | Pass | 0.010124565 | 0.016804976 | Pass | Pass |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000006805 | 0.000011418 | Pass | Pass | 0.013263792 | 0.021931434 | Pass | Pass |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000004677 | 0.000007573 | Pass | Pass | 0.010121273 | 0.016798346 | Pass | Pass |
| 6 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000001880 | 0.000002879 | Pass | Pass | 0.010122423 | 0.016802315 | Pass | Pass |
| 7 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000007018 | 0.000011784 | Pass | Pass | 0.013264168 | 0.021932377 | Pass | Pass |
| 8 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000001766 | 0.000002438 | Pass | Pass | 0.010125034 | 0.016806766 | Pass | Pass |
| 9 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000002491 | 0.000003949 | Pass | Pass | 0.011205377 | 0.018193354 | Pass | Pass |
| 10 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000068320 | 0.000303670 | Pass | Pass | 0.015354156 | 0.024923112 | Pass | Pass |
| 11 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000004237 | 0.000006687 | Pass | Pass | 0.011201330 | 0.018185267 | Pass | Pass |
| 12 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000001254 | 0.000001826 | Pass | Pass | 0.011203512 | 0.018190943 | Pass | Pass |
| 13 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000064467 | 0.000295195 | Pass | Pass | 0.015364968 | 0.024851591 | Pass | Pass |
| 14 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000002561 | 0.000004067 | Pass | Pass | 0.011206552 | 0.018195005 | Pass | Pass |
| 15 | ATTIC | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000065493 | 0.000055089 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 16 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000005064 | 0.000007537 | Pass | Pass | 0.008720609 | 0.013497250 | Pass | Pass |
| 17 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000021564 | 0.000143587 | Pass | Pass | 0.008725901 | 0.013502705 | Pass | Pass |
| 18 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000002683 | 0.000004064 | Pass | Pass | 0.008720089 | 0.013497871 | Pass | Pass |
| 19 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000007275 | 0.000011303 | Pass | Pass | 0.011081326 | 0.017107338 | Pass | Pass |
| 20 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000007448 | 0.000011575 | Pass | Pass | 0.011079150 | 0.017104187 | Pass | Pass |
| 21 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000003211 | 0.000004779 | Pass | Pass | 0.008719952 | 0.013497323 | Pass | Pass |
| 22 | UNHEATEDBSMT | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.025033634 | 0.012530751 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 23 | BREEZEWAY | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.073952389 | 0.040878467 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 24 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003641 | 0.000007861 | Pass | Pass | 0.122188636 | 0.052330777 | Pass | Pass |
| 25 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000001749 | 0.000004273 | Pass | Pass | 0.082773891 | 0.054671170 | Pass | Pass |
| 26 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002699 | 0.000005470 | Pass | Pass | 0.103215665 | 0.105226818 | Pass | Pass |
| 27 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000006095 | 0.000023166 | Pass | Pass | 0.120388168 | 0.054261016 | Pass | Pass |
| 28 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000001979 | 0.000004341 | Pass | Pass | 0.076987149 | 0.053839639 | Pass | Pass |
| 29 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002514 | 0.000005115 | Pass | Pass | 0.100693490 | 0.109462960 | Pass | Pass |
| 30 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003356 | 0.000007798 | Pass | Pass | 0.106032871 | 0.041617293 | Pass | Pass |
| 31 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000001936 | 0.000004462 | Pass | Pass | 0.069226657 | 0.046505031 | Pass | Pass |
| 32 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002437 | 0.000005353 | Pass | Pass | 0.088633918 | 0.084796695 | Pass | Pass |
| 33 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003390 | 0.000007673 | Pass | Pass | 0.104065942 | 0.040841923 | Pass | Pass |
| 34 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000001828 | 0.000004167 | Pass | Pass | 0.064532712 | 0.043294979 | Pass | Pass |
| 35 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002250 | 0.000005094 | Pass | Pass | 0.086433167 | 0.088283833 | Pass | Pass |
| 36 | ATTIC | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.661190176 | 0.473963992 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 37 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002760 | 0.000005940 | Pass | Pass | 0.088016876 | 0.087617695 | Pass | Pass |
| 38 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002971 | 0.000006075 | Pass | Pass | 0.088914888 | 0.085098366 | Pass | Pass |
| 39 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003806 | 0.000008244 | Pass | Pass | 0.108483301 | 0.041960281 | Pass | Pass |
| 40 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002374 | 0.000005193 | Pass | Pass | 0.072588393 | 0.040976692 | Pass | Pass |
| 41 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002338 | 0.000005231 | Pass | Pass | 0.072855790 | 0.048701056 | Pass | Pass |
| 42 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003953 | 0.000008288 | Pass | Pass | 0.108000359 | 0.039039395 | Pass | Pass |
| 43 | UNHEATEDBSMT | RunPeriod: ANNUAL | 0.026515756 | 0.023022745 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 44 | BREEZEWAY | RunPeriod: ANNUAL | 0.033985644 | 0.021579735 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 45 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041741920 | 0.072859248 | Pass | Pass | 0.350482866 | 0.999955316 | Pass | Pass |
| 46 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.042236370 | 0.074124822 | Pass | Pass | 0.261107805 | 0.530158969 | Pass | Pass |
| 47 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.063700106 | 0.144941409 | Pass | Pass | 0.249793574 | 0.557955084 | Pass | Pass |
| 48 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.091723352 | 0.300489530 | Pass | Pass | 0.690486700 | 2.883565170 | Pass | Pass |
| 49 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.032347821 | 0.136510519 | Pass | Pass | 0.362694753 | 1.187932105 | Pass | Pass |
| 50 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.004208292 | 0.016086413 | Pass | Pass | 0.326478137 | 1.011887051 | Pass | Pass |
| 51 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041691346 | 0.070045119 | Pass | Pass | 0.392156272 | 0.888610466 | Pass | Pass |
| 52 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041661353 | 0.072578085 | Pass | Pass | 0.292312785 | 0.497828165 | Pass | Pass |
| 53 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.067439981 | 0.177478223 | Pass | Pass | 0.328129089 | 0.863396164 | Pass | Pass |
| 54 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.084767938 | 0.309772955 | Pass | Pass | 0.838341996 | 4.343442956 | Pass | Pass |
| 55 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.028426216 | 0.114120174 | Pass | Pass | 0.432970375 | 1.661842953 | Pass | Pass |
| 56 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.004546472 | 0.019814794 | Pass | Pass | 0.238169445 | 0.728250258 | Pass | Pass |
| 57 | ATTIC | RunPeriod: ANNUAL | 0.498672078 | 0.625305340 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 58 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000214848 | 0.001573619 | Pass | Pass | 0.158699156 | 0.348540489 | Pass | Pass |
| 59 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.062369663 | 0.122230739 | Pass | Pass | 0.362089468 | 1.271723941 | Pass | Pass |
| 60 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.044122008 | 0.083941401 | Pass | Pass | 0.608595409 | 3.371584291 | Pass | Pass |
| 61 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.002242330 | 0.014062189 | Pass | Pass | 0.156318390 | 0.502221059 | Pass | Pass |
| 62 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.042279862 | 0.063533421 | Pass | Pass | 0.235740574 | 0.600659525 | Pass | Pass |
| 63 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.096353656 | 0.369369162 | Pass | Pass | 0.703393094 | 3.982420021 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Annual Heat Emissions Summary| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [kBtu] | 2656442.34 | 416085.35 | 197402.11 | 0.00 | 330330.14 | 3600262.83 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Heat Index Hours| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 8559.50 | 200.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 7596.83 | 683.33 | 448.17 | 31.67 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 7596.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 683.33 | 448.17 | 31.67 | 0.00 |
| Average | 8695.06 | 42.09 | 21.34 | 1.51 | 0.00 |
| Sum | 182596.33 | 883.83 | 448.17 | 31.67 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 10339.18 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| UNHEATEDBSMT | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 7837.17 | 855.83 | 59.83 | 7.17 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 7837.17 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 855.83 | 59.83 | 7.17 | 0.00 |
| Average | 8716.06 | 40.75 | 2.85 | 0.34 | 0.00 |
| Sum | 183037.17 | 855.83 | 59.83 | 7.17 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 10339.18 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| UNHEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| UNHEATEDBSMT | 0.00 | - | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7508.57 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.13 | 0.15 | 0.13 | 28.59 | 29.25 | 28.59 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.11 | 0.14 | 0.11 | 5.43 | 4.05 | 5.43 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.15 | 0.15 | 0.15 | 161.79 | 310.83 | 161.79 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.11 | 0.14 | 0.11 | 1033.33 | 721.74 | 1033.33 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.56 | 0.94 | 0.56 | 152.25 | 112.38 | 152.25 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.12 | 0.13 | 0.12 | 66.57 | 130.58 | 66.57 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.14 | 0.17 | 0.14 | 46.94 | 44.90 | 46.94 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.12 | 0.15 | 0.12 | 1.21 | 1.07 | 1.21 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.15 | 0.16 | 0.15 | 206.32 | 403.45 | 206.32 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.12 | 0.15 | 0.12 | 930.63 | 662.16 | 930.63 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.29 | 0.49 | 0.29 | 90.30 | 71.67 | 90.30 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.10 | 0.12 | 0.10 | 92.49 | 183.23 | 92.49 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.12 | 0.14 | 0.12 | 65.56 | 129.65 | 65.56 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.14 | 0.13 | 0.14 | 131.05 | 255.14 | 131.05 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.13 | 0.14 | 0.13 | 166.90 | 147.35 | 166.90 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.36 | 0.61 | 0.36 | 77.78 | 64.71 | 77.78 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.15 | 0.21 | 0.15 | 8.86 | 5.29 | 8.86 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.11 | 0.14 | 0.11 | 957.80 | 606.22 | 957.80 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.56 | 0.94 | 0.56 | 1033.33 | 721.74 | 1033.33 |
| Average | 0.15 | 0.20 | 0.15 | 201.13 | 184.94 | 201.13 |
| Sum | 3.11 | 4.25 | 3.11 | 4223.79 | 3883.67 | 4223.79 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
SizingPeriod:DesignDay| Maximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
| DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -0.2 | 0.00 | -0.2 | Wetbulb [F] | 492.15 | 180.00 |
| DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 93.02 | 26.64 | 59.00 | Wetbulb [F] | 708.70 | 30.00 |
| Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
| Jan | 0.43 | 10 | |||
| Feb | 0.59 | 16 | |||
| Mar | 3.46 | 32 | |||
| Apr | 6.26 | 54 | |||
| May | 1.18 | 24 | |||
| Jun | 0.43 | 4 | |||
| Jul | 6.57 | 26 | |||
| Aug | 1.30 | 24 | |||
| Sep | 0.31 | 8 | |||
| Oct | 0.51 | 10 | |||
| Nov | 0.47 | 22 | |||
| Dec | 0.43 | 18 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Opaque Exterior| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| BGWALL_UPPER_LDF | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 180.00 | 90.00 | S |
| BGWALL_LOWER_LDF | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 180.00 | 90.00 | S |
| BGWALL_UPPER_SDR | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 90.00 | 90.00 | E |
| BGWALL_LOWER_SDR | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 90.00 | 90.00 | E |
| BGWALL_UPPER_LDB | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 59.96 | 59.96 | 0.00 | 90.00 | N |
| BGWALL_LOWER_LDB | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 839.40 | 839.40 | 0.00 | 90.00 | N |
| BGWALL_UPPER_SDL | BASEMENT WALL | 0.30 | 0.367 | 0.534 | 32.56 | 32.56 | 270.00 | 90.00 | W |
| BGWALL_LOWER_SDL | BASEMENT WALL | 0.30 | 0.392 | 0.534 | 455.77 | 455.77 | 270.00 | 90.00 | W |
| BGFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 7794.39 | 7794.39 | 0.00 | 180.00 | |
| BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 599.39 | 599.39 | 0.00 | 180.00 | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
| ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
| ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
| ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.060 | 0.063 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | iz-EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.033 | 0.034 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 599.39 | 599.39 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.022 | 0.022 | 1200.55 | 1200.55 | 180.00 | 0.00 |
| Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.320 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.320 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| Total or Average | 2126.74 | 0.320 | 0.335 | 0.883 | |||||||||||||||||
| North Total or Average | 531.68 | 0.320 | 0.335 | 0.883 | |||||||||||||||||
| Non-North Total or Average | 1595.05 | 0.320 | 0.335 | 0.883 |
| Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.252 | 0.320 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
| LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.4843 | 1200.55 | 581.41 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 523.13 |
| LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| Interior Lighting Total | 0.3333 | 43219.92 | 14404.00 | 12960.20 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| Exterior Lighting Total | 1377.69 | 6034.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Central Plant| Type | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| CENTRAL BOILER | Boiler:HotWater | 431028.79 | 0.80 |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15983.17 | 12794.60 | 3188.57 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8253.84 | 6433.30 | 1820.54 | 0.78 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 11179.00 | 8954.02 | 2224.98 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 15313.48 | 12253.76 | 3059.71 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7126.77 | 5701.88 | 1424.89 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 10416.40 | 8340.96 | 2075.44 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 16067.24 | 12869.53 | 3197.71 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7798.55 | 6242.90 | 1555.65 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11507.43 | 9209.28 | 2298.15 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15428.65 | 12353.97 | 3074.68 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7428.87 | 5950.09 | 1478.77 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10709.03 | 8577.06 | 2131.97 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16959.29 | 13579.34 | 3379.95 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8691.45 | 6953.84 | 1737.60 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11486.52 | 9199.87 | 2286.65 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 16830.31 | 13479.31 | 3351.01 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 8818.54 | 7063.07 | 1755.47 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 10679.35 | 8548.41 | 2130.94 | 0.80 | 4.09 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.3 | 3.32 | 11.34 | 12.02 | 11.55 | 11.59 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.7 | 3.39 | 11.58 | 12.27 | 11.80 | 11.96 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.2 | 3.32 | 11.34 | 12.01 | 11.54 | 11.58 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.8 | 3.31 | 11.30 | 11.96 | 11.50 | 11.51 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.33 | 11.36 | 12.03 | 11.56 | 11.61 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.32 | 11.34 | 12.02 | 11.55 | 11.59 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.9 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.7 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 0.9 | 3.33 | 11.36 | 12.03 | 11.57 | 11.61 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.3 | 3.32 | 11.32 | 11.99 | 11.53 | 11.55 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.7 | 3.31 | 11.29 | 11.96 | 11.49 | 11.50 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.32 | 11.32 | 11.99 | 11.53 | 11.56 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.19 | 10.89 | 11.52 | 11.39 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.27 | 11.16 | 11.81 | 11.68 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.19 | 10.88 | 11.51 | 11.38 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.19 | 10.89 | 11.52 | 11.39 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.19 | 10.88 | 11.51 | 11.38 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.18 | 10.84 | 11.46 | 11.33 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.19 | 10.88 | 11.51 | 11.38 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.20 | 10.91 | 11.54 | 11.41 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.19 | 10.90 | 11.52 | 11.39 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.19 | 10.88 | 11.50 | 11.37 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.18 | 10.85 | 11.48 | 11.35 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.18 | 10.85 | 11.48 | 11.35 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.19 | 10.88 | 11.50 | 11.37 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.18 | 10.85 | 11.48 | 11.35 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.20 | 10.91 | 11.54 | 11.41 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.19 | 10.87 | 11.49 | 11.36 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.17 | 10.83 | 11.45 | 11.32 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.19 | 10.87 | 11.50 | 11.37 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
| Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 31429.34 | 32793.79 | - |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 16325.27 | 16082.71 | - |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | 23053.66 | 23542.81 | - |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 30304.51 | 31551.04 | - |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 15890.63 | 15598.54 | - |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | 22015.70 | 22394.41 | - |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 31698.39 | 33087.87 | - |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 16935.96 | 16761.13 | - |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | 23534.13 | 24072.23 | - |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 30627.64 | 31904.95 | - |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 16573.06 | 16357.35 | - |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | 22439.92 | 22862.02 | - |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | 33340.45 | 34898.28 | - |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | 18838.46 | 18874.73 | - |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | 23358.23 | 23877.56 | - |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | 33215.37 | 34760.38 | - |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | 19195.76 | 19271.14 | - |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | 22252.32 | 22654.29 | - |
| Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 556.90 | 210.06 | 0.38 | 1.00 | 2.04 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 258.05 | 97.34 | 0.38 | 1.00 | 3.01 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 391.18 | 147.55 | 0.38 | 1.00 | 2.40 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 534.64 | 201.66 | 0.38 | 1.00 | 2.08 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 249.45 | 94.09 | 0.38 | 1.00 | 3.07 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 370.64 | 139.80 | 0.38 | 1.00 | 2.47 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 562.25 | 212.08 | 0.38 | 1.00 | 2.04 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 270.14 | 101.90 | 0.38 | 1.00 | 2.93 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 400.70 | 151.14 | 0.38 | 1.00 | 2.37 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 541.06 | 204.08 | 0.38 | 1.00 | 2.07 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 262.96 | 99.19 | 0.38 | 1.00 | 2.98 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 379.05 | 142.97 | 0.38 | 1.00 | 2.44 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 594.71 | 224.32 | 0.38 | 1.00 | 1.99 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 307.78 | 116.09 | 0.38 | 1.00 | 2.72 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 397.20 | 149.82 | 0.38 | 1.00 | 2.38 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 592.24 | 223.39 | 0.38 | 1.00 | 1.99 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 314.85 | 118.76 | 0.38 | 1.00 | 2.69 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 375.32 | 141.57 | 0.38 | 1.00 | 2.45 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
| BOILER CIRC PUMP | Pump:VariableSpeed | Intermittent | 0.00 | 44.243687 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 36002.06 | 0.80 | 0.82 | 0.60 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Zone Sensible Cooling| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10618.03 | 10618.03 | 8.84 | 556.899 | 556.899 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00748 | 87.96 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4920.19 | 4920.19 | 4.10 | 258.051 | 258.051 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 75.00 | 75.00 | 0.00731 | 93.02 | 0.00548 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 7458.34 | 7458.34 | 6.21 | 391.177 | 391.177 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 75.00 | 75.00 | 0.00737 | 85.56 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10193.67 | 10193.67 | 8.49 | 534.643 | 534.643 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00749 | 87.51 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4756.06 | 4756.06 | 3.96 | 249.451 | 249.451 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00758 | 83.30 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 7066.75 | 7066.75 | 5.89 | 370.640 | 370.640 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00737 | 83.56 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10719.90 | 10719.90 | 8.93 | 562.246 | 562.246 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00752 | 87.51 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5150.60 | 5150.60 | 4.29 | 270.145 | 270.145 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00761 | 84.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7639.87 | 7639.87 | 6.36 | 400.700 | 400.700 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 75.00 | 75.00 | 0.00741 | 86.23 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10315.92 | 10315.92 | 8.59 | 541.059 | 541.059 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00753 | 87.07 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5013.67 | 5013.67 | 4.18 | 262.964 | 262.964 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00764 | 82.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 7227.06 | 7227.06 | 6.02 | 379.049 | 379.049 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 75.00 | 75.00 | 0.00740 | 84.23 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 7156.02 | 7156.02 | 5.96 | 375.321 | 375.321 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 75.00 | 75.00 | 0.00737 | 84.89 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 7573.23 | 7573.23 | 6.31 | 397.203 | 397.203 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 75.00 | 75.00 | 0.00737 | 86.89 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 11338.95 | 11338.95 | 9.44 | 594.712 | 594.712 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00750 | 87.51 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 6002.90 | 6002.90 | 5.00 | 314.847 | 314.847 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00758 | 82.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 5868.11 | 5868.11 | 4.89 | 307.778 | 307.778 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00757 | 83.30 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 11291.74 | 11291.74 | 9.41 | 592.237 | 592.237 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00750 | 87.07 | 0.00547 | 44.995 | 0.00 |
| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 10064.44 | 10064.44 | 8.38 | 225.671 | 225.671 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00631 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 7688.71 | 7688.71 | 6.40 | 172.404 | 172.404 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00603 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 10067.22 | 10067.22 | 8.39 | 225.733 | 225.733 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00631 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10066.89 | 10066.89 | 8.39 | 225.726 | 225.726 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00631 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 7688.33 | 7688.33 | 6.40 | 172.395 | 172.395 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00603 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10064.08 | 10064.08 | 8.38 | 225.663 | 225.663 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00631 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8946.66 | 8946.66 | 7.45 | 200.617 | 200.617 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00649 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 6562.24 | 6562.24 | 5.47 | 147.151 | 147.151 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00619 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8949.28 | 8949.28 | 7.45 | 200.675 | 200.675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00649 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8948.61 | 8948.61 | 7.45 | 200.660 | 200.660 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00649 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6561.57 | 6561.57 | 5.47 | 147.136 | 147.136 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00619 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8946.00 | 8946.00 | 7.45 | 200.602 | 200.602 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00649 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 11441.88 | 11441.88 | 9.53 | 256.557 | 256.557 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 11445.50 | 11445.50 | 9.53 | 256.638 | 256.638 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 11443.60 | 11443.60 | 9.53 | 256.595 | 256.595 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 9056.46 | 9056.46 | 7.54 | 203.072 | 203.072 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00624 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 9058.18 | 9058.18 | 7.55 | 203.111 | 203.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00624 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 11443.75 | 11443.75 | 9.53 | 256.598 | 256.598 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00646 | -0.2 | 0.00096 | 44.995 | 0.00 |
| Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.90 | 556.90 | 225.67 | 225.67 | 556.8993 | 556.8993 | 556.8993 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.05 | 258.05 | 172.40 | 172.40 | 258.0514 | 258.0514 | 258.0514 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.18 | 391.18 | 225.73 | 225.73 | 391.1770 | 391.1770 | 391.1770 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.64 | 534.64 | 225.73 | 225.73 | 534.6432 | 534.6432 | 534.6432 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.45 | 249.45 | 172.40 | 172.40 | 249.4514 | 249.4514 | 249.4514 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.64 | 370.64 | 225.66 | 225.66 | 370.6397 | 370.6397 | 370.6397 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.25 | 562.25 | 200.62 | 200.62 | 562.2462 | 562.2462 | 562.2462 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.14 | 270.14 | 147.15 | 147.15 | 270.1450 | 270.1450 | 270.1450 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.70 | 400.70 | 200.68 | 200.68 | 400.6997 | 400.6997 | 400.6997 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.06 | 541.06 | 200.66 | 200.66 | 541.0593 | 541.0593 | 541.0593 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.96 | 262.96 | 147.14 | 147.14 | 262.9642 | 262.9642 | 262.9642 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.05 | 379.05 | 200.60 | 200.60 | 379.0486 | 379.0486 | 379.0486 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.71 | 594.71 | 256.60 | 256.60 | 594.7119 | 594.7119 | 594.7119 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.78 | 307.78 | 203.11 | 203.11 | 307.7778 | 307.7778 | 307.7778 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.20 | 397.20 | 256.64 | 256.64 | 397.2026 | 397.2026 | 397.2026 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.24 | 592.24 | 256.60 | 256.60 | 592.2371 | 592.2371 | 592.2371 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.85 | 314.85 | 203.07 | 203.07 | 314.8474 | 314.8474 | 314.8474 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.32 | 375.32 | 256.56 | 256.56 | 375.3210 | 375.3210 | 375.3210 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 15983.170 | 12794.603 | 556.899267 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 14813.14 | 14813.14 | 556.899267 | 77.49 | 56.67 | 0.00731768 | 53.60 | 47.74 | 0.00731768 | 87.96 | 0.00547095 | 57.46 | 8.0796 | 75.00 | 0.00746052 | 32.8713 | 10610.46 | 0.00 | 15989.84 | 11544.54 |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 31429.342 | 31429.342 | 556.899267 | 0.43117562 | 470.584 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 31429.34 | 27733.83 | 556.899267 | 66.15 | 50.22 | 0.00587589 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 8.0796 | 71.99 | 0.00630840 | 30.8126 | 10064.44 | 0.00 | 32766.61 | 32766.61 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 8253.841 | 6433.303 | 258.051437 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 7461.80 | 7461.80 | 258.051437 | 79.59 | 56.90 | 0.00699314 | 53.60 | 47.16 | 0.00699314 | 93.02 | 0.00547527 | 59.13 | 17.4364 | 75.00 | 0.00731370 | 32.2314 | 4920.19 | 0.00 | 8257.29 | 5828.52 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 16325.273 | 16325.273 | 258.051437 | 0.22396460 | 236.960 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 16325.27 | 14405.72 | 258.051437 | 59.40 | 46.17 | 0.00514113 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 17.4364 | 71.99 | 0.00602514 | 29.4415 | 7688.71 | 0.00 | 16060.30 | 16060.30 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 11179.000 | 8954.020 | 391.177027 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | 10475.11 | 10475.11 | 391.177027 | 77.66 | 56.48 | 0.00715018 | 53.60 | 47.44 | 0.00715018 | 85.56 | 0.00546891 | 56.64 | 11.5025 | 75.00 | 0.00736714 | 32.4645 | 7421.43 | 0.00 | 11183.66 | 8078.80 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 23053.664 | 23053.664 | 391.177027 | 0.31627064 | 341.120 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 23053.66 | 20342.98 | 391.177027 | 63.68 | 48.93 | 0.00569296 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 11.5025 | 71.99 | 0.00630874 | 30.8143 | 10067.22 | 0.00 | 23519.92 | 23519.92 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 15313.475 | 12253.762 | 534.643158 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 14224.96 | 14224.96 | 534.643158 | 77.50 | 56.68 | 0.00732371 | 53.60 | 47.76 | 0.00732371 | 87.51 | 0.00547057 | 57.31 | 8.4159 | 75.00 | 0.00749400 | 33.0172 | 10193.67 | 0.00 | 15319.87 | 11057.53 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 30304.508 | 30304.508 | 534.643158 | 0.41574415 | 453.165 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 30304.51 | 26741.26 | 534.643158 | 65.91 | 50.10 | 0.00585816 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 8.4159 | 71.99 | 0.00630870 | 30.8141 | 10066.89 | 0.00 | 31524.46 | 31524.46 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 7126.773 | 5701.879 | 249.451370 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 6758.58 | 6758.58 | 249.451370 | 77.94 | 56.64 | 0.00719555 | 53.60 | 47.52 | 0.00719555 | 83.30 | 0.00546700 | 55.86 | 18.0376 | 75.00 | 0.00756500 | 33.3264 | 4742.38 | 0.00 | 7129.75 | 5145.55 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 15890.629 | 15890.629 | 249.451370 | 0.21800175 | 230.211 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15890.63 | 14022.18 | 249.451370 | 58.96 | 45.93 | 0.00511059 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 18.0376 | 71.99 | 0.00602507 | 29.4412 | 7688.33 | 0.00 | 15576.38 | 15576.38 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 10416.396 | 8340.956 | 370.639678 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 9852.64 | 9852.64 | 370.639678 | 77.49 | 56.40 | 0.00713722 | 53.60 | 47.42 | 0.00713722 | 83.56 | 0.00546722 | 55.95 | 12.1398 | 75.00 | 0.00736543 | 32.4571 | 7048.68 | 0.00 | 10420.74 | 7524.35 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 22015.697 | 22015.697 | 370.639678 | 0.30203088 | 325.066 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22015.70 | 19427.06 | 370.639678 | 63.22 | 48.68 | 0.00565850 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 12.1398 | 71.99 | 0.00630835 | 30.8124 | 10064.08 | 0.00 | 22372.02 | 22372.02 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 16067.236 | 12869.530 | 562.246242 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 14927.87 | 14927.87 | 562.246242 | 77.45 | 56.72 | 0.00735978 | 53.60 | 47.82 | 0.00735978 | 87.51 | 0.00547057 | 57.31 | 8.0027 | 75.00 | 0.00750891 | 33.0821 | 10718.03 | 0.00 | 16073.94 | 11611.55 |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 31698.391 | 31698.391 | 562.246242 | 0.43486667 | 474.660 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 31698.39 | 27971.24 | 562.246242 | 66.21 | 50.54 | 0.00604450 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 8.0027 | 71.99 | 0.00648721 | 31.6745 | 8946.66 | 0.00 | 33063.89 | 33063.89 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 7798.555 | 6242.902 | 270.144975 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 7352.17 | 7352.17 | 270.144975 | 78.05 | 56.76 | 0.00725090 | 53.60 | 47.62 | 0.00725090 | 84.63 | 0.00546812 | 56.32 | 16.6559 | 75.00 | 0.00737212 | 32.4861 | 5050.38 | 0.00 | 7801.81 | 5632.51 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 16935.960 | 16935.960 | 270.144975 | 0.23234254 | 246.399 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 16935.96 | 14944.60 | 270.144975 | 59.96 | 46.74 | 0.00532181 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 16.6559 | 71.99 | 0.00619445 | 30.2584 | 6562.24 | 0.00 | 16739.94 | 16739.94 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11507.427 | 9209.282 | 400.699749 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 10751.26 | 10751.26 | 400.699749 | 77.71 | 56.55 | 0.00718810 | 53.60 | 47.51 | 0.00718810 | 86.23 | 0.00546947 | 56.87 | 11.2291 | 75.00 | 0.00740532 | 32.6309 | 7635.83 | 0.00 | 11512.23 | 8309.83 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 23534.129 | 23534.129 | 400.699749 | 0.32286208 | 348.492 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 23534.13 | 20766.95 | 400.699749 | 63.88 | 49.31 | 0.00586631 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 11.2291 | 71.99 | 0.00648754 | 31.6761 | 8949.28 | 0.00 | 24051.53 | 24051.53 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15428.648 | 12353.969 | 541.059286 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 14366.74 | 14366.74 | 541.059286 | 77.45 | 56.72 | 0.00736103 | 53.60 | 47.82 | 0.00736103 | 87.07 | 0.00547019 | 57.16 | 8.3161 | 75.00 | 0.00753253 | 33.1851 | 10315.92 | 0.00 | 15435.09 | 11147.26 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 30627.641 | 30627.641 | 541.059286 | 0.42017718 | 458.080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 30627.64 | 27026.40 | 541.059286 | 65.99 | 50.42 | 0.00602739 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 8.3161 | 71.99 | 0.00648746 | 31.6757 | 8948.61 | 0.00 | 31881.43 | 31881.43 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 7428.865 | 5950.092 | 262.964167 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7069.66 | 7069.66 | 262.964167 | 77.75 | 56.68 | 0.00726688 | 53.60 | 47.65 | 0.00726688 | 82.63 | 0.00546644 | 55.63 | 17.1107 | 75.00 | 0.00762106 | 33.5705 | 4977.69 | 0.00 | 7431.96 | 5367.14 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 16573.061 | 16573.061 | 262.964167 | 0.22736396 | 240.768 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 16573.06 | 14624.37 | 262.964167 | 59.64 | 46.56 | 0.00529787 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 17.1107 | 71.99 | 0.00619432 | 30.2578 | 6561.57 | 0.00 | 16336.33 | 16336.33 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 10709.027 | 8577.061 | 379.048589 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 10100.40 | 10100.40 | 379.048589 | 77.54 | 56.47 | 0.00717391 | 53.60 | 47.48 | 0.00717391 | 84.23 | 0.00546778 | 56.18 | 11.8705 | 75.00 | 0.00740222 | 32.6174 | 7217.08 | 0.00 | 10713.50 | 7736.77 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 22439.919 | 22439.919 | 379.048589 | 0.30785074 | 331.573 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22439.92 | 19801.40 | 379.048589 | 63.42 | 49.07 | 0.00583046 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 11.8705 | 71.99 | 0.00648712 | 31.6741 | 8946.00 | 0.00 | 22841.72 | 22841.72 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 16959.288 | 13579.336 | 594.711918 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 15753.28 | 15753.28 | 594.711918 | 77.39 | 56.68 | 0.00734363 | 53.60 | 47.79 | 0.00734363 | 87.51 | 0.00547057 | 57.31 | 7.5658 | 75.00 | 0.00748258 | 32.9674 | 11324.20 | 0.00 | 16966.37 | 12252.97 |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 33340.451 | 33340.451 | 594.711918 | 0.45739390 | 500.016 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 33340.45 | 29420.23 | 594.711918 | 66.53 | 50.66 | 0.00604593 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 7.5658 | 71.99 | 0.00646261 | 31.5581 | 11443.60 | 0.00 | 34873.13 | 34873.13 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 8691.445 | 6953.842 | 307.777757 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 8242.67 | 8242.67 | 307.777757 | 77.66 | 56.65 | 0.00726381 | 53.60 | 47.65 | 0.00726381 | 83.30 | 0.00546700 | 55.86 | 14.6193 | 75.00 | 0.00751730 | 33.1187 | 5820.88 | 0.00 | 8695.07 | 6273.78 |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 18838.457 | 18838.457 | 307.777757 | 0.25844268 | 275.902 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18838.46 | 16623.40 | 307.777757 | 61.43 | 47.61 | 0.00546763 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 14.6193 | 71.99 | 0.00624027 | 30.4825 | 9058.18 | 0.00 | 18853.09 | 18853.09 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 11486.519 | 9199.868 | 397.202634 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 10695.10 | 10695.10 | 397.202634 | 77.79 | 56.53 | 0.00715406 | 53.60 | 47.45 | 0.00715406 | 86.89 | 0.00547004 | 57.10 | 11.3280 | 75.00 | 0.00736417 | 32.4512 | 7547.02 | 0.00 | 11491.31 | 8299.48 |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 23358.227 | 23358.227 | 397.202634 | 0.32044890 | 345.777 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 23358.23 | 20611.73 | 397.202634 | 63.81 | 49.24 | 0.00583891 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 11.3280 | 71.99 | 0.00646280 | 31.5591 | 11445.50 | 0.00 | 23856.60 | 23856.60 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 16830.313 | 13479.307 | 592.237078 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 15668.22 | 15668.22 | 592.237078 | 77.36 | 56.68 | 0.00734967 | 53.60 | 47.80 | 0.00734967 | 87.07 | 0.00547019 | 57.16 | 7.5975 | 75.00 | 0.00750421 | 33.0617 | 11291.74 | 0.00 | 16837.34 | 12162.61 |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 33215.371 | 33215.371 | 592.237078 | 0.45567795 | 498.085 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 33215.37 | 29309.86 | 592.237078 | 66.50 | 50.65 | 0.00604420 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 7.5975 | 71.99 | 0.00646262 | 31.5582 | 11443.75 | 0.00 | 34735.28 | 34735.28 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 8818.539 | 7063.071 | 314.847428 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 8389.24 | 8389.24 | 314.847428 | 77.54 | 56.62 | 0.00727457 | 53.60 | 47.67 | 0.00727457 | 82.63 | 0.00546644 | 55.63 | 14.2910 | 75.00 | 0.00756253 | 33.3157 | 5975.51 | 0.00 | 8822.22 | 6371.43 |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 19195.757 | 19195.757 | 314.847428 | 0.26334444 | 281.437 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 19195.76 | 16938.69 | 314.847428 | 61.67 | 47.74 | 0.00548477 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 14.2910 | 71.99 | 0.00624003 | 30.4813 | 9056.46 | 0.00 | 19249.31 | 19249.31 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 10679.350 | 8548.411 | 375.320958 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 10038.38 | 10038.38 | 375.320958 | 77.63 | 56.45 | 0.00713794 | 53.60 | 47.42 | 0.00713794 | 84.89 | 0.00546834 | 56.41 | 11.9884 | 75.00 | 0.00736391 | 32.4505 | 7142.98 | 0.00 | 10683.81 | 7714.01 |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 22252.315 | 22252.315 | 375.320958 | 0.30527702 | 328.676 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 22252.32 | 19635.85 | 375.320958 | 63.33 | 48.98 | 0.00580221 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | 11.9884 | 71.99 | 0.00646243 | 31.5573 | 11441.88 | 0.00 | 22633.75 | 22633.75 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15983.170 | 12794.603 | 556.899267 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 556.899267 | 0.56641866 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 14813.14 | 14813.14 | 0.9268 | 0.56641866 | 556.899267 | 77.49 | 56.67 | 0.00731768 | 10.5 | 53.60 | 47.74 | 0.00731768 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 716.719 | 14096.42 | 87.96 | 0.00547095 | 57.46 | 44.99498340 | 8.0796 | 75.00 | 0.00748000 | 75.00 | 0.00746052 | 32.8713 | 10610.46 | 0.00 | 15989.84 | 11544.54 | 0.54404940 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.85 | 55.20 | 0.00911473 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 31429.342 | 31429.342 | 556.899267 | 0.43117562 | 470.584 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 556.899267 | 0.56641866 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 7.1479 | 7.291704 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 31429.34 | 27733.83 | 1.0000 | 0.56641866 | 556.899267 | 66.15 | 50.22 | 0.00587589 | 8.1 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.44862323 | 140.00 | 120.20 | 19.80 | 0.000 | 31429.34 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 8.0796 | 71.99 | 0.00630840 | 71.99 | 0.00630840 | 30.8126 | 10064.44 | 0.00 | 32766.61 | 32766.61 | 0.56641866 | 61.88 | 51.82 | 0.00587589 | 7.5 | 128.12 | 74.30 | 0.00587589 | 16.5 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8253.841 | 6433.303 | 258.051437 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 258.051437 | 0.26246245 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 7461.80 | 7461.80 | 0.9040 | 0.26246245 | 258.051437 | 79.59 | 56.90 | 0.00699314 | 10.6 | 53.60 | 47.16 | 0.00699314 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 332.107 | 7129.69 | 93.02 | 0.00547527 | 59.13 | 44.99498340 | 17.4364 | 75.00 | 0.00731370 | 75.00 | 0.00731370 | 32.2314 | 4920.19 | 0.00 | 8257.29 | 5828.52 | 0.25209717 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.67 | 53.65 | 0.00874398 | 8.2 | |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 16325.273 | 16325.273 | 258.051437 | 0.22396460 | 236.960 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 258.051437 | 0.26246245 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 3.7128 | 3.787513 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 16325.27 | 14405.72 | 1.0000 | 0.26246245 | 258.051437 | 59.40 | 46.17 | 0.00514113 | 6.