Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:41
Tabular Output Report in Format: HTML
Building: US+MF+CZ5B+elecres+slab+IECC_2006
Environment: ANNUAL ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695
Simulation Timestamp: 2024-06-27 17:41:15
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Values gathered over 8760.00 hours| Total Energy [kBtu] | Energy Per Total Building Area [kBtu/ft2] | Energy Per Conditioned Building Area [kBtu/ft2] | |
| Total Site Energy | 963147.93 | 30.86 | 44.57 |
| Net Site Energy | 963147.93 | 30.86 | 44.57 |
| Total Source Energy | 3050289.51 | 97.73 | 141.15 |
| Net Source Energy | 3050289.51 | 97.73 | 141.15 |
| Site=>Source Conversion Factor | |
| Electricity | 3.167 |
| Natural Gas | 1.084 |
| District Cooling | 1.056 |
| District Heating | 3.613 |
| Steam | 1.200 |
| Gasoline | 1.050 |
| Diesel | 1.050 |
| Coal | 1.050 |
| Fuel Oil No 1 | 1.050 |
| Fuel Oil No 2 | 1.050 |
| Propane | 1.050 |
| Other Fuel 1 | 1.000 |
| Other Fuel 2 | 1.000 |
| Area [ft2] | |
| Total Building Area | 31210.83 |
| Net Conditioned Building Area | 21609.96 |
| Unconditioned Building Area | 9600.87 |
| Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | 298308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 43135.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 60500.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 36699.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 202396.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 963147.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Subcategory | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | General | 298308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 43135.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 60500.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 10546.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 41096.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 5385.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 42687.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 30929.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 160227.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 10631.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 17305.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 19394.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 | |
| Water Heater | 202396.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Space Type | Electricity [kBtu] | Natural Gas [kBtu] | Gasoline [kBtu] | Diesel [kBtu] | Coal [kBtu] | Fuel Oil No 1 [kBtu] | Fuel Oil No 2 [kBtu] | Propane [kBtu] | Other Fuel 1 [kBtu] | Other Fuel 2 [kBtu] | District Cooling [kBtu] | District Heating [kBtu] | Water [gal] | |
| Heating | Unassigned | 298308.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | Unassigned | 43135.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | GENERAL | 60500.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Unassigned | 20603.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | GENERAL | 301503.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Unassigned | 36699.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | Unassigned | 202396.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 370400.12 |
| Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 3.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 26.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
| Other | 13.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 44.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.14 |
| Electricity Intensity [kBtu/ft2] | Natural Gas Intensity [kBtu/ft2] | Gasoline Intensity [kBtu/ft2] | Diesel Intensity [kBtu/ft2] | Coal Intensity [kBtu/ft2] | Fuel Oil No 1 Intensity [kBtu/ft2] | Fuel Oil No 2 Intensity [kBtu/ft2] | Propane Intensity [kBtu/ft2] | Other Fuel 1 Intensity [kBtu/ft2] | Other Fuel 2 Intensity [kBtu/ft2] | District Cooling Intensity [kBtu/ft2] | District Heating Intensity [kBtu/ft2] | Water Intensity [gal/ft2] | |
| Lighting | 2.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| HVAC | 18.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
| Other | 9.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total | 30.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 11.87 |
| Electricity [kBtu] | Percent Electricity [%] | |
| Fuel-Fired Power Generation | 0.000 | 0.00 |
| High Temperature Geothermal* | 0.000 | 0.00 |
| Photovoltaic Power | 0.000 | 0.00 |
| Wind Power | 0.000 | 0.00 |
| Power Conversion | 0.000 | 0.00 |
| Net Decrease in On-Site Storage | 0.000 | 0.00 |
| Total On-Site Electric Sources | 0.000 | 0.00 |
| Electricity Coming From Utility | 963147.934 | 100.00 |
| Surplus Electricity Going To Utility | 0.000 | 0.00 |
| Net Electricity From Utility | 963147.934 | 100.00 |
| Total On-Site and Utility Electric Sources | 963147.934 | 100.00 |
| Total Electricity End Uses | 963147.934 | 100.00 |
| Heat [kBtu] | Percent Heat [%] | |
| Water-Side Heat Recovery | 0.00 | |
| Air to Air Heat Recovery for Cooling | 0.00 | |
| Air to Air Heat Recovery for Heating | 0.00 | |
| High-Temperature Geothermal* | 0.00 | |
| Solar Water Thermal | 0.00 | |
| Solar Air Thermal | 0.00 | |
| Total On-Site Thermal Sources | 0.00 |
| Water [gal] | Percent Water [%] | |
| Rainwater Collection | 0.00 | 0.00 |
| Condensate Collection | 0.00 | 0.00 |
| Groundwater Well | 0.00 | 0.00 |
| Total On Site Water Sources | 0.00 | 0.00 |
| - | - | - |
| Initial Storage | 0.00 | 0.00 |
| Final Storage | 0.00 | 0.00 |
| Change in Storage | 0.00 | 0.00 |
| - | - | - |
| Water Supplied by Utility | 370400.12 | 100.00 |
| - | - | - |
| Total On Site, Change in Storage, and Utility Water Sources | 370400.12 | 100.00 |
| Total Water End Uses | 370400.12 | 100.00 |
| Degrees [deltaF] | |
| Tolerance for Zone Heating Setpoint Not Met Time | 0.36 |
| Tolerance for Zone Cooling Setpoint Not Met Time | 0.36 |
| Facility [Hours] | |
| Time Setpoint Not Met During Occupied Heating | 0.00 |
| Time Setpoint Not Met During Occupied Cooling | 1.50 |
| Time Not Comfortable Based on Simple ASHRAE 55-2004 | 908.00 |
Table of Contents
TopFANSPLIT
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |COILLOADS
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |WATER HEATER: LOADS
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |HEATING AND COOLING LOADS
| BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
General| Value | |
| Program Version and Build | EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 17:41 |
| RunPeriod | ANNUAL |
| Weather File | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
| Latitude [deg] | 39.72 |
| Longitude [deg] | -104.8 |
| Elevation [ft] | 5663.01 |
| Time Zone | -7.0 |
| North Axis Angle [deg] | 0.00 |
| Rotation for Appendix G [deg] | 0.00 |
| Hours Simulated [hrs] | 8760.00 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
| Above Ground Wall Area [ft2] | 16177.97 | 6115.58 | 1973.41 | 6115.58 | 1973.41 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
| Above Ground Window-Wall Ratio [%] | 13.15 | 8.69 | 26.94 | 8.69 | 26.94 |
| Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
| Gross Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
| Above Ground Wall Area [ft2] | 15296.60 | 6115.58 | 1532.73 | 6115.58 | 1532.73 |
| Window Opening Area [ft2] | 2126.74 | 531.68 | 531.68 | 531.68 | 531.68 |
| Gross Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
| Above Ground Window-Wall Ratio [%] | 13.90 | 8.69 | 34.69 | 8.69 | 34.69 |
| Total | |
| Gross Roof Area [ft2] | 8451.30 |
| Skylight Area [ft2] | 0.00 |
| Skylight-Roof Ratio [%] | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [ft3] | Multipliers | Above Ground Gross Wall Area [ft2] | Underground Gross Wall Area [ft2] | Window Glass Area [ft2] | Opening Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| BREEZEWAY | 1798.16 | No | Yes | 30553.25 | 1.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 10207.81 | 1.00 | 934.97 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| ATTIC | 7802.71 | No | Yes | 52795.56 | 1.00 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 679.51 | 0.00 | 59.08 | 59.08 | 0.9113 | 600.28 | 2.9092 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 10207.71 | 1.00 | 934.96 | 0.00 | 147.69 | 147.69 | 0.9113 | 600.28 | 2.9092 |
| Total | 31210.83 | 267088.19 | 16177.97 | 0.00 | 2126.74 | 2126.74 | 0.6310 | 866.97 | 2.0143 | |||
| Conditioned Total | 21609.96 | 183739.38 | 15296.60 | 0.00 | 2126.74 | 2126.74 | 0.9113 | 600.28 | 2.9092 | |||
| Unconditioned Total | 9600.87 | 83348.81 | 881.37 | 0.00 | 0.00 | 0.00 | 0.0000 | 0.0000 | ||||
| Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Area [ft2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | Tags | |
| BREEZEWAY | 1798.16 | No | Yes | 1.00 | BREEZEWAY | GENERAL | BREEZEWAY | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.9113 | 600.28 | 2.9092 | |
| ATTIC | 7802.71 | No | Yes | 1.00 | ATTIC | GENERAL | ATTIC | 0.0000 | 0.00 | 0.0000 | |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | Yes | Yes | 1.00 | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.9113 | 600.28 | 2.9092 | |
| Total | 31210.83 | 0.6310 | 866.97 | 2.0143 | |||||||
| Conditioned Total | 21609.96 | 0.9113 | 600.28 | 2.9092 | |||||||
| Unconditioned Total | 9600.87 | 0.0000 | 0.00 | 0.0000 | |||||||
| Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
| Total Area [ft2] | Conditioned Area [ft2] | Unconditioned Area [ft2] | Not Part of Total Area [ft2] | Lighting [Btu/h-ft2] | People [ft2 per person] | Plug and Process [Btu/h-ft2] | |
| GENERAL | 31210.83 | 21609.96 | 9600.87 | 0.00 | 0.6310 | 866.97 | 2.0143 |
| Total | 31210.83 | 21609.96 | 9600.87 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
End Uses| Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Time of Peak | 05-JAN-08:09 | - | - | - | - | - | - | - | - | - | - | - | 14-JAN-09:00 |
| Heating | 191.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 33.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 8.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 199.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total End Uses | 437.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 |
| Subcategory | Electricity [kBtuh] | Natural Gas [kBtuh] | Gasoline [kBtuh] | Diesel [kBtuh] | Coal [kBtuh] | Fuel Oil No 1 [kBtuh] | Fuel Oil No 2 [kBtuh] | Propane [kBtuh] | Other Fuel 1 [kBtuh] | Other Fuel 2 [kBtuh] | District Cooling [kBtuh] | Steam [kBtuh] | Water [gal/min] | |
| Heating | General | 191.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | General | 3.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | Exterior-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Interior Equipment | dishwasher | 1.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| refrigerator | 4.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| clotheswasher | 1.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_dryer | 5.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_range | 3.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| electric_mels | 16.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| IECC_adj | 1.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Ventilation | 1.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| General | 6.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.34 | |
| Water Heater | 199.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
| Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Values gathered over 8760.00 hours| Source Electricity [kBtu] | Source Natural Gas [kBtu] | Source Gasoline [kBtu] | Source Diesel [kBtu] | Source Coal [kBtu] | Source Fuel Oil No 1 [kBtu] | Source Fuel Oil No 2 [kBtu] | Source Propane [kBtu] | Source Other Fuel 1 [kBtu] | Source Other Fuel 2 [kBtu] | Source District Cooling [kBtu] | Source District Heating [kBtu] | |
| Heating | 944742.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 136608.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 191605.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 65251.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 954861.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 116227.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 640991.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 3050289.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 43.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 6.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 8.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 3.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 44.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 5.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 29.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 141.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Source Electricity [kBtu/ft2] | Source Natural Gas [kBtu/ft2] | Source Gasoline [kBtu/ft2] | Source Diesel [kBtu/ft2] | Source Coal [kBtu/ft2] | Source Fuel Oil No 1 [kBtu/ft2] | Source Fuel Oil No 2 [kBtu/ft2] | Source Propane [kBtu/ft2] | Source Other Fuel 1 [kBtu/ft2] | Source Other Fuel 2 [kBtu/ft2] | Source District Cooling [kBtu/ft2] | Source District Heating [kBtu/ft2] | |
| Heating | 30.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling | 4.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting | 6.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting | 2.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment | 30.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans | 3.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems | 20.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Source Energy End Use Components | 97.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
AirTerminal:SingleDuct:ConstantVolume:NoReheat| Design Size Maximum Air Flow Rate [ft3/min] | |
| ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | 243.38 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 |
| ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 |
| ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | 243.38 |
| ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 |
| ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 |
| ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 |
| ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 |
| ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | 395.90 |
| ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | 427.94 |
| ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | 631.51 |
| ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | 341.33 |
| ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | 335.29 |
| ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | 628.62 |
| Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | Sum of Air Terminal Maximum Flow Rates [ft3/min] | Adjusted Heating Design Air Flow Rate [ft3/min] | Adjusted Cooling Design Air Flow Rate [ft3/min] | Adjusted Main Design Air Flow Rate [ft3/min] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 | 490.90 | 490.90 | 490.90 | 490.90 | 490.90 | 1.00 | 1.00 | 490.90 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 243.38 | 243.38 | 243.38 | 243.38 | 243.38 | 243.38 | 1.00 | 1.00 | 243.38 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 | 325.39 | 325.39 | 325.39 | 325.39 | 325.39 | 1.00 | 1.00 | 325.39 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 | 470.61 | 470.61 | 470.61 | 470.61 | 470.61 | 1.00 | 1.00 | 470.61 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 243.38 | 243.38 | 243.38 | 243.38 | 243.38 | 243.38 | 1.00 | 1.00 | 243.38 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 | 303.49 | 303.49 | 303.49 | 303.49 | 303.49 | 1.00 | 1.00 | 303.49 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 | 563.96 | 563.96 | 563.96 | 563.96 | 563.96 | 1.00 | 1.00 | 563.96 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 | 268.32 | 268.32 | 268.32 | 268.32 | 268.32 | 1.00 | 1.00 | 268.32 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 | 388.90 | 388.90 | 388.90 | 388.90 | 388.90 | 1.00 | 1.00 | 388.90 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 | 542.27 | 542.27 | 542.27 | 542.27 | 542.27 | 1.00 | 1.00 | 542.27 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 | 261.32 | 261.32 | 261.32 | 261.32 | 261.32 | 1.00 | 1.00 | 261.32 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 | 365.23 | 365.23 | 365.23 | 365.23 | 365.23 | 1.00 | 1.00 | 365.23 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.51 | 631.51 | 631.51 | 631.51 | 631.51 | 631.51 | 1.00 | 1.00 | 631.51 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.29 | 335.29 | 335.29 | 335.29 | 335.29 | 335.29 | 1.00 | 1.00 | 335.29 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.94 | 427.94 | 427.94 | 427.94 | 427.94 | 427.94 | 1.00 | 1.00 | 427.94 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.62 | 628.62 | 628.62 | 628.62 | 628.62 | 628.62 | 1.00 | 1.00 | 628.62 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.33 | 341.33 | 341.33 | 341.33 | 341.33 | 341.33 | 1.00 | 1.00 | 341.33 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.90 | 395.90 | 395.90 | 395.90 | 395.90 | 395.90 | 1.00 | 1.00 | 395.90 |
| Design Size Rated Air Flow Rate [ft3/min] | Design Size Gross Rated Total Cooling Capacity [ton] | Design Size Gross Rated Sensible Heat Ratio | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 | 1.19 | 0.800033 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 243.38 | 0.659298 | 0.772518 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 | 0.788647 | 0.800993 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 | 1.14 | 0.800658 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 243.38 | 0.590883 | 0.800423 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 | 0.718033 | 0.800221 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 | 1.34 | 0.800953 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 | 0.640989 | 0.800906 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 | 0.938361 | 0.800511 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 | 1.29 | 0.800675 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 | 0.615601 | 0.800723 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 | 0.867247 | 0.800975 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 631.51 | 1.50 | 0.800353 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 335.29 | 0.797148 | 0.800546 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 427.94 | 1.09 | 0.798418 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 628.62 | 1.49 | 0.800516 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 341.33 | 0.799778 | 0.800580 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 395.90 | 0.951716 | 0.800769 |
| Supply Air Flow Rate [ft3/min] | Supply Air Flow Rate During Heating Operation [ft3/min] | Supply Air Flow Rate During Cooling Operation [ft3/min] | Nominal Heating Capacity [Btu/h] | Nominal Cooling Capacity [ton] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
| ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 | 490.90 | 490.90 | 16193.88 | 1.19 | 1.00 |
| ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | 243.38 | 243.38 | 243.38 | 13552.33 | 0.659298 | 1.00 |
| ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 | 325.39 | 325.39 | 16196.52 | 0.788647 | 1.00 |
| ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 | 470.61 | 470.61 | 16196.37 | 1.14 | 1.00 |
| ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | 243.38 | 243.38 | 243.38 | 13552.14 | 0.590883 | 1.00 |
| ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 | 303.49 | 303.49 | 16193.70 | 0.718033 | 1.00 |
| ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 | 563.96 | 563.96 | 13729.11 | 1.34 | 1.00 |
| ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 | 268.32 | 268.32 | 10867.32 | 0.640989 | 1.00 |
| ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 | 388.90 | 388.90 | 13731.83 | 0.938361 | 1.00 |
| ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 | 542.27 | 542.27 | 13730.97 | 1.29 | 1.00 |
| ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 | 261.32 | 261.32 | 10866.47 | 0.615601 | 1.00 |
| ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 | 365.23 | 365.23 | 13728.27 | 0.867247 | 1.00 |
| ACANDF_UNIT1_FRONTROW_TOPFLOOR | 631.51 | 631.51 | 631.51 | 18320.37 | 1.50 | 1.00 |
| ACANDF_UNIT2_FRONTROW_TOPFLOOR | 335.29 | 335.29 | 335.29 | 15441.16 | 0.797148 | 1.00 |
| ACANDF_UNIT3_FRONTROW_TOPFLOOR | 427.94 | 427.94 | 427.94 | 18322.35 | 1.09 | 1.00 |
| ACANDF_UNIT1_BACKROW_TOPFLOOR | 628.62 | 628.62 | 628.62 | 18320.18 | 1.49 | 1.00 |
| ACANDF_UNIT2_BACKROW_TOPFLOOR | 341.33 | 341.33 | 341.33 | 15439.02 | 0.799778 | 1.00 |
| ACANDF_UNIT3_BACKROW_TOPFLOOR | 395.90 | 395.90 | 395.90 | 18318.23 | 0.951716 | 1.00 |
| Design Size Maximum Flow Rate [ft3/min] | |
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | 243.38 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | 243.38 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | 631.51 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | 335.29 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | 427.94 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | 628.62 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | 341.33 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | 395.90 |
| Design Size Nominal Capacity [Btu/h] | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 18622.96 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 15585.18 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 18626.00 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 18625.83 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 15584.96 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 18622.76 |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 15788.48 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 12497.42 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 15791.60 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 15790.62 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 12496.44 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 15787.50 |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | 21068.42 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | 17757.34 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | 21070.70 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | 21068.21 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | 17754.87 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | 21065.96 |
| Maximum Loop Flow Rate [ft3/min] | Plant Loop Volume [ft3] | |
| DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT1_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT2_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| DHW LOOP_UNIT3_BACKROW_TOPFLOOR | 1.04 | 2.09 |
| Design Flow Rate [ft3/min] | |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | 1.04 |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | 1.04 |
| Maximum Heater Capacity [Btu/h] | Use Side Design Flow Rate [ft3/min] | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 15354.00 | 1.04 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces| Possible Shadow Receivers | |
| OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | |
| OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | |
| BREEZEWAY_MIDDLEFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | |
| BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | |
| Possible Shadow Receivers | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Time Not Meeting the Adaptive Comfort Models during Occupied Hours| ASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Version| Version ID | |
| 1 | 23.1 |
| #TimeSteps | Minutes per TimeStep {minutes} | |
| 1 | 6 | 10 |
| Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
| 1 | 1 | 20 | 2 | 8 |
| Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
| 1 | Yes | Yes | No | Yes | Yes | No |
| Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
| 1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
| Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
| 1 | 0.200 | 0.200 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 | 64.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 30.67 | 34.30 | 41.36 | 48.06 | 60.73 | 67.39 | 69.22 | 65.84 | 58.05 | 48.31 | 38.71 | 32.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 | 55.40 |
| Jan{F} | Feb{F} | Mar{F} | Apr{F} | May{F} | Jun{F} | Jul{F} | Aug{F} | Sep{F} | Oct{F} | Nov{F} | Dec{F} | |
| 1 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 | 60.80 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Normal | Daylighting {dimensionless} | |
| 1 | 1.000 | 1.000 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
| 1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
| Wind Sensor Height Above Ground {ft} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Sensor Height Above Ground {ft} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
| 1 | 32.810 | 0.140 | 885.870 | 4.921 | 1.586 | 9.750E-003 |
| Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {ft} | Standard Pressure at Elevation {psi} | Standard RhoAir at Elevation | |
| 1 | Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 | 39.72 | -104.75 | -7.00 | 5663.01 | 12. | 0.9774 |
| Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{F} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} | Fixed Default Water Mains Temperature{F} | |
| 1 | Correlation | NA | 49.91 | 42.66 | NA |
| Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
| 1 | US+MF+CZ5B+elecres+slab+IECC_2006 | 0.000 | Suburbs | 4.00000E-002 | 0.40000 | FullExterior | 25 | 6 |
| Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
| 1 | TARP |
| Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
| 1 | DOE-2 |
| Value {Anisotropic} | |
| 1 | Anisotropic |
| Algorithm {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
Space Heat Balance Sizing |
Space Heat Balance Simulation |
|
| 1 | ThirdOrderBackwardDifference | No | No |
| Simulation {Yes/No} | Carbon Dioxide Concentration | |
| 1 | No | N/A |
| Simulation {Yes/No} | Generic Contaminant Concentration | |
| 1 | No | N/A |
| Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
| 1 | No | N/A | N/A | N/A |
| Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
| 1 | RegulaFalsi |
| Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {ft} | Air Temperature Gradient Coefficient {F/ft} | |
| 1 | 0.220 | 1213.970 | 0.003566 |
| Material Name | ThermalResistance {m2-K/w} | Roughness | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | Absorptance:Thermal | Absorptance:Solar | Absorptance:Visible | |
| 1 | SHEATHING_CONSOL_LAYER | 0.1351 | Rough | 0.0417 | 9.402E-002 | 42.764 | 0.280 | 0.9000 | 0.7000 | 0.7000 |
| 2 | CEIL_CONSOL_LAYER | 6.1981 | Rough | 1.2550 | 6.172E-002 | 2.618 | 0.185 | 0.9000 | 0.7000 | 0.7000 |
| 3 | FLOOR_CONSOL_LAYER | 1.9554E-005 | Rough | 0.0008 | 12.990 | 3.438 | 0.219 | 0.9000 | 0.7000 | 0.7000 |
| 4 | BSMTWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 5 | CRAWLWALL_CONSOL_LAYER | 2.3423E-005 | Rough | 0.0008 | 10.844 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 6 | WALL_CONSOL_LAYER | 2.2607 | Rough | 0.4584 | 6.179E-002 | 7.541 | 0.248 | 0.9000 | 0.7000 | 0.7000 |
| 7 | VERY HIGH REFLECTIVITY SURFACE | 2.1097E-006 | Smooth | 0.0016 | 237.000 | 168.680 | 0.216 | 0.9000 | 5.0000E-002 | 5.0000E-002 |
| 8 | GYPSUMBOARD-5/16IN | 5.0054E-002 | Rough | 0.0260 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 9 | COPPERPIPE | 4.7506E-005 | MediumRough | 0.0625 | 401.000 | 140.026 | 0.200 | 0.9000 | 0.6500 | 0.6500 |
| 10 | F08 METAL SURFACE | 1.7668E-005 | Smooth | 0.0026 | 45.280 | 488.437 | 0.119 | 0.9000 | 0.7000 | 0.7000 |
| 11 | CONCRETE_4IN | 7.7356E-002 | Rough | 0.3330 | 1.312 | 140.014 | 0.111 | 0.9000 | 0.7000 | 0.7000 |
| 12 | ASPHALT_SHINGLE | 7.7448E-002 | MediumRough | 0.0208 | 8.186E-002 | 70.000 | 0.300 | 0.9000 | 0.7500 | 0.7000 |
| 13 | WOOD_SHINGLE | 0.1115 | MediumSmooth | 0.0417 | 0.114 | 26.600 | 0.390 | 0.9000 | 0.7000 | 0.7000 |
| 14 | SLATE_SHINGLE | 8.8061E-003 | MediumSmooth | 0.0417 | 1.442 | 100.000 | 0.300 | 0.9000 | 0.7000 | 0.7000 |
| 15 | CEMENT_STUCCO | 2.6422E-002 | MediumSmooth | 0.0625 | 0.721 | 116.464 | 0.210 | 0.9000 | 0.7000 | 0.7000 |
| 16 | SYN_STUCCO | 3.5237E-002 | MediumSmooth | 0.0100 | 8.650E-002 | 24.971 | 0.210 | 0.7000 | 0.7000 | 0.7000 |
| 17 | DRYWALL_1/2IN | 7.9331E-002 | MediumSmooth | 0.0417 | 0.160 | 50.000 | 0.260 | 0.9000 | 0.7000 | 0.7000 |
| 18 | OSB_5/8IN | 0.1365 | MediumSmooth | 0.0521 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 19 | OSB_7/16IN | 9.5550E-002 | MediumSmooth | 0.0365 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 20 | BLOWN_R30 | 5.1614 | MediumRough | 0.6975 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 21 | BLOWN_R30_TOP | 2.8489 | MediumRough | 0.3849 | 4.119E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 22 | PLYWOOD_3/4IN | 0.1650 | Rough | 0.0625 | 0.115 | 34.003 | 0.161 | 0.9000 | 0.7000 | 0.7000 |
| 23 | BATT_R19 | 7.3089 | MediumRough | 0.0833 | 3.475E-003 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 24 | LUMBER_2X4 | 0.7709 | Rough | 0.2920 | 0.115 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 25 | CARPET_N_PAD | 0.4224 | MediumSmooth | 0.0833 | 6.013E-002 | 2.000 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 26 | BATT_R13 | 2.2936 | MediumRough | 0.2917 | 3.876E-002 | 0.600 | 0.200 | 0.9000 | 0.7000 | 0.7000 |
| 27 | OSB_1/2IN | 0.1092 | MediumSmooth | 0.0417 | 0.116 | 34.000 | 0.290 | 0.9000 | 0.7000 | 0.7000 |
| 28 | SOIL_12IN | 0.1761 | Rough | 1.0000 | 1.731 | 115.011 | 0.056 | 0.9000 | 0.7000 | 0.7000 |
| 29 | DOOR_CONST | 0.5031 | Smooth | 0.1189 | 7.201E-002 | 32.003 | 0.183 | 0.9000 | 0.7000 | 0.7000 |
| 30 | GYP_BOARD_1/2IN | 8.0130E-002 | Rough | 0.0417 | 0.159 | 39.954 | 0.270 | 0.9000 | 0.4000 | 0.1000 |
| 31 | STD WOOD 6INCH | 1.2500 | MediumSmooth | 0.4921 | 0.120 | 33.711 | 0.289 | 0.9000 | 0.7000 | 0.7000 |
| 32 | PIPE INSULATION | 0.3830 | VeryRough | 0.0417 | 3.317E-002 | 5.681 | 0.200 | 0.9000 | 0.5000 | 0.5000 |
| 33 | MANF_WALL_AIRGAP | 0.1200 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 34 | BLDG_PAPER_FELT | 1.0567E-002 | Smooth | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 35 | R_HIGH | 177.0000 | MediumRough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.9000 | 0.7000 | 0.7000 |
| 36 | CLEAR ACRYLIC PLASTIC | 3.3333E-003 | VerySmooth | 0.0098 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 37 | DIFFUSING ACRYLIC PLASTIC | 2.4444E-003 | VerySmooth | 0.0072 | 0.900 | 0.000 | 0.000 | 0.9000 | 0.0000 | 0.0000 |
| 38 | INT_BLIND | 0.0000 | Rough | 0.0000 | 0.000 | 0.000 | 0.000 | 0.0000 | 0.0000 | 0.0000 |
| 39 | GLASS | 0.3300 | VerySmooth | 0.1230 | 0.114 | 0.000 | 0.000 | 0.8400 | 0.0000 | 0.0000 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
| 1 | LowerLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
| Name | Combined convective/radiative film coefficient {Btu/h-ft2-F} | User selected Constant Temperature {F} | Coefficient modifying the constant temperature term | Coefficient modifying the external dry bulb temperature term | Coefficient modifying the ground temperature term | Coefficient modifying the wind speed term {s/m} | Coefficient modifying the zone air temperature term | Constant Temperature Schedule Name | Sinusoidal Variation | Period of Sinusoidal Variation | Previous Other Side Temperature Coefficient | Minimum Other Side Temperature {F} | Maximum Other Side Temperature {F} | |
| 1 | SURFPROPOTHSDCOEFSLABAVERAGE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABAVERAGESURFACETEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 2 | SURFPROPOTHSDCOEFSLABPERIMETER | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABPERIMETERTEMP | NO | 24.000 | 0.000 | N/A | N/A |
| 3 | SURFPROPOTHSDCOEFSLABCORE | N/A | N/A | 1.000 | 0.000 | 0.000 | 0.000 | 0.000 | SCHEDULEOSCSLABCORETEMP | NO | 24.000 | 0.000 | N/A | N/A |
| Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{F} |
Surface Convection Coefficient Lower Limit {Btu/h-ft2-F} |
Surface Convection Coefficient Upper Limit {Btu/h-ft2-F} |
|
| 1 | CTF - ConductionTransferFunction | 392. | 0.02 | 176.1 |
| Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
| 1 | 0 | 0 | 60 |
| Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
| 1 | 20 | 171 | 48 |
| Zone Name | North Axis {deg} | Origin X-Coordinate {ft} | Origin Y-Coordinate {ft} | Origin Z-Coordinate {ft} | Centroid X-Coordinate {ft} | Centroid Y-Coordinate {ft} | Centroid Z-Coordinate {ft} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {ft} | Maximum X {ft} | Minimum Y {ft} | Maximum Y {ft} | Minimum Z {ft} | Maximum Z {ft} | Ceiling Height {ft} | Volume {ft3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {ft2} | Exterior Gross Wall Area {ft2} | Exterior Net Wall Area {ft2} | Exterior Window Area {ft2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
| 1 | BREEZEWAY | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 32.55 | 13.26 | 1 | 1 | 1 | 0.00 | 119.89 | 30.05 | 35.04 | 0.49 | 25.99 | 17.00 | 30553.07 | TARP | DOE-2 | 1798.18 | 0.00 | 0.00 | 0.00 | 4 | 0 | 0 | Yes |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 4.76 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 4.76 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 4.76 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 0.49 | 8.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 13.26 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 13.26 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 13.26 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 8.99 | 17.49 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 14 | ATTIC | 0.0 | -134.9 | 51.61 | 0.00 | 59.94 | 32.55 | 29.56 | 1 | 1 | 1 | 0.00 | 119.89 | 0.00 | 65.10 | 25.99 | 39.54 | 6.76 | 52795.39 | TARP | DOE-2 | 7802.66 | 881.33 | 881.33 | 0.00 | 11 | 0 | 0 | Yes |
| 15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 50.07 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 99.91 | 15.03 | 21.75 | 1 | 1 | 1 | 79.93 | 119.89 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 15.03 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| 18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 50.07 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 59.94 | 15.03 | 21.75 | 1 | 1 | 1 | 39.96 | 79.93 | 0.00 | 30.05 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 679.48 | 599.39 | 59.10 | 6 | 2 | 2 | Yes |
| 20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0 | 0.00 | 0.00 | 0.00 | 19.98 | 50.07 | 21.75 | 1 | 1 | 1 | 0.00 | 39.96 | 35.04 | 65.10 | 17.49 | 25.99 | 8.50 | 10207.79 | TARP | DOE-2 | 1200.51 | 934.94 | 766.25 | 147.70 | 6 | 3 | 4 | Yes |
| Zone Name | Floor Area {ft2} | # Occupants | Area per Occupant {ft2/person} | Occupant per Area {person/ft2} | Interior Lighting {Btu/h-ft2} | Electric Load {Btu/h-ft2} | Gas Load {Btu/h-ft2} | Other Load {Btu/h-ft2} | Hot Water Eq {Btu/h-ft2} | Steam Equipment {Btu/h-ft2} | Sum Loads per Area {Btu/h-ft2} | Outdoor Controlled Baseboard Heat | |
| 1 | BREEZEWAY | 1798.18 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 14 | ATTIC | 7802.66 | 0.0 | N/A | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | No |
| 15 | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 18 | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| 20 | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 600.276 | 0.002 | 0.911 | 2.909 | 0.000 | 0.000 | 0.000 | 0.000 | 3.821 | No |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Number of People {} | People/Floor Area {person/ft2} | Floor Area per person {ft2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | |
| 1 | PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 2 | PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 3 | PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 4 | PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 5 | PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 6 | PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 7 | PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 8 | PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 9 | PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 10 | PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 11 | PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 12 | PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 13 | PEOPLE_UNIT1_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 14 | PEOPLE_UNIT2_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 15 | PEOPLE_UNIT3_FRONTROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 16 | PEOPLE_UNIT1_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 17 | PEOPLE_UNIT2_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| 18 | PEOPLE_UNIT3_BACKROW_TOPFLOOR | OCCUPANCY | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 2.0 | 0.002 | 600.276 | 0.000 | 1.000 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 2 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Lighting Level {Btu/h} | Lights/Floor Area {Btu/h-ft2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {Btu/h} | Nominal Maximum Lighting Level {Btu/h} | |
| 1 | LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 2 | LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 3 | LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 4 | LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 5 | LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 6 | LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 7 | LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 8 | LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 9 | LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 10 | LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 11 | LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 12 | LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 13 | LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 14 | LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 15 | LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 16 | LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 17 | LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 18 | LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 19 | LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 20 | LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 21 | LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 22 | LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 23 | LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 24 | LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 25 | LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 26 | LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 27 | LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 28 | LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 29 | LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 30 | LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 31 | LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 32 | LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 33 | LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 34 | LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| 35 | LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 875.250 | 0.729 | 128.261 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 60.174 | 875.250 |
| 36 | LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | INTERIORLIGHTINGHE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 218.812 | 0.182 | 32.065 | 0.000 | 0.600 | 0.200 | 0.200 | 0.000 | General | 15.044 | 218.812 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Equipment Level {Btu/h} | Equipment/Floor Area {Btu/h-ft2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {Btu/h} | Nominal Maximum Equipment Level {Btu/h} | |
| 1 | DISHWASHER1_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 2 | REFRIGERATOR1_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 3 | CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 4 | ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 5 | ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 6 | TELEVISION1_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 7 | ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 8 | IECC_ADJ1_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 9 | DISHWASHER2_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 10 | REFRIGERATOR2_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 11 | CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 12 | ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 13 | ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 14 | TELEVISION2_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 15 | ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 16 | IECC_ADJ2_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 17 | DISHWASHER3_FRONTROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 18 | REFRIGERATOR3_FRONTROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 19 | CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 20 | ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 21 | ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 22 | TELEVISION3_FRONTROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 23 | ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 24 | IECC_ADJ3_FRONTROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 25 | DISHWASHER1_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 26 | REFRIGERATOR1_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 27 | CLOTHESWASHER1_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 28 | ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 29 | ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 30 | TELEVISION1_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 31 | ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 32 | IECC_ADJ1_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 33 | DISHWASHER2_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 34 | REFRIGERATOR2_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 35 | CLOTHESWASHER2_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 36 | ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 37 | ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 38 | TELEVISION2_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 39 | ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 40 | IECC_ADJ2_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 41 | DISHWASHER3_BACKROW_BOTTOMFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 42 | REFRIGERATOR3_BACKROW_BOTTOMFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 43 | CLOTHESWASHER3_BACKROW_BOTTOMFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 44 | ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 45 | ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 46 | TELEVISION3_BACKROW_BOTTOMFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 47 | ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 48 | IECC_ADJ3_BACKROW_BOTTOMFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 49 | DISHWASHER1_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 50 | REFRIGERATOR1_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 51 | CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 52 | ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 53 | ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 54 | TELEVISION1_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 55 | ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 56 | IECC_ADJ1_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 57 | DISHWASHER2_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 58 | REFRIGERATOR2_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 59 | CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 60 | ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 61 | ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 62 | TELEVISION2_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 63 | ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 64 | IECC_ADJ2_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 65 | DISHWASHER3_FRONTROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 66 | REFRIGERATOR3_FRONTROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 67 | CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 68 | ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 69 | ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 70 | TELEVISION3_FRONTROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 71 | ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 72 | IECC_ADJ3_FRONTROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 73 | DISHWASHER1_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 74 | REFRIGERATOR1_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 75 | CLOTHESWASHER1_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 76 | ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 77 | ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 78 | TELEVISION1_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 79 | ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 80 | IECC_ADJ1_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 81 | DISHWASHER2_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 82 | REFRIGERATOR2_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 83 | CLOTHESWASHER2_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 84 | ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 85 | ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 86 | TELEVISION2_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 87 | ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 88 | IECC_ADJ2_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 89 | DISHWASHER3_BACKROW_MIDDLEFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 90 | REFRIGERATOR3_BACKROW_MIDDLEFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 91 | CLOTHESWASHER3_BACKROW_MIDDLEFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 92 | ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 93 | ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 94 | TELEVISION3_BACKROW_MIDDLEFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 95 | ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 96 | IECC_ADJ3_BACKROW_MIDDLEFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 97 | DISHWASHER1_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 98 | REFRIGERATOR1_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 99 | CLOTHESWASHER1_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 100 | ELECTRIC_DRYER1_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 101 | ELECTRIC_RANGE1_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 102 | TELEVISION1_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 103 | ELECTRIC_MELS1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 104 | IECC_ADJ1_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 105 | DISHWASHER2_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 106 | REFRIGERATOR2_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 107 | CLOTHESWASHER2_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 108 | ELECTRIC_DRYER2_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 109 | ELECTRIC_RANGE2_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 110 | TELEVISION2_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 111 | ELECTRIC_MELS2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 112 | IECC_ADJ2_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 113 | DISHWASHER3_FRONTROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 114 | REFRIGERATOR3_FRONTROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 115 | CLOTHESWASHER3_FRONTROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 116 | ELECTRIC_DRYER3_FRONTROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 117 | ELECTRIC_RANGE3_FRONTROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 118 | TELEVISION3_FRONTROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 119 | ELECTRIC_MELS3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 120 | IECC_ADJ3_FRONTROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 121 | DISHWASHER1_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 122 | REFRIGERATOR1_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 123 | CLOTHESWASHER1_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 124 | ELECTRIC_DRYER1_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 125 | ELECTRIC_RANGE1_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 126 | TELEVISION1_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 127 | ELECTRIC_MELS1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 128 | IECC_ADJ1_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 129 | DISHWASHER2_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 130 | REFRIGERATOR2_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 131 | CLOTHESWASHER2_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 132 | ELECTRIC_DRYER2_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 133 | ELECTRIC_RANGE2_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 134 | TELEVISION2_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 135 | ELECTRIC_MELS2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 136 | IECC_ADJ2_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| 137 | DISHWASHER3_BACKROW_TOPFLOOR | DISHWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 186.821 | 0.156 | 27.377 | 0.150 | 0.600 | 0.250 | 0.000 | dishwasher | 0.000 | 186.821 |
| 138 | REFRIGERATOR3_BACKROW_TOPFLOOR | REFRIGERATOR | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 310.690 | 0.259 | 45.529 | 0.000 | 1.000 | 0.000 | 0.000 | refrigerator | 227.232 | 310.690 |
| 139 | CLOTHESWASHER3_BACKROW_TOPFLOOR | CLOTHESWASHER_EQUIP_SCH | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 80.974 | 0.068 | 11.866 | 0.000 | 0.800 | 0.200 | 0.000 | clotheswasher | 0.000 | 80.974 |
| 140 | ELECTRIC_DRYER3_BACKROW_TOPFLOOR | CLOTHESDRYER | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 605.958 | 0.505 | 88.798 | 5.000E-002 | 0.150 | 0.800 | 0.000 | electric_dryer | 0.000 | 605.958 |
| 141 | ELECTRIC_RANGE3_BACKROW_TOPFLOOR | COOKINGRANGE | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 705.353 | 0.588 | 103.363 | 0.300 | 0.400 | 0.300 | 0.000 | electric_range | 16.610 | 705.353 |
| 142 | TELEVISION3_BACKROW_TOPFLOOR | INTERIORLIGHTING | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 1.000 | 0.000 | 0.000 | television | 0.000 | 0.000 |
| 143 | ELECTRIC_MELS3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 1503.167 | 1.252 | 220.277 | 6.000E-002 | 0.690 | 0.250 | 0.000 | electric_mels | 777.172 | 1503.167 |
| 144 | IECC_ADJ3_BACKROW_TOPFLOOR | MISCPLUGLOAD | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 99.736 | 0.083 | 14.616 | 6.244E-002 | 0.412 | 0.251 | 0.275 | IECC_adj | 51.566 | 99.736 |
| Construction Name | Index | #Layers | #CTFs | Time Step {Hours} | ThermalConductance {Btu/h-ft2-F} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
| 1 | EXTERIOR WALL | 1 | 5 | 11 | 0.167 | 0.0676 | 0.700 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 2 | CEILING-FLOOR-LAYER | 3 | 1 | 5 | 0.167 | 0.228 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 3 | EXTERIOR FLOOR | 4 | 3 | 4 | 0.167 | 0.300 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 4 | INTERIOR CEILING | 6 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | Rough |
| 5 | ATTIC FLOOR | 7 | 2 | 10 | 0.167 | 0.0281 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 6 | INTERIORWALL | 9 | 3 | 5 | 0.167 | 0.597 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| 7 | EXTERIOR ROOF | 11 | 2 | 4 | 0.167 | 0.943 | 0.900 | 0.900 | 0.750 | 0.700 | MediumRough |
| 8 | EXTERIOR DOOR | 14 | 1 | 5 | 0.167 | 0.350 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
| 9 | GABLE_END | 16 | 5 | 6 | 0.167 | 0.428 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
| Material Name | Thickness {ft} | Conductivity {w/m-K} | Density {lb/ft3} | Specific Heat {Btu/lbm-R} | ThermalResistance {m2-K/w} | |
| 1 | SYN_STUCCO | 0.0098 | 0.086 | 24.971 | 0.210 | 0.3524E-01 |
| 2 | SHEATHING_CONSOL_LAYER | 0.0417 | 0.094 | 42.764 | 0.280 | 0.1351 |
| 3 | OSB_7/16IN | 0.0364 | 0.116 | 34.000 | 0.290 | 0.9555E-01 |
| 4 | WALL_CONSOL_LAYER | 0.4584 | 0.062 | 7.541 | 0.248 | 2.261 |
| 5 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 6 | LUMBER_2X4 | 0.2920 | 0.115 | 32.003 | 0.183 | 0.7709 |
| 7 | FLOOR_CONSOL_LAYER | 0.0010 | 12.990 | 3.438 | 0.219 | 0.1955E-04 |
| 8 | PLYWOOD_3/4IN | 0.0627 | 0.115 | 34.003 | 0.161 | 0.1650 |
| 9 | CARPET_N_PAD | 0.0833 | 0.060 | 2.000 | 0.200 | 0.4224 |
| 10 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
| 11 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 12 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 13 | CEIL_CONSOL_LAYER | 1.2550 | 0.062 | 2.618 | 0.185 | 6.198 |
| 14 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 15 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 16 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| 17 | ASPHALT_SHINGLE | 0.0207 | 0.082 | 70.000 | 0.300 | 0.7745E-01 |
| 18 | OSB_1/2IN | 0.0417 | 0.116 | 34.000 | 0.290 | 0.1092 |
| 19 | DOOR_CONST | 0.1188 | 0.072 | 32.003 | 0.183 | 0.5031 |
| 20 | CEMENT_STUCCO | 0.0627 | 0.721 | 116.464 | 0.210 | 0.2642E-01 |
| 21 | BLDG_PAPER_FELT | 0.0000 | 0.000 | 0.000 | 0.000 | 0.1057E-01 |
| 22 | OSB_5/8IN | 0.0522 | 0.116 | 34.000 | 0.290 | 0.1365 |
| 23 | DRYWALL_1/2IN | 0.0417 | 0.160 | 50.000 | 0.260 | 0.7933E-01 |
| Material Name | ThermalResistance {m2-K/w} | |
| 1 | AIR_4_IN_VERT | 0.1585 |
| 2 | 3/4IN_AIR_SPACE | 8.5130E-002 |
| 3 | 3/4IN_REFLECTIVE_AIR_SPACE | 0.2466 |
| 4 | AIR_4_IN_VERT | 0.1585 |
| Time | Outside | Cross | Inside | Flux (except final one) | |
| 1 | 11 | -0.34101926E-11 | -0.22660516E-14 | -0.36581558E-11 | 0.16728159E-15 |
| 2 | 10 | 0.15746244E-06 | 0.26117201E-13 | 0.37441303E-06 | -0.26565902E-11 |
| 3 | 9 | -0.13979360E-03 | 0.28489944E-10 | -0.22155512E-03 | 0.11859456E-06 |
| 4 | 8 | 0.70301011E-02 | 0.18070797E-07 | 0.11303620E-01 | -0.67587366E-04 |
| 5 | 7 | -0.13302090 | 0.17034159E-05 | -0.22730680 | 0.23466961E-02 |
| 6 | 6 | 1.2909310 | 0.37978735E-04 | 2.3248636 | -0.33737981E-01 |
| 7 | 5 | -7.2229067 | 0.25362208E-03 | -13.350394 | 0.25636671 |
| 8 | 4 | 24.415372 | 0.55187385E-03 | 44.930686 | -1.1177284 |
| 9 | 3 | -50.177464 | 0.37819951E-03 | -89.626047 | 2.8539798 |
| 10 | 2 | 60.756437 | 0.67524003E-04 | 103.62079 | -4.1716530 |
| 11 | 1 | -39.537176 | 0.17896284E-05 | -63.895203 | 3.2071249 |
| 12 | 0 | 10.602231 | 0.51349130E-09 | 16.212826 | |
| 13 | 5 | -0.10726087E-01 | 0.44268190E-05 | -0.10726087E-01 | 0.97389233E-03 |
| 14 | 4 | 0.31857203 | 0.80150166E-03 | 0.31857203 | -0.30727185E-01 |
| 15 | 3 | -2.8372473 | 0.12516450E-01 | -2.8372473 | 0.30041224 |
| 16 | 2 | 9.6667056 | 0.33176537E-01 | 9.6667056 | -1.1584571 |
| 17 | 1 | -13.322214 | 0.15207483E-01 | -13.322214 | 1.8397512 |
| 18 | 0 | 6.2472388 | 0.62260140E-03 | 6.2472388 | |
| 19 | 4 | 0.29631924E-13 | -0.40788276E-14 | 0.60443234E-14 | -0.77798347E-16 |
| 20 | 3 | -0.11254351E-04 | 0.79669069E-06 | -0.23145793E-05 | 0.39394231E-13 |
| 21 | 2 | 0.49771861 | 0.29587917E-01 | 0.78801895E-01 | -0.76025120E-05 |
| 22 | 1 | -8.3915550 | 0.80192706 | -1.1535996 | 0.21114735 |
| 23 | 0 | 9.2367617 | 0.51139848 | 2.4177143 | |
| 24 | 10 | 0.25332408E-17 | -0.22101509E-14 | 0.15157692E-08 | 0.28211904E-17 |
| 25 | 9 | -0.31506112E-08 | -0.26974675E-14 | -0.81843868E-03 | 0.20118786E-08 |
| 26 | 8 | 0.42861811E-03 | 0.11354105E-09 | 0.39097097E-01 | -0.27370296E-03 |
| 27 | 7 | -0.11368907E-01 | 0.51842634E-07 | -0.64553953 | 0.74324363E-02 |
| 28 | 6 | 0.12484615 | 0.25047115E-05 | 5.3130581 | -0.83937451E-01 |
| 29 | 5 | -0.73775399 | 0.27964547E-04 | -24.889648 | 0.51283867 |
| 30 | 4 | 2.5553417 | 0.92755650E-04 | 70.144414 | -1.8477174 |
| 31 | 3 | -5.2989438 | 0.96002462E-04 | -120.51707 | 4.0111012 |
| 32 | 2 | 6.4233118 | 0.27752742E-04 | 123.06129 | -5.1209931 |
| 33 | 1 | -4.1707712 | 0.15163054E-05 | -68.409714 | 3.5199891 |
| 34 | 0 | 1.1151582 | 0.34288690E-08 | 15.905180 | |
| 35 | 10 | 0.15157692E-08 | -0.22101509E-14 | 0.25332408E-17 | 0.28211904E-17 |
| 36 | 9 | -0.81843868E-03 | -0.26974675E-14 | -0.31506112E-08 | 0.20118786E-08 |
| 37 | 8 | 0.39097097E-01 | 0.11354105E-09 | 0.42861811E-03 | -0.27370296E-03 |
| 38 | 7 | -0.64553953 | 0.51842634E-07 | -0.11368907E-01 | 0.74324363E-02 |
| 39 | 6 | 5.3130581 | 0.25047115E-05 | 0.12484615 | -0.83937451E-01 |
| 40 | 5 | -24.889648 | 0.27964547E-04 | -0.73775399 | 0.51283867 |
| 41 | 4 | 70.144414 | 0.92755650E-04 | 2.5553417 | -1.8477174 |
| 42 | 3 | -120.51707 | 0.96002462E-04 | -5.2989438 | 4.0111012 |
| 43 | 2 | 123.06129 | 0.27752742E-04 | 6.4233118 | -5.1209931 |
| 44 | 1 | -68.409714 | 0.15163054E-05 | -4.1707712 | 3.5199891 |
| 45 | 0 | 15.905180 | 0.34288690E-08 | 1.1151582 | |
| 46 | 5 | -0.27590492E-07 | 0.65241430E-08 | -0.27590492E-07 | 0.17331255E-13 |
| 47 | 4 | 0.68608714E-03 | 0.11323974E-03 | 0.68608714E-03 | -0.15705033E-07 |
| 48 | 3 | -0.21538511 | 0.37821720E-01 | -0.21538511 | 0.25667047E-03 |
| 49 | 2 | 5.0173519 | 0.62258424 | 5.0173519 | -0.50236511E-01 |
| 50 | 1 | -19.904252 | 0.86481321 | -19.904252 | 0.58144210 |
| 51 | 0 | 16.688993 | 0.62060609E-01 | 16.688993 | |
| 52 | 4 | 0.75441920E-10 | 0.23883683E-10 | 0.47514224E-10 | -0.69373194E-20 |
| 53 | 3 | -0.33730907E-03 | 0.89366797E-04 | -0.22574866E-03 | 0.77828620E-10 |
| 54 | 2 | 0.58624422 | 0.18542418 | 0.49024360 | -0.17301269E-03 |
| 55 | 1 | -11.299243 | 2.8799011 | -8.6239668 | 0.15905732 |
| 56 | 0 | 15.219762 | 1.4410112 | 12.640375 | |
| 57 | 5 | -0.24423608E-08 | 0.10315694E-08 | -0.24423608E-08 | 0.46347327E-11 |
| 58 | 4 | 0.46481418E-04 | 0.19988510E-04 | 0.46481418E-04 | -0.22728163E-06 |
| 59 | 3 | -0.31887091E-01 | 0.95525843E-02 | -0.31887091E-01 | 0.49135354E-03 |
| 60 | 2 | 1.3495466 | 0.25081638 | 1.3495466 | -0.51058024E-01 |
| 61 | 1 | -7.0688408 | 0.57876498 | -7.0688408 | 0.58136590 |
| 62 | 0 | 6.6836766 | 0.93387740E-01 | 6.6836766 | |
| 63 | 6 | 0.97988530E-11 | 0.43917118E-12 | 0.24496810E-11 | -0.34892153E-15 |
| 64 | 5 | -0.75005310E-05 | 0.16499726E-06 | -0.28271466E-05 | 0.19166609E-11 |
| 65 | 4 | 0.32354224E-01 | 0.66949565E-03 | 0.10283773E-01 | -0.11111676E-05 |
| 66 | 3 | -1.8201547 | 0.67148336E-01 | -0.62076152 | 0.38788549E-02 |
| 67 | 2 | 21.173821 | 0.53241617 | 7.5279938 | -0.97325542E-01 |
| 68 | 1 | -64.420211 | 0.46601667 | -21.697519 | 0.64629334 |
| 69 | 0 | 46.121323 | 0.20873329E-01 | 15.867130 |
| Construction Name | Index | #Layers | Roughness | Conductance {Btu/h-ft2-F} | Conductance (Before Adjusted) {Btu/h-ft2-F} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
| 1 | EXTERIOR WINDOW | 12 | 1 | VerySmooth | 0.350 | 0.350 | 1.000 | 0.335 | ||
| 2 | INTERIOR WINDOW | 13 | 1 | VerySmooth | 0.350 | 0.350 | 1.000 | 0.335 | ||
| 3 | WINDOW_W_BLINDS | 18 | 2 | VerySmooth | 0.350 | 0.350 | 1.000 | 0.309 | ||
| 4 | TDD DOME | 22 | 1 | VerySmooth | 1.071 | 1.071 | 1.000 | 0.929 | ||
| 5 | TDD DIFFUSER | 23 | 1 | VerySmooth | 1.077 | 1.077 | 1.000 | 0.906 |
| Material Name | Optical Data Type | Spectral Data Set Name | Thickness {ft} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
| 1 | GLASS | SpectralAverage | 0.12304 | 0.24698 | 0.54587 | 0.54587 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
| 2 | GLASS | SpectralAverage | 0.12304 | 0.24698 | 0.54587 | 0.54587 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
| 3 | GLASS | SpectralAverage | 0.12304 | 0.24698 | 0.54587 | 0.54587 | 0.88000 | 0.11900 | 0.11900 | 0.00000 | 0.84000 | 0.84000 | 0.11365 | 1.00000 | No | |
| 4 | CLEAR ACRYLIC PLASTIC | SpectralAverage | 0.00984 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.92000 | 5.00000E-002 | 5.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No | |
| 5 | DIFFUSING ACRYLIC PLASTIC | SpectralAverage | 0.00722 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.90000 | 8.00000E-002 | 8.00000E-002 | 0.00000 | 0.90000 | 0.90000 | 0.90000 | 1.00000 | No |
| Material Name | Slat Width {ft} | Slat Separation {ft} | Slat Thickness {ft} | Slat Angle {deg} | Slat Beam Solar Transmittance | Slat Beam Solar Front Reflectance | Blind To Glass Distance {ft} | |
| 1 | INT_BLIND | 0.0820 | 0.0615 | 0.0033 | 45.000 | 0.000 | 0.500 | 0.164 |
| Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
| 1 | PolygonClipping | Periodic | 20 | 15000. | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
| Type | Name | Volume {ft3} | Maximum Capacity {Btu/h} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
| 1 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 2 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 3 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 4 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 5 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 6 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 7 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 8 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 9 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 10 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 11 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 12 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 13 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 14 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 15 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 16 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 17 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| 18 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | 6.9509 | 15354.0 | 1.069 | 0.9773 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
| 1 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 2 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 3 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 4 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 5 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 6 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 7 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 8 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 9 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 10 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 11 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 12 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 13 | LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 14 | LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 15 | LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 16 | LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 17 | LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 18 | LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| 19 | ATTICVENT | ALWAYS_AVAIL | ATTIC | 7802.66 | 0.0 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| Name | Schedule Name | Zone Name | Zone Floor Area {ft2} | # Zone Occupants | Design Volume Flow Rate {ft3/min} | Volume Flow Rate/Floor Area {ft3/min-ft2} | Volume Flow Rate/person Area {ft3/min-person} | ACH - Air Changes per Hour | Fan Type {Exhaust;Intake;Natural} | Fan Pressure Rise {psi} | Fan Efficiency {} | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | Minimum Indoor Temperature{F}/Schedule | Maximum Indoor Temperature{F}/Schedule | Delta Temperature{F}/Schedule | Minimum Outdoor Temperature{F}/Schedule | Maximum Outdoor Temperature{F}/Schedule | Maximum WindSpeed{ft/min} | |
| 1 | VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 2 | VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 3 | VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 4 | VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 5 | VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 6 | VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 7 | VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 8 | VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 9 | VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 10 | VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 11 | VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 12 | VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 13 | VENTILATION_UNIT1_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 14 | VENTILATION_UNIT2_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 15 | VENTILATION_UNIT3_FRONTROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 16 | VENTILATION_UNIT1_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 17 | VENTILATION_UNIT2_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| 18 | VENTILATION_UNIT3_BACKROW_TOPFLOOR | ALWAYS_AVAIL | LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.51 | 2.0 | 45.000 | 0.037 | 22.500 | 0.265 | Exhaust | 0.000 | 0.6 | 1.000 | 0.000 | 0.000 | 0.000 | -148.0 | 212.00 | -148.0 | -148.0 | 212.00 | 7874.40 |
| Simple | |
| 1 | Simple |
| Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
| 1 | BREEZEWAY | Mixing/Well-Stirred |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Mixing/Well-Stirred |
| 8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Mixing/Well-Stirred |
| 14 | ATTIC | Mixing/Well-Stirred |
| 15 | LIVING_UNIT3_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 18 | LIVING_UNIT2_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| 19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Mixing/Well-Stirred |
| 20 | LIVING_UNIT1_BACKROW_TOPFLOOR | Mixing/Well-Stirred |
| No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
| 1 | NoMultizoneOrDistribution |
| Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
| 1 | 1.000 | 1.000 | 1.000 | 1.000 |
| Value | |
| 1 | 6 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Sizing Factor ID | Value | |
| 1 | Global | 1.0000 |
| Zone Name | Load Type | Calc Des Load {Btu/h} | User Des Load {Btu/h} | Calc Des Air Flow Rate {ft3/min} | User Des Air Flow Rate {ft3/min} | Design Day Name | Date/Time of Peak | Temperature at Peak {F} | Humidity Ratio at Peak {lbWater/lbDryAir} | Floor Area {ft2} | # Occupants | Calc Outdoor Air Flow Rate {ft3/min} | Calc DOAS Heat Addition Rate {Btu/h} | |