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.23302737 | 140.00 | 120.20 | 19.80 | 0.000 | 16325.27 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 17.4364 | 71.99 | 0.00602514 | 71.99 | 0.00602514 | 29.4415 | 7688.71 | 0.00 | 16060.30 | 16060.30 | 0.26246245 | 61.88 | 50.42 | 0.00514113 | 7.1 | 132.04 | 74.48 | 0.00514113 | 16.5 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11179.000 | 8954.020 | 391.177027 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 391.177027 | 0.39786363 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | Sensible | 10475.11 | 10475.11 | 0.9370 | 0.39786363 | 391.177027 | 77.66 | 56.48 | 0.00715018 | 10.4 | 53.60 | 47.44 | 0.00715018 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 503.438 | 9971.68 | 85.56 | 0.00546891 | 56.64 | 44.99498340 | 11.5025 | 75.00 | 0.00736870 | 75.00 | 0.00736714 | 32.4645 | 7421.43 | 0.00 | 11183.66 | 8078.80 | 0.38215103 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.94 | 55.26 | 0.00912640 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 23053.664 | 23053.664 | 391.177027 | 0.31627064 | 341.120 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 391.177027 | 0.39786363 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.2430 | 5.348521 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 23053.66 | 20342.98 | 1.0000 | 0.39786363 | 391.177027 | 63.68 | 48.93 | 0.00569296 | 7.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.32906859 | 140.00 | 120.20 | 19.80 | 0.000 | 23053.66 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 11.5025 | 71.99 | 0.00630874 | 71.99 | 0.00630874 | 30.8143 | 10067.22 | 0.00 | 23519.92 | 23519.92 | 0.39786363 | 61.88 | 51.48 | 0.00569296 | 7.4 | 129.59 | 74.48 | 0.00569296 | 16.5 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15313.475 | 12253.762 | 534.643158 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 534.643158 | 0.54378211 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 14224.96 | 14224.96 | 0.9289 | 0.54378211 | 534.643158 | 77.50 | 56.68 | 0.00732371 | 10.5 | 53.60 | 47.76 | 0.00732371 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 688.076 | 13536.89 | 87.51 | 0.00547057 | 57.31 | 44.99498340 | 8.4159 | 75.00 | 0.00749400 | 75.00 | 0.00749400 | 33.0172 | 10193.67 | 0.00 | 15319.87 | 11057.53 | 0.52230683 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.90 | 55.23 | 0.00911731 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 30304.508 | 30304.508 | 534.643158 | 0.41574415 | 453.165 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 534.643158 | 0.54378211 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 6.8920 | 7.030739 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 30304.51 | 26741.26 | 1.0000 | 0.54378211 | 534.643158 | 65.91 | 50.10 | 0.00585816 | 8.1 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.43256732 | 140.00 | 120.20 | 19.80 | 0.000 | 30304.51 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 8.4159 | 71.99 | 0.00630870 | 71.99 | 0.00630870 | 30.8141 | 10066.89 | 0.00 | 31524.46 | 31524.46 | 0.54378211 | 61.88 | 51.79 | 0.00585816 | 7.5 | 128.26 | 74.32 | 0.00585816 | 16.5 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7126.773 | 5701.879 | 249.451370 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 249.451370 | 0.25371538 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 6758.58 | 6758.58 | 0.9483 | 0.25371538 | 249.451370 | 77.94 | 56.64 | 0.00719555 | 10.5 | 53.60 | 47.52 | 0.00719555 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 321.039 | 6437.54 | 83.30 | 0.00546700 | 55.86 | 44.99498340 | 18.0376 | 75.00 | 0.00757596 | 75.00 | 0.00756500 | 33.3264 | 4742.38 | 0.00 | 7129.75 | 5145.55 | 0.24369554 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.97 | 55.26 | 0.00912199 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 15890.629 | 15890.629 | 249.451370 | 0.21800175 | 230.211 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 249.451370 | 0.25371538 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 3.6139 | 3.686675 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15890.63 | 14022.18 | 1.0000 | 0.25371538 | 249.451370 | 58.96 | 45.93 | 0.00511059 | 6.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.22682324 | 140.00 | 120.20 | 19.80 | 0.000 | 15890.63 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 18.0376 | 71.99 | 0.00602507 | 71.99 | 0.00602507 | 29.4412 | 7688.33 | 0.00 | 15576.38 | 15576.38 | 0.25371538 | 61.88 | 50.36 | 0.00511059 | 7.1 | 132.27 | 74.51 | 0.00511059 | 16.5 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10416.396 | 8340.956 | 370.639678 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 370.639678 | 0.37697523 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 9852.64 | 9852.64 | 0.9459 | 0.37697523 | 370.639678 | 77.49 | 56.40 | 0.00713722 | 10.4 | 53.60 | 47.42 | 0.00713722 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 477.006 | 9375.63 | 83.56 | 0.00546722 | 55.95 | 44.99498340 | 12.1398 | 75.00 | 0.00736797 | 75.00 | 0.00736543 | 32.4571 | 7048.68 | 0.00 | 10420.74 | 7524.35 | 0.36208756 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.35 | 55.48 | 0.00915821 | 8.8 | |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 22015.697 | 22015.697 | 370.639678 | 0.30203088 | 325.066 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 370.639678 | 0.37697523 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.0069 | 5.107709 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 22015.70 | 19427.06 | 1.0000 | 0.37697523 | 370.639678 | 63.22 | 48.68 | 0.00565850 | 7.6 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.31425262 | 140.00 | 120.20 | 19.80 | 0.000 | 22015.70 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 12.1398 | 71.99 | 0.00630835 | 71.99 | 0.00630835 | 30.8124 | 10064.08 | 0.00 | 22372.02 | 22372.02 | 0.37697523 | 61.88 | 51.41 | 0.00565850 | 7.4 | 129.86 | 74.51 | 0.00565850 | 16.6 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 16067.236 | 12869.530 | 562.246242 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 562.246242 | 0.57185703 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 14927.87 | 14927.87 | 0.9291 | 0.57185703 | 562.246242 | 77.45 | 56.72 | 0.00735978 | 10.5 | 53.60 | 47.82 | 0.00735978 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 723.600 | 14204.27 | 87.51 | 0.00547057 | 57.31 | 44.99498340 | 8.0027 | 75.00 | 0.00752412 | 75.00 | 0.00750891 | 33.0821 | 10718.03 | 0.00 | 16073.94 | 11611.55 | 0.54927300 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.94 | 55.26 | 0.00912654 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 31698.391 | 31698.391 | 562.246242 | 0.43486667 | 474.660 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 562.246242 | 0.57185703 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 7.2090 | 7.354124 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 31698.39 | 27971.24 | 1.0000 | 0.57185703 | 562.246242 | 66.21 | 50.54 | 0.00604450 | 8.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.45246364 | 140.00 | 120.20 | 19.80 | 0.000 | 31698.39 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 8.0027 | 71.99 | 0.00648721 | 71.99 | 0.00648721 | 31.6745 | 8946.66 | 0.00 | 33063.89 | 33063.89 | 0.57185703 | 61.88 | 52.14 | 0.00604450 | 7.6 | 128.06 | 74.49 | 0.00604450 | 16.6 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7798.555 | 6242.902 | 270.144975 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 270.144975 | 0.27476271 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 7352.17 | 7352.17 | 0.9428 | 0.27476271 | 270.144975 | 78.05 | 56.76 | 0.00725090 | 10.6 | 53.60 | 47.62 | 0.00725090 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 347.672 | 7004.50 | 84.63 | 0.00546812 | 56.32 | 44.99498340 | 16.6559 | 75.00 | 0.00760718 | 75.00 | 0.00737212 | 32.4861 | 5050.38 | 0.00 | 7801.81 | 5632.51 | 0.26391166 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.71 | 55.12 | 0.00910232 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 16935.960 | 16935.960 | 270.144975 | 0.23234254 | 246.399 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 270.144975 | 0.27476271 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 3.8517 | 3.929195 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 16935.96 | 14944.60 | 1.0000 | 0.27476271 | 270.144975 | 59.96 | 46.74 | 0.00532181 | 6.9 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.24174432 | 140.00 | 120.20 | 19.80 | 0.000 | 16935.96 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 16.6559 | 71.99 | 0.00619445 | 71.99 | 0.00619445 | 30.2584 | 6562.24 | 0.00 | 16739.94 | 16739.94 | 0.27476271 | 61.88 | 50.77 | 0.00532181 | 7.2 | 131.71 | 74.61 | 0.00532181 | 16.6 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11507.427 | 9209.282 | 400.699749 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 400.699749 | 0.40754913 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | Sensible | 10751.26 | 10751.26 | 0.9343 | 0.40754913 | 400.699749 | 77.71 | 56.55 | 0.00718810 | 10.5 | 53.60 | 47.51 | 0.00718810 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 515.693 | 10235.57 | 86.23 | 0.00546947 | 56.87 | 44.99498340 | 11.2291 | 75.00 | 0.00740550 | 75.00 | 0.00740532 | 32.6309 | 7635.83 | 0.00 | 11512.23 | 8309.83 | 0.39145402 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.84 | 55.19 | 0.00911219 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 23534.129 | 23534.129 | 400.699749 | 0.32286208 | 348.492 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 400.699749 | 0.40754913 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.3523 | 5.459990 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 23534.13 | 20766.95 | 1.0000 | 0.40754913 | 400.699749 | 63.88 | 49.31 | 0.00586631 | 7.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.33592675 | 140.00 | 120.20 | 19.80 | 0.000 | 23534.13 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 11.2291 | 71.99 | 0.00648754 | 71.99 | 0.00648754 | 31.6761 | 8949.28 | 0.00 | 24051.53 | 24051.53 | 0.40754913 | 61.88 | 51.81 | 0.00586631 | 7.5 | 129.45 | 74.65 | 0.00586631 | 16.6 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15428.648 | 12353.969 | 541.059286 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 541.059286 | 0.55030791 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 14366.74 | 14366.74 | 0.9312 | 0.55030791 | 541.059286 | 77.45 | 56.72 | 0.00736103 | 10.5 | 53.60 | 47.82 | 0.00736103 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 696.333 | 13670.41 | 87.07 | 0.00547019 | 57.16 | 44.99498340 | 8.3161 | 75.00 | 0.00753253 | 75.00 | 0.00753253 | 33.1851 | 10315.92 | 0.00 | 15435.09 | 11147.26 | 0.52857491 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.00 | 55.29 | 0.00912961 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 30627.641 | 30627.641 | 541.059286 | 0.42017718 | 458.080 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 541.059286 | 0.55030791 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 6.9655 | 7.105707 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 30627.64 | 27026.40 | 1.0000 | 0.55030791 | 541.059286 | 65.99 | 50.42 | 0.00602739 | 8.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.43717973 | 140.00 | 120.20 | 19.80 | 0.000 | 30627.64 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 8.3161 | 71.99 | 0.00648746 | 71.99 | 0.00648746 | 31.6757 | 8948.61 | 0.00 | 31881.43 | 31881.43 | 0.55030791 | 61.88 | 52.11 | 0.00602739 | 7.6 | 128.20 | 74.50 | 0.00602739 | 16.6 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7428.865 | 5950.092 | 262.964167 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 262.964167 | 0.26745916 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7069.66 | 7069.66 | 0.9516 | 0.26745916 | 262.964167 | 77.75 | 56.68 | 0.00726688 | 10.5 | 53.60 | 47.65 | 0.00726688 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 338.430 | 6731.23 | 82.63 | 0.00546644 | 55.63 | 44.99498340 | 17.1107 | 75.00 | 0.00763854 | 75.00 | 0.00762106 | 33.5705 | 4977.69 | 0.00 | 7431.96 | 5367.14 | 0.25689654 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.22 | 55.41 | 0.00914847 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 16573.061 | 16573.061 | 262.964167 | 0.22736396 | 240.768 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 262.964167 | 0.26745916 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 3.7691 | 3.845001 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 16573.06 | 14624.37 | 1.0000 | 0.26745916 | 262.964167 | 59.64 | 46.56 | 0.00529787 | 6.9 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.23656429 | 140.00 | 120.20 | 19.80 | 0.000 | 16573.06 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 17.1107 | 71.99 | 0.00619432 | 71.99 | 0.00619432 | 30.2578 | 6561.57 | 0.00 | 16336.33 | 16336.33 | 0.26745916 | 61.88 | 50.72 | 0.00529787 | 7.2 | 131.89 | 74.63 | 0.00529787 | 16.6 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10709.027 | 8577.061 | 379.048589 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 379.048589 | 0.38552788 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 10100.40 | 10100.40 | 0.9432 | 0.38552788 | 379.048589 | 77.54 | 56.47 | 0.00717391 | 10.4 | 53.60 | 47.48 | 0.00717391 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 487.828 | 9612.57 | 84.23 | 0.00546778 | 56.18 | 44.99498340 | 11.8705 | 75.00 | 0.00740371 | 75.00 | 0.00740222 | 32.6174 | 7217.08 | 0.00 | 10713.50 | 7736.77 | 0.37030244 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.22 | 55.41 | 0.00914821 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 22439.919 | 22439.919 | 379.048589 | 0.30785074 | 331.573 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 379.048589 | 0.38552788 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.1034 | 5.206130 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 22439.92 | 19801.40 | 1.0000 | 0.38552788 | 379.048589 | 63.42 | 49.07 | 0.00583046 | 7.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.32030798 | 140.00 | 120.20 | 19.80 | 0.000 | 22439.92 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 11.8705 | 71.99 | 0.00648712 | 71.99 | 0.00648712 | 31.6741 | 8946.00 | 0.00 | 22841.72 | 22841.72 | 0.38552788 | 61.88 | 51.74 | 0.00583046 | 7.5 | 129.72 | 74.68 | 0.00583046 | 16.7 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 16959.288 | 13579.336 | 594.711918 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 594.711918 | 0.60487766 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 15753.28 | 15753.28 | 0.9289 | 0.60487766 | 594.711918 | 77.39 | 56.68 | 0.00734363 | 10.5 | 53.60 | 47.79 | 0.00734363 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 765.383 | 14987.90 | 87.51 | 0.00547057 | 57.31 | 44.99498340 | 7.5658 | 75.00 | 0.00749694 | 75.00 | 0.00748258 | 32.9674 | 11324.20 | 0.00 | 16966.37 | 12252.97 | 0.58098957 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.00 | 55.29 | 0.00912944 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 33340.451 | 33340.451 | 594.711918 | 0.45739390 | 500.016 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 594.711918 | 0.60487766 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 7.5825 | 7.735087 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 33340.45 | 29420.23 | 1.0000 | 0.60487766 | 594.711918 | 66.53 | 50.66 | 0.00604593 | 8.3 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.47590244 | 140.00 | 120.20 | 19.80 | 0.000 | 33340.45 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 7.5658 | 71.99 | 0.00646261 | 71.99 | 0.00646261 | 31.5581 | 11443.60 | 0.00 | 34873.13 | 34873.13 | 0.60487766 | 61.88 | 52.14 | 0.00604593 | 7.6 | 127.87 | 74.44 | 0.00604593 | 16.5 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8691.445 | 6953.842 | 307.777757 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 307.777757 | 0.31303877 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 8242.67 | 8242.67 | 0.9484 | 0.31303877 | 307.777757 | 77.66 | 56.65 | 0.00726381 | 10.5 | 53.60 | 47.65 | 0.00726381 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 396.104 | 7846.56 | 83.30 | 0.00546700 | 55.86 | 44.99498340 | 14.6193 | 75.00 | 0.00757147 | 75.00 | 0.00751730 | 33.1187 | 5820.88 | 0.00 | 8695.07 | 6273.78 | 0.30067611 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.25 | 55.41 | 0.00914461 | 8.8 | |
| MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 18838.457 | 18838.457 | 307.777757 | 0.25844268 | 275.902 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 307.777757 | 0.31303877 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 4.2844 | 4.370580 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18838.46 | 16623.40 | 1.0000 | 0.31303877 | 307.777757 | 61.43 | 47.61 | 0.00546763 | 7.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.26890062 | 140.00 | 120.20 | 19.80 | 0.000 | 18838.46 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 14.6193 | 71.99 | 0.00624027 | 71.99 | 0.00624027 | 30.4825 | 9058.18 | 0.00 | 18853.09 | 18853.09 | 0.31303877 | 61.88 | 51.05 | 0.00546763 | 7.3 | 130.89 | 74.56 | 0.00546763 | 16.6 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11486.519 | 9199.868 | 397.202634 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 397.202634 | 0.40399224 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | Sensible | 10695.10 | 10695.10 | 0.9311 | 0.40399224 | 397.202634 | 77.79 | 56.53 | 0.00715406 | 10.5 | 53.60 | 47.45 | 0.00715406 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 511.192 | 10183.91 | 86.89 | 0.00547004 | 57.10 | 44.99498340 | 11.3280 | 75.00 | 0.00736920 | 75.00 | 0.00736417 | 32.4512 | 7547.02 | 0.00 | 11491.31 | 8299.48 | 0.38803760 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.65 | 55.10 | 0.00910085 | 8.6 | |
| MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 23358.227 | 23358.227 | 397.202634 | 0.32044890 | 345.777 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 397.202634 | 0.40399224 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.3123 | 5.419180 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 23358.23 | 20611.73 | 1.0000 | 0.40399224 | 397.202634 | 63.81 | 49.24 | 0.00583891 | 7.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.33341592 | 140.00 | 120.20 | 19.80 | 0.000 | 23358.23 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 11.3280 | 71.99 | 0.00646280 | 71.99 | 0.00646280 | 31.5591 | 11445.50 | 0.00 | 23856.60 | 23856.60 | 0.40399224 | 61.88 | 51.75 | 0.00583891 | 7.5 | 129.50 | 74.63 | 0.00583891 | 16.6 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 16830.313 | 13479.307 | 592.237078 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 592.237078 | 0.60236052 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 15668.22 | 15668.22 | 0.9310 | 0.60236052 | 592.237078 | 77.36 | 56.68 | 0.00734967 | 10.5 | 53.60 | 47.80 | 0.00734967 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 762.198 | 14906.03 | 87.07 | 0.00547019 | 57.16 | 44.99498340 | 7.5975 | 75.00 | 0.00750421 | 75.00 | 0.00750421 | 33.0617 | 11291.74 | 0.00 | 16837.34 | 12162.61 | 0.57857183 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.07 | 55.33 | 0.00913779 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 33215.371 | 33215.371 | 592.237078 | 0.45567795 | 498.085 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 592.237078 | 0.60236052 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 7.5540 | 7.706068 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 33215.37 | 29309.86 | 1.0000 | 0.60236052 | 592.237078 | 66.50 | 50.65 | 0.00604420 | 8.3 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.47411705 | 140.00 | 120.20 | 19.80 | 0.000 | 33215.37 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 7.5975 | 71.99 | 0.00646262 | 71.99 | 0.00646262 | 31.5582 | 11443.75 | 0.00 | 34735.28 | 34735.28 | 0.60236052 | 61.88 | 52.14 | 0.00604420 | 7.6 | 127.89 | 74.44 | 0.00604420 | 16.5 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8818.539 | 7063.071 | 314.847428 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 314.847428 | 0.32022929 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 8389.24 | 8389.24 | 0.9513 | 0.32022929 | 314.847428 | 77.54 | 56.62 | 0.00727457 | 10.5 | 53.60 | 47.67 | 0.00727457 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 405.203 | 7984.04 | 82.63 | 0.00546644 | 55.63 | 44.99498340 | 14.2910 | 75.00 | 0.00757606 | 75.00 | 0.00756253 | 33.3157 | 5975.51 | 0.00 | 8822.22 | 6371.43 | 0.30758265 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.42 | 55.52 | 0.00916612 | 8.8 | |
| MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 19195.757 | 19195.757 | 314.847428 | 0.26334444 | 281.437 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 314.847428 | 0.32022929 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 4.3656 | 4.453474 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 19195.76 | 16938.69 | 1.0000 | 0.32022929 | 314.847428 | 61.67 | 47.74 | 0.00548477 | 7.3 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.27400072 | 140.00 | 120.20 | 19.80 | 0.000 | 19195.76 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 14.2910 | 71.99 | 0.00624003 | 71.99 | 0.00624003 | 30.4813 | 9056.46 | 0.00 | 19249.31 | 19249.31 | 0.32022929 | 61.88 | 51.08 | 0.00548477 | 7.3 | 130.76 | 74.54 | 0.00548477 | 16.6 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10679.350 | 8548.411 | 375.320958 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 375.320958 | 0.38173653 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | Sensible | 10038.38 | 10038.38 | 0.9400 | 0.38173653 | 375.320958 | 77.63 | 56.45 | 0.00713794 | 10.4 | 53.60 | 47.42 | 0.00713794 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 483.031 | 9555.35 | 84.89 | 0.00546834 | 56.41 | 44.99498340 | 11.9884 | 75.00 | 0.00736536 | 75.00 | 0.00736391 | 32.4505 | 7142.98 | 0.00 | 10683.81 | 7714.01 | 0.36666082 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.05 | 55.31 | 0.00913277 | 8.7 | |
| MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Water | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | Yes | Yes | No | 22252.315 | 22252.315 | 375.320958 | 0.30527702 | 328.676 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 375.320958 | 0.38173653 | 1.0027 | 62.4216 | 6.15251592 | 159.80 | 179.60 | 19.80 | 439703.42 | 5.0608 | 5.162605 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 22252.32 | 19635.85 | 1.0000 | 0.38173653 | 375.320958 | 63.33 | 48.98 | 0.00580221 | 7.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | 0.31763011 | 140.00 | 120.20 | 19.80 | 0.000 | 22252.32 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | 11.9884 | 71.99 | 0.00646243 | 71.99 | 0.00646243 | 31.5573 | 11441.88 | 0.00 | 22633.75 | 22633.75 | 0.38173653 | 61.88 | 51.68 | 0.00580221 | 7.5 | 129.78 | 74.66 | 0.00580221 | 16.6 |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1663.83 | 5335.17 | 265.67 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 758.83 | 5349.33 | 107.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1650.00 | 5128.83 | 257.50 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1572.83 | 6060.50 | 514.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 662.00 | 6260.67 | 141.83 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1415.83 | 5925.83 | 315.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1793.50 | 5030.83 | 192.33 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 967.67 | 4883.83 | 42.50 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1814.17 | 4845.00 | 181.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1666.50 | 5783.67 | 405.50 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 752.17 | 5853.50 | 51.17 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1604.00 | 5643.50 | 231.33 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1902.00 | 5736.00 | 438.17 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1972.83 | 5198.67 | 379.33 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1936.50 | 5365.33 | 408.17 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1050.67 | 5970.83 | 202.67 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1126.00 | 5395.50 | 147.17 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1993.83 | 5888.17 | 668.17 |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 |
| Facility | 2917.33 | 6516.50 | 841.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 25.67 | 0.00 | 25.67 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5.67 | 0.00 | 5.67 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 184.83 | 0.00 | 184.83 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 401.83 | 0.00 | 401.83 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 115.00 | 0.50 | 115.00 | 0.50 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 84.17 | 0.00 | 84.17 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 42.50 | 0.00 | 42.50 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.83 | 0.00 | 0.83 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 211.67 | 0.00 | 211.67 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 413.67 | 0.00 | 413.67 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 89.00 | 0.00 | 89.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 109.33 | 0.00 | 109.33 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 85.17 | 0.00 | 85.17 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 153.00 | 0.00 | 153.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 120.83 | 0.00 | 120.83 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 73.17 | 0.00 | 73.17 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8.33 | 0.00 | 8.33 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 405.00 | 0.00 | 405.00 | 0.00 |
| UNHEATEDBSMT | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 1341.83 | 0.50 | 1341.83 | 0.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.111 | 0.000 | 0.278 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.110 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.278 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.040 | 0.000 | 0.278 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.278 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.040 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.055 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.125 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.110 | 0.000 | 0.277 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.110 | 0.000 | 0.278 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.125 | 0.000 | 0.277 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.000 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 11117504.38 | 35737644.66 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 9801386.63 | 34421526.91 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 11124552.26 | 35744692.54 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 11074464.44 | 35694604.72 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 9760251.03 | 34380391.30 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 11093698.52 | 35713838.80 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 4875574.80 | 29497183.13 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 3551315.98 | 28172924.31 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 4878394.07 | 29500002.40 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 4856770.57 | 29478378.90 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 3535847.68 | 28157456.01 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 4864198.14 | 29485806.47 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 11099642.02 | 35722719.96 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 11125818.19 | 35748896.12 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 11117956.95 | 35741034.88 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 9767588.73 | 34390666.67 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 9800850.31 | 34423928.25 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 11081424.12 | 35704502.06 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| Total Facility | 0.00 | 0.443189E+09 | 0.443189E+09 | 0.154527E+09 | 0.597716E+09 | 0.428131E+09 | 1097.33 | 1608.50 | 6117.83 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 21.0313 | 67.6060 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 18.5416 | 65.1163 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 21.0447 | 67.6194 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 20.9499 | 67.5246 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 18.4638 | 65.0385 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 20.9863 | 67.5610 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 9.2233 | 55.8007 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 6.7181 | 53.2956 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 9.2286 | 55.8061 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 9.1877 | 55.7652 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 6.6889 | 53.2663 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 9.2018 | 55.7792 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 20.9975 | 67.5778 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 21.0471 | 67.6273 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 21.0322 | 67.6124 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 18.4777 | 65.0579 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 18.5406 | 65.1208 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 20.9631 | 67.5433 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| Total Facility | 0.0000 | 838.3944 | 838.3944 | 292.3240 | 1130.7184 | 809.9097 | 1097.33 | 1608.50 | 6117.83 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Surfaces by Class| Total | Outdoors | |
| Wall | 82 | 58 |
| Floor | 29 | 4 |
| Roof | 27 | 2 |
| Internal Mass | 0 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 30 | 30 |
| Door | 18 | 18 |
| Glass Door | 0 | 0 |
| Shading | 60 | 60 |
| Overhang | 30 | 30 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 18 |
| Conditioned Zones | 18 |
| Unconditioned Zones | 3 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1965 |
| Defaulted Fields | 1710 |
| Fields with Defaults | 6385 |
| Autosized Fields | 382 |
| Autosizable Fields | 546 |
| Autocalculated Fields | 162 |
| Autocalculatable Fields | 350 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Annual and Peak Values - Electricity| Electricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| Electricity:Building | 101263.28 | 6311.77 | 02-JAN-03:10 | 19306.63 | 01-JAN-18:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 101263.28 | 6311.77 | 02-JAN-03:10 | 19306.63 | 01-JAN-18:10 |
| InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
| General:InteriorLights:Electricity | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:SpaceType:GENERAL | 12960.20 | 290.23 | 01-JAN-00:10 | 4221.57 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5625.74 | 350.65 | 02-JAN-03:10 | 1072.59 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 720.01 | 16.12 | 01-JAN-00:10 | 234.53 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| Fans:Electricity | 10679.52 | 578.57 | 19-FEB-02:10 | 3162.84 | 26-JUN-17:30 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| ElectricityPurchased:Plant | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| Cogeneration:ElectricityPurchased | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| General:Cogeneration:ElectricityPurchased | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| ElectricityNet:Plant | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| Cogeneration:ElectricityNet | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| General:Cogeneration:ElectricityNet | 133681.62 | 8268.04 | 16-MAR-03:10 | 37169.61 | 26-JUN-18:10 |
| Electricity:HVAC | 26384.03 | 578.57 | 19-FEB-02:10 | 17030.74 | 26-JUN-17:30 |
| Ventilation:Fans:Electricity | 5068.29 | 578.57 | 01-JAN-00:10 | 578.57 | 01-JAN-00:10 |
| General:Fans:Electricity | 5611.23 | 0.00 | 19-FEB-02:10 | 2584.27 | 26-JUN-17:30 |
| ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Exterior-Lights:ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:Electricity | 15704.51 | 0.00 | 01-JAN-00:10 | 13867.90 | 26-JUN-17:30 |
| General:Cooling:Electricity | 15704.51 | 0.00 | 01-JAN-00:10 | 13867.90 | 26-JUN-17:30 |
| Electricity:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Boiler Parasitic:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| NaturalGas:Facility | 2102.09 | 0.00 | 09-JAN-13:20 | 224034.58 | 22-DEC-04:00 |
| NaturalGas:Plant | 2102.09 | 0.00 | 09-JAN-13:20 | 224034.58 | 22-DEC-04:00 |
| Heating:NaturalGas | 2102.09 | 0.00 | 09-JAN-13:20 | 224034.58 | 22-DEC-04:00 |
| Boiler:Heating:NaturalGas | 2102.09 | 0.00 | 09-JAN-13:20 | 224034.58 | 22-DEC-04:00 |
| Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| Water:Plant | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| WaterSystems:Water | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| Domestic Hot Water:WaterSystems:Water | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| MainsWater:Facility | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| MainsWater:Plant | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| WaterSystems:MainsWater | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| Domestic Hot Water:WaterSystems:MainsWater | 44570.30 | 0.01 | 02-JAN-02:10 | 0.16 | 01-JAN-08:20 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1066693.94 | 819.35 | 15-SEP-04:00 | 556187.38 | 23-DEC-07:10 |
| EnergyTransfer:Building | 386937.47 | 0.00 | 19-FEB-02:10 | 184709.92 | 22-DEC-04:00 |
| EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer | 175383.72 | 0.00 | 09-JAN-13:50 | 184709.92 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer | 175383.72 | 0.00 | 09-JAN-13:50 | 184709.92 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer | 211553.75 | 0.00 | 01-JAN-00:10 | 159823.44 | 26-JUN-18:10 |
| Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer | 211553.75 | 0.00 | 01-JAN-00:10 | 159823.44 | 26-JUN-18:10 |
| General:Cooling:EnergyTransfer:Zone:UNHEATEDBSMT | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 23908.02 | 0.00 | 01-JAN-10:00 | 12352.66 | 16-AUG-16:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9875.61 | 0.00 | 01-JAN-10:00 | 11155.95 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9875.61 | 0.00 | 01-JAN-10:00 | 11155.95 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 14032.41 | 0.00 | 01-JAN-00:10 | 12352.66 | 16-AUG-16:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 14032.41 | 0.00 | 01-JAN-00:10 | 12352.66 | 16-AUG-16:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16574.69 | 0.00 | 01-JAN-09:30 | 8437.78 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6446.93 | 0.00 | 01-JAN-09:30 | 8437.78 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 6446.93 | 0.00 | 01-JAN-09:30 | 8437.78 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10127.76 | 0.00 | 01-JAN-00:10 | 6584.96 | 28-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10127.76 | 0.00 | 01-JAN-00:10 | 6584.96 | 28-SEP-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 23752.54 | 0.00 | 01-JAN-08:50 | 11188.13 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9520.13 | 0.00 | 01-JAN-08:50 | 11188.13 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 9520.13 | 0.00 | 01-JAN-08:50 | 11188.13 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14232.41 | 0.00 | 01-JAN-00:10 | 8870.85 | 16-AUG-10:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 14232.41 | 0.00 | 01-JAN-00:10 | 8870.85 | 16-AUG-10:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22290.50 | 0.00 | 01-JAN-15:10 | 12014.19 | 26-JUN-17:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12098.49 | 0.00 | 01-JAN-15:10 | 11237.45 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12098.49 | 0.00 | 01-JAN-15:10 | 11237.45 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10192.01 | 0.00 | 01-JAN-00:10 | 12014.19 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 10192.01 | 0.00 | 01-JAN-00:10 | 12014.19 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 15850.25 | 0.00 | 09-JAN-13:00 | 8542.69 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9136.92 | 0.00 | 09-JAN-13:00 | 8542.69 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 9136.92 | 0.00 | 09-JAN-13:00 | 8542.69 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6713.33 | 0.00 | 01-JAN-00:10 | 6058.92 | 26-JUN-19:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 6713.33 | 0.00 | 01-JAN-00:10 | 6058.92 | 26-JUN-19:30 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22563.15 | 0.00 | 01-JAN-09:50 | 11259.75 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12095.84 | 0.00 | 01-JAN-09:50 | 11259.75 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12095.84 | 0.00 | 01-JAN-09:50 | 11259.75 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10467.30 | 0.00 | 01-JAN-00:10 | 8129.40 | 01-JUL-08:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 10467.30 | 0.00 | 01-JAN-00:10 | 8129.40 | 01-JUL-08:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 23098.09 | 0.00 | 01-JAN-10:00 | 12286.17 | 16-AUG-16:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7761.51 | 0.00 | 01-JAN-10:00 | 9674.63 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 7761.51 | 0.00 | 01-JAN-10:00 | 9674.63 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15336.59 | 0.00 | 01-JAN-00:10 | 12286.17 | 16-AUG-16:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 15336.59 | 0.00 | 01-JAN-00:10 | 12286.17 | 16-AUG-16:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 16257.93 | 0.00 | 01-JAN-00:10 | 6944.53 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4596.26 | 0.00 | 01-JAN-00:10 | 6944.53 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4596.26 | 0.00 | 01-JAN-00:10 | 6944.53 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11661.67 | 0.00 | 01-JAN-00:10 | 6649.53 | 28-SEP-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 11661.67 | 0.00 | 01-JAN-00:10 | 6649.53 | 28-SEP-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 23135.81 | 0.00 | 01-JAN-08:50 | 9683.69 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7473.97 | 0.00 | 01-JAN-08:50 | 9683.69 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7473.97 | 0.00 | 01-JAN-08:50 | 9683.69 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15661.84 | 0.00 | 01-JAN-00:10 | 8919.67 | 16-AUG-10:50 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15661.84 | 0.00 | 01-JAN-00:10 | 8919.67 | 16-AUG-10:50 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 21086.89 | 0.00 | 01-JAN-15:10 | 11983.40 | 26-JUN-17:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9746.91 | 0.00 | 01-JAN-15:10 | 9839.19 | 11-FEB-14:50 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9746.91 | 0.00 | 01-JAN-15:10 | 9839.19 | 11-FEB-14:50 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11339.98 | 0.00 | 01-JAN-00:10 | 11983.40 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11339.98 | 0.00 | 01-JAN-00:10 | 11983.40 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 14791.03 | 0.00 | 08-JAN-19:20 | 7042.11 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6843.88 | 0.00 | 08-JAN-19:20 | 7042.11 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6843.88 | 0.00 | 08-JAN-19:20 | 7042.11 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7947.15 | 0.00 | 01-JAN-00:10 | 6307.53 | 26-JUN-19:20 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 7947.15 | 0.00 | 01-JAN-00:10 | 6307.53 | 26-JUN-19:20 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 21474.40 | 0.00 | 01-JAN-09:50 | 9750.91 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9743.53 | 0.00 | 01-JAN-09:50 | 9750.91 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9743.53 | 0.00 | 01-JAN-09:50 | 9750.91 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11730.87 | 0.00 | 01-JAN-00:10 | 8212.02 | 01-JUL-09:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11730.87 | 0.00 | 01-JAN-00:10 | 8212.02 | 01-JUL-09:00 |
| EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 25902.61 | 0.00 | 09-JAN-09:40 | 12618.40 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 13914.28 | 0.00 | 09-JAN-09:40 | 12618.40 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 13914.28 | 0.00 | 09-JAN-09:40 | 12618.40 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 11988.34 | 0.00 | 01-JAN-00:10 | 8868.56 | 26-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 11988.34 | 0.00 | 01-JAN-00:10 | 8868.56 | 26-JUN-18:30 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 25942.92 | 0.00 | 01-JAN-09:20 | 12548.08 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11328.67 | 0.00 | 01-JAN-09:20 | 12548.08 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 11328.67 | 0.00 | 01-JAN-09:20 | 12548.08 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 14614.25 | 0.00 | 01-JAN-00:10 | 9114.43 | 16-AUG-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 14614.25 | 0.00 | 01-JAN-00:10 | 9114.43 | 16-AUG-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 26159.20 | 0.00 | 01-JAN-11:50 | 13003.07 | 26-JUN-17:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11690.22 | 0.00 | 01-JAN-11:50 | 12556.31 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 11690.22 | 0.00 | 01-JAN-11:50 | 12556.31 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 14468.98 | 0.00 | 01-JAN-00:10 | 13003.07 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 14468.98 | 0.00 | 01-JAN-00:10 | 13003.07 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19405.66 | 0.00 | 09-JAN-13:50 | 9909.86 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 10948.31 | 0.00 | 09-JAN-13:50 | 9909.86 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 10948.31 | 0.00 | 09-JAN-13:50 | 9909.86 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 8457.35 | 0.00 | 01-JAN-00:10 | 7475.84 | 26-JUN-19:20 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 8457.35 | 0.00 | 01-JAN-00:10 | 7475.84 | 26-JUN-19:20 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 18982.14 | 0.00 | 01-JAN-10:10 | 9821.74 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8165.41 | 0.00 | 01-JAN-10:10 | 9821.74 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 8165.41 | 0.00 | 01-JAN-10:10 | 9821.74 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 10816.73 | 0.00 | 01-JAN-00:10 | 7303.00 | 26-JUN-19:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 10816.73 | 0.00 | 01-JAN-00:10 | 7303.00 | 26-JUN-19:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 25761.62 | 0.00 | 09-JAN-13:20 | 13159.98 | 26-JUN-17:40 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 13996.86 | 0.00 | 09-JAN-13:20 | 12597.09 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 13996.86 | 0.00 | 09-JAN-13:20 | 12597.09 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 11764.77 | 0.00 | 01-JAN-00:10 | 13159.98 | 26-JUN-17:40 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 11764.77 | 0.00 | 01-JAN-00:10 | 13159.98 | 26-JUN-17:40 |
| PlantLoopHeatingDemand:Facility | 276922.99 | 726.63 | 15-AUG-03:00 | 200084.16 | 23-DEC-07:20 |
| PlantLoopHeatingDemand:Plant | 108875.01 | 726.63 | 15-AUG-03:00 | 29279.62 | 19-FEB-09:00 |
| WaterSystems:PlantLoopHeatingDemand | 108875.01 | 726.63 | 15-AUG-03:00 | 29279.62 | 19-FEB-09:00 |
| General:WaterSystems:PlantLoopHeatingDemand | 108875.01 | 726.63 | 15-AUG-03:00 | 29279.62 | 19-FEB-09:00 |
| EnergyTransfer:HVAC | 402714.66 | 0.00 | 09-JAN-23:40 | 179637.56 | 22-DEC-04:00 |
| HeatingCoils:EnergyTransfer | 168047.98 | 0.00 | 09-JAN-13:20 | 179637.56 | 22-DEC-04:00 |
| PlantLoopHeatingDemand:HVAC | 168047.98 | 0.00 | 09-JAN-13:20 | 179637.56 | 22-DEC-04:00 |
| HeatingCoils:PlantLoopHeatingDemand | 168047.98 | 0.00 | 09-JAN-13:20 | 179637.56 | 22-DEC-04:00 |
| CoolingCoils:EnergyTransfer | 234666.68 | 0.00 | 01-JAN-00:10 | 168563.55 | 26-JUN-18:10 |
| EnergyTransfer:Plant | 277041.81 | 726.63 | 15-AUG-03:00 | 199782.37 | 23-DEC-07:20 |
| WaterSystems:EnergyTransfer | 108875.01 | 726.63 | 15-AUG-03:00 | 29279.62 | 19-FEB-09:00 |
| Domestic Hot Water:WaterSystems:EnergyTransfer | 108875.01 | 726.63 | 15-AUG-03:00 | 29279.62 | 19-FEB-09:00 |
| Boilers:EnergyTransfer | 168166.80 | 0.00 | 09-JAN-13:20 | 179227.66 | 22-DEC-04:00 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| FuelOilNo2:Facility | 284762.85 | 0.00 | 01-JAN-00:10 | 225024.84 | 01-JAN-08:20 |
| FuelOilNo2:Plant | 284762.85 | 0.00 | 01-JAN-00:10 | 225024.84 | 01-JAN-08:20 |
| WaterSystems:FuelOilNo2 | 284762.85 | 0.00 | 01-JAN-00:10 | 225024.84 | 01-JAN-08:20 |
| Water Heater:WaterSystems:FuelOilNo2 | 284762.85 | 0.00 | 01-JAN-00:10 | 225024.84 | 01-JAN-08:20 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 9875.492 | -1168.58 | 0.000 | 0.000 | 3021.363 | 2458.419 | 10464.601 | 13268.973 | 0.000 | 465.535 | 0.027 | 0.000 | -6673.86 | 0.000 | -13661.70 | -5186.48 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 6446.858 | -843.41 | 0.000 | 0.000 | 3007.238 | 2458.419 | 10464.601 | 6789.792 | 0.000 | 449.291 | 0.013 | 0.000 | -2711.04 | 0.000 | -13181.03 | -3596.41 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 9520.012 | -1185.23 | 0.000 | 0.000 | 3022.183 | 2458.419 | 10464.601 | 13829.394 | 0.000 | 465.534 | 0.005 | 0.000 | -6555.56 | 0.000 | -13693.55 | -5278.72 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 12098.371 | -848.77 | 0.000 | 0.000 | 3043.815 | 2458.419 | 10464.601 | 8140.052 | 0.000 | 465.535 | 0.000 | 0.000 | -6809.71 | 0.000 | -13445.41 | -6223.68 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 9136.840 | -559.07 | 0.000 | 0.000 | 3035.416 | 2458.419 | 10464.601 | 1495.207 | 0.000 | 449.265 | 0.000 | 0.000 | -2860.25 | 0.000 | -12967.71 | -4498.46 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 12095.730 | -871.69 | 0.000 | 0.000 | 3039.503 | 2458.419 | 10464.601 | 8652.359 | 0.000 | 465.535 | 0.000 | 0.000 | -6670.22 | 0.000 | -13539.86 | -6498.82 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 7761.412 | -1277.19 | 0.000 | 0.000 | 3006.488 | 2458.419 | 10464.601 | 13208.863 | 0.000 | 387.654 | 0.002 | 0.000 | -6802.01 | 0.000 | -11176.00 | -3972.87 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 4596.208 | -971.16 | 0.000 | 0.000 | 2988.372 | 2458.419 | 10464.601 | 6755.299 | 0.000 | 371.471 | 0.052 | 0.000 | -2763.50 | 0.000 | -10696.09 | -2513.12 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 7473.874 | -1304.28 | 0.000 | 0.000 | 3008.613 | 2458.419 | 10464.601 | 13760.198 | 0.000 | 387.653 | 0.106 | 0.000 | -6676.76 | 0.000 | -11199.34 | -4015.49 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 9746.809 | -944.37 | 0.000 | 0.000 | 3030.810 | 2458.419 | 10464.601 | 8097.151 | 0.000 | 387.654 | 0.000 | 0.000 | -6931.80 | 0.000 | -11003.92 | -4909.74 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 6843.814 | -661.82 | 0.000 | 0.000 | 3020.735 | 2458.419 | 10464.601 | 1482.350 | 0.000 | 371.463 | 0.000 | 0.000 | -2909.83 | 0.000 | -10517.66 | -3266.72 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 9743.444 | -976.92 | 0.000 | 0.000 | 3028.638 | 2458.419 | 10464.601 | 8602.240 | 0.000 | 387.654 | 0.000 | 0.000 | -6784.07 | 0.000 | -11069.39 | -5100.71 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 13914.151 | -998.36 | 0.000 | 0.000 | 3036.923 | 2458.419 | 10464.601 | 8615.396 | 0.000 | 462.075 | 0.000 | 0.000 | -6762.64 | 0.000 | -13569.76 | -6630.86 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 11328.547 | -1217.03 | 0.000 | 0.000 | 3022.727 | 2458.419 | 10464.601 | 13787.413 | 0.000 | 462.075 | 0.000 | 0.000 | -6631.34 | 0.000 | -13694.86 | -6583.41 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 11690.087 | -1204.94 | 0.000 | 0.000 | 3022.032 | 2458.419 | 10464.601 | 13233.796 | 0.000 | 462.076 | 0.002 | 0.000 | -6750.92 | 0.000 | -13661.40 | -6449.74 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 10948.219 | -704.31 | 0.000 | 0.000 | 3031.965 | 2458.419 | 10464.601 | 1486.421 | 0.000 | 445.941 | 0.000 | 0.000 | -2895.34 | 0.000 | -13010.34 | -4472.52 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 8165.317 | -900.79 | 0.000 | 0.000 | 3009.392 | 2458.419 | 10464.601 | 6763.690 | 0.000 | 445.954 | 0.003 | 0.000 | -2739.00 | 0.000 | -13176.71 | -4574.94 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 13996.722 | -979.74 | 0.000 | 0.000 | 3039.807 | 2458.419 | 10464.601 | 8106.059 | 0.000 | 462.076 | 0.000 | 0.000 | -6905.32 | 0.000 | -13488.15 | -6369.44 |
| UNHEATEDBSMT | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 19107.469 | 155148.777 | 0.000 | 0.000 | 0.000 | -174256.25 | -8.66 |
| Total Facility | 0.000 | 0.000 | 175381.906 | -17617.66 | 0.000 | 0.000 | 54416.018 | 44251.534 | 188362.826 | 156074.650 | 0.000 | 26901.911 | 155148.988 | 0.000 | -97833.18 | 0.000 | -401009.13 | -90150.79 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 16-AUG-16:36 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.35 | 385.11 | 1350.56 | 8910.45 | 0.00 | 1186.71 | 380.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 28-SEP-13:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 103.15 | 1084.63 | 3764.96 | 0.00 | 632.44 | 885.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-AUG-10:13 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1089.80 | 7437.95 | 0.00 | 928.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -803.2 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 26-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.16 | 536.40 | 1664.02 | 8001.26 | 0.00 | 1348.47 | 200.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 26-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.16 | 800.22 | 1664.78 | 199.01 | 0.00 | 958.55 | 2022.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 01-JUL-07:02 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 420.19 | 343.85 | 1225.98 | 8369.21 | 0.00 | 193.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2421.2 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16-AUG-16:30 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.35 | 385.11 | 1350.56 | 8892.17 | 0.00 | 1003.10 | 515.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 28-SEP-13:02 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 103.15 | 1084.63 | 3753.02 | 0.00 | 522.71 | 1071.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-AUG-10:52 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 103.15 | 1089.80 | 6309.74 | 0.00 | 858.24 | 447.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.15 | 536.40 | 1664.02 | 7992.05 | 0.00 | 1118.05 | 409.82 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 26-JUN-19:26 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.93 | 800.22 | 1664.78 | 582.50 | 0.00 | 831.67 | 2005.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 01-JUL-08:00 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 194.42 | 151.29 | 1179.68 | 7375.13 | 0.00 | 176.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -866.3 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 426.44 | 722.08 | 1724.99 | 1985.57 | 0.00 | 1232.46 | 2798.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 16-AUG-13:00 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.09 | 103.15 | 1084.63 | 4138.61 | 0.00 | 1265.48 | 2408.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 26-JUN-17:34 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 263.15 | 536.40 | 1664.02 | 7398.79 | 0.00 | 1345.02 | 1796.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 26-JUN-19:30 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 425.42 | 800.22 | 1664.78 | 194.66 | 0.00 | 955.57 | 3458.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 26-JUN-18:03 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 426.17 | 722.08 | 1724.99 | 354.13 | 0.00 | 1113.74 | 2968.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 26-JUN-17:45 | 0.00 | 0.00 | 0.00 | -1.1 | 0.00 | 0.00 | 263.16 | 536.40 | 1664.02 | 7617.13 | 0.00 | 1332.33 | 1747.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 26-JUN-18:15 | 0.00 | 0.00 | 0.00 | -13.3 | 0.00 | 0.00 | 7678.61 | 12997.36 | 31049.73 | 52653.98 | 0.00 | 21583.76 | 57427.99 | 0.00 | 0.00 | 0.00 | -23562.3 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 27-MAR-09:57 | 0.00 | 0.00 | 18823.95 | 0.00 | 0.00 | 0.00 | 137.12 | 103.15 | 1096.02 | 2506.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3167.7 | -19498.7 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 11-FEB-17:33 | 0.00 | 0.00 | 10673.23 | 0.00 | 0.00 | 0.00 | 305.80 | 536.40 | 1685.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1006.2 | 0.00 | -3926.7 | -8267.7 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 18-DEC-17:51 | 0.00 | 0.00 | 15002.54 | 0.00 | 0.00 | 0.00 | 301.24 | 536.40 | 1664.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2353.2 | 0.00 | -4158.1 | -10992.9 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13-FEB-11:46 | 0.00 | 0.00 | 23530.66 | 0.00 | 0.00 | 0.00 | 149.29 | 103.15 | 1092.38 | 108.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1981.8 | -23002.4 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 31-JAN-16:03 | 0.00 | 0.00 | 13986.31 | 0.00 | 0.00 | 0.00 | 168.93 | 385.11 | 1350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -622.6 | 0.00 | -2340.4 | -12927.9 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 11259.64 | 0.00 | 0.00 | 0.00 | 526.23 | 55.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3296.9 | 0.00 | -6212.6 | -3178.8 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11-APR-09:25 | 0.00 | 0.00 | 10849.62 | 0.00 | 0.00 | 0.00 | 133.26 | 103.15 | 1096.02 | 1939.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1417.3 | -12704.5 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 6944.45 | 0.00 | 0.00 | 0.00 | 526.23 | 55.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1373.9 | 0.00 | -4480.7 | -2518.6 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 15-JAN-22:02 | 0.00 | 0.00 | 15177.59 | 0.00 | 0.00 | 0.00 | 556.83 | 336.97 | 1356.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2508.3 | 0.00 | -3283.9 | -11635.6 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 16-JAN-13:43 | 0.00 | 0.00 | 23851.42 | 0.00 | 0.00 | 0.00 | 146.98 | 103.15 | 1084.63 | 2196.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1830.9 | -25551.5 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 09-FEB-16:06 | 0.00 | 0.00 | 14538.08 | 0.00 | 0.00 | 0.00 | 165.44 | 385.11 | 1350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -604.3 | 0.00 | -2010.2 | -13824.6 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 9750.81 | 0.00 | 0.00 | 0.00 | 526.22 | 55.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3331.2 | 0.00 | -4784.8 | -3063.4 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12618.28 | 0.00 | 0.00 | 0.00 | 526.23 | 55.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3319.9 | 0.00 | -6218.8 | -4508.2 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12547.96 | 0.00 | 0.00 | 0.00 | 526.22 | 55.02 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3344.9 | 0.00 | -6218.9 | -4412.8 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 27-MAR-12:16 | 0.00 | 0.00 | 22698.95 | 0.00 | 0.00 | 0.00 | 139.17 | 103.15 | 1090.63 | 2732.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3924.8 | -22839.4 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 13-NOV-16:45 | 0.00 | 0.00 | 13854.44 | 0.00 | 0.00 | 0.00 | 163.92 | 385.11 | 1350.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -546.8 | 0.00 | -1974.3 | -13233.0 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 11-FEB-16:54 | 0.00 | 0.00 | 14976.05 | 0.00 | 0.00 | 0.00 | 163.84 | 385.11 | 1371.36 | 28.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3876.4 | -13048.0 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 02-JAN-12:33 | 0.00 | 0.00 | 24281.51 | 0.00 | 0.00 | 0.00 | 147.07 | 103.15 | 1090.63 | 250.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2159.6 | -23713.7 |
| UNHEATEDBSMT | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 22-DEC-03:00 | 0.00 | 0.00 | 184708.06 | 0.00 | 0.00 | 0.00 | 9472.25 | 990.28 | 15253.70 | 0.00 | 0.00 | 8230.75 | 0.00 | 0.00 | -48239.1 | 0.00 | -101472.4 | -68943.6 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.8993 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 556.8993 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.0514 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 258.0514 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.1770 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 391.1770 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.6432 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 534.6432 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.4514 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 249.4514 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.6397 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 370.6397 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.2462 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 562.2462 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.1450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 270.1450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.6997 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 400.6997 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.0593 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 541.0593 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.9642 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 262.9642 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.0486 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 379.0486 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.7119 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 594.7119 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.7778 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 307.7778 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.2026 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 397.2026 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.2371 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 592.2371 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.8474 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 314.8474 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.3210 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 375.3210 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.8993 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 556.8993 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.0514 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 258.0514 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.1770 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 391.1770 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.6432 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 534.6432 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.4514 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 249.4514 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.6397 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 370.6397 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.2462 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 562.2462 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.1450 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 270.1450 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.6997 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 400.6997 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.0593 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 541.0593 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.9642 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 262.9642 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.0486 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 379.0486 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.7119 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 594.7119 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.7778 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 307.7778 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.2026 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 397.2026 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.2371 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 592.2371 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.8474 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 314.8474 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.3210 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 375.3210 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 556.8993 | 556.8993 | 556.8993 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 258.0514 | 258.0514 | 258.0514 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 391.1770 | 391.1770 | 391.1770 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 534.6432 | 534.6432 | 534.6432 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 249.4514 | 249.4514 | 249.4514 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 370.6397 | 370.6397 | 370.6397 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 562.2462 | 562.2462 | 562.2462 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 270.1450 | 270.1450 | 270.1450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 400.6997 | 400.6997 | 400.6997 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 541.0593 | 541.0593 | 541.0593 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 262.9642 | 262.9642 | 262.9642 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.0486 | 379.0486 | 379.0486 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 375.3210 | 375.3210 | 375.3210 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 397.2026 | 397.2026 | 397.2026 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 594.7119 | 594.7119 | 594.7119 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 314.8474 | 314.8474 | 314.8474 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 307.7778 | 307.7778 | 307.7778 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 592.2371 | 592.2371 | 592.2371 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.8993 | 556.8993 | 556.8993 | 556.8993 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.0514 | 258.0514 | 258.0514 | 258.0514 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.1770 | 391.1770 | 391.1770 | 391.1770 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.6432 | 534.6432 | 534.6432 | 534.6432 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.4514 | 249.4514 | 249.4514 | 249.4514 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.6397 | 370.6397 | 370.6397 | 370.6397 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.2462 | 562.2462 | 562.2462 | 562.2462 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.1450 | 270.1450 | 270.1450 | 270.1450 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.6997 | 400.6997 | 400.6997 | 400.6997 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.0593 | 541.0593 | 541.0593 | 541.0593 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.9642 | 262.9642 | 262.9642 | 262.9642 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.0486 | 379.0486 | 379.0486 | 379.0486 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.7119 | 594.7119 | 594.7119 | 594.7119 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.7778 | 307.7778 | 307.7778 | 307.7778 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.2026 | 397.2026 | 397.2026 | 397.2026 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.2371 | 592.2371 | 592.2371 | 592.2371 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.8474 | 314.8474 | 314.8474 | 314.8474 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.3210 | 375.3210 | 375.3210 | 375.3210 | 0.0000 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 556.8993 | 556.8993 | 556.8993 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 258.0514 | 258.0514 | 258.0514 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 391.1770 | 391.1770 | 391.1770 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 534.6432 | 534.6432 | 534.6432 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 249.4514 | 249.4514 | 249.4514 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 370.6397 | 370.6397 | 370.6397 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 562.2462 | 562.2462 | 562.2462 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 270.1450 | 270.1450 | 270.1450 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 400.6997 | 400.6997 | 400.6997 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 541.0593 | 541.0593 | 541.0593 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 262.9642 | 262.9642 | 262.9642 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 379.0486 | 379.0486 | 379.0486 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 375.3210 | 375.3210 | 375.3210 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 397.2026 | 397.2026 | 397.2026 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 594.7119 | 594.7119 | 594.7119 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 314.8474 | 314.8474 | 314.8474 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 307.7778 | 307.7778 | 307.7778 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 592.2371 | 592.2371 | 592.2371 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 556.8993 | 556.8993 | 556.8993 | 556.8993 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 258.0514 | 258.0514 | 258.0514 | 258.0514 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 391.1770 | 391.1770 | 391.1770 | 391.1770 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 534.6432 | 534.6432 | 534.6432 | 534.6432 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 249.4514 | 249.4514 | 249.4514 | 249.4514 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 370.6397 | 370.6397 | 370.6397 | 370.6397 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 562.2462 | 562.2462 | 562.2462 | 562.2462 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 270.1450 | 270.1450 | 270.1450 | 270.1450 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 400.6997 | 400.6997 | 400.6997 | 400.6997 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 541.0593 | 541.0593 | 541.0593 | 541.0593 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 262.9642 | 262.9642 | 262.9642 | 262.9642 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 379.0486 | 379.0486 | 379.0486 | 379.0486 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 594.7119 | 594.7119 | 594.7119 | 594.7119 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 307.7778 | 307.7778 | 307.7778 | 307.7778 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 397.2026 | 397.2026 | 397.2026 | 397.2026 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 592.2371 | 592.2371 | 592.2371 | 592.2371 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 314.8474 | 314.8474 | 314.8474 | 314.8474 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 375.3210 | 375.3210 | 375.3210 | 375.3210 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Sec1.1A-General Information| Data | |
| Weather File | ANNUAL ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
| Total gross floor area [ft2] | 39005.22 |
| Principal Heating Source | Natural Gas |
| Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| UNHEATEDBSMT | 7794.39 | 0.00 | 7794.39 | 0.00 |
| BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
| ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
| Totals | 39005.22 | 21609.96 | 17395.26 |
| Data | |
| Number of hours heating loads not met | 1341.83 |
| Number of hours cooling loads not met | 0.50 |
| Number of hours not met | 1342.33 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
| Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler | 0.00 | 0.00 | 2102.09 | 224034.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heating -- Boiler Parasitic | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 15704.51 | 13867.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- General | 12960.20 | 4221.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Exterior-Lights | 6034.31 | 1377.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- dishwasher | 3088.82 | 985.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- clotheswasher | 1577.30 | 427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation | 5068.29 | 578.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 5611.23 | 2584.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284762.85 | 225024.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
| Electricity | 301503.54 | 456444.83 |
| Natural Gas | 0.00 | 210208.50 |
| Additional | 0.00 | 284762.85 |
| Total | 301503.54 | 951416.18 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [kWh/ft2] | |
| Interior Lighting (All) | 0.33 |
| Space Heating | 0.00 |
| Space Cooling | 0.40 |
| Fans (All) | 0.27 |
| Service Water Heating | 0.00 |
| Receptacle Equipment | 2.26 |
| Miscellaneous (All) | 3.43 |
| Subtotal | 3.43 |
| Natural Gas [kWh/ft2] | |
| Space Heating | 1.58 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 1.58 |
| Subtotal | 1.58 |
| Additional [kBtu/ft2] | |
| Subtotal | 7.29 |
| Miscellaneous | 7.29 |
| Percent [%] | |
| Interior Lighting (All) | 4.65 |
| Space Heating | 22.09 |
| Space Cooling | 5.64 |
| Fans (All) | 3.83 |
| Service Water Heating | 29.93 |
| Receptacle Equipment | 31.69 |
| Miscellaneous | 2.17 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCCUPANCY | 6031. | 8760. |
| INTERIORLIGHTING | 2852. | 8760. |
| INTERIORLIGHTINGHE | 3070. | 8760. |
| INTERIORLIGHTINGHE_OS | 2910. | 8760. |
| INTERIORLIGHTINGHE_VS | 2149. | 8760. |
| EXTERIORLIGHTING | 4380. | 4380. |
| REFRIGERATOR | 7343. | 8760. |
| MISCPLUGLOAD | 5918. | 8760. |
| COOKINGRANGE | 2434. | 8760. |
| DISHWASHER_FLOW_SCH | 2821. | 8760. |
| CLOTHESWASHER_FLOW_SCH | 3323. | 8760. |
| DISHWASHER_EQUIP_SCH | 3134. | 8760. |
| CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
| CLOTHESDRYER | 3911. | 8760. |
| SHADING_2012IECC | 0. | 0. |
| SHADING_2012IECC_HERS | 7007. | 8760. |
| SINKSENSSCHEDULE | 6025. | 8760. |
| SINKLATSCHEDULE | 2735. | 8760. |
| SHOWERSENSSCHEDULE | 4492. | 8760. |
| SHOWERLATSCHEDULE | 4268. | 8760. |
| BATHSENSSCHEDULE | 8760. | 8760. |
| BATHLATSCHEDULE | 0. | 0. |
| First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
| HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
| COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:37:00
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 148.482 | 5.737 | 455.439 | 19.174 | 19.276 |
| February | 120.739 | 5.261 | 431.553 | 19.935 | 21.008 |
| March | 188.975 | 10.208 | 415.625 | 21.775 | 24.662 |
| April | 170.789 | 7.245 | 379.228 | 16.861 | 23.673 |
| May | 391.575 | 17.172 | 90.972 | 18.341 | 21.990 |
| June | 663.764 | 41.822 | 0.000 | 41.822 | 41.858 |
| July | 703.861 | 42.655 | 0.000 | 42.655 | 42.655 |
| August | 689.578 | 42.240 | 0.000 | 42.240 | 42.240 |
| September | 552.444 | 32.121 | 34.833 | 32.681 | 33.257 |
| October | 262.800 | 14.133 | 329.697 | 22.945 | 25.038 |
| November | 175.202 | 7.826 | 402.028 | 18.947 | 19.080 |
| December | 105.228 | 4.575 | 532.986 | 24.836 | 24.851 |
| Annual Sum or Average | 4173.437 | 230.995 | 3072.361 | 322.212 | 339.587 |
| Minimum of Months | 105.228 | 4.575 | 0.000 | 16.861 | 19.080 |
| Maximum of Months | 703.861 | 42.655 | 532.986 | 42.655 | 42.655 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 161.917 | 3.618 | 395.681 | 7.961 | 8.131 |
| February | 130.486 | 2.869 | 398.111 | 7.918 | 8.718 |
| March | 189.547 | 5.584 | 381.842 | 9.511 | 9.837 |
| April | 169.131 | 3.507 | 364.333 | 6.743 | 6.909 |
| May | 414.625 | 9.874 | 68.722 | 10.142 | 10.142 |
| June | 700.556 | 26.392 | 0.000 | 26.392 | 26.392 |
| July | 725.953 | 28.764 | 0.000 | 28.764 | 28.764 |
| August | 728.167 | 28.498 | 0.000 | 28.498 | 28.498 |
| September | 606.575 | 22.003 | 20.250 | 22.136 | 22.136 |
| October | 290.500 | 8.955 | 287.206 | 11.800 | 11.824 |
| November | 203.036 | 5.158 | 342.731 | 8.684 | 8.946 |
| December | 116.792 | 3.144 | 485.323 | 10.505 | 10.681 |
| Annual Sum or Average | 4437.283 | 148.367 | 2744.199 | 179.053 | 180.976 |
| Minimum of Months | 116.792 | 2.869 | 0.000 | 6.743 | 6.909 |
| Maximum of Months | 728.167 | 28.764 | 485.323 | 28.764 | 28.764 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 147.108 | 4.546 | 373.138 | 17.197 | 25.444 |
| February | 138.554 | 4.642 | 379.294 | 18.681 | 24.331 |
| March | 208.241 | 9.275 | 343.300 | 19.919 | 26.379 |
| April | 202.542 | 7.354 | 325.417 | 16.363 | 23.103 |
| May | 442.386 | 17.452 | 51.583 | 18.317 | 23.632 |
| June | 675.403 | 42.511 | 0.000 | 42.511 | 42.558 |
| July | 710.694 | 44.596 | 0.000 | 44.596 | 44.596 |
| August | 695.861 | 43.824 | 0.000 | 43.824 | 43.824 |
| September | 570.069 | 32.427 | 17.917 | 32.861 | 35.011 |
| October | 290.931 | 13.092 | 270.458 | 21.464 | 29.160 |
| November | 186.320 | 6.799 | 329.940 | 17.377 | 25.876 |
| December | 111.539 | 3.890 | 471.313 | 23.566 | 30.099 |
| Annual Sum or Average | 4379.647 | 230.406 | 2562.360 | 316.673 | 374.013 |
| Minimum of Months | 111.539 | 3.890 | 0.000 | 16.363 | 23.103 |
| Maximum of Months | 710.694 | 44.596 | 471.313 | 44.596 | 44.596 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 27.250 | 0.505 | 497.126 | 17.023 | 42.364 |
| February | 27.889 | 0.558 | 487.144 | 17.817 | 33.250 |
| March | 120.750 | 4.191 | 434.404 | 16.059 | 28.152 |
| April | 124.306 | 3.987 | 402.375 | 13.485 | 22.936 |
| May | 374.844 | 14.783 | 95.269 | 15.875 | 20.072 |
| June | 671.833 | 40.342 | 0.333 | 40.342 | 40.342 |
| July | 706.806 | 40.618 | 0.000 | 40.618 | 40.618 |
| August | 687.483 | 36.692 | 0.000 | 36.692 | 36.692 |
| September | 524.608 | 24.077 | 37.056 | 24.643 | 26.374 |
| October | 164.319 | 5.357 | 371.392 | 14.467 | 21.149 |
| November | 54.083 | 1.194 | 452.878 | 14.550 | 33.455 |
| December | 25.153 | 0.433 | 560.941 | 23.744 | 41.674 |
| Annual Sum or Average | 3509.325 | 172.735 | 3338.918 | 275.316 | 387.078 |
| Minimum of Months | 25.153 | 0.433 | 0.000 | 13.485 | 20.072 |
| Maximum of Months | 706.806 | 40.618 | 560.941 | 40.618 | 42.364 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 1.583 | 0.002 | 618.519 | 7.418 | 10.103 |
| February | 10.833 | 0.058 | 562.210 | 7.674 | 11.586 |
| March | 89.083 | 1.093 | 465.694 | 6.023 | 8.533 |
| April | 88.722 | 1.264 | 416.150 | 4.848 | 6.795 |
| May | 386.520 | 8.691 | 72.264 | 8.990 | 9.159 |
| June | 703.375 | 27.722 | 0.000 | 27.722 | 27.722 |
| July | 727.750 | 29.735 | 0.000 | 29.735 | 29.735 |
| August | 726.792 | 26.088 | 0.000 | 26.088 | 26.088 |
| September | 575.111 | 16.467 | 28.681 | 16.631 | 16.679 |
| October | 129.194 | 1.694 | 363.547 | 5.007 | 5.868 |
| November | 39.167 | 0.265 | 536.797 | 5.877 | 9.411 |
| December | 3.944 | 0.011 | 644.231 | 10.444 | 12.453 |
| Annual Sum or Average | 3482.075 | 113.089 | 3708.092 | 156.456 | 174.131 |
| Minimum of Months | 1.583 | 0.002 | 0.000 | 4.848 | 5.868 |
| Maximum of Months | 727.750 | 29.735 | 644.231 | 29.735 | 29.735 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 11.167 | 0.100 | 622.809 | 18.643 | 21.298 |
| February | 25.764 | 0.318 | 557.032 | 18.741 | 20.017 |
| March | 158.622 | 3.393 | 438.431 | 15.635 | 20.296 |
| April | 168.897 | 4.110 | 372.806 | 13.640 | 18.884 |
| May | 433.989 | 15.293 | 53.583 | 16.189 | 21.413 |
| June | 677.194 | 41.547 | 0.000 | 41.547 | 41.577 |
| July | 711.750 | 43.132 | 0.000 | 43.132 | 43.132 |
| August | 693.722 | 39.083 | 0.000 | 39.083 | 39.083 |
| September | 554.153 | 24.964 | 26.333 | 25.478 | 27.226 |
| October | 187.853 | 3.799 | 320.556 | 12.936 | 19.406 |
| November | 53.425 | 0.788 | 541.323 | 15.559 | 19.033 |
| December | 10.694 | 0.079 | 645.901 | 25.072 | 26.727 |
| Annual Sum or Average | 3687.231 | 176.607 | 3578.774 | 285.654 | 318.092 |
| Minimum of Months | 10.694 | 0.079 | 0.000 | 12.936 | 18.884 |
| Maximum of Months | 711.750 | 43.132 | 645.901 | 43.132 | 43.132 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 170.689 | 6.201 | 414.238 | 17.072 | 17.711 |
| February | 139.556 | 5.779 | 385.750 | 17.667 | 20.981 |
| March | 210.322 | 11.067 | 366.600 | 20.103 | 24.436 |
| April | 195.367 | 8.167 | 335.683 | 15.530 | 20.715 |
| May | 439.056 | 19.520 | 57.556 | 20.152 | 22.535 |
| June | 700.750 | 45.590 | 0.000 | 45.590 | 45.590 |
| July | 728.611 | 46.586 | 0.000 | 46.586 | 46.586 |
| August | 725.069 | 46.185 | 0.000 | 46.185 | 46.185 |
| September | 603.569 | 35.194 | 23.250 | 35.566 | 35.736 |
| October | 286.308 | 15.305 | 284.625 | 22.227 | 25.204 |
| November | 201.072 | 8.512 | 356.472 | 17.380 | 18.384 |
| December | 122.778 | 4.900 | 497.704 | 21.557 | 21.693 |
| Annual Sum or Average | 4523.147 | 253.006 | 2721.878 | 325.616 | 345.754 |
| Minimum of Months | 122.778 | 4.900 | 0.000 | 15.530 | 17.711 |
| Maximum of Months | 728.611 | 46.586 | 497.704 | 46.586 | 46.586 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 197.728 | 4.778 | 345.273 | 7.844 | 7.986 |
| February | 161.311 | 3.946 | 346.250 | 7.574 | 7.963 |
| March | 221.264 | 7.179 | 330.778 | 9.875 | 9.962 |
| April | 208.614 | 4.956 | 303.233 | 7.135 | 7.167 |
| May | 501.500 | 13.481 | 38.667 | 13.603 | 13.612 |
| June | 712.889 | 32.442 | 0.000 | 32.442 | 32.442 |
| July | 741.417 | 35.078 | 0.000 | 35.078 | 35.078 |
| August | 741.083 | 34.886 | 0.000 | 34.886 | 34.886 |
| September | 651.758 | 27.376 | 12.917 | 27.461 | 27.461 |
| October | 329.239 | 11.370 | 236.167 | 13.359 | 13.363 |
| November | 240.347 | 6.717 | 289.956 | 9.172 | 9.312 |
| December | 143.292 | 4.031 | 435.014 | 9.331 | 9.528 |
| Annual Sum or Average | 4850.442 | 186.239 | 2338.254 | 207.760 | 208.759 |
| Minimum of Months | 143.292 | 3.946 | 0.000 | 7.135 | 7.167 |
| Maximum of Months | 741.417 | 35.078 | 435.014 | 35.078 | 35.078 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 167.665 | 5.029 | 325.745 | 14.834 | 24.817 |
| February | 155.626 | 5.255 | 324.319 | 16.232 | 24.384 |
| March | 237.024 | 10.262 | 301.983 | 18.371 | 25.153 |
| April | 230.258 | 8.470 | 279.306 | 15.128 | 22.130 |
| May | 491.250 | 20.029 | 28.417 | 20.465 | 23.889 |
| June | 705.167 | 45.951 | 0.000 | 45.951 | 45.951 |
| July | 729.778 | 48.135 | 0.000 | 48.135 | 48.135 |
| August | 728.500 | 47.384 | 0.000 | 47.384 | 47.384 |
| September | 619.014 | 35.333 | 11.167 | 35.617 | 36.862 |
| October | 315.553 | 14.327 | 223.633 | 20.634 | 29.297 |
| November | 212.300 | 7.456 | 278.553 | 15.520 | 25.744 |
| December | 125.824 | 4.236 | 423.917 | 19.780 | 28.524 |
| Annual Sum or Average | 4717.959 | 251.868 | 2197.039 | 318.051 | 382.270 |
| Minimum of Months | 125.824 | 4.236 | 0.000 | 14.834 | 22.130 |
| Maximum of Months | 729.778 | 48.135 | 423.917 | 48.135 | 48.135 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 35.111 | 0.546 | 467.063 | 13.999 | 40.746 |
| February | 36.722 | 0.656 | 445.886 | 14.443 | 33.371 |
| March | 138.014 | 4.765 | 395.865 | 14.028 | 25.828 |
| April | 149.583 | 4.689 | 357.061 | 11.854 | 19.146 |
| May | 428.111 | 17.118 | 58.444 | 17.711 | 20.456 |
| June | 703.153 | 44.212 | 0.000 | 44.212 | 44.212 |
| July | 730.306 | 44.635 | 0.000 | 44.635 | 44.635 |
| August | 724.083 | 40.772 | 0.000 | 40.772 | 40.772 |
| September | 579.931 | 27.133 | 22.153 | 27.488 | 28.928 |
| October | 191.278 | 6.104 | 322.553 | 13.121 | 19.874 |
| November | 64.917 | 1.315 | 412.029 | 11.871 | 32.148 |
| December | 31.333 | 0.449 | 533.990 | 19.494 | 40.033 |
| Annual Sum or Average | 3812.542 | 192.393 | 3015.045 | 273.628 | 390.150 |
| Minimum of Months | 31.333 | 0.449 | 0.000 | 11.854 | 19.146 |
| Maximum of Months | 730.306 | 44.635 | 533.990 | 44.635 | 44.635 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 6.056 | 0.028 | 582.283 | 5.668 | 8.644 |
| February | 17.500 | 0.143 | 532.537 | 5.863 | 10.385 |
| March | 120.083 | 1.717 | 416.023 | 5.186 | 7.364 |
| April | 132.417 | 2.000 | 342.481 | 4.412 | 5.473 |
| May | 487.653 | 11.489 | 43.722 | 11.634 | 11.661 |
| June | 714.292 | 31.783 | 0.000 | 31.783 | 31.783 |
| July | 742.500 | 33.901 | 0.000 | 33.901 | 33.901 |
| August | 740.583 | 30.385 | 0.000 | 30.385 | 30.385 |
| September | 630.639 | 20.003 | 15.583 | 20.104 | 20.108 |
| October | 166.917 | 2.513 | 301.967 | 4.839 | 5.518 |
| November | 50.167 | 0.478 | 491.850 | 4.618 | 8.208 |
| December | 12.194 | 0.046 | 624.093 | 7.935 | 9.482 |
| Annual Sum or Average | 3821.000 | 134.486 | 3350.539 | 166.329 | 182.911 |
| Minimum of Months | 6.056 | 0.028 | 0.000 | 4.412 | 5.473 |
| Maximum of Months | 742.500 | 33.901 | 624.093 | 33.901 | 33.901 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 17.958 | 0.131 | 589.905 | 15.105 | 19.764 |
| February | 34.778 | 0.453 | 526.681 | 15.257 | 17.824 |
| March | 178.147 | 4.209 | 396.592 | 13.498 | 18.827 |
| April | 190.433 | 5.093 | 311.556 | 12.052 | 18.753 |
| May | 479.608 | 17.908 | 30.889 | 18.379 | 21.702 |
| June | 706.111 | 45.060 | 0.000 | 45.060 | 45.060 |
| July | 730.361 | 46.739 | 0.000 | 46.739 | 46.739 |
| August | 727.833 | 42.807 | 0.000 | 42.807 | 42.807 |
| September | 602.000 | 27.986 | 14.083 | 28.292 | 29.961 |
| October | 215.567 | 4.693 | 268.000 | 11.563 | 19.514 |
| November | 61.242 | 0.979 | 500.401 | 12.650 | 18.077 |
| December | 15.833 | 0.113 | 622.154 | 20.440 | 23.383 |
| Annual Sum or Average | 3959.872 | 196.172 | 3260.260 | 281.842 | 322.409 |
| Minimum of Months | 15.833 | 0.113 | 0.000 | 11.563 | 17.824 |