| 1 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | 9359.89513 | 9359.89513 | 490.91095 | 490.91095 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 88.40241 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | 13536.17276 | 13536.17276 | 303.47454 | 303.47454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | 4343.48255 | 4343.48255 | 227.79658 | 227.79658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 93.02000 | 0.00548 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 4 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | 10855.52540 | 10855.52540 | 243.38980 | 243.38980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 5 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | 6204.04154 | 6204.04154 | 325.38131 | 325.38131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 86.22680 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 6 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | 13538.85343 | 13538.85343 | 303.53810 | 303.53810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 7 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | 8973.00917 | 8973.00917 | 470.61435 | 470.61435 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 87.95840 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 8 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Heating | 13538.70337 | 13538.70337 | 303.53810 | 303.53810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 9 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | 4082.29661 | 4082.29661 | 214.11014 | 214.11014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 83.96240 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 10 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Heating | 10855.32993 | 10855.32993 | 243.38980 | 243.38980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 11 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | 5786.43711 | 5786.43711 | 303.49572 | 303.49572 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 83.56280 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 12 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Heating | 13535.99155 | 13535.99155 | 303.47454 | 303.47454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 13 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | 10752.55943 | 10752.55943 | 563.96179 | 563.96179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 87.51439 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 14 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | 11034.74203 | 11034.74203 | 247.41522 | 247.41522 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 15 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | 5115.84051 | 5115.84051 | 268.32624 | 268.32624 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 83.96240 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 16 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | 8130.58998 | 8130.58998 | 182.31163 | 182.31163 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 17 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | 7414.97850 | 7414.97850 | 388.89826 | 388.89826 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 86.89280 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 18 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | 11037.50002 | 11037.50002 | 247.47878 | 247.47878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 19 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | 10339.14009 | 10339.14009 | 542.26688 | 542.26688 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 87.07041 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 20 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Heating | 11036.63385 | 11036.63385 | 247.45760 | 247.45760 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 21 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | 4982.42657 | 4982.42657 | 261.33471 | 261.33471 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 82.63040 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 22 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Heating | 8129.72757 | 8129.72757 | 182.29235 | 182.29235 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 23 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | 6963.64497 | 6963.64497 | 365.23300 | 365.23300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 84.89480 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 24 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Heating | 11033.88600 | 11033.88600 | 247.41522 | 247.41522 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 25 | LIVING_UNIT3_BACKROW_TOPFLOOR | Cooling | 7548.48378 | 7548.48378 | 395.91097 | 395.91097 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 86.62640 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 26 | LIVING_UNIT3_BACKROW_TOPFLOOR | Heating | 15691.92608 | 15691.92608 | 351.80080 | 351.80080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 27 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Cooling | 8159.51279 | 8159.51279 | 427.94486 | 427.94486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 93.02000 | 0.00548 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 28 | LIVING_UNIT3_FRONTROW_TOPFLOOR | Heating | 15696.10398 | 15696.10398 | 351.90674 | 351.90674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 29 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Cooling | 12040.70919 | 12040.70919 | 631.50416 | 631.50416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 87.51439 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 30 | LIVING_UNIT1_FRONTROW_TOPFLOOR | Heating | 15694.09373 | 15694.09373 | 351.86436 | 351.86436 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 31 | LIVING_UNIT2_BACKROW_TOPFLOOR | Cooling | 6507.81989 | 6507.81989 | 341.33470 | 341.33470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 83.29640 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 32 | LIVING_UNIT2_BACKROW_TOPFLOOR | Heating | 12770.09697 | 12770.09697 | 286.31352 | 286.31352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 33 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Cooling | 6392.75947 | 6392.75947 | 335.29657 | 335.29657 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 84.62840 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 34 | LIVING_UNIT2_FRONTROW_TOPFLOOR | Heating | 12772.27536 | 12772.27536 | 286.35590 | 286.35590 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 35 | LIVING_UNIT1_BACKROW_TOPFLOOR | Cooling | 11985.63334 | 11985.63334 | 628.62280 | 628.62280 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 87.07041 | 0.00547 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| 36 | LIVING_UNIT1_BACKROW_TOPFLOOR | Heating | 15693.90822 | 15693.90822 | 351.84318 | 351.84318 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | -0.2200 | 0.00096 | 1200.55323 | 2.00000 | 44.99491 | 0.00000 |
| System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [ft3/min] | User Des Air Flow Rate [ft3/min] | Design Day Name | Date/Time of Peak | |
| 1 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 2861.04 | 490.91095 | 490.91095 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 2 | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4746.15 | 303.47454 | 303.47454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 3 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1464.42 | 227.79658 | 227.79658 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 4 | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 3971.96 | 243.38980 | 243.38980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 5 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Cooling | Sensible | 1923.55 | 325.38131 | 325.38131 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 6 | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Heating | Sensible | 4746.93 | 303.53810 | 303.53810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 7 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 2744.06 | 470.61435 | 470.61435 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 8 | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4746.89 | 303.53810 | 303.53810 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 9 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1283.96 | 214.11014 | 214.11014 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 10 | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Heating | Sensible | 3971.91 | 243.38980 | 243.38980 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 11 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Cooling | Sensible | 1771.95 | 303.49572 | 303.49572 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 12 | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Heating | Sensible | 4746.10 | 303.47454 | 303.47454 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 13 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 3253.35 | 563.96179 | 563.96179 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 14 | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4023.77 | 247.41522 | 247.41522 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 15 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 1582.74 | 268.32624 | 268.32624 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 16 | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 3185.03 | 182.31163 | 182.31163 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 17 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Cooling | Sensible | 2281.32 | 388.89826 | 388.89826 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 18 | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Heating | Sensible | 4024.57 | 247.47878 | 247.47878 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 19 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 3128.69 | 542.26688 | 542.26688 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 20 | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4024.32 | 247.45760 | 247.45760 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 21 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 1528.73 | 261.33471 | 261.33471 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 22 | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Heating | Sensible | 3184.78 | 182.29235 | 182.29235 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 23 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Cooling | Sensible | 2127.70 | 365.23300 | 365.23300 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 24 | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Heating | Sensible | 4023.52 | 247.41522 | 247.41522 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 25 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Cooling | Sensible | 3625.72 | 631.50416 | 631.50416 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 26 | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Heating | Sensible | 5369.39 | 351.86436 | 351.86436 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 27 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Cooling | Sensible | 1959.58 | 335.29657 | 335.29657 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 28 | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Heating | Sensible | 4525.55 | 286.35590 | 286.35590 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 29 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Cooling | Sensible | 2567.55 | 427.94486 | 427.94486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 30 | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Heating | Sensible | 5369.97 | 351.90674 | 351.90674 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 31 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Cooling | Sensible | 3604.65 | 628.62280 | 628.62280 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 32 | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Heating | Sensible | 5369.34 | 351.84318 | 351.84318 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 33 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Cooling | Sensible | 1977.41 | 341.33470 | 341.33470 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 34 | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Heating | Sensible | 4524.92 | 286.31352 | 286.31352 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| 35 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Cooling | Sensible | 2316.83 | 395.91097 | 395.91097 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
| 36 | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Heating | Sensible | 5368.77 | 351.80080 | 351.80080 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| Component Type | Component Name | Input Field Description | Value | |
| 1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 490.91095 |
| 2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 243.38980 |
| 3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 325.38131 |
| 4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 470.61435 |
| 5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 243.38980 |
| 6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 303.49572 |
| 7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 563.96179 |
| 8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 268.32624 |
| 9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 388.89826 |
| 10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 542.26688 |
| 11 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 261.33471 |
| 12 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 365.23300 |
| 13 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 395.91097 |
| 14 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 427.94486 |
| 15 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 631.50416 |
| 16 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 341.33470 |
| 17 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 335.29657 |
| 18 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Air Flow Rate [ft3/min] | 628.62280 |
| 19 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 490.91095 |
| 20 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 490.91095 |
| 21 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 490.91095 |
| 22 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 490.91095 |
| 23 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 490.91095 |
| 24 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 490.91095 |
| 25 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 26 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 27 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 243.38980 |
| 28 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 243.38980 |
| 29 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 243.38980 |
| 30 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 243.38980 |
| 31 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 243.38980 |
| 32 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 243.38980 |
| 33 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 34 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 35 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 325.38131 |
| 36 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 325.38131 |
| 37 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 325.38131 |
| 38 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 325.38131 |
| 39 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 325.38131 |
| 40 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 325.38131 |
| 41 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 42 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 43 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 470.61435 |
| 44 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 470.61435 |
| 45 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 470.61435 |
| 46 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 470.61435 |
| 47 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 470.61435 |
| 48 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 470.61435 |
| 49 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 50 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 51 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 243.38980 |
| 52 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 243.38980 |
| 53 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 243.38980 |
| 54 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 243.38980 |
| 55 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 243.38980 |
| 56 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 243.38980 |
| 57 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 58 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 59 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 303.49572 |
| 60 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 303.49572 |
| 61 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 303.49572 |
| 62 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 303.49572 |
| 63 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 303.49572 |
| 64 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 303.49572 |
| 65 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 66 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 67 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 563.96179 |
| 68 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 563.96179 |
| 69 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 563.96179 |
| 70 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 563.96179 |
| 71 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 563.96179 |
| 72 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 563.96179 |
| 73 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 74 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 75 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 268.32624 |
| 76 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 268.32624 |
| 77 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 268.32624 |
| 78 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 268.32624 |
| 79 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 268.32624 |
| 80 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 268.32624 |
| 81 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 82 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 83 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 388.89826 |
| 84 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 388.89826 |
| 85 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 388.89826 |
| 86 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 388.89826 |
| 87 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 388.89826 |
| 88 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 388.89826 |
| 89 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 90 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 91 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 542.26688 |
| 92 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 542.26688 |
| 93 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 542.26688 |
| 94 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 542.26688 |
| 95 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 542.26688 |
| 96 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 542.26688 |
| 97 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 98 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 99 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 261.33471 |
| 100 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 261.33471 |
| 101 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 261.33471 |
| 102 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 261.33471 |
| 103 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 261.33471 |
| 104 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 261.33471 |
| 105 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 106 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 107 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 365.23300 |
| 108 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 365.23300 |
| 109 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 365.23300 |
| 110 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 365.23300 |
| 111 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 365.23300 |
| 112 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 365.23300 |
| 113 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 114 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 115 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 631.50416 |
| 116 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 631.50416 |
| 117 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 631.50416 |
| 118 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 631.50416 |
| 119 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 631.50416 |
| 120 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 631.50416 |
| 121 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 122 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 123 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 335.29657 |
| 124 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 335.29657 |
| 125 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 335.29657 |
| 126 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 335.29657 |
| 127 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 335.29657 |
| 128 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 335.29657 |
| 129 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 130 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 131 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 427.94486 |
| 132 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 427.94486 |
| 133 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 427.94486 |
| 134 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 427.94486 |
| 135 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 427.94486 |
| 136 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 427.94486 |
| 137 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 138 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 139 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 628.62280 |
| 140 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 628.62280 |
| 141 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 628.62280 |
| 142 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 628.62280 |
| 143 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 628.62280 |
| 144 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 628.62280 |
| 145 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 146 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 147 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 341.33470 |
| 148 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 341.33470 |
| 149 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 341.33470 |
| 150 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 341.33470 |
| 151 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 341.33470 |
| 152 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 341.33470 |
| 153 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 154 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 155 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] | 395.91097 |
| 156 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] | 395.91097 |
| 157 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Sum of Air Terminal Maximum Flow Rates [ft3/min] | 395.91097 |
| 158 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Heating Design Air Flow Rate [ft3/min] | 395.91097 |
| 159 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Cooling Design Air Flow Rate [ft3/min] | 395.91097 |
| 160 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Adjusted Main Design Air Flow Rate [ft3/min] | 395.91097 |
| 161 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | User Heating Air Flow Ratio [] | 1.00000 |
| 162 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Calculated Heating Air Flow Ratio [] | 1.00000 |
| 163 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 490.91095 |
| 164 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 243.38980 |
| 165 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 325.38131 |
| 166 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 470.61435 |
| 167 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 243.38980 |
| 168 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | Design Supply Air Flow Rate [ft3/min] | 303.49572 |
| 169 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 563.96179 |
| 170 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 268.32624 |
| 171 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 388.89826 |
| 172 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 542.26688 |
| 173 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 261.33471 |
| 174 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | Design Supply Air Flow Rate [ft3/min] | 365.23300 |
| 175 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 631.50416 |
| 176 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 335.29657 |
| 177 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 427.94486 |
| 178 | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 628.62280 |
| 179 | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 341.33470 |
| 180 | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | Design Supply Air Flow Rate [ft3/min] | 395.91097 |
| 181 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 490.91095 |
| 182 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.18615 |
| 183 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80003 |
| 184 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 490.91095 |
| 185 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 490.91095 |
| 186 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 490.91095 |
| 187 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 16193.87878 |
| 188 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.18615 |
| 189 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 190 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 490.91095 |
| 191 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 18622.96060 |
| 192 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 243.38980 |
| 193 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.65930 |
| 194 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.77252 |
| 195 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 243.38980 |
| 196 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 243.38980 |
| 197 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 243.38980 |
| 198 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 13552.33322 |
| 199 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.65930 |
| 200 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 201 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 243.38980 |
| 202 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 15585.18320 |
| 203 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 325.38131 |
| 204 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.78865 |
| 205 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80099 |
| 206 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 325.38131 |
| 207 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 325.38131 |
| 208 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 325.38131 |
| 209 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 16196.52038 |
| 210 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.78865 |
| 211 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 212 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 325.38131 |
| 213 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 18625.99844 |
| 214 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 470.61435 |
| 215 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.13502 |
| 216 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80066 |
| 217 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 470.61435 |
| 218 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 470.61435 |
| 219 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 470.61435 |
| 220 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 16196.37251 |
| 221 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 1.13502 |
| 222 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 223 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 470.61435 |
| 224 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 18625.82839 |
| 225 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 243.38980 |
| 226 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.59088 |
| 227 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80042 |
| 228 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 243.38980 |
| 229 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 243.38980 |
| 230 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 243.38980 |
| 231 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 13552.14058 |
| 232 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.59088 |
| 233 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 234 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 243.38980 |
| 235 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 15584.96166 |
| 236 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 303.49572 |
| 237 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.71803 |
| 238 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80022 |
| 239 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate [ft3/min] | 303.49572 |
| 240 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 303.49572 |
| 241 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 303.49572 |
| 242 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Heating Capacity [Btu/h] | 16193.70023 |
| 243 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Nominal Cooling Capacity [ton] | 0.71803 |
| 244 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_BOTTOMFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 245 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Maximum Flow Rate [ft3/min] | 303.49572 |
| 246 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Design Size Nominal Capacity [Btu/h] | 18622.75527 |
| 247 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 563.96179 |
| 248 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.34311 |
| 249 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80095 |
| 250 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 563.96179 |
| 251 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 563.96179 |
| 252 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 563.96179 |
| 253 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 13729.10877 |
| 254 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.34311 |
| 255 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 256 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 563.96179 |
| 257 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15788.47507 |
| 258 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 268.32624 |
| 259 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.64099 |
| 260 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80091 |
| 261 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 268.32624 |
| 262 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 268.32624 |
| 263 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 268.32624 |
| 264 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 10867.31840 |
| 265 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.64099 |
| 266 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 267 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 268.32624 |
| 268 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 12497.41614 |
| 269 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 388.89826 |
| 270 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.93836 |
| 271 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80051 |
| 272 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 388.89826 |
| 273 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 388.89826 |
| 274 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 388.89826 |
| 275 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 13731.82656 |
| 276 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.93836 |
| 277 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 278 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 388.89826 |
| 279 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15791.60053 |
| 280 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 542.26688 |
| 281 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.28876 |
| 282 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80068 |
| 283 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 542.26688 |
| 284 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 542.26688 |
| 285 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 542.26688 |
| 286 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 13730.97302 |
| 287 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 1.28876 |
| 288 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 289 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 542.26688 |
| 290 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15790.61897 |