| Maximum of Months | 730.361 | 46.739 | 622.154 | 46.739 | 46.739 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 113.314 | 3.932 | 473.813 | 20.905 | 23.144 |
| February | 100.222 | 3.770 | 438.736 | 21.794 | 28.333 |
| March | 175.403 | 9.230 | 405.344 | 23.131 | 31.477 |
| April | 161.242 | 6.646 | 362.172 | 18.013 | 30.361 |
| May | 391.060 | 18.109 | 68.247 | 19.259 | 27.743 |
| June | 683.806 | 47.048 | 0.000 | 47.048 | 47.048 |
| July | 715.472 | 48.261 | 0.000 | 48.261 | 48.261 |
| August | 708.689 | 47.034 | 0.000 | 47.034 | 47.034 |
| September | 564.056 | 34.404 | 29.236 | 35.031 | 36.375 |
| October | 250.125 | 13.063 | 310.278 | 23.475 | 30.735 |
| November | 151.458 | 6.237 | 410.778 | 20.083 | 23.301 |
| December | 85.222 | 3.300 | 555.460 | 28.570 | 29.651 |
| Annual Sum or Average | 4100.068 | 241.035 | 3054.065 | 352.605 | 403.462 |
| Minimum of Months | 85.222 | 3.300 | 0.000 | 18.013 | 23.144 |
| Maximum of Months | 715.472 | 48.261 | 555.460 | 48.261 | 48.261 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 107.508 | 2.592 | 436.721 | 8.411 | 8.854 |
| February | 93.528 | 2.057 | 436.410 | 8.638 | 9.379 |
| March | 173.903 | 5.804 | 410.822 | 10.884 | 11.358 |
| April | 157.319 | 3.711 | 377.992 | 7.814 | 8.297 |
| May | 418.875 | 12.358 | 70.978 | 12.719 | 12.741 |
| June | 705.917 | 34.816 | 0.000 | 34.816 | 34.816 |
| July | 732.111 | 37.677 | 0.000 | 37.677 | 37.677 |
| August | 729.833 | 36.740 | 0.000 | 36.740 | 36.740 |
| September | 612.500 | 27.214 | 21.389 | 27.386 | 27.386 |
| October | 277.661 | 9.288 | 295.000 | 12.875 | 13.125 |
| November | 163.625 | 4.418 | 373.472 | 9.081 | 9.590 |
| December | 94.528 | 2.445 | 527.172 | 11.946 | 12.372 |
| Annual Sum or Average | 4267.308 | 179.121 | 2949.956 | 218.989 | 222.336 |
| Minimum of Months | 93.528 | 2.057 | 0.000 | 7.814 | 8.297 |
| Maximum of Months | 732.111 | 37.677 | 527.172 | 37.677 | 37.677 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 102.499 | 2.862 | 422.145 | 16.793 | 24.890 |
| February | 107.860 | 3.006 | 409.694 | 18.129 | 22.950 |
| March | 189.602 | 8.173 | 373.874 | 19.482 | 25.471 |
| April | 184.539 | 6.456 | 338.278 | 15.845 | 21.987 |
| May | 444.800 | 17.884 | 52.167 | 18.739 | 23.665 |
| June | 695.181 | 46.511 | 0.000 | 46.511 | 46.511 |
| July | 721.431 | 48.849 | 0.000 | 48.849 | 48.849 |
| August | 712.833 | 47.395 | 0.000 | 47.395 | 47.395 |
| September | 584.694 | 33.874 | 19.333 | 34.324 | 36.175 |
| October | 280.647 | 11.612 | 279.736 | 20.326 | 26.980 |
| November | 153.955 | 5.063 | 362.361 | 16.546 | 24.050 |
| December | 88.127 | 2.589 | 515.898 | 23.821 | 28.702 |
| Annual Sum or Average | 4266.168 | 234.275 | 2773.487 | 326.761 | 377.625 |
| Minimum of Months | 88.127 | 2.589 | 0.000 | 15.845 | 21.987 |
| Maximum of Months | 721.431 | 48.849 | 515.898 | 48.849 | 48.849 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 25.417 | 0.408 | 522.429 | 21.363 | 47.167 |
| February | 26.861 | 0.530 | 490.374 | 21.616 | 39.730 |
| March | 122.125 | 4.733 | 445.794 | 19.434 | 31.975 |
| April | 129.361 | 4.425 | 395.144 | 15.932 | 28.483 |
| May | 378.778 | 16.691 | 93.250 | 17.980 | 22.756 |
| June | 689.500 | 46.530 | 0.000 | 46.530 | 46.530 |
| July | 718.167 | 47.255 | 0.000 | 47.255 | 47.255 |
| August | 707.225 | 43.518 | 0.000 | 43.518 | 43.518 |
| September | 540.681 | 28.452 | 37.806 | 29.135 | 30.679 |
| October | 171.028 | 6.007 | 366.628 | 17.095 | 25.555 |
| November | 53.528 | 1.198 | 457.425 | 17.722 | 39.288 |
| December | 19.778 | 0.300 | 582.814 | 29.311 | 46.794 |
| Annual Sum or Average | 3582.447 | 200.046 | 3391.665 | 326.890 | 449.731 |
| Minimum of Months | 19.778 | 0.300 | 0.000 | 15.932 | 22.756 |
| Maximum of Months | 718.167 | 47.255 | 582.814 | 47.255 | 47.255 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 3.667 | 0.011 | 639.476 | 9.268 | 10.984 |
| February | 12.750 | 0.101 | 569.844 | 9.354 | 13.307 |
| March | 103.028 | 1.838 | 471.359 | 7.919 | 10.452 |
| April | 104.889 | 1.920 | 420.186 | 6.417 | 8.285 |
| May | 399.200 | 11.078 | 75.222 | 11.477 | 11.722 |
| June | 708.000 | 34.553 | 0.000 | 34.553 | 34.553 |
| July | 733.889 | 36.952 | 0.000 | 36.952 | 36.952 |
| August | 729.083 | 33.560 | 0.000 | 33.560 | 33.560 |
| September | 584.931 | 21.472 | 27.333 | 21.679 | 21.750 |
| October | 142.417 | 2.596 | 365.222 | 6.764 | 7.713 |
| November | 41.750 | 0.432 | 546.955 | 7.475 | 11.246 |
| December | 4.167 | 0.014 | 657.500 | 12.727 | 14.306 |
| Annual Sum or Average | 3567.769 | 144.527 | 3773.097 | 198.146 | 214.831 |
| Minimum of Months | 3.667 | 0.011 | 0.000 | 6.417 | 7.713 |
| Maximum of Months | 733.889 | 36.952 | 657.500 | 36.952 | 36.952 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 9.611 | 0.063 | 633.763 | 18.657 | 21.229 |
| February | 19.806 | 0.264 | 576.025 | 18.490 | 19.696 |
| March | 158.756 | 3.719 | 450.750 | 15.829 | 20.700 |
| April | 162.558 | 4.280 | 378.319 | 13.647 | 18.606 |
| May | 438.647 | 16.634 | 56.556 | 17.482 | 22.224 |
| June | 696.319 | 46.324 | 0.000 | 46.324 | 46.324 |
| July | 722.333 | 48.238 | 0.000 | 48.238 | 48.238 |
| August | 712.250 | 44.536 | 0.000 | 44.536 | 44.536 |
| September | 572.581 | 28.471 | 25.667 | 28.960 | 30.551 |
| October | 184.117 | 4.254 | 319.444 | 13.212 | 19.521 |
| November | 51.903 | 0.805 | 556.512 | 15.523 | 18.892 |
| December | 8.917 | 0.047 | 659.296 | 24.935 | 26.596 |
| Annual Sum or Average | 3737.797 | 197.632 | 3656.332 | 305.834 | 337.115 |
| Minimum of Months | 8.917 | 0.047 | 0.000 | 13.212 | 18.606 |
| Maximum of Months | 722.333 | 48.238 | 659.296 | 48.238 | 48.238 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1880.59 | 0.00 | 0.00 |
| February | 2273.11 | 0.00 | 0.00 |
| March | 1619.41 | 0.00 | 0.00 |
| April | 1391.39 | 0.00 | 0.00 |
| May | 163.72 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 81.10 | 0.00 | 0.00 |
| October | 1233.83 | 0.00 | 0.00 |
| November | 1608.99 | 0.00 | 0.00 |
| December | 2832.89 | 0.00 | 0.00 |
| Annual Sum or Average | 1084.21 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2832.89 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1209.99 | 0.00 | 0.00 |
| February | 1548.08 | 0.00 | 0.00 |
| March | 1105.88 | 0.00 | 0.00 |
| April | 957.02 | 0.00 | 0.00 |
| May | 80.11 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 39.80 | 0.00 | 0.00 |
| October | 801.14 | 0.00 | 0.00 |
| November | 1026.77 | 0.00 | 0.00 |
| December | 1955.56 | 0.00 | 0.00 |
| Annual Sum or Average | 722.70 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1955.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1777.33 | 0.00 | 0.00 |
| February | 2183.01 | 0.00 | 0.00 |
| March | 1495.92 | 0.00 | 0.00 |
| April | 1308.51 | 0.00 | 0.00 |
| May | 121.63 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 63.05 | 0.00 | 0.00 |
| October | 1176.69 | 0.00 | 0.00 |
| November | 1536.26 | 0.00 | 0.00 |
| December | 2761.03 | 0.00 | 0.00 |
| Annual Sum or Average | 1029.23 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2761.03 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2456.54 | 0.00 | 0.00 |
| February | 2840.72 | 0.00 | 0.00 |
| March | 1765.14 | 0.00 | 0.00 |
| April | 1459.68 | 0.00 | 0.00 |
| May | 162.49 | 0.00 | 0.00 |
| June | 0.04 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 87.07 | 0.00 | 0.00 |
| October | 1355.06 | 0.00 | 0.00 |
| November | 2053.03 | 0.00 | 0.00 |
| December | 3462.28 | 0.00 | 0.00 |
| Annual Sum or Average | 1295.29 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3462.28 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2059.28 | 0.00 | 0.00 |
| February | 2326.47 | 0.00 | 0.00 |
| March | 1384.70 | 0.00 | 0.00 |
| April | 1059.96 | 0.00 | 0.00 |
| May | 89.05 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 49.43 | 0.00 | 0.00 |
| October | 936.51 | 0.00 | 0.00 |
| November | 1634.89 | 0.00 | 0.00 |
| December | 2762.83 | 0.00 | 0.00 |
| Annual Sum or Average | 1018.28 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2762.83 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2651.82 | 0.00 | 0.00 |
| February | 2915.81 | 0.00 | 0.00 |
| March | 1751.09 | 0.00 | 0.00 |
| April | 1408.87 | 0.00 | 0.00 |
| May | 128.31 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 75.91 | 0.00 | 0.00 |
| October | 1307.32 | 0.00 | 0.00 |
| November | 2183.62 | 0.00 | 0.00 |
| December | 3570.31 | 0.00 | 0.00 |
| Annual Sum or Average | 1324.30 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3570.31 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1497.13 | 0.00 | 0.00 |
| February | 1812.13 | 0.00 | 0.00 |
| March | 1244.98 | 0.00 | 0.00 |
| April | 1048.40 | 0.00 | 0.00 |
| May | 87.09 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 53.04 | 0.00 | 0.00 |
| October | 953.75 | 0.00 | 0.00 |
| November | 1262.58 | 0.00 | 0.00 |
| December | 2291.58 | 0.00 | 0.00 |
| Annual Sum or Average | 849.24 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2291.58 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 867.13 | 0.00 | 0.00 |
| February | 1135.14 | 0.00 | 0.00 |
| March | 772.32 | 0.00 | 0.00 |
| April | 652.50 | 0.00 | 0.00 |
| May | 36.35 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 25.78 | 0.00 | 0.00 |
| October | 566.90 | 0.00 | 0.00 |
| November | 725.29 | 0.00 | 0.00 |
| December | 1443.73 | 0.00 | 0.00 |
| Annual Sum or Average | 515.54 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 1443.73 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1397.13 | 0.00 | 0.00 |
| February | 1731.19 | 0.00 | 0.00 |
| March | 1155.96 | 0.00 | 0.00 |
| April | 980.68 | 0.00 | 0.00 |
| May | 62.28 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 41.80 | 0.00 | 0.00 |
| October | 899.06 | 0.00 | 0.00 |
| November | 1187.96 | 0.00 | 0.00 |
| December | 2212.76 | 0.00 | 0.00 |
| Annual Sum or Average | 800.90 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2212.76 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2016.46 | 0.00 | 0.00 |
| February | 2286.88 | 0.00 | 0.00 |
| March | 1388.36 | 0.00 | 0.00 |
| April | 1109.60 | 0.00 | 0.00 |
| May | 88.91 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 54.90 | 0.00 | 0.00 |
| October | 1051.72 | 0.00 | 0.00 |
| November | 1635.14 | 0.00 | 0.00 |
| December | 2850.95 | 0.00 | 0.00 |
| Annual Sum or Average | 1033.73 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2850.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1594.67 | 0.00 | 0.00 |
| February | 1786.27 | 0.00 | 0.00 |
| March | 992.77 | 0.00 | 0.00 |
| April | 721.41 | 0.00 | 0.00 |
| May | 42.75 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 30.34 | 0.00 | 0.00 |
| October | 664.40 | 0.00 | 0.00 |
| November | 1224.35 | 0.00 | 0.00 |
| December | 2148.19 | 0.00 | 0.00 |
| Annual Sum or Average | 761.71 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2148.19 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2185.78 | 0.00 | 0.00 |
| February | 2391.52 | 0.00 | 0.00 |
| March | 1356.37 | 0.00 | 0.00 |
| April | 1050.12 | 0.00 | 0.00 |
| May | 68.77 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 46.15 | 0.00 | 0.00 |
| October | 1003.32 | 0.00 | 0.00 |
| November | 1761.06 | 0.00 | 0.00 |
| December | 2963.75 | 0.00 | 0.00 |
| Annual Sum or Average | 1061.92 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2963.75 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2275.06 | 0.00 | 0.00 |
| February | 2674.07 | 0.00 | 0.00 |
| March | 1864.17 | 0.00 | 0.00 |
| April | 1575.56 | 0.00 | 0.00 |
| May | 154.30 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 86.92 | 0.00 | 0.00 |
| October | 1396.51 | 0.00 | 0.00 |
| November | 1918.68 | 0.00 | 0.00 |
| December | 3383.64 | 0.00 | 0.00 |
| Annual Sum or Average | 1270.12 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3383.64 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1576.70 | 0.00 | 0.00 |
| February | 1974.81 | 0.00 | 0.00 |
| March | 1390.83 | 0.00 | 0.00 |
| April | 1172.71 | 0.00 | 0.00 |
| May | 100.86 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 49.47 | 0.00 | 0.00 |
| October | 980.41 | 0.00 | 0.00 |
| November | 1319.08 | 0.00 | 0.00 |
| December | 2476.79 | 0.00 | 0.00 |
| Annual Sum or Average | 914.59 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2476.79 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2191.76 | 0.00 | 0.00 |
| February | 2633.34 | 0.00 | 0.00 |
| March | 1779.78 | 0.00 | 0.00 |
| April | 1527.14 | 0.00 | 0.00 |
| May | 134.68 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 73.23 | 0.00 | 0.00 |
| October | 1371.83 | 0.00 | 0.00 |
| November | 1867.54 | 0.00 | 0.00 |
| December | 3336.82 | 0.00 | 0.00 |
| Annual Sum or Average | 1235.70 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3336.82 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2915.59 | 0.00 | 0.00 |
| February | 3247.05 | 0.00 | 0.00 |
| March | 2045.54 | 0.00 | 0.00 |
| April | 1654.68 | 0.00 | 0.00 |
| May | 179.47 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 98.27 | 0.00 | 0.00 |
| October | 1543.25 | 0.00 | 0.00 |
| November | 2376.45 | 0.00 | 0.00 |
| December | 4031.66 | 0.00 | 0.00 |
| Annual Sum or Average | 1498.57 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4031.66 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2492.49 | 0.00 | 0.00 |
| February | 2761.78 | 0.00 | 0.00 |
| March | 1649.62 | 0.00 | 0.00 |
| April | 1270.34 | 0.00 | 0.00 |
| May | 109.35 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 58.51 | 0.00 | 0.00 |
| October | 1131.77 | 0.00 | 0.00 |
| November | 1975.92 | 0.00 | 0.00 |
| December | 3304.95 | 0.00 | 0.00 |
| Annual Sum or Average | 1221.39 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3304.95 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3101.29 | 0.00 | 0.00 |
| February | 3364.59 | 0.00 | 0.00 |
| March | 2020.27 | 0.00 | 0.00 |
| April | 1615.21 | 0.00 | 0.00 |
| May | 141.59 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 84.47 | 0.00 | 0.00 |
| October | 1494.88 | 0.00 | 0.00 |
| November | 2537.76 | 0.00 | 0.00 |
| December | 4146.70 | 0.00 | 0.00 |
| Annual Sum or Average | 1532.54 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4146.70 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.08 |
| April | 0.00 | 0.00 | 0.06 |
| May | 0.00 | 0.00 | 0.13 |
| June | 0.00 | 0.00 | 0.32 |
| July | 0.00 | 0.00 | 0.31 |
| August | 0.00 | 0.00 | 0.31 |
| September | 0.00 | 0.00 | 0.25 |
| October | 0.00 | 0.00 | 0.11 |
| November | 0.00 | 0.00 | 0.06 |
| December | 0.00 | 0.00 | 0.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.15 |
| Minimum of Months | 0.00 | 0.00 | 0.04 |
| Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.03 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.08 |
| June | 0.00 | 0.00 | 0.23 |
| July | 0.00 | 0.00 | 0.24 |
| August | 0.00 | 0.00 | 0.24 |
| September | 0.00 | 0.00 | 0.19 |
| October | 0.00 | 0.00 | 0.08 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.04 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.06 |
| May | 0.00 | 0.00 | 0.13 |
| June | 0.00 | 0.00 | 0.33 |
| July | 0.00 | 0.00 | 0.34 |
| August | 0.00 | 0.00 | 0.33 |
| September | 0.00 | 0.00 | 0.25 |
| October | 0.00 | 0.00 | 0.10 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.15 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.11 |
| June | 0.00 | 0.00 | 0.31 |
| July | 0.00 | 0.00 | 0.30 |
| August | 0.00 | 0.00 | 0.27 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.04 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.07 |
| June | 0.00 | 0.00 | 0.22 |
| July | 0.00 | 0.00 | 0.23 |
| August | 0.00 | 0.00 | 0.20 |
| September | 0.00 | 0.00 | 0.13 |
| October | 0.00 | 0.00 | 0.01 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.07 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.02 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.11 |
| June | 0.00 | 0.00 | 0.32 |
| July | 0.00 | 0.00 | 0.32 |
| August | 0.00 | 0.00 | 0.29 |
| September | 0.00 | 0.00 | 0.19 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.05 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.09 |
| April | 0.00 | 0.00 | 0.06 |
| May | 0.00 | 0.00 | 0.15 |
| June | 0.00 | 0.00 | 0.35 |
| July | 0.00 | 0.00 | 0.34 |
| August | 0.00 | 0.00 | 0.34 |
| September | 0.00 | 0.00 | 0.27 |
| October | 0.00 | 0.00 | 0.12 |
| November | 0.00 | 0.00 | 0.07 |
| December | 0.00 | 0.00 | 0.04 |
| Annual Sum or Average | 0.00 | 0.00 | 0.16 |
| Minimum of Months | 0.00 | 0.00 | 0.04 |
| Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.06 |
| April | 0.00 | 0.00 | 0.04 |
| May | 0.00 | 0.00 | 0.10 |
| June | 0.00 | 0.00 | 0.26 |
| July | 0.00 | 0.00 | 0.27 |
| August | 0.00 | 0.00 | 0.27 |
| September | 0.00 | 0.00 | 0.22 |
| October | 0.00 | 0.00 | 0.09 |
| November | 0.00 | 0.00 | 0.06 |
| December | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.12 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.04 |
| February | 0.00 | 0.00 | 0.05 |
| March | 0.00 | 0.00 | 0.08 |
| April | 0.00 | 0.00 | 0.07 |
| May | 0.00 | 0.00 | 0.15 |
| June | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.00 | 0.37 |
| August | 0.00 | 0.00 | 0.36 |
| September | 0.00 | 0.00 | 0.28 |
| October | 0.00 | 0.00 | 0.11 |
| November | 0.00 | 0.00 | 0.06 |
| December | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.16 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.04 |
| May | 0.00 | 0.00 | 0.13 |
| June | 0.00 | 0.00 | 0.34 |
| July | 0.00 | 0.00 | 0.33 |
| August | 0.00 | 0.00 | 0.30 |
| September | 0.00 | 0.00 | 0.20 |
| October | 0.00 | 0.00 | 0.05 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.12 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.09 |
| June | 0.00 | 0.00 | 0.25 |
| July | 0.00 | 0.00 | 0.26 |
| August | 0.00 | 0.00 | 0.23 |
| September | 0.00 | 0.00 | 0.15 |
| October | 0.00 | 0.00 | 0.02 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.04 |
| May | 0.00 | 0.00 | 0.13 |
| June | 0.00 | 0.00 | 0.35 |
| July | 0.00 | 0.00 | 0.35 |
| August | 0.00 | 0.00 | 0.32 |
| September | 0.00 | 0.00 | 0.21 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.12 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.03 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.05 |
| May | 0.00 | 0.00 | 0.13 |
| June | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.00 | 0.35 |
| August | 0.00 | 0.00 | 0.35 |
| September | 0.00 | 0.00 | 0.26 |
| October | 0.00 | 0.00 | 0.10 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.15 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.02 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.09 |
| June | 0.00 | 0.00 | 0.27 |
| July | 0.00 | 0.00 | 0.28 |
| August | 0.00 | 0.00 | 0.28 |
| September | 0.00 | 0.00 | 0.21 |
| October | 0.00 | 0.00 | 0.07 |
| November | 0.00 | 0.00 | 0.03 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.28 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.06 |
| April | 0.00 | 0.00 | 0.05 |
| May | 0.00 | 0.00 | 0.14 |
| June | 0.00 | 0.00 | 0.37 |
| July | 0.00 | 0.00 | 0.38 |
| August | 0.00 | 0.00 | 0.37 |
| September | 0.00 | 0.00 | 0.27 |
| October | 0.00 | 0.00 | 0.09 |
| November | 0.00 | 0.00 | 0.04 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.15 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.38 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.12 |
| June | 0.00 | 0.00 | 0.35 |
| July | 0.00 | 0.00 | 0.34 |
| August | 0.00 | 0.00 | 0.32 |
| September | 0.00 | 0.00 | 0.21 |
| October | 0.00 | 0.00 | 0.04 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.12 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.08 |
| June | 0.00 | 0.00 | 0.26 |
| July | 0.00 | 0.00 | 0.27 |
| August | 0.00 | 0.00 | 0.25 |
| September | 0.00 | 0.00 | 0.16 |
| October | 0.00 | 0.00 | 0.02 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.09 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.27 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.12 |
| June | 0.00 | 0.00 | 0.36 |
| July | 0.00 | 0.00 | 0.37 |
| August | 0.00 | 0.00 | 0.34 |
| September | 0.00 | 0.00 | 0.22 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.13 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.37 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.80 | 1191.09 |
| February | 0.00 | 0.00 | 1622.01 | 1090.76 |
| March | 0.00 | 0.00 | 1594.85 | 1187.41 |
| April | 0.00 | 0.00 | 1536.20 | 1106.85 |
| May | 0.00 | 0.00 | 1437.41 | 1070.19 |
| June | 0.00 | 0.00 | 1344.17 | 968.49 |
| July | 0.00 | 0.00 | 1285.01 | 956.72 |
| August | 0.00 | 0.00 | 1260.07 | 938.16 |
| September | 0.00 | 0.00 | 1290.06 | 929.50 |
| October | 0.00 | 0.00 | 1364.50 | 1015.91 |
| November | 0.00 | 0.00 | 1450.53 | 1045.12 |
| December | 0.00 | 0.00 | 1543.90 | 1149.47 |
| Annual Sum or Average | 0.00 | 0.00 | 1443.00 | 12649.68 |
| Minimum of Months | 0.00 | 0.00 | 1260.07 | 929.50 |
| Maximum of Months | 0.00 | 0.00 | 1622.01 | 1191.09 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.58 | 1190.93 |
| February | 0.00 | 0.00 | 1619.62 | 1089.15 |
| March | 0.00 | 0.00 | 1594.64 | 1187.25 |
| April | 0.00 | 0.00 | 1535.34 | 1106.23 |
| May | 0.00 | 0.00 | 1434.27 | 1067.85 |
| June | 0.00 | 0.00 | 1344.32 | 968.60 |
| July | 0.00 | 0.00 | 1284.96 | 956.68 |