| 291 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 261.33471 |
| 292 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.61560 |
| 293 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80072 |
| 294 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 261.33471 |
| 295 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 261.33471 |
| 296 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 261.33471 |
| 297 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 10866.46854 |
| 298 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.61560 |
| 299 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 300 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 261.33471 |
| 301 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 12496.43881 |
| 302 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 365.23300 |
| 303 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.86725 |
| 304 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80097 |
| 305 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate [ft3/min] | 365.23300 |
| 306 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 365.23300 |
| 307 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 365.23300 |
| 308 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Heating Capacity [Btu/h] | 13728.26522 |
| 309 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Nominal Cooling Capacity [ton] | 0.86725 |
| 310 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_MIDDLEFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 311 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Maximum Flow Rate [ft3/min] | 365.23300 |
| 312 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Design Size Nominal Capacity [Btu/h] | 15787.50497 |
| 313 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 631.50416 |
| 314 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.49788 |
| 315 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80035 |
| 316 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 631.50416 |
| 317 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 631.50416 |
| 318 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 631.50416 |
| 319 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 18320.36523 |
| 320 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.49788 |
| 321 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 322 | Fan:OnOff | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 631.50416 |
| 323 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 21068.42002 |
| 324 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 335.29657 |
| 325 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79715 |
| 326 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80055 |
| 327 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 335.29657 |
| 328 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 335.29657 |
| 329 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 335.29657 |
| 330 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 15441.16206 |
| 331 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.79715 |
| 332 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 333 | Fan:OnOff | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 335.29657 |
| 334 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 17757.33637 |
| 335 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 427.94486 |
| 336 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.08746 |
| 337 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.79842 |
| 338 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 427.94486 |
| 339 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 427.94486 |
| 340 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 427.94486 |
| 341 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 18322.34617 |
| 342 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.08746 |
| 343 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_FRONTROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 344 | Fan:OnOff | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 427.94486 |
| 345 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 21070.69808 |
| 346 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 628.62280 |
| 347 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 1.48602 |
| 348 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80052 |
| 349 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 628.62280 |
| 350 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 628.62280 |
| 351 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 628.62280 |
| 352 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 18320.18242 |
| 353 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 1.48602 |
| 354 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT1_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 355 | Fan:OnOff | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 628.62280 |
| 356 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 21068.20978 |
| 357 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 341.33470 |
| 358 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.79978 |
| 359 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80058 |
| 360 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 341.33470 |
| 361 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 341.33470 |
| 362 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 341.33470 |
| 363 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 15439.01541 |
| 364 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.79978 |
| 365 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT2_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 366 | Fan:OnOff | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 341.33470 |
| 367 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 17754.86772 |
| 368 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Rated Air Flow Rate [ft3/min] | 395.91097 |
| 369 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Total Cooling Capacity [ton] | 0.95172 |
| 370 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Gross Rated Sensible Heat Ratio | 0.80077 |
| 371 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate [ft3/min] | 395.91097 |
| 372 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Heating Operation [ft3/min] | 395.91097 |
| 373 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Supply Air Flow Rate During Cooling Operation [ft3/min] | 395.91097 |
| 374 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Heating Capacity [Btu/h] | 18318.22915 |
| 375 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Nominal Cooling Capacity [ton] | 0.95172 |
| 376 | AirLoopHVAC:UnitaryHeatCool | ACANDF_UNIT3_BACKROW_TOPFLOOR | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
| 377 | Fan:OnOff | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Design Size Maximum Flow Rate [ft3/min] | 395.91097 |
| 378 | Coil:Heating:Electric | MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Design Size Nominal Capacity [Btu/h] | 21065.96352 |
| 379 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 380 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 381 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 382 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 383 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 384 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 385 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 386 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 387 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 388 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 389 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 390 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 391 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 392 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 393 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 394 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 395 | PlantLoop | DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 396 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 397 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 398 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 399 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 400 | PlantLoop | DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 401 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 402 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 403 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 404 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 405 | PlantLoop | DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 406 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 407 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 408 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 409 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 410 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 411 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 412 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 413 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 414 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 415 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 416 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 417 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 418 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 419 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 420 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 421 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 422 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 423 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 424 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 425 | PlantLoop | DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 426 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 427 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 428 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 429 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 430 | PlantLoop | DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 431 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 432 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 433 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 434 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 435 | PlantLoop | DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 436 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 437 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 438 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 439 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 440 | PlantLoop | DHW LOOP_UNIT1_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 441 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 442 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 443 | WaterHeater:Mixed | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 444 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 445 | PlantLoop | DHW LOOP_UNIT2_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 446 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 447 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 448 | WaterHeater:Mixed | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 449 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 450 | PlantLoop | DHW LOOP_UNIT3_FRONTROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 451 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 452 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 453 | WaterHeater:Mixed | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 454 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 455 | PlantLoop | DHW LOOP_UNIT1_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 456 | Pump:VariableSpeed | MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 457 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 458 | WaterHeater:Mixed | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 459 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 460 | PlantLoop | DHW LOOP_UNIT2_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 461 | Pump:VariableSpeed | MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 462 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 463 | WaterHeater:Mixed | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| 464 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Maximum Loop Flow Rate [ft3/min] | 1.04461 |
| 465 | PlantLoop | DHW LOOP_UNIT3_BACKROW_TOPFLOOR | Plant Loop Volume [ft3] | 2.08975 |
| 466 | Pump:VariableSpeed | MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Design Flow Rate [ft3/min] | 1.04461 |
| 467 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Maximum Heater Capacity [Btu/h] | 15354.00000 |
| 468 | WaterHeater:Mixed | WATER HEATER_UNIT3_BACKROW_TOPFLOOR | Use Side Design Flow Rate [ft3/min] | 1.04461 |
| Component Type | Component Name | Standard Rating (Net) Cooling Capacity {ton} | Standard Rated Net COP {Btuh/Btuh} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
| 1 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.33 | 11.37 | 12.04 | 11.57 | 11.62 |
| 2 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.20 | 10.92 | 11.55 | 11.42 | -99999. |
| 3 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.40 | 11.61 | 12.31 | 11.83 | 12.02 |
| 4 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.28 | 11.20 | 11.85 | 11.72 | -99999. |
| 5 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.33 | 11.37 | 12.05 | 11.58 | 11.63 |
| 6 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.7 | 3.20 | 10.93 | 11.56 | 11.43 | -99999. |
| 7 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.33 | 11.36 | 12.04 | 11.57 | 11.62 |
| 8 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.20 | 10.92 | 11.54 | 11.41 | -99999. |
| 9 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.33 | 11.38 | 12.05 | 11.58 | 11.64 |
| 10 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.20 | 10.93 | 11.56 | 11.43 | -99999. |
| 11 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.32 | 11.32 | 11.99 | 11.52 | 11.55 |
| 12 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.18 | 10.87 | 11.49 | 11.36 | -99999. |
| 13 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 |
| 14 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.19 | 10.88 | 11.51 | 11.38 | -99999. |
| 15 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.32 | 11.34 | 12.01 | 11.55 | 11.58 |
| 16 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.19 | 10.89 | 11.52 | 11.39 | -99999. |
| 17 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 12.04 | 11.57 | 11.62 |
| 18 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.20 | 10.92 | 11.55 | 11.42 | -99999. |
| 19 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 |
| 20 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.19 | 10.88 | 11.50 | 11.37 | -99999. |
| 21 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 |
| 22 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.18 | 10.86 | 11.48 | 11.35 | -99999. |
| 23 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 |
| 24 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.19 | 10.88 | 11.50 | 11.37 | -99999. |
| 25 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.32 | 11.33 | 11.99 | 11.53 | 11.56 |
| 26 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.19 | 10.87 | 11.50 | 11.37 | -99999. |
| 27 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 |
| 28 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.19 | 10.88 | 11.51 | 11.38 | -99999. |
| 29 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.36 | 11.48 | 12.16 | 11.69 | 11.80 |
| 30 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.24 | 11.04 | 11.69 | 11.55 | -99999. |
| 31 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | 3.32 | 11.32 | 11.99 | 11.52 | 11.55 |
| 32 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | 3.18 | 10.86 | 11.49 | 11.36 | -99999. |
| 33 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.31 | 11.30 | 11.96 | 11.50 | 11.51 |
| 34 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.18 | 10.84 | 11.46 | 11.33 | -99999. |
| 35 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.33 | 11.35 | 12.03 | 11.56 | 11.60 |
| 36 | Coil:Cooling:DX:SingleSpeed | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.20 | 10.91 | 11.54 | 11.41 | -99999. |
| Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
| 1 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | SizingPeriod:DesignDay | 12/21 | 12/21 | WinterDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 2 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | SizingPeriod:DesignDay | 07/21 | 07/21 | SummerDesignDay | 1 | N/A | N/A | N/A | N/A | N/A | N/A | Clark and Allen |
| 3 | ANNUAL | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | Yes | Yes | No | Yes | Yes | Clark and Allen |
| Daylight Saving Indicator | Source | Start Date | End Date | |
| 1 | No | SizingPeriod:DesignDay | ||
| 2 | No | SizingPeriod:DesignDay | ||
| 3 | No |
| NumberofWarmupDays | |
| 1 | 6 |
| 2 | 6 |
| 3 | 6 |
| Max Dry-Bulb Temp {F} | Temp Range {dC} | Temp Range Ind Type | Hum Ind Type | Hum Ind Value at Max Temp | Hum Ind Units | Pressure {psi} | Wind Direction {deg CW from N} | Wind Speed {ft/min} | Clearness | Rain | Snow | |
| 1 | -0.2 | 0.00 | DefaultMultipliers | Wetbulb | -17.90 | {C} | 12. | 180 | 492.2 | 0.00 | No | No |
| 2 | 93.02 | 14.80 | DefaultMultipliers | Wetbulb | 15.00 | {C} | 12. | 30 | 708.7 | 0.00 | No | No |
| DayOfYear | ASHRAE A Coeff | ASHRAE B Coeff | ASHRAE C Coeff | Solar Constant-Annual Variation | Eq of Time {minutes} | Solar Declination Angle {deg} | Solar Model | |
| 1 | 355 | 1232.8 | 0.1424 | 5.7719E-002 | 1.0 | 2.45 | -24. | ASHRAEClearSky |
| 2 | 202 | 1084.4 | 0.2082 | 0.1365 | 1.0 | -6.23 | 20.6 | ASHRAETau |
| Style | Unit Conversion | |
| 1 | Commaandhtml | commaandhtml |
| Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaF} | Std Dev Warmup Temperature Difference {deltaF} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {Btu/h} | Std Dev Warmup Load Difference {Btu/h} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
| 1 | BREEZEWAY | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000002904 | 0.000001564 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 2 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007391040 | 0.013798128 | Pass | Pass |
| 3 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009119162 | 0.016942429 | Pass | Pass |
| 4 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007389686 | 0.013795577 | Pass | Pass |
| 5 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007389629 | 0.013795447 | Pass | Pass |
| 6 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009119103 | 0.016942340 | Pass | Pass |
| 7 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.007391009 | 0.013798042 | Pass | Pass |
| 8 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009554454 | 0.016499279 | Pass | Pass |
| 9 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.012957104 | 0.022408594 | Pass | Pass |
| 10 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009552148 | 0.016495187 | Pass | Pass |
| 11 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009552992 | 0.016496655 | Pass | Pass |
| 12 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.012958627 | 0.022411276 | Pass | Pass |
| 13 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.009555331 | 0.016500760 | Pass | Pass |
| 14 | ATTIC | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000135891 | 0.000117199 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 15 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006705210 | 0.010915511 | Pass | Pass |
| 16 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006703320 | 0.010912396 | Pass | Pass |
| 17 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006704129 | 0.010913750 | Pass | Pass |
| 18 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008229197 | 0.013349276 | Pass | Pass |
| 19 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.008227616 | 0.013344658 | Pass | Pass |
| 20 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 0.000000000 | 0.000000000 | Pass | Pass | 0.006704394 | 0.010914162 | Pass | Pass |
| 21 | BREEZEWAY | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.454920192 | 0.265887532 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 22 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000004216 | 0.000007156 | Pass | Pass | 0.227404526 | 0.188509122 | Pass | Pass |
| 23 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002517 | 0.000006042 | Pass | Pass | 0.144571971 | 0.108936894 | Pass | Pass |
| 24 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003415 | 0.000004954 | Pass | Pass | 0.199184017 | 0.237137641 | Pass | Pass |
| 25 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000004229 | 0.000007105 | Pass | Pass | 0.220710487 | 0.184453656 | Pass | Pass |
| 26 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002404 | 0.000003862 | Pass | Pass | 0.136164507 | 0.113227531 | Pass | Pass |
| 27 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003333 | 0.000004748 | Pass | Pass | 0.192309703 | 0.232521013 | Pass | Pass |
| 28 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000004709 | 0.000008415 | Pass | Pass | 0.128128978 | 0.056335474 | Pass | Pass |
| 29 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002579 | 0.000004959 | Pass | Pass | 0.085570386 | 0.058733530 | Pass | Pass |
| 30 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003605 | 0.000006110 | Pass | Pass | 0.108318782 | 0.107740463 | Pass | Pass |
| 31 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000005063 | 0.000009054 | Pass | Pass | 0.125758806 | 0.056703058 | Pass | Pass |
| 32 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000002447 | 0.000004586 | Pass | Pass | 0.080905014 | 0.055804565 | Pass | Pass |
| 33 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003385 | 0.000005675 | Pass | Pass | 0.105055576 | 0.111462976 | Pass | Pass |
| 34 | ATTIC | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.662109479 | 0.475104418 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 35 | LIVING_UNIT3_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003967 | 0.000006376 | Pass | Pass | 0.120866155 | 0.125037248 | Pass | Pass |
| 36 | LIVING_UNIT3_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000008741 | 0.000039269 | Pass | Pass | 0.123107028 | 0.122745142 | Pass | Pass |
| 37 | LIVING_UNIT1_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000005235 | 0.000008891 | Pass | Pass | 0.145278130 | 0.068671710 | Pass | Pass |
| 38 | LIVING_UNIT2_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003388 | 0.000005467 | Pass | Pass | 0.101331069 | 0.060233202 | Pass | Pass |
| 39 | LIVING_UNIT2_FRONTROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000003216 | 0.000005485 | Pass | Pass | 0.102450249 | 0.067165353 | Pass | Pass |
| 40 | LIVING_UNIT1_BACKROW_TOPFLOOR | SizingPeriod: DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 0.000005602 | 0.000009099 | Pass | Pass | 0.144081749 | 0.066521584 | Pass | Pass |
| 41 | BREEZEWAY | RunPeriod: ANNUAL | 0.250387524 | 0.214055015 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 42 | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.041669274 | 0.111667302 | Pass | Pass | 0.291011941 | 1.127001963 | Pass | Pass |
| 43 | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.016754346 | 0.041405027 | Pass | Pass | 0.287806471 | 1.080167046 | Pass | Pass |
| 44 | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.022733314 | 0.055075863 | Pass | Pass | 0.199520466 | 0.647425029 | Pass | Pass |
| 45 | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000004094 | 0.000008899 | Pass | Pass | 0.096228307 | 0.101686319 | Pass | Pass |
| 46 | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000003353 | 0.000007215 | Pass | Pass | 0.059882268 | 0.066151687 | Pass | Pass |
| 47 | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | RunPeriod: ANNUAL | 0.000004202 | 0.000009352 | Pass | Pass | 0.094129781 | 0.144350545 | Pass | Pass |
| 48 | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.041668463 | 0.083023839 | Pass | Pass | 0.500561171 | 2.218434315 | Pass | Pass |
| 49 | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.042104577 | 0.065090790 | Pass | Pass | 0.306124101 | 1.141474669 | Pass | Pass |
| 50 | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.042341200 | 0.091964231 | Pass | Pass | 0.474045510 | 2.417892791 | Pass | Pass |
| 51 | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000002206 | 0.000004915 | Pass | Pass | 0.153704114 | 0.240062458 | Pass | Pass |
| 52 | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000001689 | 0.000003809 | Pass | Pass | 0.068083234 | 0.075568961 | Pass | Pass |
| 53 | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | RunPeriod: ANNUAL | 0.000002392 | 0.000005664 | Pass | Pass | 0.129233953 | 0.223946308 | Pass | Pass |
| 54 | ATTIC | RunPeriod: ANNUAL | 0.496422613 | 0.616125683 | Pass | Pass | 0.000000000 | 0.000000000 | Pass | Pass |
| 55 | LIVING_UNIT3_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000004344 | 0.000009674 | Pass | Pass | 0.080906749 | 0.113507323 | Pass | Pass |
| 56 | LIVING_UNIT3_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.020588183 | 0.044189184 | Pass | Pass | 0.271762423 | 0.732785326 | Pass | Pass |
| 57 | LIVING_UNIT1_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.041669372 | 0.100274806 | Pass | Pass | 0.290900698 | 0.801875401 | Pass | Pass |
| 58 | LIVING_UNIT2_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000003480 | 0.000007450 | Pass | Pass | 0.060749617 | 0.054192008 | Pass | Pass |
| 59 | LIVING_UNIT2_FRONTROW_TOPFLOOR | RunPeriod: ANNUAL | 0.023000138 | 0.049047492 | Pass | Pass | 0.227835257 | 0.539824150 | Pass | Pass |
| 60 | LIVING_UNIT1_BACKROW_TOPFLOOR | RunPeriod: ANNUAL | 0.000004127 | 0.000009058 | Pass | Pass | 0.097085814 | 0.098691076 | Pass | Pass |
Report: Annual Heat Emissions Report
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Annual Heat Emissions Summary| Envelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
| Heat Emissions [kBtu] | 2648905.63 | 518562.41 | 188075.65 | 0.00 | 226869.07 | 3582415.40 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Heat Index Hours| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| BREEZEWAY | 7975.17 | 683.83 | 101.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 7594.83 | 684.83 | 449.17 | 31.17 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 7594.83 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 684.83 | 449.17 | 31.17 | 0.00 |
| Average | 8662.50 | 68.43 | 27.51 | 1.56 | 0.00 |
| Sum | 173250.00 | 1368.67 | 550.17 | 31.17 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 10856.14 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 217122.86 | 0.00 | 0.00 | 0.00 | 0.00 |
| Safe (≤ 80.1°F) [hr] | Caution (> 80.1°F, ≤ 90.0°F) [hr] | Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] | Danger (> 102.9, ≤ 125.1°F) [hr] | Extreme Danger (> 125.1°F) [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 7884.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| BREEZEWAY | 8475.67 | 284.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 7835.50 | 857.00 | 60.33 | 7.17 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| Min | 7835.50 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 857.00 | 60.33 | 7.17 | 0.00 |
| Average | 8697.52 | 59.11 | 3.02 | 0.36 | 0.00 |
| Sum | 173950.33 | 1182.17 | 60.33 | 7.17 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 12051.54 | 10.84 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 12053.13 | 9.26 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 12053.38 | 9.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 12052.13 | 10.26 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 12053.42 | 8.96 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 12053.38 | 9.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 12061.71 | 0.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 12057.05 | 5.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 12057.05 | 5.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12056.05 | 6.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12062.38 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 12056.05 | 6.33 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 12062.38 | 10.84 | 0.00 | 0.00 | 0.00 |
| Average | 10852.08 | 4.07 | 0.00 | 0.00 | 0.00 |
| Sum | 217041.55 | 81.32 | 0.00 | 0.00 | 0.00 |
| Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8754.50 | 5.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8755.33 | 4.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8754.83 | 5.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8759.67 | 0.33 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8757.33 | 2.67 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8756.83 | 3.17 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | 5.50 | 0.00 | 0.00 | 0.00 |
| Average | 7881.96 | 2.04 | 0.00 | 0.00 | 0.00 |
| Sum | 157639.17 | 40.83 | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Hours of Safety [hr] | End Time of the Safety Duration | Safe Temperature Exceedance Hours [hr] | Safe Temperature Exceedance OccupantHours [hr] | Safe Temperature Exceedance OccupiedHours [hr] | |
| BREEZEWAY | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | - | 0.00 | 0.00 | 0.00 |
| Max | 8760.00 | - | 0.00 | 0.00 | 0.00 |
| Average | 7884.00 | - | 0.00 | 0.00 | 0.00 |
| Sum | 157680.00 | - | 0.00 | 0.00 | 0.00 |
| Cooling Setpoint Unmet Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] | Heating Setpoint Unmet Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] | Heating Setpoint Unmet Occupied Degree-Hours [°C·hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.10 | 0.10 | 0.10 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.07 | 0.09 | 0.07 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.14 | 0.12 | 0.14 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.09 | 0.10 | 0.09 | 0.02 | 0.01 | 0.02 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.06 | 0.08 | 0.06 | 0.02 | 0.03 | 0.02 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.10 | 0.10 | 0.10 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.13 | 0.15 | 0.13 | 0.01 | 0.01 | 0.01 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.16 | 0.19 | 0.16 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.13 | 0.13 | 0.13 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.11 | 0.13 | 0.11 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.57 | 0.98 | 0.57 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.11 | 0.13 | 0.11 | 0.01 | 0.02 | 0.01 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.93 | 1.30 | 0.93 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.11 | 0.10 | 0.11 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.12 | 0.12 | 0.12 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.17 | 1.91 | 1.17 | 0.02 | 0.02 | 0.02 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.63 | 0.97 | 0.63 | 0.01 | 0.02 | 0.01 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.10 | 0.11 | 0.10 | 0.02 | 0.02 | 0.02 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 1.17 | 1.91 | 1.17 | 0.02 | 0.03 | 0.02 |
| Average | 0.24 | 0.34 | 0.24 | 0.01 | 0.02 | 0.01 |
| Sum | 4.82 | 6.82 | 4.82 | 0.30 | 0.35 | 0.30 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
| Very-cold Exceedance OccupantHours [hr] | Cool Exceedance OccupantHours [hr] | Warm Exceedance OccupantHours [hr] | Very-hot Exceedance OccupantHours [hr] | |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| Min | 0.00 | 0.00 | 0.00 | 0.00 |
| Max | 0.00 | 0.00 | 0.00 | 0.00 |
| Average | 0.00 | 0.00 | 0.00 | 0.00 |
| Sum | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
SizingPeriod:DesignDay| Maximum Dry Bulb [F] | Daily Temperature Range [deltaF] | Humidity Value | Humidity Type | Wind Speed [ft/min] | Wind Direction | |
| DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | -0.2 | 0.00 | -0.2 | Wetbulb [F] | 492.15 | 180.00 |
| DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 93.02 | 26.64 | 59.00 | Wetbulb [F] | 708.70 | 30.00 |
| Monthly Total Precipitation from .epw [in] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [in] | Monthly Total Roof Irrigation Depth [in] | Monthly Total Rain Collection Volume [ft3] | |
| Jan | 0.43 | 10 | |||
| Feb | 0.59 | 16 | |||
| Mar | 3.46 | 32 | |||
| Apr | 6.26 | 54 | |||
| May | 1.18 | 24 | |||
| Jun | 0.43 | 4 | |||
| Jul | 6.57 | 26 | |||
| Aug | 1.30 | 24 | |||
| Sep | 0.31 | 8 | |||
| Oct | 0.51 | 10 | |||
| Nov | 0.47 | 22 | |||
| Dec | 0.43 | 18 |
| Value | |
| None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Opaque Exterior| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| BREEZEWAY_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_MIDDLEFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| BREEZEWAY_TOPFLOOR | EXTERIOR FLOOR | 0.30 | 0.226 | 0.300 | 599.39 | 599.39 | 0.00 | 180.00 | |
| WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.46 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.46 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.76 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| ROOF_RIGHT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 90.00 | 90.00 | E |
| ROOF_LEFT | GABLE_END | 0.30 | 0.314 | 0.428 | 440.68 | 440.68 | 270.00 | 90.00 | W |
| ROOF_BACK | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 0.00 | 22.59 | |
| ROOF_FRONT | EXTERIOR ROOF | 0.25 | 0.543 | 0.943 | 4225.65 | 4225.65 | 180.00 | 22.59 | |
| WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 90.00 | 90.00 | E |
| WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 180.00 | 90.00 | S |
| WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 0.00 | 90.00 | N |
| WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 280.68 | 0.00 | 90.00 | N |
| WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 255.45 | 166.84 | 270.00 | 90.00 | W |
| WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR | EXTERIOR WALL | 0.30 | 0.064 | 0.068 | 339.75 | 318.74 | 180.00 | 90.00 | S |
| Construction | Reflectance | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Net Area [ft2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| BREEZEWAYROOF | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.46 | 255.46 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR FLOOR | 0.30 | 0.235 | 0.300 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_BOTTOMFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_MIDDLEFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| iz-BREEZEWAYROOF | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 599.39 | 599.39 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT3_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT2_FRONTROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| iz-CEILING_UNIT1_BACKROW_TOPFLOOR | ATTIC FLOOR | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT3_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT3_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT2_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 270.00 | 90.00 | W |
| FLOOR_UNIT2_FRONTROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT2_FRONTROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 | |
| WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR | INTERIORWALL | 0.30 | 0.329 | 0.597 | 255.45 | 255.45 | 90.00 | 90.00 | E |
| FLOOR_UNIT1_BACKROW_TOPFLOOR | CEILING-FLOOR-LAYER | 0.30 | 0.169 | 0.228 | 1200.55 | 1200.55 | 0.00 | 180.00 | |
| CEILING_UNIT1_BACKROW_TOPFLOOR | INTERIOR CEILING | 0.30 | 0.027 | 0.028 | 1200.55 | 1200.55 | 180.00 | 0.00 |
| Construction | Frame and Divider | Glass Area [ft2] | Frame Area [ft2] | Divider Area [ft2] | Area of One Opening [ft2] | Area of Multiplied Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [Btu/h-ft2-F] | Divider Conductance [Btu/h-ft2-F] | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | 90.00 | 90.00 | E | |||||||
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | 180.00 | 90.00 | S | |||||||
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 59.08 | 0.00 | 0.00 | 59.08 | 59.08 | 0.350 | 0.335 | 0.883 | Yes | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR | 0.00 | 90.00 | N | |||||||
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | EXTERIOR WINDOW | 88.61 | 0.00 | 0.00 | 88.61 | 88.61 | 0.350 | 0.335 | 0.883 | Yes | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | 270.00 | 90.00 | W | |||||||
| Total or Average | 2126.74 | 0.350 | 0.335 | 0.883 | |||||||||||||||||
| North Total or Average | 531.68 | 0.350 | 0.335 | 0.883 | |||||||||||||||||
| Non-North Total or Average | 1595.05 | 0.350 | 0.335 | 0.883 |
| Frame and Divider | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [Btu/h-ft2-F] | Assembly SHGC | Assembly Visible Transmittance | |
| None |
| Construction | Area of One Opening [ft2] | Area of Openings [ft2] | Glass U-Factor [Btu/h-ft2-F] | Glass SHGC | Glass Visible Transmittance | Parent Surface | |
| Total or Average | 0.00 | - | - | - |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR |
| DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
| DOOR_LDF_UNIT3_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR |
| DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT2_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR |
| DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
| DOOR_LDF_UNIT1_BACKROW_TOPFLOOR | EXTERIOR DOOR | 0.270 | 0.350 | 21.01 | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
| Construction | U-Factor with Film [Btu/h-ft2-F] | U-Factor no Film [Btu/h-ft2-F] | Gross Area [ft2] | Parent Surface | |
| None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Sunlit Fraction| March 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | 1.00 | 0.95 | 0.00 | 0.99 | 0.90 | 0.00 | 1.00 | 0.94 | 0.00 |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | 0.99 | 0.99 | 0.99 | 0.92 | 0.97 | 0.96 | 1.00 | 1.00 | 1.00 |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 0.99 | 0.00 | 0.00 | 1.00 |
| Name | Type | Shaded Construction | Control | Glare Control | |
| WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR | SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR | SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR | SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
| WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR | SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR | Interior Blind | WINDOW_W_BLINDS | AlwaysOff | No |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Interior Lighting| Zone Name | Space Name | Space Type | Lighting Power Density [Btu/h-ft2] | Space Area [ft2] | Total Power [Btu/h] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [kWh] | |
| LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.7290 | 1200.55 | 875.25 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 787.52 |
| LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | GENERAL | 0.1823 | 1200.55 | 218.81 | General | INTERIORLIGHTINGHE | 58.88 | 168.00 | 58.88 | 0.0000 | Y | 196.88 |
| Interior Lighting Total | 0.4556 | 43219.92 | 19693.13 | 17719.17 |
| Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [Btu/h] | Lighting Controlled [Btu/h] | |
| None |
| Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [kWh] | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 76.54 | Schedule | EXTERIORLIGHTING | 84.00 | 84.00 | 84.00 | 335.24 |
| GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR | 0.00 | Schedule | INTERIORLIGHTINGHE | 58.88 | 0.00 | 0.00 | |
| Exterior Lighting Total | 1377.69 | 6034.31 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Central Plant| Type | Reference Capacity [Btu/h] | Reference Efficiency [Btuh/Btuh] | Rated Capacity [Btu/h] | Rated Efficiency [Btuh/Btuh] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
| None |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Sensible Capacity [Btu/h] | Nominal Latent Capacity [Btu/h] | Nominal Sensible Heat Ratio | Nominal Efficiency [Btuh/Btuh] | Nominal Coil UA Value [Btu/h-F] | Nominal Coil Surface Area [ft2] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 14233.77 | 11387.49 | 2846.28 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7911.58 | 6111.83 | 1799.74 | 0.77 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 9463.76 | 7580.41 | 1883.35 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 13620.27 | 10905.18 | 2715.09 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 7090.60 | 5675.47 | 1415.12 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 8616.40 | 6895.02 | 1721.38 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 16117.33 | 12909.23 | 3208.10 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7691.87 | 6160.46 | 1531.41 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 11260.33 | 9014.02 | 2246.32 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 15465.12 | 12382.54 | 3082.58 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 7387.21 | 5915.11 | 1472.10 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 10406.97 | 8335.72 | 2071.25 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17974.58 | 14386.01 | 3588.57 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9565.77 | 7657.84 | 1907.93 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 13049.58 | 10419.01 | 2630.56 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 17832.19 | 14274.95 | 3557.24 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 9597.33 | 7683.43 | 1913.90 | 0.80 | 4.09 | |||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 11420.60 | 9145.26 | 2275.34 | 0.80 | 4.09 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP [Btuh/Btuh] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | 1.1 | 3.33 | 11.37 | 12.04 | 11.57 | 11.62 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | 0.6 | 3.40 | 11.61 | 12.31 | 11.83 | 12.02 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | 0.8 | 3.33 | 11.37 | 12.05 | 11.58 | 11.63 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | 1.1 | 3.33 | 11.36 | 12.04 | 11.57 | 11.62 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | 0.6 | 3.33 | 11.38 | 12.05 | 11.58 | 11.64 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | 0.7 | 3.32 | 11.32 | 11.99 | 11.52 | 11.55 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | 1.3 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | 0.6 | 3.32 | 11.34 | 12.01 | 11.55 | 11.58 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | 0.9 | 3.33 | 11.36 | 12.04 | 11.57 | 11.62 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | 1.2 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | 0.6 | 3.31 | 11.31 | 11.98 | 11.51 | 11.53 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | 0.8 | 3.32 | 11.33 | 12.00 | 11.53 | 11.56 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | 1.4 | 3.32 | 11.33 | 11.99 | 11.53 | 11.56 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | 0.8 | 3.32 | 11.33 | 12.00 | 11.54 | 11.57 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | 1.0 | 3.36 | 11.48 | 12.16 | 11.69 | 11.80 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | 1.4 | 3.32 | 11.32 | 11.99 | 11.52 | 11.55 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | 0.8 | 3.31 | 11.30 | 11.96 | 11.50 | 11.51 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | 0.9 | 3.33 | 11.35 | 12.03 | 11.56 | 11.60 |
| DX Cooling Coil Type | Standard Rated Net Cooling Capacity [ton] | Standard Rated Net COP2 [Btuh/Btuh] | EER2 [Btu/W-h] | SEER2 User [Btu/W-h] | SEER2 Standard [Btu/W-h] | IEER2 [Btu/W-h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.20 | 10.92 | 11.55 | 11.42 | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.28 | 11.20 | 11.85 | 11.72 | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.20 | 10.93 | 11.56 | 11.43 | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 1.1 | 3.20 | 10.92 | 11.54 | 11.41 | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.20 | 10.93 | 11.56 | 11.43 | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | 0.7 | 3.18 | 10.87 | 11.49 | 11.36 | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.3 | 3.19 | 10.88 | 11.51 | 11.38 | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.19 | 10.89 | 11.52 | 11.39 | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.20 | 10.92 | 11.55 | 11.42 | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 1.2 | 3.19 | 10.88 | 11.50 | 11.37 | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.6 | 3.18 | 10.86 | 11.48 | 11.35 | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.19 | 10.88 | 11.50 | 11.37 | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.19 | 10.87 | 11.50 | 11.37 | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.19 | 10.88 | 11.51 | 11.38 | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.0 | 3.24 | 11.04 | 11.69 | 11.55 | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 1.4 | 3.18 | 10.86 | 11.49 | 11.36 | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.8 | 3.18 | 10.84 | 11.46 | 11.33 | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | 0.9 | 3.20 | 10.91 | 11.54 | 11.41 |
| DX Cooling Coil Type | Rated Net Cooling Capacity Test A [ton] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [ton] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [ton] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [ton] | Rated Electric Power Test D [W] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | ||||||||
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed |
| Coil Type | Rated Total Capacity [Btu/h] | Rated Sensible Capacity [Btu/h] | Rated Power[Btu/h] | Rated COP [Btuh/Btuh] | Rated Air Dry-bulb Temperature [F] | Rated Air Wet-bulb Temperature [F] | Rated Water Temperature [F] | Design Day used for Sizing | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF [Btu/W-h] | Region Number | |
| None |
| DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [Btu/h] | Low Temperature Heating (net) Rating Capacity [Btu/h] | HSPF2 [Btu/W-h] | Region Number | |
| None |
| Type | Design Coil Load [Btu/h] | Nominal Total Capacity [Btu/h] | Nominal Efficiency [Btuh/Btuh] | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 18622.96 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 15585.18 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | 18626.00 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 18625.83 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 15584.96 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | 18622.76 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 15788.48 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 12497.42 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | 15791.60 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 15790.62 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 12496.44 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | 15787.50 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 21068.42 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 17757.34 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | 21070.70 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | 21068.21 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | 17754.87 | 1.00 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | 21065.96 | 1.00 |
| Type | Total Efficiency [Btuh/Btuh] | Delta Pressure [psi] | Max Air Flow Rate [ft3/min] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-min/ft3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
| ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR | Fan:ZoneExhaust | 0.60 | 0.13 | 44.99 | 32.14 | 0.71 | 1.00 | 10.37 | Ventilation | ||
| SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 490.90 | 185.17 | 0.38 | 1.00 | 2.16 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 243.38 | 91.80 | 0.38 | 1.00 | 3.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 325.39 | 122.73 | 0.38 | 1.00 | 2.64 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 470.61 | 177.51 | 0.38 | 1.00 | 2.20 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 243.38 | 91.80 | 0.38 | 1.00 | 3.12 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 0.50 | 0.06 | 303.49 | 114.47 | 0.38 | 1.00 | 2.74 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 563.96 | 212.72 | 0.38 | 1.00 | 2.03 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 268.32 | 101.21 | 0.38 | 1.00 | 2.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 388.90 | 146.69 | 0.38 | 1.00 | 2.41 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 542.27 | 204.54 | 0.38 | 1.00 | 2.07 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 261.32 | 98.57 | 0.38 | 1.00 | 2.99 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 0.50 | 0.06 | 365.23 | 137.76 | 0.38 | 1.00 | 2.49 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 631.51 | 238.20 | 0.38 | 1.00 | 1.94 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 335.29 | 126.47 | 0.38 | 1.00 | 2.60 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 427.94 | 161.42 | 0.38 | 1.00 | 2.30 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 628.62 | 237.11 | 0.38 | 1.00 | 1.95 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 341.33 | 128.75 | 0.38 | 1.00 | 2.58 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 0.50 | 0.06 | 395.90 | 149.33 | 0.38 | 1.00 | 2.39 | General | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 |
| Type | Control | Head [psi] | Water Flow [gal/min] | Electricity Rate [W] | Power Per Water Flow Rate [W-min/gal] | Motor Efficiency [Btuh/Btuh] | End Use Subcategory | |
| MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR | Pump:VariableSpeed | Intermittent | 0.00 | 7.815904 | 0.00 | 0.00 | 1.00 | General |
| Type | Storage Volume [ft3] | Input [Btu/h] | Thermal Efficiency [Btuh/Btuh] | Recovery Efficiency [Btuh/Btuh] | Energy Factor | |
| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
| WATER HEATER_UNIT3_BACKROW_TOPFLOOR | WaterHeater:Mixed | 6.95 | 15354.00 | 1.00 | 1.07 | 0.98 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Zone Sensible Cooling| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 9359.90 | 9359.90 | 7.80 | 490.903 | 490.903 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 75.00 | 75.00 | 0.00736 | 88.40 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4343.48 | 4343.48 | 3.62 | 227.803 | 227.803 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00715 | 93.02 | 0.00548 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 6204.04 | 6204.04 | 5.17 | 325.388 | 325.388 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 75.00 | 75.00 | 0.00723 | 86.23 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 8973.01 | 8973.01 | 7.47 | 470.613 | 470.613 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 75.00 | 75.00 | 0.00738 | 87.96 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4082.30 | 4082.30 | 3.40 | 214.111 | 214.111 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00741 | 83.96 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5786.44 | 5786.44 | 4.82 | 303.486 | 303.486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 75.00 | 75.00 | 0.00723 | 83.56 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 10752.56 | 10752.56 | 8.96 | 563.956 | 563.956 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00749 | 87.51 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5115.84 | 5115.84 | 4.26 | 268.321 | 268.321 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 75.00 | 75.00 | 0.00757 | 83.96 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 7414.98 | 7414.98 | 6.18 | 388.902 | 388.902 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 75.00 | 75.00 | 0.00736 | 86.89 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 10339.14 | 10339.14 | 8.61 | 542.274 | 542.274 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00749 | 87.07 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4982.43 | 4982.43 | 4.15 | 261.324 | 261.324 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 75.00 | 75.00 | 0.00759 | 82.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 6963.64 | 6963.64 | 5.80 | 365.231 | 365.231 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 75.00 | 75.00 | 0.00735 | 84.89 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 7548.48 | 7548.48 | 6.29 | 395.904 | 395.904 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 75.00 | 75.00 | 0.00740 | 86.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 8159.51 | 8159.51 | 6.80 | 427.940 | 427.940 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 75.00 | 75.00 | 0.00727 | 93.02 | 0.00548 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 12040.71 | 12040.71 | 10.03 | 631.509 | 631.509 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 75.00 | 75.00 | 0.00743 | 87.51 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 6507.82 | 6507.82 | 5.42 | 341.327 | 341.327 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 75.00 | 75.00 | 0.00746 | 83.30 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 6392.76 | 6392.76 | 5.32 | 335.291 | 335.291 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 75.00 | 75.00 | 0.00744 | 84.63 | 0.00547 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 11985.63 | 11985.63 | 9.98 | 628.622 | 628.622 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 75.00 | 75.00 | 0.00743 | 87.07 | 0.00547 | 44.995 | 0.00 |
| Calculated Design Load [Btu/h] | User Design Load [Btu/h] | User Design Load per Area [Btu/h-ft2] | Calculated Design Air Flow [ft3/min] | User Design Air Flow [ft3/min] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [F] | Indoor Temperature at Peak Load [F] | Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Outdoor Temperature at Peak Load [F] | Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] | Minimum Outdoor Air Flow Rate [ft3/min] | Heat Gain Rate from DOAS [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 13536.17 | 13536.17 | 11.27 | 303.477 | 303.477 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 10855.53 | 10855.53 | 9.04 | 243.385 | 243.385 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00580 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 13538.85 | 13538.85 | 11.28 | 303.537 | 303.537 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 13538.70 | 13538.70 | 11.28 | 303.534 | 303.534 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 10855.33 | 10855.33 | 9.04 | 243.380 | 243.380 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00580 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 13535.99 | 13535.99 | 11.27 | 303.473 | 303.473 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00600 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 11034.74 | 11034.74 | 9.19 | 247.424 | 247.424 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00634 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 8130.59 | 8130.59 | 6.77 | 182.312 | 182.312 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00612 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11037.50 | 11037.50 | 9.19 | 247.486 | 247.486 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00634 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 11036.63 | 11036.63 | 9.19 | 247.466 | 247.466 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00634 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 8129.73 | 8129.73 | 6.77 | 182.292 | 182.292 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00612 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 11033.89 | 11033.89 | 9.19 | 247.405 | 247.405 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.99 | 0.00634 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 15691.93 | 15691.93 | 13.07 | 351.808 | 351.808 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 15696.10 | 15696.10 | 13.07 | 351.902 | 351.902 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 15694.09 | 15694.09 | 13.07 | 351.857 | 351.857 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 12770.10 | 12770.10 | 10.64 | 286.310 | 286.310 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00603 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 12772.28 | 12772.28 | 10.64 | 286.358 | 286.358 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00603 | -0.2 | 0.00096 | 44.995 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 15693.91 | 15693.91 | 13.07 | 351.852 | 351.852 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 72.00 | 71.98 | 0.00620 | -0.2 | 0.00096 | 44.995 | 0.00 |
| Calculated cooling [ft3/min] | User cooling [ft3/min] | Calculated heating [ft3/min] | User heating [ft3/min] | Adjusted cooling [ft3/min] | Adjusted heating [ft3/min] | Adjusted main [ft3/min] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.90 | 490.90 | 303.48 | 303.48 | 490.9034 | 490.9034 | 490.9034 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 227.80 | 227.80 | 243.38 | 243.38 | 243.3845 | 243.3845 | 243.3845 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.39 | 325.39 | 303.54 | 303.54 | 325.3883 | 325.3883 | 325.3883 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.61 | 470.61 | 303.53 | 303.53 | 470.6134 | 470.6134 | 470.6134 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 214.11 | 214.11 | 243.38 | 243.38 | 243.3802 | 243.3802 | 243.3802 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.49 | 303.49 | 303.47 | 303.47 | 303.4864 | 303.4864 | 303.4864 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.96 | 563.96 | 247.42 | 247.42 | 563.9556 | 563.9556 | 563.9556 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.32 | 268.32 | 182.31 | 182.31 | 268.3213 | 268.3213 | 268.3213 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.90 | 388.90 | 247.49 | 247.49 | 388.9023 | 388.9023 | 388.9023 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.27 | 542.27 | 247.47 | 247.47 | 542.2735 | 542.2735 | 542.2735 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.32 | 261.32 | 182.29 | 182.29 | 261.3244 | 261.3244 | 261.3244 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.23 | 365.23 | 247.40 | 247.40 | 365.2311 | 365.2311 | 365.2311 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.51 | 631.51 | 351.86 | 351.86 | 631.5090 | 631.5090 | 631.5090 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.29 | 335.29 | 286.36 | 286.36 | 335.2910 | 335.2910 | 335.2910 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.94 | 427.94 | 351.90 | 351.90 | 427.9402 | 427.9402 | 427.9402 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.62 | 628.62 | 351.85 | 351.85 | 628.6223 | 628.6223 | 628.6223 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.33 | 341.33 | 286.31 | 286.31 | 341.3265 | 341.3265 | 341.3265 | 1.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.90 | 395.90 | 351.81 | 351.81 | 395.9038 | 395.9038 | 395.9038 | 1.0000 | 1.0000 |
| Previous Design Volume Flow Rate [ft3/min] | Algorithm Volume Flow Rate [ft3/min] | Coincident Design Volume Flow Rate [ft3/min] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
| None |
| Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 14233.768 | 11387.485 | 490.903442 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | 13154.16 | 13154.16 | 490.903442 | 77.67 | 56.54 | 0.00719006 | 53.60 | 47.51 | 0.00719006 | 88.40 | 0.00547132 | 57.61 | 9.1658 | 75.00 | 0.00734419 | 32.3643 | 9351.43 | 0.00 | 14239.71 | 10274.48 |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 18622.961 | 18622.961 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18622.96 | 18622.96 | -999. | 65.36 | 49.32 | 0.00553627 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00599853 | 29.3200 | 13536.17 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 7911.575 | 6111.833 | 243.384536 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 7148.55 | 7148.55 | 243.384536 | 80.01 | 56.78 | 0.00681859 | 53.60 | 46.84 | 0.00681859 | 93.02 | 0.00547527 | 59.13 | 18.4872 | 75.00 | 0.00714922 | 31.5144 | 4343.48 | 0.00 | 7914.88 | 5544.72 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 15585.183 | 15585.183 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15585.18 | 15585.18 | -999. | 58.64 | 45.40 | 0.00490474 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00580049 | 28.3596 | 10855.53 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 9463.763 | 7580.409 | 325.388284 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | 8833.30 | 8833.30 | 325.388284 | 78.00 | 56.35 | 0.00698885 | 53.60 | 47.15 | 0.00698885 | 86.23 | 0.00546947 | 56.87 | 13.8281 | 75.00 | 0.00721440 | 31.7987 | 6138.65 | 0.00 | 9467.71 | 6837.86 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 18625.998 | 18625.998 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18626.00 | 18626.00 | -999. | 62.00 | 47.54 | 0.00530138 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00599881 | 29.3213 | 13538.85 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 13620.273 | 10905.182 | 470.613354 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | 12616.09 | 12616.09 | 470.613354 | 77.68 | 56.56 | 0.00719648 | 53.60 | 47.53 | 0.00719648 | 87.96 | 0.00547095 | 57.46 | 9.5609 | 75.00 | 0.00737890 | 32.5157 | 8973.01 | 0.00 | 13625.96 | 9838.32 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 18625.828 | 18625.828 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18625.83 | 18625.83 | -999. | 65.08 | 49.18 | 0.00551658 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00599879 | 29.3212 | 13538.70 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 7090.595 | 5675.475 | 243.380152 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 6696.74 | 6696.74 | 243.380152 | 78.33 | 56.48 | 0.00700233 | 53.60 | 47.17 | 0.00700233 | 83.96 | 0.00546756 | 56.09 | 18.4875 | 75.00 | 0.00737049 | 32.4792 | 4040.70 | 0.00 | 7093.55 | 5119.97 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 15584.962 | 15584.962 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15584.96 | 15584.96 | -999. | 58.63 | 45.40 | 0.00490470 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00580046 | 28.3594 | 10855.33 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 8616.396 | 6895.017 | 303.486433 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | 8142.91 | 8142.91 | 303.486433 | 77.72 | 56.22 | 0.00696897 | 53.60 | 47.11 | 0.00696897 | 83.56 | 0.00546722 | 55.95 | 14.8260 | 75.00 | 0.00722231 | 31.8334 | 5757.45 | 0.00 | 8619.99 | 6220.22 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 18622.755 | 18622.755 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 18622.76 | 18622.76 | -999. | 61.28 | 47.16 | 0.00525079 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00599851 | 29.3199 | 13535.99 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 16117.329 | 12909.226 | 563.955581 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 14970.58 | 14970.58 | 563.955581 | 77.44 | 56.67 | 0.00732635 | 53.60 | 47.76 | 0.00732635 | 87.51 | 0.00547057 | 57.31 | 7.9785 | 75.00 | 0.00747212 | 32.9219 | 10751.52 | 0.00 | 16124.05 | 11647.43 |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 15788.475 | 15788.475 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15788.48 | 15788.48 | -999. | 66.23 | 50.31 | 0.00590847 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00633793 | 30.9562 | 11034.74 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 7691.867 | 6160.461 | 268.321318 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | 7272.02 | 7272.02 | 268.321318 | 77.95 | 56.68 | 0.00721637 | 53.60 | 47.56 | 0.00721637 | 83.96 | 0.00546756 | 56.09 | 16.7691 | 75.00 | 0.00731690 | 32.2454 | 4962.75 | 0.00 | 7695.08 | 5558.18 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 12497.416 | 12497.416 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12497.42 | 12497.42 | -999. | 59.88 | 46.58 | 0.00525258 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00611839 | 29.8928 | 8130.59 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 11260.335 | 9014.017 | 388.902314 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | 10483.77 | 10483.77 | 388.902314 | 77.82 | 56.52 | 0.00713801 | 53.60 | 47.42 | 0.00713801 | 86.89 | 0.00547004 | 57.10 | 11.5697 | 75.00 | 0.00734899 | 32.3853 | 7261.75 | 0.00 | 11265.03 | 8132.37 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 15791.601 | 15791.601 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15791.60 | 15791.60 | -999. | 63.63 | 48.95 | 0.00571544 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00633824 | 30.9577 | 11037.50 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15465.120 | 12382.538 | 542.273547 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 14396.85 | 14396.85 | 542.273547 | 77.45 | 56.67 | 0.00732630 | 53.60 | 47.76 | 0.00732630 | 87.07 | 0.00547019 | 57.16 | 8.2975 | 75.00 | 0.00749425 | 33.0183 | 10339.14 | 0.00 | 15471.57 | 11173.12 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 15790.619 | 15790.619 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15790.62 | 15790.62 | -999. | 66.00 | 50.19 | 0.00589149 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00633814 | 30.9572 | 11036.63 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 7387.212 | 5915.109 | 261.324358 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | 7027.43 | 7027.43 | 261.324358 | 77.76 | 56.62 | 0.00722088 | 53.60 | 47.57 | 0.00722088 | 82.63 | 0.00546644 | 55.63 | 17.2181 | 75.00 | 0.00757794 | 33.3827 | 4970.71 | 0.00 | 7390.29 | 5335.82 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 12496.439 | 12496.439 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 12496.44 | 12496.44 | -999. | 59.56 | 46.40 | 0.00522928 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00611825 | 29.8922 | 8129.73 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 10406.969 | 8335.719 | 365.231119 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | 9781.54 | 9781.54 | 365.231119 | 77.66 | 56.43 | 0.00711947 | 53.60 | 47.39 | 0.00711947 | 84.89 | 0.00546834 | 56.41 | 12.3196 | 75.00 | 0.00734973 | 32.3887 | 6945.17 | 0.00 | 10411.31 | 7521.15 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 15787.505 | 15787.505 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 15787.50 | 15787.50 | -999. | 63.09 | 48.66 | 0.00567472 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.99 | 0.00633783 | 30.9557 | 11033.89 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 17974.576 | 14386.007 | 631.509032 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | 16687.77 | 16687.77 | 631.509032 | 77.34 | 56.57 | 0.00728641 | 53.60 | 47.69 | 0.00728641 | 87.51 | 0.00547057 | 57.31 | 7.1250 | 75.00 | 0.00741239 | 32.6615 | 12034.90 | 0.00 | 17982.08 | 12982.07 |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 21068.420 | 21068.420 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 21068.42 | 21068.42 | -999. | 66.84 | 50.40 | 0.00582483 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00619840 | 30.2873 | 15694.09 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 9565.775 | 7657.842 | 335.291003 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | 9007.82 | 9007.82 | 335.291003 | 77.74 | 56.55 | 0.00717734 | 53.60 | 47.49 | 0.00717734 | 84.63 | 0.00546812 | 56.32 | 13.4197 | 75.00 | 0.00739752 | 32.5969 | 6360.13 | 0.00 | 9569.77 | 6910.06 |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 17757.336 | 17757.336 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 17757.34 | 17757.34 | -999. | 62.29 | 47.75 | 0.00535026 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00603147 | 29.4781 | 12772.28 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 13049.577 | 10419.012 | 427.940210 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 11782.28 | 11782.28 | 427.940210 | 78.34 | 56.61 | 0.00708141 | 53.60 | 47.32 | 0.00708141 | 93.02 | 0.00547527 | 59.13 | 10.5143 | 75.00 | 0.00727013 | 32.0410 | 8159.51 | 0.00 | 13055.02 | 9402.95 |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 21070.698 | 21070.698 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 21070.70 | 21070.70 | -999. | 64.39 | 49.13 | 0.00564727 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00619857 | 30.2882 | 15696.10 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 17832.190 | 14274.953 | 628.622285 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | 16592.22 | 16592.22 | 628.622285 | 77.31 | 56.57 | 0.00729149 | 53.60 | 47.70 | 0.00729149 | 87.07 | 0.00547019 | 57.16 | 7.1577 | 75.00 | 0.00742528 | 32.7177 | 11971.12 | 0.00 | 17839.63 | 12877.16 |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 21068.210 | 21068.210 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 21068.21 | 21068.21 | -999. | 66.81 | 50.39 | 0.00582310 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00619839 | 30.2873 | 15693.91 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 9597.335 | 7683.434 | 341.326513 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | 9094.88 | 9094.88 | 341.326513 | 77.54 | 56.51 | 0.00719746 | 53.60 | 47.53 | 0.00719746 | 83.30 | 0.00546700 | 55.86 | 13.1824 | 75.00 | 0.00744264 | 32.7935 | 6477.67 | 0.00 | 9601.34 | 6931.45 |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 17754.868 | 17754.868 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 17754.87 | 17754.87 | -999. | 62.47 | 47.85 | 0.00536210 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00603123 | 29.4769 | 12770.10 | 0.00 | -999.0 | -999.0 |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 11420.596 | 9145.261 | 395.903826 | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | 10649.18 | 10649.18 | 395.903826 | 77.77 | 56.56 | 0.00717698 | 53.60 | 47.49 | 0.00717698 | 86.63 | 0.00546981 | 57.01 | 11.3651 | 75.00 | 0.00725543 | 31.9772 | 7512.89 | 0.00 | 11425.36 | 8250.76 |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 21065.964 | 21065.964 | -999. | -999. | -999.00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | 21065.96 | 21065.96 | -999. | 63.78 | 48.81 | 0.00560235 | 122.00 | 70.53 | 0.00800000 | -0.2 | 0.00095524 | -0.2 | -999.000 | 71.98 | 0.00619822 | 30.2865 | 15691.93 | 0.00 | -999.0 | -999.0 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Coils| Coil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [Btu/h] | Coil Final Gross Sensible Capacity [Btu/h] | Coil Final Reference Air Volume Flow Rate [ft3/min] | Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] | Coil U-value Times Area Value [Btu/h-F] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [Btu/lbm-R] | Dry Air Heat Capacity [Btu/lbm-R] | Standard Air Density Adjusted for Elevation [lb/ft3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [ft3/min] | Supply Fan Maximum Air Mass Flow Rate [lb/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [Btu/lbm-R] | Plant Fluid Density [lb/ft3] | Plant Maximum Fluid Mass Flow Rate [lb/s] | Plant Design Fluid Return Temperature [F] | Plant Design Fluid Supply Temperature [F] | Plant Design Fluid Temperature Difference [deltaF] | Plant Design Capacity [Btu/h] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [Btu/h] | Coil Sensible Capacity at Ideal Loads Peak [Btu/h] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] | Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Coil Entering Air Drybulb at Ideal Loads Peak [F] | Coil Entering Air Wetbulb at Ideal Loads Peak [F] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Leaving Air Drybulb at Ideal Loads Peak [F] | Coil Leaving Air Wetbulb at Ideal Loads Peak [F] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] | Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] | Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] | Outdoor Air Drybulb at Ideal Loads Peak [F] | Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [F] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [F] | System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Drybulb at Ideal Loads Peak [F] | Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] | Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] | Coil Total Capacity at Rating Conditions [Btu/h] | Coil Sensible Capacity at Rating Conditions [Btu/h] | Coil Air Mass Flow Rate at Rating Conditions [lb/s] | Coil Entering Air Drybulb at Rating Conditions [F] | Coil Entering Air Wetbulb at Rating Conditions [F] | Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] | Coil Leaving Air Drybulb at Rating Conditions [F] | Coil Leaving Air Wetbulb at Rating Conditions [F] | Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R] | |
| DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 14233.768 | 11387.485 | 490.903442 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 490.903442 | 0.49929473 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:10:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:20:00 | Sensible | 13154.16 | 13154.16 | 0.9242 | 0.49929473 | 490.903442 | 77.67 | 56.54 | 0.00719006 | 10.5 | 53.60 | 47.51 | 0.00719006 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 631.784 | 12522.38 | 88.40 | 0.00547132 | 57.61 | 44.99498340 | 9.1658 | 75.00 | 0.00736349 | 75.00 | 0.00734419 | 32.3643 | 9351.43 | 0.00 | 14239.71 | 10274.48 | 0.47957636 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.61 | 55.06 | 0.00909005 | 8.6 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 18622.961 | 18622.961 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 490.903442 | 0.49929473 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18622.96 | 18622.96 | 1.0000 | -0.215270E+04 | -999. | 65.36 | 49.32 | 0.00553627 | 7.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 18622.96 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00599853 | 71.98 | 0.00599853 | 29.3200 | 13536.17 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7911.575 | 6111.833 | 243.384536 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2430 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 243.384536 | 0.24754484 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 7148.55 | 7148.55 | 0.9036 | 0.24754484 | 243.384536 | 80.01 | 56.78 | 0.00681859 | 10.6 | 53.60 | 46.84 | 0.00681859 | 7.0 | -999. | -999.0 | -999.0 | -999.0 | 313.231 | 6835.32 | 93.02 | 0.00547527 | 59.13 | 44.99498340 | 18.4872 | 75.00 | 0.00714922 | 75.00 | 0.00714922 | 31.5144 | 4343.48 | 0.00 | 7914.88 | 5544.72 | 0.23776869 | 80.00 | 67.00 | 0.01118466 | 13.2 | 53.43 | 53.40 | 0.00865935 | 8.1 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15585.183 | 15585.183 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 243.384536 | 0.24754484 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15585.18 | 15585.18 | 1.0000 | -0.215270E+04 | -999. | 58.64 | 45.40 | 0.00490474 | 6.5 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15585.18 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00580049 | 71.98 | 0.00580049 | 28.3596 | 10855.53 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9463.763 | 7580.409 | 325.388284 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 325.388284 | 0.33095033 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:50:00 | Sensible | 8833.30 | 8833.30 | 0.9334 | 0.33095033 | 325.388284 | 78.00 | 56.35 | 0.00698885 | 10.4 | 53.60 | 47.15 | 0.00698885 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 418.769 | 8414.53 | 86.23 | 0.00546947 | 56.87 | 44.99498340 | 13.8281 | 75.00 | 0.00723266 | 75.00 | 0.00721440 | 31.7987 | 6138.65 | 0.00 | 9467.71 | 6837.86 | 0.31788029 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.51 | 55.02 | 0.00908881 | 8.6 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 18625.998 | 18625.998 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR | Fan:OnOff | 325.388284 | 0.33095033 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18626.00 | 18626.00 | 1.0000 | -0.215270E+04 | -999. | 62.00 | 47.54 | 0.00530138 | 7.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 18626.00 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00599881 | 71.98 | 0.00599881 | 29.3213 | 13538.85 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13620.273 | 10905.182 | 470.613354 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 470.613354 | 0.47865781 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | Sensible | 12616.09 | 12616.09 | 0.9263 | 0.47865781 | 470.613354 | 77.68 | 56.56 | 0.00719648 | 10.5 | 53.60 | 47.53 | 0.00719648 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 605.671 | 12010.42 | 87.96 | 0.00547095 | 57.46 | 44.99498340 | 9.5609 | 75.00 | 0.00737890 | 75.00 | 0.00737890 | 32.5157 | 8973.01 | 0.00 | 13625.96 | 9838.32 | 0.45975445 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.64 | 55.09 | 0.00909760 | 8.6 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 18625.828 | 18625.828 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR | Fan:OnOff | 470.613354 | 0.47865781 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18625.83 | 18625.83 | 1.0000 | -0.215270E+04 | -999. | 65.08 | 49.18 | 0.00551658 | 7.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 18625.83 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00599879 | 71.98 | 0.00599879 | 29.3212 | 13538.70 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7090.595 | 5675.475 | 243.380152 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 243.380152 | 0.24754038 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 6696.74 | 6696.74 | 0.9445 | 0.24754038 | 243.380152 | 78.33 | 56.48 | 0.00700233 | 10.4 | 53.60 | 47.17 | 0.00700233 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 313.226 | 6383.51 | 83.96 | 0.00546756 | 56.09 | 44.99498340 | 18.4875 | 75.00 | 0.00741067 | 75.00 | 0.00737049 | 32.4792 | 4040.70 | 0.00 | 7093.55 | 5119.97 | 0.23776441 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.49 | 55.00 | 0.00908184 | 8.6 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15584.962 | 15584.962 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR | Fan:OnOff | 243.380152 | 0.24754038 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15584.96 | 15584.96 | 1.0000 | -0.215270E+04 | -999. | 58.63 | 45.40 | 0.00490470 | 6.5 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15584.96 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00580046 | 71.98 | 0.00580046 | 28.3594 | 10855.33 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 8616.396 | 6895.017 | 303.486433 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 303.486433 | 0.30867410 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:10:00 | Sensible | 8142.91 | 8142.91 | 0.9450 | 0.30867410 | 303.486433 | 77.72 | 56.22 | 0.00696897 | 10.3 | 53.60 | 47.11 | 0.00696897 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 390.581 | 7752.33 | 83.56 | 0.00546722 | 55.95 | 44.99498340 | 14.8260 | 75.00 | 0.00723038 | 75.00 | 0.00722231 | 31.8334 | 5757.45 | 0.00 | 8619.99 | 6220.22 | 0.29648380 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.12 | 55.34 | 0.00913415 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 18622.755 | 18622.755 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR | Fan:OnOff | 303.486433 | 0.30867410 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 18622.76 | 18622.76 | 1.0000 | -0.215270E+04 | -999. | 61.28 | 47.16 | 0.00525079 | 7.1 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 18622.76 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00599851 | 71.98 | 0.00599851 | 29.3199 | 13535.99 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 16117.329 | 12909.226 | 563.955581 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 563.955581 | 0.57359559 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 14970.58 | 14970.58 | 0.9288 | 0.57359559 | 563.955581 | 77.44 | 56.67 | 0.00732635 | 10.5 | 53.60 | 47.76 | 0.00732635 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 725.800 | 14244.78 | 87.51 | 0.00547057 | 57.31 | 44.99498340 | 7.9785 | 75.00 | 0.00748725 | 75.00 | 0.00747212 | 32.9219 | 10751.52 | 0.00 | 16124.05 | 11647.43 | 0.55094290 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.94 | 55.26 | 0.00912623 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15788.475 | 15788.475 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 563.955581 | 0.57359559 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15788.48 | 15788.48 | 1.0000 | -0.215270E+04 | -999. | 66.23 | 50.31 | 0.00590847 | 8.1 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15788.48 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00633793 | 71.99 | 0.00633793 | 30.9562 | 11034.74 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7691.867 | 6160.461 | 268.321318 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 268.321318 | 0.27290788 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | Sensible | 7272.02 | 7272.02 | 0.9454 | 0.27290788 | 268.321318 | 77.95 | 56.68 | 0.00721637 | 10.5 | 53.60 | 47.56 | 0.00721637 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 345.325 | 6926.70 | 83.96 | 0.00546756 | 56.09 | 44.99498340 | 16.7691 | 75.00 | 0.00756871 | 75.00 | 0.00731690 | 32.2454 | 4962.75 | 0.00 | 7695.08 | 5558.18 | 0.26213009 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.87 | 55.22 | 0.00911947 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12497.416 | 12497.416 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 268.321318 | 0.27290788 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12497.42 | 12497.42 | 1.0000 | -0.215270E+04 | -999. | 59.88 | 46.58 | 0.00525258 | 6.9 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12497.42 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00611839 | 71.99 | 0.00611839 | 29.8928 | 8130.59 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11260.335 | 9014.017 | 388.902314 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 388.902314 | 0.39555004 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 11:00:00 | Sensible | 10483.77 | 10483.77 | 0.9310 | 0.39555004 | 388.902314 | 77.82 | 56.52 | 0.00713801 | 10.5 | 53.60 | 47.42 | 0.00713801 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 500.510 | 9983.26 | 86.89 | 0.00547004 | 57.10 | 44.99498340 | 11.5697 | 75.00 | 0.00735624 | 75.00 | 0.00734899 | 32.3853 | 7261.75 | 0.00 | 11265.03 | 8132.37 | 0.37992880 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.64 | 55.08 | 0.00909582 | 8.6 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15791.601 | 15791.601 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR | Fan:OnOff | 388.902314 | 0.39555004 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15791.60 | 15791.60 | 1.0000 | -0.215270E+04 | -999. | 63.63 | 48.95 | 0.00571544 | 7.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15791.60 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00633824 | 71.99 | 0.00633824 | 30.9577 | 11037.50 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 15465.120 | 12382.538 | 542.273547 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2433 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 542.273547 | 0.55154293 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 14396.85 | 14396.85 | 0.9309 | 0.55154293 | 542.273547 | 77.45 | 56.67 | 0.00732630 | 10.5 | 53.60 | 47.76 | 0.00732630 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 697.896 | 13698.95 | 87.07 | 0.00547019 | 57.16 | 44.99498340 | 8.2975 | 75.00 | 0.00749425 | 75.00 | 0.00749425 | 33.0183 | 10339.14 | 0.00 | 15471.57 | 11173.12 | 0.52976115 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.99 | 55.28 | 0.00912913 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15790.619 | 15790.619 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR | Fan:OnOff | 542.273547 | 0.55154293 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15790.62 | 15790.62 | 1.0000 | -0.215270E+04 | -999. | 66.00 | 50.19 | 0.00589149 | 8.1 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15790.62 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00633814 | 71.99 | 0.00633814 | 30.9572 | 11036.63 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 7387.212 | 5915.109 | 261.324358 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 261.324358 | 0.26579132 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 19:00:00 | Sensible | 7027.43 | 7027.43 | 0.9513 | 0.26579132 | 261.324358 | 77.76 | 56.62 | 0.00722088 | 10.5 | 53.60 | 47.57 | 0.00722088 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 336.320 | 6691.11 | 82.63 | 0.00546644 | 55.63 | 44.99498340 | 17.2181 | 75.00 | 0.00758579 | 75.00 | 0.00757794 | 33.3827 | 4970.71 | 0.00 | 7390.29 | 5335.82 | 0.25529457 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.21 | 55.40 | 0.00914596 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 12496.439 | 12496.439 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR | Fan:OnOff | 261.324358 | 0.26579132 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 12496.44 | 12496.44 | 1.0000 | -0.215270E+04 | -999. | 59.56 | 46.40 | 0.00522928 | 6.8 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 12496.44 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00611825 | 71.99 | 0.00611825 | 29.8922 | 8129.73 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 10406.969 | 8335.719 | 365.231119 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 365.231119 | 0.37147422 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 10:30:00 | Sensible | 9781.54 | 9781.54 | 0.9399 | 0.37147422 | 365.231119 | 77.66 | 56.43 | 0.00711947 | 10.4 | 53.60 | 47.39 | 0.00711947 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 470.046 | 9311.49 | 84.89 | 0.00546834 | 56.41 | 44.99498340 | 12.3196 | 75.00 | 0.00735146 | 75.00 | 0.00734973 | 32.3887 | 6945.17 | 0.00 | 10411.31 | 7521.15 | 0.35680379 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.01 | 55.30 | 0.00913262 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 15787.505 | 15787.505 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR | Fan:OnOff | 365.231119 | 0.37147422 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 15787.50 | 15787.50 | 1.0000 | -0.215270E+04 | -999. | 63.09 | 48.66 | 0.00567472 | 7.6 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 15787.50 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.99 | 0.00633783 | 71.99 | 0.00633783 | 30.9557 | 11033.89 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17974.576 | 14386.007 | 631.509032 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 631.509032 | 0.64230377 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | Sensible | 16687.77 | 16687.77 | 0.9284 | 0.64230377 | 631.509032 | 77.34 | 56.57 | 0.00728641 | 10.5 | 53.60 | 47.69 | 0.00728641 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 812.740 | 15875.03 | 87.51 | 0.00547057 | 57.31 | 44.99498340 | 7.1250 | 75.00 | 0.00742571 | 75.00 | 0.00741239 | 32.6615 | 12034.90 | 0.00 | 17982.08 | 12982.07 | 0.61693762 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.05 | 55.31 | 0.00913150 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 21068.420 | 21068.420 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR | Fan:OnOff | 631.509032 | 0.64230377 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 21068.42 | 21068.42 | 1.0000 | -0.215270E+04 | -999. | 66.84 | 50.40 | 0.00582483 | 8.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 21068.42 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00619840 | 71.98 | 0.00619840 | 30.2873 | 15694.09 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9565.775 | 7657.842 | 335.291003 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 335.291003 | 0.34102232 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | Sensible | 9007.82 | 9007.82 | 0.9417 | 0.34102232 | 335.291003 | 77.74 | 56.55 | 0.00717734 | 10.5 | 53.60 | 47.49 | 0.00717734 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 431.513 | 8576.31 | 84.63 | 0.00546812 | 56.32 | 44.99498340 | 13.4197 | 75.00 | 0.00744226 | 75.00 | 0.00739752 | 32.5969 | 6360.13 | 0.00 | 9569.77 | 6910.06 | 0.32755452 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.99 | 55.28 | 0.00912762 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 17757.336 | 17757.336 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR | Fan:OnOff | 335.291003 | 0.34102232 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 17757.34 | 17757.34 | 1.0000 | -0.215270E+04 | -999. | 62.29 | 47.75 | 0.00535026 | 7.3 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17757.34 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00603147 | 71.98 | 0.00603147 | 29.4781 | 12772.28 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 13049.577 | 10419.012 | 427.940210 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2431 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 427.940210 | 0.43525523 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 11782.28 | 11782.28 | 0.9029 | 0.43525523 | 427.940210 | 78.34 | 56.61 | 0.00708141 | 10.5 | 53.60 | 47.32 | 0.00708141 | 7.1 | -999. | -999.0 | -999.0 | -999.0 | 550.751 | 11231.53 | 93.02 | 0.00547527 | 59.13 | 44.99498340 | 10.5143 | 75.00 | 0.00727013 | 75.00 | 0.00727013 | 32.0410 | 8159.51 | 0.00 | 13055.02 | 9402.95 | 0.41806594 | 80.00 | 67.00 | 0.01118466 | 13.2 | 54.39 | 54.36 | 0.00897163 | 8.4 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 21070.698 | 21070.698 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR | Fan:OnOff | 427.940210 | 0.43525523 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 21070.70 | 21070.70 | 1.0000 | -0.215270E+04 | -999. | 64.39 | 49.13 | 0.00564727 | 7.7 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 21070.70 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00619857 | 71.98 | 0.00619857 | 30.2882 | 15696.10 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 17832.190 | 14274.953 | 628.622285 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 628.622285 | 0.63936768 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 17:50:00 | Sensible | 16592.22 | 16592.22 | 0.9305 | 0.63936768 | 628.622285 | 77.31 | 56.57 | 0.00729149 | 10.5 | 53.60 | 47.70 | 0.00729149 | 7.3 | -999. | -999.0 | -999.0 | -999.0 | 809.025 | 15783.19 | 87.07 | 0.00547019 | 57.16 | 44.99498340 | 7.1577 | 75.00 | 0.00743190 | 75.00 | 0.00742528 | 32.7177 | 11971.12 | 0.00 | 17839.63 | 12877.16 | 0.61411749 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.13 | 55.35 | 0.00913756 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 21068.210 | 21068.210 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR | Fan:OnOff | 628.622285 | 0.63936768 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 21068.21 | 21068.21 | 1.0000 | -0.215270E+04 | -999. | 66.81 | 50.39 | 0.00582310 | 8.2 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 21068.21 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00619839 | 71.98 | 0.00619839 | 30.2873 | 15693.91 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 9597.335 | 7683.434 | 341.326513 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 341.326513 | 0.34716100 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:40:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:50:00 | Sensible | 9094.88 | 9094.88 | 0.9476 | 0.34716100 | 341.326513 | 77.54 | 56.51 | 0.00719746 | 10.5 | 53.60 | 47.53 | 0.00719746 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 439.281 | 8655.60 | 83.30 | 0.00546700 | 55.86 | 44.99498340 | 13.1824 | 75.00 | 0.00746022 | 75.00 | 0.00744264 | 32.7935 | 6477.67 | 0.00 | 9601.34 | 6931.45 | 0.33345076 | 80.00 | 67.00 | 0.01118466 | 13.2 | 56.34 | 55.47 | 0.00915625 | 8.8 | |
| MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 17754.868 | 17754.868 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR | Fan:OnOff | 341.326513 | 0.34716100 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 17754.87 | 17754.87 | 1.0000 | -0.215270E+04 | -999. | 62.47 | 47.85 | 0.00536210 | 7.3 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 17754.87 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00603123 | 71.98 | 0.00603123 | 29.4769 | 12770.10 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. | |
| DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Cooling:DX:SingleSpeed | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedCoolingCapacity | N/A | Yes | Yes | unknown | No | 11420.596 | 9145.261 | 395.903826 | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2432 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 395.903826 | 0.40267123 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:20:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 15:30:00 | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN CLG .4% CONDNS DB=>MWB | 7/21 18:00:00 | Sensible | 10649.18 | 10649.18 | 0.9325 | 0.40267123 | 395.903826 | 77.77 | 56.56 | 0.00717698 | 10.5 | 53.60 | 47.49 | 0.00717698 | 7.2 | -999. | -999.0 | -999.0 | -999.0 | 509.521 | 10139.66 | 86.63 | 0.00546981 | 57.01 | 44.99498340 | 11.3651 | 75.00 | 0.00739588 | 75.00 | 0.00725543 | 31.9772 | 7512.89 | 0.00 | 11425.36 | 8250.76 | 0.38676876 | 80.00 | 67.00 | 0.01118466 | 13.2 | 55.72 | 55.13 | 0.00910530 | 8.7 | |
| MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR | Coil:Heating:Electric | AirLoop | AirLoopHVAC | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_BACKROW_TOPFLOOR | Non-Coincident | FractionOfAutosizedHeatingCapacity | N/A | Yes | No | unknown | No | 21065.964 | 21065.964 | -999. | -999. | -999.00 | -999.0000 | 1.00000 | 1.00000 | 0.2436 | 0.2400 | 0.0610 | SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR | Fan:OnOff | 395.903826 | 0.40267123 | -999.000 | -999.000 | -999. | -999.0 | -999.0 | -999.0 | -999.0 | -999.000 | -999. | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | unknown | unknown | DENVER-AURORA-BUCKLEY.AFB_CO_USA ANN HTG 99.6% CONDNS DB | 12/21 15:00:00 | Sensible | 21065.96 | 21065.96 | 1.0000 | -0.215270E+04 | -999. | 63.78 | 48.81 | 0.00560235 | 7.6 | 122.00 | 70.53 | 0.00800000 | 17.0 | -999. | -999.0 | -999.0 | -999.0 | 0.000 | 21065.96 | -0.2 | 0.00095524 | -0.2 | 44.99498340 | -999.000 | 71.98 | 0.00619822 | 71.98 | 0.00619822 | 30.2865 | 15691.93 | 0.00 | -999.0 | -999.0 | -999. | -999.0 | -999.0 | -999. | -999. | -999.0 | -999.0 | -999. | -999. |
Report: System Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Economizer| High Limit Shutoff Control | Minimum Outdoor Air [ft3/min] | Maximum Outdoor Air [ft3/min] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [F] | Outdoor Air Enthalpy Limit [F] | |
| None |
| Controller:MechanicalVentilation Name | Outdoor Air Per Person [ft3/min-person] | Outdoor Air Per Area [ft3/min-ft2] | Outdoor Air Per Zone [ft3/min] | Outdoor Air ACH [ACH] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
| None |
| Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1278.00 | 6447.83 | 453.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 601.50 | 6839.50 | 248.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1265.67 | 6345.83 | 435.17 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1172.50 | 6894.67 | 535.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 604.17 | 7248.17 | 317.33 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1149.00 | 6751.83 | 493.50 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1770.83 | 5459.00 | 317.33 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1004.83 | 5459.17 | 125.33 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1778.67 | 5278.67 | 300.67 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1551.17 | 6120.83 | 380.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 835.50 | 6221.67 | 154.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1599.50 | 5967.17 | 357.67 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 2087.67 | 6104.83 | 718.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 2125.50 | 5637.83 | 642.67 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 2093.67 | 5815.17 | 667.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1210.00 | 6368.50 | 388.67 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1253.00 | 5911.33 | 308.83 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 2047.00 | 6257.00 | 793.67 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 |
| Facility | 2730.50 | 7387.17 | 908.00 |
| During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.67 | 0.00 | 0.67 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 1.00 | 0.00 | 1.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 1.50 | 0.00 | 1.50 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | 0.00 | 0.00 | 0.00 | 0.00 |
| Facility | 0.00 | 1.50 | 0.00 | 1.50 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Average Outdoor Air During Occupied Hours| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.332 | 0.000 | 0.277 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.293 | 0.000 | 0.277 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.332 | 0.000 | 0.277 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.331 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.292 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.332 | 0.000 | 0.277 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.146 | 0.000 | 0.277 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.277 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.146 | 0.000 | 0.277 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.146 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.106 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.146 | 0.000 | 0.277 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.332 | 0.000 | 0.277 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.333 | 0.000 | 0.277 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.333 | 0.000 | 0.277 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.293 | 0.000 | 0.277 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.293 | 0.000 | 0.277 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.332 | 0.000 | 0.277 |
| Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Mechanical Ventilation [ACH] | Infiltration [ACH] | AFN Infiltration [ACH] | Simple Ventilation [ACH] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.001 | 0.000 | 0.005 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 0.000 | 0.002 | 0.000 | 0.005 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Mechanical Ventilation Parameters by Zone| AirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [ft3] | Zone Area [ft2] | Design Zone Outdoor Airflow - Voz [ft3/min] | Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 1.38 | 2.00 | 10207.81 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 1.38 | 2.00 | 10207.71 | 1200.55 | 0.0000 | 0.000 |