| August | 0.00 | 0.00 | 1260.13 | 938.20 |
| September | 0.00 | 0.00 | 1287.95 | 927.98 |
| October | 0.00 | 0.00 | 1362.21 | 1014.20 |
| November | 0.00 | 0.00 | 1450.38 | 1045.02 |
| December | 0.00 | 0.00 | 1543.75 | 1149.37 |
| Annual Sum or Average | 0.00 | 0.00 | 1442.07 | 12641.48 |
| Minimum of Months | 0.00 | 0.00 | 1260.13 | 927.98 |
| Maximum of Months | 0.00 | 0.00 | 1619.62 | 1190.93 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.75 | 1191.06 |
| February | 0.00 | 0.00 | 1621.83 | 1090.64 |
| March | 0.00 | 0.00 | 1592.61 | 1185.74 |
| April | 0.00 | 0.00 | 1535.91 | 1106.64 |
| May | 0.00 | 0.00 | 1435.73 | 1068.94 |
| June | 0.00 | 0.00 | 1344.17 | 968.49 |
| July | 0.00 | 0.00 | 1284.85 | 956.60 |
| August | 0.00 | 0.00 | 1260.23 | 938.28 |
| September | 0.00 | 0.00 | 1287.88 | 927.93 |
| October | 0.00 | 0.00 | 1364.37 | 1015.81 |
| November | 0.00 | 0.00 | 1452.67 | 1046.66 |
| December | 0.00 | 0.00 | 1541.67 | 1147.82 |
| Annual Sum or Average | 0.00 | 0.00 | 1442.43 | 12644.62 |
| Minimum of Months | 0.00 | 0.00 | 1260.23 | 927.93 |
| Maximum of Months | 0.00 | 0.00 | 1621.83 | 1191.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1608.90 | 1197.87 |
| February | 0.00 | 0.00 | 1628.19 | 1094.92 |
| March | 0.00 | 0.00 | 1598.58 | 1190.19 |
| April | 0.00 | 0.00 | 1538.42 | 1108.45 |
| May | 0.00 | 0.00 | 1437.80 | 1070.48 |
| June | 0.00 | 0.00 | 1344.27 | 968.56 |
| July | 0.00 | 0.00 | 1284.94 | 956.67 |
| August | 0.00 | 0.00 | 1260.24 | 938.28 |
| September | 0.00 | 0.00 | 1290.01 | 929.47 |
| October | 0.00 | 0.00 | 1368.93 | 1019.21 |
| November | 0.00 | 0.00 | 1457.30 | 1050.00 |
| December | 0.00 | 0.00 | 1550.39 | 1154.31 |
| Annual Sum or Average | 0.00 | 0.00 | 1446.28 | 12678.41 |
| Minimum of Months | 0.00 | 0.00 | 1260.24 | 929.47 |
| Maximum of Months | 0.00 | 0.00 | 1628.19 | 1197.87 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.52 | 1196.10 |
| February | 0.00 | 0.00 | 1627.66 | 1094.56 |
| March | 0.00 | 0.00 | 1598.73 | 1190.30 |
| April | 0.00 | 0.00 | 1538.56 | 1108.55 |
| May | 0.00 | 0.00 | 1435.92 | 1069.08 |
| June | 0.00 | 0.00 | 1343.13 | 967.74 |
| July | 0.00 | 0.00 | 1284.01 | 955.98 |
| August | 0.00 | 0.00 | 1259.98 | 938.09 |
| September | 0.00 | 0.00 | 1289.82 | 929.33 |
| October | 0.00 | 0.00 | 1366.90 | 1017.69 |
| November | 0.00 | 0.00 | 1459.55 | 1051.62 |
| December | 0.00 | 0.00 | 1546.39 | 1151.33 |
| Annual Sum or Average | 0.00 | 0.00 | 1445.36 | 12670.36 |
| Minimum of Months | 0.00 | 0.00 | 1259.98 | 929.33 |
| Maximum of Months | 0.00 | 0.00 | 1627.66 | 1196.10 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.37 | 1195.98 |
| February | 0.00 | 0.00 | 1624.71 | 1092.58 |
| March | 0.00 | 0.00 | 1596.99 | 1189.00 |
| April | 0.00 | 0.00 | 1535.79 | 1106.55 |
| May | 0.00 | 0.00 | 1437.66 | 1070.38 |
| June | 0.00 | 0.00 | 1344.20 | 968.51 |
| July | 0.00 | 0.00 | 1282.96 | 955.20 |
| August | 0.00 | 0.00 | 1260.93 | 938.80 |
| September | 0.00 | 0.00 | 1289.12 | 928.83 |
| October | 0.00 | 0.00 | 1366.58 | 1017.46 |
| November | 0.00 | 0.00 | 1457.18 | 1049.91 |
| December | 0.00 | 0.00 | 1547.84 | 1152.41 |
| Annual Sum or Average | 0.00 | 0.00 | 1444.82 | 12665.61 |
| Minimum of Months | 0.00 | 0.00 | 1260.93 | 928.83 |
| Maximum of Months | 0.00 | 0.00 | 1624.71 | 1195.98 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.64 | 1190.98 |
| February | 0.00 | 0.00 | 1619.36 | 1088.98 |
| March | 0.00 | 0.00 | 1594.67 | 1187.27 |
| April | 0.00 | 0.00 | 1533.92 | 1105.20 |
| May | 0.00 | 0.00 | 1435.41 | 1068.70 |
| June | 0.00 | 0.00 | 1344.32 | 968.59 |
| July | 0.00 | 0.00 | 1284.94 | 956.67 |
| August | 0.00 | 0.00 | 1260.12 | 938.19 |
| September | 0.00 | 0.00 | 1287.86 | 927.92 |
| October | 0.00 | 0.00 | 1364.41 | 1015.84 |
| November | 0.00 | 0.00 | 1450.24 | 1044.91 |
| December | 0.00 | 0.00 | 1541.66 | 1147.81 |
| Annual Sum or Average | 0.00 | 0.00 | 1442.02 | 12641.09 |
| Minimum of Months | 0.00 | 0.00 | 1260.12 | 927.92 |
| Maximum of Months | 0.00 | 0.00 | 1619.36 | 1190.98 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1597.36 | 1189.28 |
| February | 0.00 | 0.00 | 1619.45 | 1089.04 |
| March | 0.00 | 0.00 | 1592.48 | 1185.64 |
| April | 0.00 | 0.00 | 1533.78 | 1105.11 |
| May | 0.00 | 0.00 | 1431.33 | 1065.66 |
| June | 0.00 | 0.00 | 1344.20 | 968.51 |
| July | 0.00 | 0.00 | 1284.95 | 956.68 |
| August | 0.00 | 0.00 | 1260.11 | 938.19 |
| September | 0.00 | 0.00 | 1287.82 | 927.89 |
| October | 0.00 | 0.00 | 1360.05 | 1012.60 |
| November | 0.00 | 0.00 | 1448.37 | 1043.57 |
| December | 0.00 | 0.00 | 1541.69 | 1147.83 |
| Annual Sum or Average | 0.00 | 0.00 | 1440.76 | 12630.00 |
| Minimum of Months | 0.00 | 0.00 | 1260.11 | 927.89 |
| Maximum of Months | 0.00 | 0.00 | 1619.45 | 1189.28 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.56 | 1190.92 |
| February | 0.00 | 0.00 | 1619.43 | 1089.03 |
| March | 0.00 | 0.00 | 1592.54 | 1185.69 |
| April | 0.00 | 0.00 | 1533.77 | 1105.10 |
| May | 0.00 | 0.00 | 1433.36 | 1067.18 |
| June | 0.00 | 0.00 | 1344.25 | 968.54 |
| July | 0.00 | 0.00 | 1284.87 | 956.62 |
| August | 0.00 | 0.00 | 1260.18 | 938.24 |
| September | 0.00 | 0.00 | 1287.91 | 927.95 |
| October | 0.00 | 0.00 | 1362.18 | 1014.18 |
| November | 0.00 | 0.00 | 1450.35 | 1045.00 |
| December | 0.00 | 0.00 | 1543.63 | 1149.28 |
| Annual Sum or Average | 0.00 | 0.00 | 1441.64 | 12637.72 |
| Minimum of Months | 0.00 | 0.00 | 1260.18 | 927.95 |
| Maximum of Months | 0.00 | 0.00 | 1619.43 | 1190.92 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1608.72 | 1197.74 |
| February | 0.00 | 0.00 | 1627.24 | 1094.28 |
| March | 0.00 | 0.00 | 1597.28 | 1189.22 |
| April | 0.00 | 0.00 | 1536.06 | 1106.75 |
| May | 0.00 | 0.00 | 1435.62 | 1068.86 |
| June | 0.00 | 0.00 | 1344.26 | 968.55 |
| July | 0.00 | 0.00 | 1284.95 | 956.68 |
| August | 0.00 | 0.00 | 1260.16 | 938.23 |
| September | 0.00 | 0.00 | 1287.88 | 927.93 |
| October | 0.00 | 0.00 | 1366.70 | 1017.55 |
| November | 0.00 | 0.00 | 1459.86 | 1051.84 |
| December | 0.00 | 0.00 | 1548.44 | 1152.86 |
| Annual Sum or Average | 0.00 | 0.00 | 1445.38 | 12670.48 |
| Minimum of Months | 0.00 | 0.00 | 1260.16 | 927.93 |
| Maximum of Months | 0.00 | 0.00 | 1627.24 | 1197.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.37 | 1195.99 |
| February | 0.00 | 0.00 | 1627.04 | 1094.14 |
| March | 0.00 | 0.00 | 1597.28 | 1189.22 |
| April | 0.00 | 0.00 | 1533.84 | 1105.15 |
| May | 0.00 | 0.00 | 1433.42 | 1067.22 |
| June | 0.00 | 0.00 | 1344.30 | 968.58 |
| July | 0.00 | 0.00 | 1284.96 | 956.69 |
| August | 0.00 | 0.00 | 1260.07 | 938.16 |
| September | 0.00 | 0.00 | 1287.85 | 927.91 |
| October | 0.00 | 0.00 | 1364.51 | 1015.91 |
| November | 0.00 | 0.00 | 1457.66 | 1050.26 |
| December | 0.00 | 0.00 | 1547.86 | 1152.42 |
| Annual Sum or Average | 0.00 | 0.00 | 1444.37 | 12661.67 |
| Minimum of Months | 0.00 | 0.00 | 1260.07 | 927.91 |
| Maximum of Months | 0.00 | 0.00 | 1627.04 | 1195.99 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.39 | 1196.00 |
| February | 0.00 | 0.00 | 1624.69 | 1092.57 |
| March | 0.00 | 0.00 | 1594.90 | 1187.45 |
| April | 0.00 | 0.00 | 1536.21 | 1106.86 |
| May | 0.00 | 0.00 | 1433.45 | 1067.24 |
| June | 0.00 | 0.00 | 1344.04 | 968.40 |
| July | 0.00 | 0.00 | 1284.84 | 956.60 |
| August | 0.00 | 0.00 | 1260.16 | 938.22 |
| September | 0.00 | 0.00 | 1287.94 | 927.97 |
| October | 0.00 | 0.00 | 1364.46 | 1015.88 |
| November | 0.00 | 0.00 | 1457.01 | 1049.79 |
| December | 0.00 | 0.00 | 1546.17 | 1151.17 |
| Annual Sum or Average | 0.00 | 0.00 | 1443.97 | 12658.14 |
| Minimum of Months | 0.00 | 0.00 | 1260.16 | 927.97 |
| Maximum of Months | 0.00 | 0.00 | 1624.69 | 1196.00 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1601.84 | 1192.62 |
| February | 0.00 | 0.00 | 1622.12 | 1090.84 |
| March | 0.00 | 0.00 | 1597.16 | 1189.13 |
| April | 0.00 | 0.00 | 1536.37 | 1106.97 |
| May | 0.00 | 0.00 | 1435.74 | 1068.95 |
| June | 0.00 | 0.00 | 1344.27 | 968.56 |
| July | 0.00 | 0.00 | 1285.03 | 956.74 |
| August | 0.00 | 0.00 | 1259.94 | 938.06 |
| September | 0.00 | 0.00 | 1290.01 | 929.47 |
| October | 0.00 | 0.00 | 1364.53 | 1015.93 |
| November | 0.00 | 0.00 | 1452.57 | 1046.60 |
| December | 0.00 | 0.00 | 1544.13 | 1149.65 |
| Annual Sum or Average | 0.00 | 0.00 | 1443.44 | 12653.50 |
| Minimum of Months | 0.00 | 0.00 | 1259.94 | 929.47 |
| Maximum of Months | 0.00 | 0.00 | 1622.12 | 1192.62 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1599.75 | 1191.06 |
| February | 0.00 | 0.00 | 1624.26 | 1092.28 |
| March | 0.00 | 0.00 | 1593.00 | 1186.03 |
| April | 0.00 | 0.00 | 1535.81 | 1106.57 |
| May | 0.00 | 0.00 | 1435.63 | 1068.86 |
| June | 0.00 | 0.00 | 1344.27 | 968.56 |
| July | 0.00 | 0.00 | 1284.86 | 956.61 |
| August | 0.00 | 0.00 | 1260.17 | 938.23 |
| September | 0.00 | 0.00 | 1287.92 | 927.96 |
| October | 0.00 | 0.00 | 1362.26 | 1014.24 |
| November | 0.00 | 0.00 | 1452.62 | 1046.63 |
| December | 0.00 | 0.00 | 1543.60 | 1149.25 |
| Annual Sum or Average | 0.00 | 0.00 | 1442.62 | 12646.29 |
| Minimum of Months | 0.00 | 0.00 | 1260.17 | 927.96 |
| Maximum of Months | 0.00 | 0.00 | 1624.26 | 1191.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1601.84 | 1192.61 |
| February | 0.00 | 0.00 | 1622.11 | 1090.83 |
| March | 0.00 | 0.00 | 1594.70 | 1187.30 |
| April | 0.00 | 0.00 | 1535.91 | 1106.64 |
| May | 0.00 | 0.00 | 1435.47 | 1068.75 |
| June | 0.00 | 0.00 | 1344.27 | 968.56 |
| July | 0.00 | 0.00 | 1283.01 | 955.24 |
| August | 0.00 | 0.00 | 1260.08 | 938.17 |
| September | 0.00 | 0.00 | 1289.97 | 929.43 |
| October | 0.00 | 0.00 | 1364.38 | 1015.82 |
| November | 0.00 | 0.00 | 1452.64 | 1046.64 |
| December | 0.00 | 0.00 | 1543.65 | 1149.29 |
| Annual Sum or Average | 0.00 | 0.00 | 1442.96 | 12649.27 |
| Minimum of Months | 0.00 | 0.00 | 1260.08 | 929.43 |
| Maximum of Months | 0.00 | 0.00 | 1622.11 | 1192.61 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1608.66 | 1197.70 |
| February | 0.00 | 0.00 | 1629.43 | 1095.76 |
| March | 0.00 | 0.00 | 1597.26 | 1189.21 |
| April | 0.00 | 0.00 | 1538.33 | 1108.39 |
| May | 0.00 | 0.00 | 1438.00 | 1070.63 |
| June | 0.00 | 0.00 | 1344.25 | 968.55 |
| July | 0.00 | 0.00 | 1284.94 | 956.68 |
| August | 0.00 | 0.00 | 1260.01 | 938.11 |
| September | 0.00 | 0.00 | 1289.98 | 929.44 |
| October | 0.00 | 0.00 | 1366.88 | 1017.68 |
| November | 0.00 | 0.00 | 1459.42 | 1051.53 |
| December | 0.00 | 0.00 | 1548.47 | 1152.88 |
| Annual Sum or Average | 0.00 | 0.00 | 1446.07 | 12676.54 |
| Minimum of Months | 0.00 | 0.00 | 1260.01 | 929.44 |
| Maximum of Months | 0.00 | 0.00 | 1629.43 | 1197.70 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.47 | 1196.06 |
| February | 0.00 | 0.00 | 1626.98 | 1094.11 |
| March | 0.00 | 0.00 | 1599.39 | 1190.79 |
| April | 0.00 | 0.00 | 1536.25 | 1106.89 |
| May | 0.00 | 0.00 | 1435.47 | 1068.75 |
| June | 0.00 | 0.00 | 1344.28 | 968.57 |
| July | 0.00 | 0.00 | 1284.98 | 956.71 |
| August | 0.00 | 0.00 | 1260.04 | 938.13 |
| September | 0.00 | 0.00 | 1287.88 | 927.93 |
| October | 0.00 | 0.00 | 1368.97 | 1019.24 |
| November | 0.00 | 0.00 | 1457.03 | 1049.81 |
| December | 0.00 | 0.00 | 1548.01 | 1152.53 |
| Annual Sum or Average | 0.00 | 0.00 | 1445.27 | 12669.51 |
| Minimum of Months | 0.00 | 0.00 | 1260.04 | 927.93 |
| Maximum of Months | 0.00 | 0.00 | 1626.98 | 1196.06 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1606.40 | 1196.01 |
| February | 0.00 | 0.00 | 1627.00 | 1094.12 |
| March | 0.00 | 0.00 | 1594.96 | 1187.49 |
| April | 0.00 | 0.00 | 1538.19 | 1108.28 |
| May | 0.00 | 0.00 | 1435.51 | 1068.78 |
| June | 0.00 | 0.00 | 1344.26 | 968.55 |
| July | 0.00 | 0.00 | 1282.98 | 955.21 |
| August | 0.00 | 0.00 | 1260.09 | 938.17 |
| September | 0.00 | 0.00 | 1290.02 | 929.47 |
| October | 0.00 | 0.00 | 1366.67 | 1017.53 |
| November | 0.00 | 0.00 | 1457.06 | 1049.82 |
| December | 0.00 | 0.00 | 1547.94 | 1152.49 |
| Annual Sum or Average | 0.00 | 0.00 | 1444.86 | 12665.92 |
| Minimum of Months | 0.00 | 0.00 | 1260.09 | 929.47 |
| Maximum of Months | 0.00 | 0.00 | 1627.00 | 1196.01 |
Report: HEATING AND COOLING LOADS
For: UNHEATEDBSMT
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 31.56 | 1446.39 |
| February | 29.28 | 1582.41 |
| March | 55.63 | 1255.18 |
| April | 38.57 | 1058.69 |
| May | 87.62 | 138.46 |
| June | 205.51 | 0.12 |
| July | 205.39 | 0.00 |
| August | 206.83 | 0.00 |
| September | 164.16 | 62.32 |
| October | 76.43 | 955.91 |
| November | 42.85 | 1197.73 |
| December | 24.77 | 2178.40 |
| Annual Sum or Average | 1168.59 | 9875.61 |
| Minimum of Months | 24.77 | 0.00 |
| Maximum of Months | 206.83 | 2178.40 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 22.54 | 916.29 |
| February | 17.85 | 1061.07 |
| March | 34.23 | 837.94 |
| April | 20.71 | 701.18 |
| May | 55.98 | 60.56 |
| June | 145.06 | 0.00 |
| July | 155.99 | 0.00 |
| August | 156.81 | 0.00 |
| September | 127.94 | 29.13 |
| October | 54.86 | 606.27 |
| November | 32.00 | 752.75 |
| December | 19.44 | 1481.75 |
| Annual Sum or Average | 843.42 | 6446.93 |
| Minimum of Months | 17.85 | 0.00 |
| Maximum of Months | 156.81 | 1481.75 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 24.86 | 1395.84 |
| February | 25.65 | 1536.23 |
| March | 50.63 | 1172.86 |
| April | 39.26 | 997.35 |
| May | 89.89 | 112.16 |
| June | 213.85 | 0.16 |
| July | 221.64 | 0.00 |
| August | 220.61 | 0.00 |
| September | 169.56 | 54.39 |
| October | 71.07 | 931.89 |
| November | 37.20 | 1173.19 |
| December | 21.01 | 2146.05 |
| Annual Sum or Average | 1185.24 | 9520.13 |
| Minimum of Months | 21.01 | 0.00 |
| Maximum of Months | 221.64 | 2146.05 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 2.59 | 1974.54 |
| February | 2.90 | 2024.16 |
| March | 22.07 | 1397.22 |
| April | 20.82 | 1116.93 |
| May | 74.79 | 139.12 |
| June | 197.58 | 0.03 |
| July | 194.57 | 0.00 |
| August | 176.96 | 0.00 |
| September | 120.36 | 70.66 |
| October | 27.83 | 1063.51 |
| November | 6.11 | 1591.65 |
| December | 2.18 | 2720.67 |
| Annual Sum or Average | 848.77 | 12098.49 |
| Minimum of Months | 2.18 | 0.00 |
| Maximum of Months | 197.58 | 2720.67 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.01 | 1568.17 |
| February | 0.30 | 1604.32 |
| March | 5.63 | 1056.64 |
| April | 6.52 | 782.68 |
| May | 43.98 | 67.90 |
| June | 137.38 | 0.00 |
| July | 145.23 | 0.00 |
| August | 126.73 | 0.00 |
| September | 83.23 | 36.34 |
| October | 8.68 | 711.58 |
| November | 1.34 | 1209.53 |
| December | 0.06 | 2099.76 |
| Annual Sum or Average | 559.07 | 9136.92 |
| Minimum of Months | 0.01 | 0.00 |
| Maximum of Months | 145.23 | 2099.76 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.48 | 2047.08 |
| February | 1.59 | 2028.27 |
| March | 17.21 | 1361.91 |
| April | 21.00 | 1066.16 |
| May | 76.80 | 116.89 |
| June | 205.68 | 0.10 |
| July | 210.50 | 0.00 |
| August | 190.43 | 0.00 |
| September | 124.72 | 62.59 |
| October | 19.03 | 1027.35 |
| November | 3.88 | 1636.03 |
| December | 0.38 | 2749.46 |
| Annual Sum or Average | 871.69 | 12095.84 |
| Minimum of Months | 0.38 | 0.00 |
| Maximum of Months | 210.50 | 2749.46 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 33.99 | 1153.95 |
| February | 32.07 | 1270.57 |
| March | 60.18 | 972.62 |
| April | 43.37 | 798.32 |
| May | 99.31 | 75.15 |
| June | 223.68 | 0.00 |
| July | 224.27 | 0.00 |
| August | 225.64 | 0.00 |
| September | 179.29 | 40.07 |
| October | 82.53 | 743.92 |
| November | 46.42 | 943.42 |
| December | 26.45 | 1763.48 |
| Annual Sum or Average | 1277.20 | 7761.51 |
| Minimum of Months | 26.45 | 0.00 |
| Maximum of Months | 225.64 | 1763.48 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 27.06 | 656.56 |
| February | 22.34 | 777.11 |
| March | 40.09 | 584.51 |
| April | 26.66 | 477.68 |
| May | 69.92 | 27.51 |
| June | 163.81 | 0.00 |
| July | 175.23 | 0.00 |
| August | 176.50 | 0.00 |
| September | 145.55 | 18.87 |
| October | 63.45 | 428.88 |
| November | 37.88 | 531.45 |
| December | 22.65 | 1093.69 |
| Annual Sum or Average | 971.16 | 4596.26 |
| Minimum of Months | 22.34 | 0.00 |
| Maximum of Months | 176.50 | 1093.69 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 27.70 | 1109.28 |
| February | 29.27 | 1230.76 |
| March | 56.40 | 912.12 |
| April | 45.53 | 753.93 |
| May | 103.76 | 59.86 |
| June | 232.73 | 0.00 |
| July | 241.00 | 0.00 |
| August | 240.00 | 0.00 |
| September | 185.60 | 35.40 |
| October | 78.23 | 721.35 |
| November | 41.02 | 919.67 |
| December | 23.04 | 1731.60 |
| Annual Sum or Average | 1304.28 | 7473.97 |
| Minimum of Months | 23.04 | 0.00 |
| Maximum of Months | 241.00 | 1731.60 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 2.81 | 1641.14 |
| February | 3.41 | 1651.40 |
| March | 25.07 | 1106.38 |
| April | 24.43 | 849.21 |
| May | 86.36 | 77.65 |
| June | 216.22 | 0.00 |
| July | 213.80 | 0.00 |
| August | 196.30 | 0.00 |
| September | 135.32 | 45.68 |
| October | 31.67 | 830.66 |
| November | 6.73 | 1285.21 |
| December | 2.26 | 2259.59 |
| Annual Sum or Average | 944.37 | 9746.91 |
| Minimum of Months | 2.26 | 0.00 |
| Maximum of Months | 216.22 | 2259.59 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.14 | 1217.04 |
| February | 0.74 | 1236.44 |
| March | 8.87 | 758.58 |
| April | 10.25 | 531.66 |
| May | 57.63 | 32.42 |
| June | 156.53 | 0.00 |
| July | 164.76 | 0.00 |
| August | 146.92 | 0.00 |
| September | 100.43 | 22.22 |
| October | 12.88 | 504.95 |
| November | 2.44 | 908.77 |
| December | 0.24 | 1631.80 |
| Annual Sum or Average | 661.82 | 6843.88 |
| Minimum of Months | 0.14 | 0.00 |
| Maximum of Months | 164.76 | 1631.80 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.64 | 1694.85 |
| February | 2.29 | 1667.83 |
| March | 21.58 | 1060.19 |
| April | 26.24 | 803.85 |
| May | 90.60 | 64.45 |
| June | 224.90 | 0.00 |
| July | 230.13 | 0.00 |
| August | 210.41 | 0.00 |
| September | 140.92 | 40.05 |
| October | 23.78 | 798.29 |
| November | 4.88 | 1327.65 |
| December | 0.55 | 2286.39 |
| Annual Sum or Average | 976.92 | 9743.53 |
| Minimum of Months | 0.55 | 0.00 |
| Maximum of Months | 230.13 | 2286.39 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.31 | 2381.56 |
| February | 1.33 | 2329.16 |
| March | 19.17 | 1562.60 |
| April | 22.17 | 1213.27 |
| May | 85.14 | 124.91 |
| June | 234.63 | 0.00 |
| July | 241.31 | 0.00 |
| August | 222.75 | 0.00 |
| September | 145.54 | 68.07 |
| October | 21.75 | 1165.85 |
| November | 4.04 | 1890.62 |
| December | 0.23 | 3178.23 |
| Annual Sum or Average | 998.36 | 13914.28 |
| Minimum of Months | 0.23 | 0.00 |
| Maximum of Months | 241.31 | 3178.23 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 15.57 | 1708.18 |
| February | 16.49 | 1839.87 |
| March | 44.70 | 1384.81 |
| April | 34.59 | 1154.05 |
| May | 93.29 | 120.43 |
| June | 238.39 | 0.00 |
| July | 247.70 | 0.00 |
| August | 242.54 | 0.00 |
| September | 179.13 | 60.76 |
| October | 63.16 | 1074.75 |
| November | 27.60 | 1411.56 |
| December | 13.89 | 2574.26 |
| Annual Sum or Average | 1217.04 | 11328.67 |
| Minimum of Months | 13.89 | 0.00 |
| Maximum of Months | 247.70 | 2574.26 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 21.14 | 1759.47 |
| February | 20.49 | 1882.23 |
| March | 49.53 | 1464.36 |
| April | 34.91 | 1216.53 |
| May | 91.80 | 147.93 |
| June | 230.65 | 0.00 |
| July | 232.22 | 0.00 |
| August | 229.33 | 0.00 |
| September | 174.39 | 69.37 |
| October | 69.59 | 1100.32 |
| November | 33.44 | 1440.75 |
| December | 17.45 | 2609.26 |
| Annual Sum or Average | 1204.94 | 11690.22 |
| Minimum of Months | 17.45 | 0.00 |
| Maximum of Months | 232.22 | 2609.26 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.06 | 1893.40 |
| February | 0.51 | 1902.70 |
| March | 9.39 | 1257.74 |
| April | 9.77 | 937.09 |
| May | 55.16 | 83.61 |
| June | 168.26 | 0.00 |
| July | 177.56 | 0.00 |
| August | 161.24 | 0.00 |
| September | 106.95 | 43.11 |
| October | 13.17 | 860.19 |
| November | 2.18 | 1460.90 |
| December | 0.07 | 2509.58 |
| Annual Sum or Average | 704.31 | 10948.31 |
| Minimum of Months | 0.06 | 0.00 |
| Maximum of Months | 177.56 | 2509.58 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 13.97 | 1195.33 |
| February | 11.05 | 1353.16 |
| March | 31.06 | 1054.50 |
| April | 19.27 | 860.63 |
| May | 62.48 | 76.40 |
| June | 171.72 | 0.00 |
| July | 183.71 | 0.00 |
| August | 180.95 | 0.00 |
| September | 140.16 | 36.23 |
| October | 49.67 | 743.04 |
| November | 23.75 | 968.12 |
| December | 13.00 | 1877.99 |
| Annual Sum or Average | 900.79 | 8165.41 |
| Minimum of Months | 11.05 | 0.00 |
| Maximum of Months | 183.71 | 1877.99 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:37:00
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 2.08 | 2332.03 |
| February | 2.73 | 2318.52 |
| March | 24.75 | 1616.26 |
| April | 22.91 | 1274.56 |
| May | 84.03 | 154.43 |
| June | 227.06 | 0.00 |
| July | 226.04 | 0.00 |
| August | 209.77 | 0.00 |
| September | 141.80 | 78.44 |
| October | 30.99 | 1216.44 |
| November | 6.09 | 1843.86 |
| December | 1.49 | 3162.33 |
| Annual Sum or Average | 979.74 | 13996.86 |
| Minimum of Months | 1.49 | 0.00 |
| Maximum of Months | 227.06 | 3162.33 |