| Total Facility | 24.79 | 36.00 | 183739.38 | 21609.96 | 0.0000 | 0.000 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Infiltration [ft3] | Total Ventilation and Infiltration [ft3] | Dynamic Target Ventilation - Voz-dyn [ft3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 29510329.31 | 54130469.59 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 25992915.06 | 50613055.34 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 29526422.28 | 54146562.56 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 29449954.74 | 54070095.02 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 25920035.25 | 50540175.53 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 29462130.90 | 54082271.18 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 12972210.74 | 37593819.07 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 9444551.30 | 34066159.63 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 12981101.93 | 37602710.26 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 12937581.75 | 37559190.08 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 9406604.40 | 34028212.73 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 12944958.02 | 37566566.35 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 29531400.32 | 54154478.25 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 29588985.33 | 54212063.26 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 29570820.17 | 54193898.11 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 25984523.61 | 50607601.54 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 26052677.52 | 50675755.45 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 29515485.31 | 54138563.24 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| Total Facility | 0.00 | 0.443189E+09 | 0.443189E+09 | 0.410793E+09 | 0.853982E+09 | 0.428131E+09 | 1097.33 | 1608.50 | 6117.83 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Infiltration [ft3/min] | Total Ventilation and Infiltration [ft3/min] | Dynamic Target Ventilation - Voz-dyn [ft3/min] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 55.8256 | 102.4003 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 49.1716 | 95.7463 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 55.8561 | 102.4307 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 55.7114 | 102.2861 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 49.0337 | 95.6084 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 55.7344 | 102.3091 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 24.5399 | 71.1174 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 17.8666 | 64.4440 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 24.5568 | 71.1342 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 24.4744 | 71.0519 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 17.7948 | 64.3722 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 24.4884 | 71.0658 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 55.8655 | 102.4457 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 55.9744 | 102.5547 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 55.9400 | 102.5203 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 49.1557 | 95.7360 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 49.2847 | 95.8649 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 55.8354 | 102.4156 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| Total Facility | 0.0000 | 838.3944 | 838.3944 | 777.1094 | 1615.5038 | 809.9097 | 1097.33 | 1608.50 | 6117.83 |
| Mechanical Ventilation [ft3] | Natural Ventilation [ft3] | Total Ventilation [ft3] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 24620140.28 | 24620140.28 | 23785081.69 | 1097.33 | 1604.33 | 6106.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 24621608.33 | 24621608.33 | 23785081.69 | 1095.33 | 1600.33 | 6112.33 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 24623077.93 | 24623077.93 | 23785081.69 | 1093.17 | 1597.00 | 6117.83 | 0.00 |
| Mechanical Ventilation [ft3/min] | Natural Ventilation [ft3/min] | Total Ventilation [ft3/min] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 46.5747 | 46.5747 | 44.9950 | 1097.33 | 1604.33 | 6106.33 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 46.5775 | 46.5775 | 44.9950 | 1095.33 | 1600.33 | 6112.33 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 46.5802 | 46.5802 | 44.9950 | 1093.17 | 1597.00 | 6117.83 |
| No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| No Limiting Factor [ft3/min] | Limits and Scheduled Limits [ft3/min] | Economizer [ft3/min] | Exhaust Flow [ft3/min] | Mixed Air Flow [ft3/min] | High Humidity [ft3/min] | Demand Controlled Ventilation [ft3/min] | Night Ventilation [ft3/min] | Demand Limiting [ft3/min] | Energy Management System [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Surfaces by Class| Total | Outdoors | |
| Wall | 74 | 50 |
| Floor | 28 | 3 |
| Roof | 21 | 2 |
| Internal Mass | 0 | 0 |
| Building Detached Shading | 0 | 0 |
| Fixed Detached Shading | 0 | 0 |
| Window | 30 | 30 |
| Door | 18 | 18 |
| Glass Door | 0 | 0 |
| Shading | 60 | 60 |
| Overhang | 30 | 30 |
| Fin | 0 | 0 |
| Tubular Daylighting Device Dome | 0 | 0 |
| Tubular Daylighting Device Diffuser | 0 | 0 |
| Count | |
| HVAC Air Loops | 18 |
| Conditioned Zones | 18 |
| Unconditioned Zones | 2 |
| Supply Plenums | 0 |
| Return Plenums | 0 |
| Count | |
| IDF Objects | 1910 |
| Defaulted Fields | 1685 |
| Fields with Defaults | 6153 |
| Autosized Fields | 342 |
| Autosizable Fields | 504 |
| Autocalculated Fields | 149 |
| Autocalculatable Fields | 328 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Annual and Peak Values - Electricity| Electricity Annual Value [kWh] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
| Electricity:Facility | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| Electricity:Building | 106022.24 | 6418.34 | 02-JAN-03:10 | 20705.41 | 01-JAN-18:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| Electricity:SpaceType:GENERAL | 106022.24 | 6418.34 | 02-JAN-03:10 | 20705.41 | 01-JAN-18:10 |
| InteriorLights:Electricity | 17719.17 | 396.81 | 01-JAN-00:10 | 5771.73 | 01-JAN-19:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| InteriorLights:Electricity:SpaceType:GENERAL | 17719.17 | 396.81 | 01-JAN-00:10 | 5771.73 | 01-JAN-19:10 |
| General:InteriorLights:Electricity | 17719.17 | 396.81 | 01-JAN-00:10 | 5771.73 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:SpaceType:GENERAL | 17719.17 | 396.81 | 01-JAN-00:10 | 5771.73 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 5890.12 | 356.57 | 02-JAN-03:10 | 1150.30 | 01-JAN-18:10 |
| InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 984.40 | 22.04 | 01-JAN-00:10 | 320.65 | 01-JAN-19:10 |
| InteriorEquipment:Electricity | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| InteriorEquipment:Electricity:SpaceType:GENERAL | 88303.07 | 5995.41 | 02-JAN-04:10 | 15497.32 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 3088.82 | 28.28 | 02-JAN-03:10 | 985.58 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL | 12036.11 | 1198.77 | 01-JAN-04:10 | 1639.04 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL | 1577.30 | 15.15 | 02-JAN-02:10 | 427.18 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL | 12502.11 | 63.73 | 02-JAN-03:10 | 3196.73 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL | 9058.39 | 87.62 | 01-JAN-02:10 | 3721.08 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| television:InteriorEquipment:Electricity:SpaceType:GENERAL | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL | 46926.68 | 4099.97 | 01-JAN-09:10 | 7929.96 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL | 3113.66 | 272.04 | 01-JAN-09:10 | 526.17 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 4905.73 | 333.08 | 02-JAN-04:10 | 860.96 | 01-JAN-18:10 |
| dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 171.60 | 1.57 | 02-JAN-03:10 | 54.75 | 01-JAN-19:10 |
| refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 668.67 | 66.60 | 01-JAN-04:10 | 91.06 | 01-JAN-18:10 |
| clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 87.63 | 0.84 | 02-JAN-02:10 | 23.73 | 01-JAN-09:10 |
| electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 694.56 | 3.54 | 02-JAN-03:10 | 177.60 | 01-JAN-11:10 |
| electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 503.24 | 4.87 | 01-JAN-02:10 | 206.73 | 01-JAN-17:10 |
| television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 2607.04 | 227.78 | 01-JAN-09:10 | 440.55 | 01-JAN-20:10 |
| IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 172.98 | 15.11 | 01-JAN-09:10 | 29.23 | 01-JAN-20:10 |
| Fans:Electricity | 10748.44 | 578.57 | 06-MAY-07:30 | 3176.88 | 26-JUN-17:20 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityPurchased:Facility | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| ElectricityPurchased:Plant | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| Cogeneration:ElectricityPurchased | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| General:Cogeneration:ElectricityPurchased | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| ElectricityNet:Facility | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| ElectricityNet:Plant | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| Cogeneration:ElectricityNet | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| General:Cogeneration:ElectricityNet | 282082.67 | 8374.61 | 08-JUN-03:50 | 128220.33 | 05-JAN-09:00 |
| Electricity:HVAC | 110748.97 | 578.57 | 06-MAY-07:30 | 75917.60 | 22-DEC-04:00 |
| Ventilation:Fans:Electricity | 5068.29 | 578.57 | 01-JAN-00:10 | 578.57 | 01-JAN-00:10 |
| General:Fans:Electricity | 5680.15 | 0.00 | 06-MAY-07:30 | 2598.31 | 26-JUN-17:20 |
| ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Exterior-Lights:ExteriorLights:Electricity | 6034.31 | 0.00 | 01-JAN-06:10 | 1377.69 | 01-JAN-00:10 |
| Garage-Lights:ExteriorLights:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:Electricity | 87367.32 | 0.00 | 20-JAN-12:30 | 72862.46 | 22-DEC-04:00 |
| General:Heating:Electricity | 87367.32 | 0.00 | 20-JAN-12:30 | 72862.46 | 22-DEC-04:00 |
| Cooling:Electricity | 12633.21 | 0.00 | 01-JAN-00:10 | 14061.11 | 26-JUN-17:20 |
| General:Cooling:Electricity | 12633.21 | 0.00 | 01-JAN-00:10 | 14061.11 | 26-JUN-17:20 |
| Electricity:Plant | 59277.15 | 0.00 | 01-JAN-00:10 | 59035.64 | 07-JAN-08:10 |
| WaterSystems:Electricity | 59277.15 | 0.00 | 01-JAN-00:10 | 59035.64 | 07-JAN-08:10 |
| Water Heater:WaterSystems:Electricity | 59277.15 | 0.00 | 01-JAN-00:10 | 59035.64 | 07-JAN-08:10 |
| Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Pumps:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Natural Gas Annual Value [therm] | Natural Gas Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Cooling Annual Value [ton-hrs] | Cooling Minimum Value [ton] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [ton] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| Water:Facility | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| Water:Plant | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| WaterSystems:Water | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| Domestic Hot Water:WaterSystems:Water | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| MainsWater:Facility | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| MainsWater:Plant | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| WaterSystems:MainsWater | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| Domestic Hot Water:WaterSystems:MainsWater | 49522.55 | 0.01 | 02-JAN-02:10 | 0.18 | 14-JAN-08:50 |
| Water Heater:WaterSystems:Water | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Water Heater:WaterSystems:MainsWater | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Annual Value [lb] | Minimum Value [lb/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [lb/s] | Timestamp of Maximum {TIMESTAMP} | |
| Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
| Annual Value [ft3] | Minimum Value [ft3/min] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [ft3/min] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [gal] | Minimum Value [gal] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [gal] | Timestamp of Maximum {TIMESTAMP} | |
| None |
| Annual Value [kBtu] | Minimum Value [Btu/h] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [Btu/h] | Timestamp of Maximum {TIMESTAMP} | |
| EnergyTransfer:Facility | 1081663.24 | 833.37 | 23-AUG-03:00 | 523904.31 | 23-DEC-07:10 |
| EnergyTransfer:Building | 474207.25 | 0.00 | 06-MAY-07:30 | 257056.75 | 22-DEC-04:00 |
| EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer | 308372.90 | 0.00 | 20-JAN-12:30 | 257056.75 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer | 308372.90 | 0.00 | 20-JAN-12:30 | 257056.75 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer | 165834.35 | 0.00 | 01-JAN-00:10 | 162180.78 | 26-JUN-17:20 |
| Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer | 165834.35 | 0.00 | 01-JAN-00:10 | 162180.78 | 26-JUN-17:20 |
| General:Cooling:EnergyTransfer:Zone:BREEZEWAY | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 28050.18 | 0.00 | 01-JAN-13:00 | 15787.90 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 19283.64 | 0.00 | 01-JAN-13:00 | 15787.90 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 19283.64 | 0.00 | 01-JAN-13:00 | 15787.90 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8766.54 | 0.00 | 01-JAN-00:10 | 11343.71 | 16-AUG-16:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 8766.54 | 0.00 | 01-JAN-00:10 | 11343.71 | 16-AUG-16:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 20421.68 | 0.00 | 01-JAN-12:00 | 12636.71 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14790.62 | 0.00 | 01-JAN-12:00 | 12636.71 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 14790.62 | 0.00 | 01-JAN-12:00 | 12636.71 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5631.05 | 0.00 | 01-JAN-00:10 | 5970.31 | 16-AUG-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 5631.05 | 0.00 | 01-JAN-00:10 | 5970.31 | 16-AUG-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 27488.95 | 0.00 | 01-JAN-09:30 | 15783.72 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 18822.88 | 0.00 | 01-JAN-09:30 | 15783.72 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 18822.88 | 0.00 | 01-JAN-09:30 | 15783.72 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8666.07 | 0.00 | 01-JAN-00:10 | 7970.50 | 16-AUG-10:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 8666.07 | 0.00 | 01-JAN-00:10 | 7970.50 | 16-AUG-10:10 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 28751.64 | 0.00 | 09-JAN-13:50 | 15812.38 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22075.46 | 0.00 | 09-JAN-13:50 | 15812.38 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22075.46 | 0.00 | 09-JAN-13:50 | 15812.38 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6676.17 | 0.00 | 01-JAN-00:10 | 10924.63 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 6676.17 | 0.00 | 01-JAN-00:10 | 10924.63 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 21996.68 | 0.00 | 20-JAN-12:10 | 12673.14 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17927.45 | 0.00 | 20-JAN-12:10 | 12673.14 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 17927.45 | 0.00 | 20-JAN-12:10 | 12673.14 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4069.22 | 0.00 | 01-JAN-00:10 | 5818.96 | 26-JUN-18:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 4069.22 | 0.00 | 01-JAN-00:10 | 5818.96 | 26-JUN-18:30 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 28415.00 | 0.00 | 19-JAN-14:00 | 15812.08 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21704.79 | 0.00 | 19-JAN-14:00 | 15812.08 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 21704.79 | 0.00 | 19-JAN-14:00 | 15812.08 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6710.21 | 0.00 | 01-JAN-00:10 | 7146.67 | 17-JUL-10:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 6710.21 | 0.00 | 01-JAN-00:10 | 7146.67 | 17-JUL-10:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 25309.11 | 0.00 | 01-JAN-11:40 | 12489.21 | 16-AUG-16:30 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12244.18 | 0.00 | 01-JAN-11:40 | 12312.19 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 12244.18 | 0.00 | 01-JAN-11:40 | 12312.19 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13064.94 | 0.00 | 01-JAN-00:10 | 12489.21 | 16-AUG-16:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 13064.94 | 0.00 | 01-JAN-00:10 | 12489.21 | 16-AUG-16:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 17169.57 | 0.00 | 01-JAN-10:00 | 8913.53 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7768.09 | 0.00 | 01-JAN-10:00 | 8913.53 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 7768.09 | 0.00 | 01-JAN-10:00 | 8913.53 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9401.49 | 0.00 | 01-JAN-00:10 | 6429.46 | 26-JUN-18:40 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 9401.49 | 0.00 | 01-JAN-00:10 | 6429.46 | 26-JUN-18:40 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 25094.29 | 0.00 | 01-JAN-09:10 | 12321.04 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11877.13 | 0.00 | 01-JAN-09:10 | 12321.04 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 11877.13 | 0.00 | 01-JAN-09:10 | 12321.04 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13217.16 | 0.00 | 01-JAN-00:10 | 8896.69 | 16-AUG-13:50 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 13217.16 | 0.00 | 01-JAN-00:10 | 8896.69 | 16-AUG-13:50 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 24587.17 | 0.00 | 09-JAN-13:30 | 12359.95 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 14865.01 | 0.00 | 09-JAN-13:30 | 12359.95 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 14865.01 | 0.00 | 09-JAN-13:30 | 12359.95 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9722.16 | 0.00 | 01-JAN-00:10 | 12229.34 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 9722.16 | 0.00 | 01-JAN-00:10 | 12229.34 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 17035.02 | 0.00 | 09-JAN-14:30 | 8973.72 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10543.84 | 0.00 | 09-JAN-14:30 | 8973.72 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 10543.84 | 0.00 | 09-JAN-14:30 | 8973.72 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6491.18 | 0.00 | 01-JAN-00:10 | 6317.36 | 26-JUN-19:40 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 6491.18 | 0.00 | 01-JAN-00:10 | 6317.36 | 26-JUN-19:40 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 24528.36 | 0.00 | 09-JAN-09:50 | 12359.29 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14576.31 | 0.00 | 09-JAN-09:50 | 12359.29 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 14576.31 | 0.00 | 09-JAN-09:50 | 12359.29 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9952.05 | 0.00 | 01-JAN-00:10 | 8123.83 | 17-JUL-10:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 9952.05 | 0.00 | 01-JAN-00:10 | 8123.83 | 17-JUL-10:00 |
| EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Heating:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| General:Cooling:EnergyTransfer:Zone:ATTIC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 33790.04 | 0.00 | 09-JAN-14:10 | 18033.21 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 23112.34 | 0.00 | 09-JAN-14:10 | 18033.21 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 23112.34 | 0.00 | 09-JAN-14:10 | 18033.21 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 10677.70 | 0.00 | 01-JAN-00:10 | 9635.74 | 26-JUN-19:10 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR | 10677.70 | 0.00 | 01-JAN-00:10 | 9635.74 | 26-JUN-19:10 |
| EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 32809.39 | 0.00 | 01-JAN-10:00 | 18001.27 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 20018.19 | 0.00 | 01-JAN-10:00 | 18001.27 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 20018.19 | 0.00 | 01-JAN-10:00 | 18001.27 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 12791.20 | 0.00 | 01-JAN-00:10 | 10032.76 | 16-AUG-14:00 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR | 12791.20 | 0.00 | 01-JAN-00:10 | 10032.76 | 16-AUG-14:00 |
| EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 33331.66 | 0.00 | 01-JAN-13:20 | 18006.62 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 20540.74 | 0.00 | 01-JAN-13:20 | 18006.62 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 20540.74 | 0.00 | 01-JAN-13:20 | 18006.62 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 12790.92 | 0.00 | 01-JAN-00:10 | 14240.37 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR | 12790.92 | 0.00 | 01-JAN-00:10 | 14240.37 | 26-JUN-17:30 |
| EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 26407.47 | 0.00 | 19-JAN-14:40 | 14635.64 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19028.49 | 0.00 | 19-JAN-14:40 | 14635.64 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 19028.49 | 0.00 | 19-JAN-14:40 | 14635.64 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7378.98 | 0.00 | 01-JAN-00:10 | 8226.03 | 26-JUN-19:50 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR | 7378.98 | 0.00 | 01-JAN-00:10 | 8226.03 | 26-JUN-19:50 |
| EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 24859.22 | 0.00 | 01-JAN-12:30 | 14594.04 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 15646.37 | 0.00 | 01-JAN-12:30 | 14594.04 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 15646.37 | 0.00 | 01-JAN-12:30 | 14594.04 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9212.85 | 0.00 | 01-JAN-00:10 | 8133.35 | 26-JUN-19:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR | 9212.85 | 0.00 | 01-JAN-00:10 | 8133.35 | 26-JUN-19:30 |
| EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 34161.83 | 0.00 | 09-JAN-14:00 | 18040.32 | 22-DEC-04:00 |
| Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 23547.37 | 0.00 | 09-JAN-14:00 | 18040.32 | 22-DEC-04:00 |
| General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 23547.37 | 0.00 | 09-JAN-14:00 | 18040.32 | 22-DEC-04:00 |
| Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 10614.46 | 0.00 | 01-JAN-00:10 | 14396.01 | 26-JUN-17:30 |
| General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR | 10614.46 | 0.00 | 01-JAN-00:10 | 14396.01 | 26-JUN-17:30 |
| PlantLoopHeatingDemand:Facility | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| PlantLoopHeatingDemand:Plant | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| WaterSystems:PlantLoopHeatingDemand | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| General:WaterSystems:PlantLoopHeatingDemand | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| EnergyTransfer:HVAC | 482042.51 | 0.00 | 06-MAY-07:30 | 248606.71 | 22-DEC-04:00 |
| HeatingCoils:EnergyTransfer | 298308.48 | 0.00 | 20-JAN-12:30 | 248606.71 | 22-DEC-04:00 |
| CoolingCoils:EnergyTransfer | 183734.03 | 0.00 | 01-JAN-00:10 | 171011.48 | 26-JUN-17:20 |
| EnergyTransfer:Plant | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| WaterSystems:EnergyTransfer | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| Domestic Hot Water:WaterSystems:EnergyTransfer | 125413.49 | 833.37 | 23-AUG-03:00 | 33480.91 | 19-FEB-09:00 |
| Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Annual Building Sensible Heat Gain Components| HVAC Zone Eq & Other Sensible Air Heating [kBtu] | HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] | HVAC Terminal Unit Sensible Air Heating [kBtu] | HVAC Terminal Unit Sensible Air Cooling [ton-hrs] | HVAC Input Heated Surface Heating [kBtu] | HVAC Input Cooled Surface Cooling [ton-hrs] | People Sensible Heat Addition [kBtu] | Lights Sensible Heat Addition [kBtu] | Equipment Sensible Heat Addition [kBtu] | Window Heat Addition [kBtu] | Interzone Air Transfer Heat Addition [kBtu] | Infiltration Heat Addition [kBtu] | Opaque Surface Conduction and Other Heat Addition [kBtu] | Equipment Sensible Heat Removal [kBtu] | Window Heat Removal [kBtu] | Interzone Air Transfer Heat Removal [kBtu] | Infiltration Heat Removal [kBtu] | Opaque Surface Conduction and Other Heat Removal [kBtu] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 19283.435 | -730.06 | 0.000 | 0.000 | 3067.919 | 3361.146 | 10464.601 | 13221.361 | 0.000 | 692.233 | 0.000 | 0.000 | -7051.28 | 0.000 | -20837.12 | -13435.78 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 14790.473 | -468.94 | 0.000 | 0.000 | 3062.368 | 3361.146 | 10464.601 | 6779.737 | 0.000 | 648.920 | 0.000 | 0.000 | -2855.30 | 0.000 | -19427.49 | -11193.41 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000 | 0.000 | 18822.678 | -721.69 | 0.000 | 0.000 | 3066.827 | 3361.146 | 10464.601 | 13792.069 | 0.000 | 692.220 | 0.000 | 0.000 | -6931.10 | 0.000 | -20865.42 | -13736.99 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 22075.262 | -555.98 | 0.000 | 0.000 | 3077.207 | 3361.146 | 10464.601 | 8097.526 | 0.000 | 692.273 | 0.000 | 0.000 | -7285.80 | 0.000 | -20692.74 | -13113.30 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 17927.306 | -338.88 | 0.000 | 0.000 | 3075.732 | 3361.146 | 10464.601 | 1498.850 | 0.000 | 649.008 | 0.000 | 0.000 | -3060.47 | 0.000 | -19255.26 | -10591.69 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 0.000 | 0.000 | 21704.594 | -558.81 | 0.000 | 0.000 | 3077.004 | 3361.146 | 10464.601 | 8627.647 | 0.000 | 692.223 | 0.000 | 0.000 | -7115.27 | 0.000 | -20707.24 | -13394.52 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 12244.033 | -1088.02 | 0.000 | 0.000 | 3030.892 | 3361.146 | 10464.601 | 13068.884 | 0.000 | 486.545 | 0.001 | 0.000 | -7327.41 | 0.000 | -14374.70 | -7889.04 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 7767.995 | -782.94 | 0.000 | 0.000 | 3018.230 | 3361.146 | 10464.601 | 6706.075 | 0.000 | 443.390 | 0.000 | 0.000 | -2974.38 | 0.000 | -12986.82 | -6398.74 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000 | 0.000 | 11876.988 | -1100.69 | 0.000 | 0.000 | 3031.199 | 3361.146 | 10464.601 | 13608.296 | 0.000 | 486.545 | 0.000 | 0.000 | -7192.06 | 0.000 | -14406.27 | -8013.32 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 14864.867 | -809.64 | 0.000 | 0.000 | 3046.771 | 3361.146 | 10464.601 | 7990.705 | 0.000 | 486.552 | 0.000 | 0.000 | -7528.59 | 0.000 | -14232.61 | -8731.26 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 10543.750 | -540.57 | 0.000 | 0.000 | 3044.124 | 3361.146 | 10464.601 | 1463.256 | 0.000 | 443.365 | 0.000 | 0.000 | -3161.07 | 0.000 | -12796.34 | -6871.63 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 0.000 | 0.000 | 14576.176 | -828.78 | 0.000 | 0.000 | 3048.433 | 3361.146 | 10464.601 | 8490.501 | 0.000 | 486.546 | 0.000 | 0.000 | -7341.70 | 0.000 | -14251.01 | -8882.66 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 0.000 | 0.000 | 23112.132 | -889.21 | 0.000 | 0.000 | 3059.008 | 3361.146 | 10464.601 | 8498.317 | 0.000 | 686.934 | 0.000 | 0.000 | -7317.66 | 0.000 | -20888.24 | -10298.55 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 20017.978 | -1065.22 | 0.000 | 0.000 | 3048.551 | 3361.146 | 10464.601 | 13636.903 | 0.000 | 687.011 | 0.000 | 0.000 | -7141.76 | 0.000 | -21035.23 | -10248.03 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 20540.529 | -1065.20 | 0.000 | 0.000 | 3048.869 | 3361.146 | 10464.601 | 13087.617 | 0.000 | 687.011 | 0.000 | 0.000 | -7267.78 | 0.000 | -21004.35 | -10126.71 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 0.000 | 0.000 | 19028.328 | -614.51 | 0.000 | 0.000 | 3055.913 | 3361.146 | 10464.601 | 1462.731 | 0.000 | 644.005 | 0.000 | 0.000 | -3144.07 | 0.000 | -19431.05 | -8062.59 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 0.000 | 0.000 | 15646.217 | -767.23 | 0.000 | 0.000 | 3041.063 | 3361.146 | 10464.601 | 6713.445 | 0.000 | 643.980 | 0.000 | 0.000 | -2947.29 | 0.000 | -19604.11 | -8106.18 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 0.000 | 0.000 | 23547.153 | -883.95 | 0.000 | 0.000 | 3058.566 | 3361.146 | 10464.601 | 7983.268 | 0.000 | 687.181 | 0.000 | 0.000 | -7486.61 | 0.000 | -20866.03 | -10134.78 |
| BREEZEWAY | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 |
| ATTIC | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 0.000 | 18493.524 | 157324.282 | 0.000 | 0.000 | 0.000 | -175817.81 | -0.69 |
| Total Facility | 0.000 | 0.000 | 308369.894 | -13810.30 | 0.000 | 0.000 | 54958.677 | 60500.637 | 188362.826 | 154727.187 | 0.000 | 29429.466 | 157324.283 | 0.000 | -105129.58 | 0.000 | -503479.84 | -179229.86 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 16-AUG-16:36 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 140.35 | 526.52 | 1350.56 | 9012.02 | 0.00 | 1727.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1411.7 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 16-AUG-13:00 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 115.09 | 141.03 | 1084.63 | 2714.89 | 0.00 | 1772.06 | 144.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 16-AUG-10:09 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 141.03 | 1089.80 | 7511.85 | 0.00 | 1386.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -2273.9 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 26-JUN-17:30 | 0.00 | 0.00 | 0.00 | -0.9 | 0.00 | 0.00 | 263.16 | 733.36 | 1664.02 | 8106.15 | 0.00 | 2027.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1869.0 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 26-JUN-18:30 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.76 | 987.22 | 1724.99 | 1340.65 | 0.00 | 1732.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -393.1 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 17-JUL-09:00 | 0.00 | 0.00 | 0.00 | -0.6 | 0.00 | 0.00 | 115.09 | 141.03 | 1096.02 | 5739.51 | 0.00 | 1478.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1422.3 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 16-AUG-16:30 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 140.35 | 526.52 | 1350.56 | 8964.20 | 0.00 | 1239.39 | 269.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 26-JUN-18:49 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 426.56 | 987.22 | 1724.99 | 418.08 | 0.00 | 1129.58 | 1747.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 16-AUG-13:50 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 141.03 | 1084.63 | 4301.06 | 0.00 | 1316.21 | 1938.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 26-JUN-17:30 | 0.00 | 0.00 | 0.00 | -1.0 | 0.00 | 0.00 | 263.16 | 733.36 | 1664.02 | 8063.64 | 0.00 | 1415.07 | 90.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 26-JUN-19:46 | 0.00 | 0.00 | 0.00 | -0.5 | 0.00 | 0.00 | 424.82 | 1094.06 | 1664.78 | 198.84 | 0.00 | 899.70 | 2039.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 17-JUL-09:03 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 115.09 | 141.03 | 1096.02 | 5700.83 | 0.00 | 1038.98 | 32.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 26-JUN-19:23 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 424.22 | 1094.06 | 1664.78 | 949.78 | 0.00 | 1569.67 | 3969.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 16-AUG-13:00 | 0.00 | 0.00 | 0.00 | -0.8 | 0.00 | 0.00 | 115.09 | 141.03 | 1084.63 | 4194.77 | 0.00 | 1885.55 | 2613.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 26-JUN-17:30 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 263.16 | 733.36 | 1664.02 | 7455.62 | 0.00 | 2022.21 | 2102.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 26-JUN-19:56 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 424.45 | 1094.06 | 1664.78 | 166.32 | 0.00 | 1221.47 | 3661.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 26-JUN-19:33 | 0.00 | 0.00 | 0.00 | -0.7 | 0.00 | 0.00 | 424.99 | 1094.06 | 1664.78 | 217.19 | 0.00 | 1384.68 | 3354.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 26-JUN-17:30 | 0.00 | 0.00 | 0.00 | -1.2 | 0.00 | 0.00 | 263.16 | 733.36 | 1664.02 | 8027.14 | 0.00 | 2022.25 | 1687.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 26-JUN-17:24 | 0.00 | 0.00 | 0.00 | -13.5 | 0.00 | 0.00 | 4732.78 | 13200.55 | 29952.39 | 66334.58 | 0.00 | 32456.32 | 62423.85 | 0.00 | 0.00 | 0.00 | -46894.6 | 0.00 |
| Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [Btu/h] | HVAC Zone Eq & Other Sensible Air Cooling [ton] | HVAC Terminal Unit Sensible Air Heating [Btu/h] | HVAC Terminal Unit Sensible Air Cooling [ton] | HVAC Input Heated Surface Heating [Btu/h] | HVAC Input Cooled Surface Cooling [ton] | People Sensible Heat Addition [Btu/h] | Lights Sensible Heat Addition [Btu/h] | Equipment Sensible Heat Addition [Btu/h] | Window Heat Addition [Btu/h] | Interzone Air Transfer Heat Addition [Btu/h] | Infiltration Heat Addition [Btu/h] | Opaque Surface Conduction and Other Heat Addition [Btu/h] | Equipment Sensible Heat Removal [Btu/h] | Window Heat Removal [Btu/h] | Interzone Air Transfer Heat Removal [Btu/h] | Infiltration Heat Removal [Btu/h] | Opaque Surface Conduction and Other Heat Removal [Btu/h] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 15787.80 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3621.3 | 0.00 | -10453.3 | -3162.1 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12636.62 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1467.2 | 0.00 | -9642.9 | -2975.4 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 15783.63 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3593.0 | 0.00 | -10453.3 | -3186.2 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 15812.28 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3601.9 | 0.00 | -10453.3 | -3206.0 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12673.06 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1447.8 | 0.00 | -9642.9 | -3031.2 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 15811.98 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3573.7 | 0.00 | -10453.3 | -3233.9 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12312.08 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3667.8 | 0.00 | -6643.0 | -3450.2 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 8913.44 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1488.8 | 0.00 | -5832.1 | -3041.5 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12320.93 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3629.3 | 0.00 | -6643.0 | -3497.5 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12359.83 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3641.2 | 0.00 | -6643.0 | -3524.6 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 8973.63 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1462.2 | 0.00 | -5832.1 | -3128.3 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 12359.18 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3602.7 | 0.00 | -6643.0 | -3562.4 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 18033.09 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3583.8 | 0.00 | -10464.4 | -5433.8 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 18001.15 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3613.0 | 0.00 | -10464.4 | -5372.6 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 18006.50 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3655.8 | 0.00 | -10464.4 | -5335.2 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 14635.54 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1453.1 | 0.00 | -9653.1 | -4978.3 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 14593.94 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -1482.5 | 0.00 | -9653.1 | -4907.3 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 22-DEC-03:00 | 0.00 | 0.00 | 18040.20 | 0.00 | 0.00 | 0.00 | 526.24 | 75.22 | 847.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -3626.5 | 0.00 | -10464.4 | -5398.2 |
| BREEZEWAY | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| ATTIC | - | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Total Facility | 22-DEC-03:00 | 0.00 | 0.00 | 257054.88 | 0.00 | 0.00 | 0.00 | 9472.36 | 1353.90 | 15253.70 | 0.00 | 0.00 | 7159.70 | 0.00 | 0.00 | -52211.5 | 0.00 | -160498.6 | -77584.5 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
System Ventilation Requirements for Cooling| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.9034 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 490.9034 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 243.3845 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 243.3845 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.3883 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 325.3883 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.6134 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.6134 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 243.3802 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 243.3802 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.4864 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 303.4864 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.9556 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 563.9556 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.3213 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 268.3213 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.9023 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 388.9023 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.2735 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 542.2735 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.3244 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 261.3244 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.2311 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 365.2311 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.5090 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 631.5090 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.2910 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 335.2910 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.9402 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 427.9402 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.6223 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 628.6223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.3265 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 341.3265 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.9038 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 395.9038 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] | System Primary Airflow - Vps [ft3/min] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [ft3/min] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.9034 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 490.9034 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 243.3845 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 243.3845 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.3883 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 325.3883 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.6134 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 470.6134 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 243.3802 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 243.3802 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.4864 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 303.4864 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.9556 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 563.9556 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.3213 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 268.3213 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.9023 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 388.9023 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.2735 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 542.2735 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.3244 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 261.3244 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.2311 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 365.2311 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.5090 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 631.5090 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.2910 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 335.2910 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.9402 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 427.9402 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.6223 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 628.6223 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.3265 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 341.3265 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 | ||
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.9038 | 0.0000 | 2.0000 | 1.0000 | Calculated from schedules | 0.0000 | 395.9038 | 0.0000 | 1.0000 | Not calculated | 0.0000 | 0.0000 |
| AirLoop Name | People Outdoor Air Rate - Rp [ft3/min-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Zone Floor Area - Az [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.0000 | 0.000000 | 1200.55 | 0.0000 | 1.0000 | 0.0000 | 1.000 | 0.0000 |
| People Outdoor Air Rate - Rp [ft3/min-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [ft3/min-ft2] | Sum of Zone Floor Area - Az-sum [ft2] | Breathing Zone Outdoor Airflow - Vbz [ft3/min] | Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] | Heating Zone Outdoor Airflow - Voz-htg [ft3/min] | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 0.000000 | 2.00 | 0.000000 | 1200.5533 | 0.0000 | 0.0000 | 0.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 490.9034 | 490.9034 | 490.9034 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 243.3845 | 243.3845 | 243.3845 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 325.3883 | 325.3883 | 325.3883 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.6134 | 470.6134 | 470.6134 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 243.3802 | 243.3802 | 243.3802 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 303.4864 | 303.4864 | 303.4864 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 563.9556 | 563.9556 | 563.9556 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 268.3213 | 268.3213 | 268.3213 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 388.9023 | 388.9023 | 388.9023 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 542.2735 | 542.2735 | 542.2735 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 261.3244 | 261.3244 | 261.3244 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 365.2311 | 365.2311 | 365.2311 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 395.9038 | 395.9038 | 395.9038 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 427.9402 | 427.9402 | 427.9402 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 631.5090 | 631.5090 | 631.5090 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 341.3265 | 341.3265 | 341.3265 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 335.2910 | 335.2910 | 335.2910 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 628.6223 | 628.6223 | 628.6223 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.9034 | 490.9034 | 490.9034 | 490.9034 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 243.3845 | 243.3845 | 243.3845 | 243.3845 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.3883 | 325.3883 | 325.3883 | 325.3883 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.6134 | 470.6134 | 470.6134 | 470.6134 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 243.3802 | 243.3802 | 243.3802 | 243.3802 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.4864 | 303.4864 | 303.4864 | 303.4864 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.9556 | 563.9556 | 563.9556 | 563.9556 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.3213 | 268.3213 | 268.3213 | 268.3213 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.9023 | 388.9023 | 388.9023 | 388.9023 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.2735 | 542.2735 | 542.2735 | 542.2735 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.3244 | 261.3244 | 261.3244 | 261.3244 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.2311 | 365.2311 | 365.2311 | 365.2311 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.5090 | 631.5090 | 631.5090 | 631.5090 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.2910 | 335.2910 | 335.2910 | 335.2910 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.9402 | 427.9402 | 427.9402 | 427.9402 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.6223 | 628.6223 | 628.6223 | 628.6223 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.3265 | 341.3265 | 341.3265 | 341.3265 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.9038 | 395.9038 | 395.9038 | 395.9038 | 0.0000 | 1.0000 |
| AirLoop Name | Box Type | Zone Primary Airflow - Vpz [ft3/min] | Zone Discharge Airflow - Vdz [ft3/min] | Minimum Zone Primary Airflow - Vpz-min [ft3/min] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 490.9034 | 490.9034 | 490.9034 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 243.3845 | 243.3845 | 243.3845 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 325.3883 | 325.3883 | 325.3883 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 470.6134 | 470.6134 | 470.6134 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 243.3802 | 243.3802 | 243.3802 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 303.4864 | 303.4864 | 303.4864 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 563.9556 | 563.9556 | 563.9556 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 268.3213 | 268.3213 | 268.3213 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 388.9023 | 388.9023 | 388.9023 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 542.2735 | 542.2735 | 542.2735 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 261.3244 | 261.3244 | 261.3244 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 365.2311 | 365.2311 | 365.2311 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 395.9038 | 395.9038 | 395.9038 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 427.9402 | 427.9402 | 427.9402 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 631.5090 | 631.5090 | 631.5090 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 341.3265 | 341.3265 | 341.3265 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 335.2910 | 335.2910 | 335.2910 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 628.6223 | 628.6223 | 628.6223 | No | 0.0000 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
| Sum of Zone Primary Airflow - Vpz-sum [ft3/min] | System Primary Airflow - Vps [ft3/min] | Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] | Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] | Zone Outdoor Airflow Heating - Voz-htg [ft3/min] | Zone Ventilation Efficiency - Evz-min | |
| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | 490.9034 | 490.9034 | 490.9034 | 490.9034 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | 243.3845 | 243.3845 | 243.3845 | 243.3845 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | 325.3883 | 325.3883 | 325.3883 | 325.3883 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | 470.6134 | 470.6134 | 470.6134 | 470.6134 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | 243.3802 | 243.3802 | 243.3802 | 243.3802 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | 303.4864 | 303.4864 | 303.4864 | 303.4864 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | 563.9556 | 563.9556 | 563.9556 | 563.9556 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | 268.3213 | 268.3213 | 268.3213 | 268.3213 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | 388.9023 | 388.9023 | 388.9023 | 388.9023 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | 542.2735 | 542.2735 | 542.2735 | 542.2735 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | 261.3244 | 261.3244 | 261.3244 | 261.3244 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | 365.2311 | 365.2311 | 365.2311 | 365.2311 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | 631.5090 | 631.5090 | 631.5090 | 631.5090 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | 335.2910 | 335.2910 | 335.2910 | 335.2910 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | 427.9402 | 427.9402 | 427.9402 | 427.9402 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | 628.6223 | 628.6223 | 628.6223 | 628.6223 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | 341.3265 | 341.3265 | 341.3265 | 341.3265 | 0.0000 | 1.0000 |
| CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | 395.9038 | 395.9038 | 395.9038 | 395.9038 | 0.0000 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Sec1.1A-General Information| Data | |
| Weather File | ANNUAL ** Denver-Aurora-Buckley AFB CO USA TMY3 WMO#=724695 |
| Total gross floor area [ft2] | 31210.83 |
| Principal Heating Source | Electricity |
| Space Area [ft2] | Regularly Occupied Area [ft2] | Unconditioned Area [ft2] | Typical Hours/Week in Operation [hr/wk] | |
| LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_BOTTOMFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_MIDDLEFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT3_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT2_FRONTROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| LIVING_UNIT1_BACKROW_TOPFLOOR | 1200.55 | 1200.55 | 0.00 | 168.00 |
| BREEZEWAY | 1798.16 | 0.00 | 1798.16 | 0.00 |
| ATTIC | 7802.71 | 0.00 | 7802.71 | 0.00 |
| Totals | 31210.83 | 21609.96 | 9600.87 |
| Data | |
| Number of hours heating loads not met | 0.00 |
| Number of hours cooling loads not met | 1.50 |
| Number of hours not met | 1.50 |
| Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
| None |
| Electricity Energy Use [kWh] | Electricity Demand [W] | Natural Gas Energy Use [therm] | Natural Gas Demand [Btu/h] | Gasoline Use [therm] | Gasoline Demand [Btu/h] | Diesel Use [kBtu] | Diesel Demand [Btu/h] | Coal Use [kBtu] | Coal Demand [Btu/h] | Fuel Oil No 1 Use [kBtu] | Fuel Oil No 1 Demand [Btu/h] | Fuel Oil No 2 Use [kBtu] | Fuel Oil No 2 Demand [Btu/h] | Propane Use [kBtu] | Propane Demand [Btu/h] | Other Fuel 1 Use [kBtu] | Other Fuel 1 Demand [Btu/h] | Other Fuel 2 Use [kBtu] | Other Fuel 2 Demand [Btu/h] | District Cooling Use [ton-hrs] | District Cooling Demand [ton] | District Heating Use [kBtu] | District Heating Demand [Btu/h] | |
| Heating -- General | 87367.32 | 72862.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Cooling -- General | 12633.21 | 14061.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Lighting -- General | 17719.17 | 5771.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Exterior-Lights | 6034.31 | 1377.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Lighting -- Garage-Lights | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- dishwasher | 3088.82 | 985.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- refrigerator | 12036.11 | 1639.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- clotheswasher | 1577.30 | 427.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_dryer | 12502.11 | 3196.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_range | 9058.39 | 3721.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- television | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- electric_mels | 46926.68 | 7929.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Interior Equipment -- IECC_adj | 3113.66 | 526.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation (simple) | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- Ventilation | 5068.29 | 578.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Fans -- General | 5680.15 | 2598.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Pumps -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Domestic Hot Water | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Water Systems -- Water Heater | 59277.15 | 59035.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
| Process Subtotal [kBtu] | Total Energy Use [kBtu] | |
| Electricity | 301503.54 | 963147.93 |
| Natural Gas | 0.00 | 0.00 |
| Additional | 0.00 | 0.00 |
| Total | 301503.54 | 963147.93 |
| Process Subtotal [$] | Total Energy Cost [$] | |
| Electricity | 0.00 | |
| Natural Gas | 0.00 | |
| Additional | 0.00 | |
| Total | 0.00 |
| Rated Capacity [kW] | Annual Energy Generated [kBtu] | |
| Photovoltaic | 0.00 | 0.00 |
| Wind | 0.00 | 0.00 |
| Electricty [kWh/ft2] | |
| Interior Lighting (All) | 0.57 |
| Space Heating | 2.80 |
| Space Cooling | 0.40 |
| Fans (All) | 0.34 |
| Service Water Heating | 1.90 |
| Receptacle Equipment | 2.83 |
| Miscellaneous (All) | 9.04 |
| Subtotal | 9.04 |
| Natural Gas [kWh/ft2] | |
| Space Heating | 0.00 |
| Service Water Heating | 0.00 |
| Miscellaneous (All) | 0.00 |
| Subtotal | 0.00 |
| Additional [kBtu/ft2] | |
| Subtotal | 0.00 |
| Miscellaneous | 0.00 |
| Percent [%] | |
| Interior Lighting (All) | 6.28 |
| Space Heating | 30.97 |
| Space Cooling | 4.48 |
| Fans (All) | 3.81 |
| Service Water Heating | 21.01 |
| Receptacle Equipment | 31.30 |
| Miscellaneous | 2.14 |
| Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
| OCCUPANCY | 6031. | 8760. |
| INTERIORLIGHTING | 2852. | 8760. |
| INTERIORLIGHTINGHE | 3070. | 8760. |
| INTERIORLIGHTINGHE_OS | 2910. | 8760. |
| INTERIORLIGHTINGHE_VS | 2149. | 8760. |
| EXTERIORLIGHTING | 4380. | 4380. |
| REFRIGERATOR | 7343. | 8760. |
| MISCPLUGLOAD | 5918. | 8760. |
| COOKINGRANGE | 2434. | 8760. |
| DISHWASHER_FLOW_SCH | 3134. | 8760. |
| CLOTHESWASHER_FLOW_SCH | 3692. | 8760. |
| DISHWASHER_EQUIP_SCH | 3134. | 8760. |
| CLOTHESWASHER_EQUIP_SCH | 3692. | 8760. |
| CLOTHESDRYER | 3911. | 8760. |
| SHADING_2012IECC | 0. | 0. |
| SHADING_2012IECC_HERS | 7007. | 8760. |
| SINKSENSSCHEDULE | 6025. | 8760. |
| SINKLATSCHEDULE | 2735. | 8760. |
| SHOWERSENSSCHEDULE | 4492. | 8760. |
| SHOWERLATSCHEDULE | 4268. | 8760. |
| BATHSENSSCHEDULE | 8760. | 8760. |
| BATHLATSCHEDULE | 0. | 0. |
| First Object Used | Month Assumed | 11am First Wednesday [F] | Days with Same 11am Value | 11pm First Wednesday [F] | Days with Same 11pm Value | |
| HEATING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | January | 72.00 | 365 | 72.00 | 365 |
| COOLING_SCH | THERMOSTAT_LIVING DUAL SP CONTROL | July | 75.00 | 365 | 75.00 | 365 |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
CO2 Level Hours| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
| Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
| None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2024-06-27 17:41:15
Illuminance Level Hours| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
| A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
| None |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 46.667 | 1.575 | 599.272 | 32.638 | 32.638 |
| February | 41.972 | 1.259 | 561.167 | 34.184 | 34.184 |
| March | 99.639 | 4.108 | 553.611 | 31.683 | 31.683 |
| April | 78.278 | 2.337 | 551.556 | 26.938 | 26.938 |
| May | 214.069 | 6.853 | 342.021 | 13.747 | 13.747 |
| June | 502.548 | 29.838 | 15.333 | 29.968 | 29.968 |
| July | 583.875 | 32.060 | 12.833 | 32.137 | 32.137 |
| August | 547.721 | 31.770 | 10.667 | 31.817 | 31.817 |
| September | 437.292 | 23.450 | 90.917 | 25.117 | 25.117 |
| October | 160.625 | 7.360 | 453.833 | 26.547 | 26.547 |
| November | 82.500 | 3.117 | 538.125 | 28.285 | 28.285 |
| December | 43.972 | 1.597 | 636.914 | 44.327 | 44.327 |
| Annual Sum or Average | 2839.157 | 145.322 | 4366.249 | 357.387 | 357.387 |
| Minimum of Months | 41.972 | 1.259 | 10.667 | 13.747 | 13.747 |
| Maximum of Months | 583.875 | 32.060 | 636.914 | 44.327 | 44.327 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 34.722 | 0.687 | 597.392 | 14.949 | 14.949 |
| February | 21.944 | 0.348 | 565.583 | 15.890 | 15.890 |
| March | 74.750 | 1.367 | 561.944 | 14.432 | 14.432 |
| April | 51.167 | 0.444 | 563.653 | 12.102 | 12.102 |
| May | 171.319 | 2.424 | 340.296 | 5.417 | 5.417 |
| June | 530.069 | 17.095 | 7.500 | 17.124 | 17.124 |
| July | 619.958 | 20.580 | 3.333 | 20.584 | 20.584 |
| August | 585.585 | 20.379 | 0.000 | 20.379 | 20.379 |
| September | 472.764 | 15.052 | 55.444 | 15.614 | 15.614 |
| October | 153.361 | 3.448 | 428.583 | 11.919 | 11.919 |
| November | 70.750 | 1.394 | 518.597 | 12.706 | 12.706 |
| December | 40.222 | 0.723 | 632.244 | 20.684 | 20.684 |
| Annual Sum or Average | 2826.612 | 83.942 | 4274.571 | 181.800 | 181.800 |
| Minimum of Months | 21.944 | 0.348 | 0.000 | 5.417 | 5.417 |
| Maximum of Months | 619.958 | 20.580 | 632.244 | 20.684 | 20.684 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 38.944 | 1.018 | 608.656 | 21.623 | 21.623 |
| February | 34.264 | 0.761 | 559.917 | 22.465 | 22.465 |
| March | 110.522 | 3.075 | 547.111 | 20.930 | 20.930 |
| April | 87.000 | 1.771 | 531.458 | 17.565 | 17.565 |
| May | 237.303 | 6.090 | 305.778 | 10.199 | 10.199 |
| June | 544.028 | 29.659 | 11.167 | 29.729 | 29.729 |
| July | 607.544 | 33.036 | 11.667 | 33.083 | 33.083 |
| August | 578.667 | 32.512 | 8.833 | 32.539 | 32.539 |
| September | 463.611 | 23.040 | 80.639 | 24.068 | 24.068 |
| October | 180.092 | 5.868 | 429.889 | 18.424 | 18.424 |
| November | 82.268 | 2.218 | 530.000 | 18.936 | 18.936 |
| December | 41.083 | 0.971 | 636.111 | 29.400 | 29.400 |
| Annual Sum or Average | 3005.327 | 140.019 | 4261.225 | 278.961 | 278.961 |
| Minimum of Months | 34.264 | 0.761 | 8.833 | 10.199 | 10.199 |
| Maximum of Months | 607.544 | 33.036 | 636.111 | 33.083 | 33.083 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 6.500 | 0.080 | 706.750 | 36.748 | 36.748 |
| February | 5.889 | 0.046 | 639.500 | 37.271 | 37.271 |
| March | 44.806 | 1.221 | 613.278 | 30.216 | 30.216 |
| April | 47.333 | 0.920 | 588.403 | 25.731 | 25.731 |
| May | 194.597 | 5.391 | 358.139 | 12.178 | 12.178 |
| June | 507.865 | 28.362 | 13.417 | 28.473 | 28.473 |
| July | 585.944 | 30.195 | 11.722 | 30.259 | 30.259 |
| August | 540.205 | 27.034 | 10.833 | 27.082 | 27.082 |
| September | 405.292 | 17.022 | 102.478 | 18.782 | 18.782 |
| October | 79.444 | 2.235 | 536.608 | 22.455 | 22.455 |
| November | 16.264 | 0.310 | 642.208 | 29.573 | 29.573 |
| December | 5.083 | 0.066 | 706.622 | 47.174 | 47.174 |
| Annual Sum or Average | 2439.223 | 112.883 | 4929.958 | 345.942 | 345.942 |
| Minimum of Months | 5.083 | 0.046 | 10.833 | 12.178 | 12.178 |
| Maximum of Months | 585.944 | 30.195 | 706.750 | 47.174 | 47.174 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 0.000 | 0.000 | 734.950 | 18.965 | 18.965 |
| February | 0.000 | 0.000 | 662.000 | 19.544 | 19.544 |
| March | 8.111 | 0.032 | 658.361 | 14.957 | 14.957 |
| April | 5.833 | 0.020 | 630.400 | 12.671 | 12.671 |
| May | 140.569 | 1.703 | 363.250 | 4.870 | 4.870 |
| June | 539.237 | 17.463 | 6.250 | 17.487 | 17.487 |
| July | 624.111 | 20.841 | 2.333 | 20.844 | 20.844 |
| August | 579.687 | 17.851 | 0.000 | 17.851 | 17.851 |
| September | 436.708 | 10.380 | 66.736 | 11.025 | 11.025 |
| October | 26.806 | 0.254 | 566.042 | 10.043 | 10.043 |
| November | 0.000 | 0.000 | 670.111 | 14.915 | 14.915 |
| December | 0.000 | 0.000 | 728.778 | 23.984 | 23.984 |
| Annual Sum or Average | 2361.062 | 68.545 | 5089.211 | 187.156 | 187.156 |
| Minimum of Months | 0.000 | 0.000 | 0.000 | 4.870 | 4.870 |
| Maximum of Months | 624.111 | 20.841 | 734.950 | 23.984 | 23.984 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 0.000 | 0.000 | 725.306 | 23.989 | 23.989 |
| February | 0.000 | 0.000 | 648.333 | 24.155 | 24.155 |
| March | 31.103 | 0.350 | 598.236 | 18.634 | 18.634 |
| April | 44.658 | 0.478 | 570.028 | 16.004 | 16.004 |
| May | 220.911 | 4.703 | 319.139 | 8.670 | 8.670 |
| June | 547.639 | 28.833 | 10.250 | 28.896 | 28.896 |
| July | 608.794 | 31.850 | 10.917 | 31.892 | 31.892 |
| August | 576.431 | 28.598 | 9.167 | 28.625 | 28.625 |
| September | 450.444 | 17.006 | 87.750 | 18.047 | 18.047 |
| October | 60.994 | 0.883 | 516.797 | 13.641 | 13.641 |
| November | 9.778 | 0.030 | 656.472 | 19.208 | 19.208 |
| December | 0.000 | 0.000 | 726.208 | 30.682 | 30.682 |
| Annual Sum or Average | 2550.753 | 112.732 | 4878.603 | 262.443 | 262.443 |
| Minimum of Months | 0.000 | 0.000 | 9.167 | 8.670 | 8.670 |
| Maximum of Months | 608.794 | 31.850 | 726.208 | 31.892 | 31.892 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 113.806 | 4.062 | 495.889 | 30.567 | 30.567 |
| February | 99.694 | 3.813 | 475.958 | 32.281 | 32.281 |
| March | 166.222 | 8.634 | 474.208 | 31.635 | 31.635 |
| April | 142.619 | 5.827 | 455.500 | 25.672 | 25.672 |
| May | 338.208 | 14.664 | 176.261 | 18.108 | 18.108 |
| June | 631.272 | 41.399 | 3.000 | 41.415 | 41.415 |
| July | 682.167 | 42.854 | 0.000 | 42.854 | 42.854 |
| August | 658.925 | 42.129 | 0.000 | 42.129 | 42.129 |
| September | 521.122 | 31.323 | 50.417 | 32.569 | 32.569 |
| October | 238.778 | 12.550 | 377.117 | 29.755 | 29.755 |
| November | 147.611 | 6.277 | 442.667 | 28.185 | 28.185 |
| December | 84.472 | 3.418 | 569.486 | 41.840 | 41.840 |
| Annual Sum or Average | 3824.897 | 216.951 | 3520.503 | 397.010 | 397.010 |
| Minimum of Months | 84.472 | 3.418 | 0.000 | 18.108 | 18.108 |
| Maximum of Months | 682.167 | 42.854 | 569.486 | 42.854 | 42.854 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 117.861 | 2.705 | 449.444 | 12.901 | 12.901 |
| February | 98.667 | 2.074 | 451.097 | 13.517 | 13.517 |
| March | 160.250 | 5.022 | 439.403 | 14.138 | 14.138 |
| April | 132.300 | 2.787 | 424.747 | 10.609 | 10.609 |
| May | 335.147 | 8.624 | 116.403 | 9.615 | 9.615 |
| June | 684.083 | 28.799 | 0.000 | 28.799 | 28.799 |
| July | 716.736 | 31.916 | 0.000 | 31.916 | 31.916 |
| August | 719.031 | 31.528 | 0.000 | 31.528 | 31.528 |
| September | 581.014 | 23.785 | 29.500 | 24.122 | 24.122 |
| October | 267.056 | 8.600 | 323.000 | 15.046 | 15.046 |
| November | 165.389 | 4.419 | 394.556 | 12.692 | 12.692 |
| December | 97.708 | 2.600 | 533.917 | 18.043 | 18.043 |
| Annual Sum or Average | 4075.242 | 152.860 | 3162.067 | 222.927 | 222.927 |
| Minimum of Months | 97.708 | 2.074 | 0.000 | 9.615 | 9.615 |
| Maximum of Months | 719.031 | 31.916 | 533.917 | 31.916 | 31.916 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 104.603 | 2.929 | 495.792 | 21.119 | 21.119 |
| February | 104.931 | 2.994 | 460.778 | 22.483 | 22.483 |
| March | 177.014 | 7.600 | 444.944 | 22.796 | 22.796 |
| April | 164.969 | 5.600 | 422.667 | 18.709 | 18.709 |
| May | 385.131 | 14.379 | 139.861 | 16.401 | 16.401 |
| June | 650.417 | 41.522 | 1.750 | 41.531 | 41.531 |
| July | 694.372 | 44.085 | 0.000 | 44.085 | 44.085 |
| August | 673.042 | 43.090 | 0.000 | 43.090 | 43.090 |
| September | 548.083 | 31.123 | 43.500 | 31.904 | 31.904 |
| October | 264.892 | 11.165 | 355.083 | 22.932 | 22.932 |
| November | 149.838 | 5.109 | 434.972 | 20.266 | 20.266 |
| December | 87.347 | 2.686 | 559.278 | 29.292 | 29.292 |
| Annual Sum or Average | 4004.638 | 212.281 | 3358.625 | 334.610 | 334.610 |
| Minimum of Months | 87.347 | 2.686 | 0.000 | 16.401 | 16.401 |
| Maximum of Months | 694.372 | 44.085 | 559.278 | 44.085 | 44.085 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 19.194 | 0.248 | 664.778 | 34.684 | 34.684 |
| February | 19.000 | 0.312 | 591.750 | 34.801 | 34.801 |
| March | 100.778 | 3.268 | 537.500 | 28.296 | 28.296 |
| April | 98.972 | 3.025 | 497.828 | 23.263 | 23.263 |
| May | 318.847 | 12.369 | 182.733 | 15.789 | 15.789 |
| June | 638.472 | 39.968 | 2.056 | 39.978 | 39.978 |
| July | 684.278 | 40.853 | 0.000 | 40.853 | 40.853 |
| August | 655.294 | 36.665 | 0.000 | 36.665 | 36.665 |
| September | 491.431 | 23.494 | 60.611 | 24.883 | 24.883 |
| October | 137.750 | 4.369 | 452.333 | 22.940 | 22.940 |
| November | 40.694 | 0.775 | 586.056 | 28.292 | 28.292 |
| December | 16.028 | 0.207 | 674.528 | 45.683 | 45.683 |
| Annual Sum or Average | 3220.739 | 165.551 | 4250.172 | 376.126 | 376.126 |
| Minimum of Months | 16.028 | 0.207 | 0.000 | 15.789 | 15.789 |
| Maximum of Months | 684.278 | 40.853 | 674.528 | 45.683 | 45.683 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 0.000 | 0.000 | 682.917 | 15.710 | 15.710 |
| February | 3.056 | 0.007 | 625.000 | 16.044 | 16.044 |
| March | 51.083 | 0.593 | 546.700 | 11.506 | 11.506 |
| April | 59.500 | 0.814 | 493.431 | 9.266 | 9.266 |
| May | 298.014 | 6.690 | 130.694 | 7.741 | 7.741 |
| June | 690.267 | 27.855 | 0.000 | 27.855 | 27.855 |
| July | 720.028 | 30.428 | 0.000 | 30.428 | 30.428 |
| August | 717.903 | 26.674 | 0.000 | 26.674 | 26.674 |
| September | 542.292 | 16.336 | 38.875 | 16.753 | 16.753 |
| October | 92.000 | 1.160 | 434.408 | 8.620 | 8.620 |
| November | 13.889 | 0.069 | 619.556 | 12.336 | 12.336 |
| December | 0.000 | 0.000 | 687.583 | 20.398 | 20.398 |
| Annual Sum or Average | 3188.031 | 110.626 | 4259.164 | 203.332 | 203.332 |
| Minimum of Months | 0.000 | 0.000 | 0.000 | 7.741 | 7.741 |
| Maximum of Months | 720.028 | 30.428 | 687.583 | 30.428 | 30.428 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 3.667 | 0.015 | 676.486 | 23.643 | 23.643 |
| February | 11.514 | 0.102 | 602.694 | 23.451 | 23.451 |
| March | 118.131 | 2.078 | 523.389 | 18.349 | 18.349 |
| April | 117.206 | 2.726 | 474.167 | 15.823 | 15.823 |
| May | 356.739 | 12.239 | 150.333 | 14.228 | 14.228 |
| June | 653.250 | 40.532 | 1.500 | 40.538 | 40.538 |
| July | 695.983 | 42.590 | 0.000 | 42.590 | 42.590 |
| August | 671.458 | 38.435 | 0.000 | 38.435 | 38.435 |
| September | 534.628 | 23.851 | 50.083 | 24.686 | 24.686 |
| October | 139.097 | 2.613 | 409.333 | 14.808 | 14.808 |
| November | 39.528 | 0.403 | 608.667 | 19.376 | 19.376 |
| December | 2.569 | 0.008 | 688.833 | 30.998 | 30.998 |
| Annual Sum or Average | 3343.769 | 165.594 | 4185.486 | 306.924 | 306.924 |
| Minimum of Months | 2.569 | 0.008 | 0.000 | 14.228 | 14.228 |
| Maximum of Months | 695.983 | 42.590 | 688.833 | 42.590 | 42.590 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 62.694 | 2.447 | 571.914 | 39.946 | 39.946 |
| February | 56.944 | 2.184 | 535.750 | 41.892 | 41.892 |
| March | 132.361 | 7.236 | 520.917 | 39.733 | 39.733 |
| April | 112.361 | 4.767 | 511.500 | 33.029 | 33.029 |
| May | 295.194 | 14.350 | 257.094 | 20.474 | 20.474 |
| June | 577.714 | 44.744 | 9.167 | 44.834 | 44.834 |
| July | 641.889 | 46.107 | 7.667 | 46.141 | 46.141 |
| August | 598.825 | 44.224 | 9.500 | 44.279 | 44.279 |
| September | 470.875 | 31.248 | 87.111 | 33.544 | 33.544 |
| October | 195.681 | 10.569 | 428.417 | 34.856 | 34.856 |
| November | 101.014 | 4.479 | 508.792 | 35.787 | 35.787 |
| December | 54.083 | 2.218 | 624.236 | 55.603 | 55.603 |
| Annual Sum or Average | 3299.637 | 214.573 | 4072.064 | 470.117 | 470.117 |
| Minimum of Months | 54.083 | 2.184 | 7.667 | 20.474 | 20.474 |
| Maximum of Months | 641.889 | 46.107 | 624.236 | 55.603 | 55.603 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 54.181 | 1.525 | 562.669 | 19.713 | 19.713 |
| February | 43.611 | 1.015 | 532.208 | 20.812 | 20.812 |
| March | 127.472 | 4.023 | 520.583 | 20.222 | 20.222 |
| April | 87.528 | 2.150 | 507.333 | 16.150 | 16.150 |
| May | 281.819 | 8.620 | 213.819 | 11.169 | 11.169 |
| June | 625.767 | 31.962 | 3.333 | 31.973 | 31.973 |
| July | 676.042 | 35.083 | 0.000 | 35.083 | 35.083 |
| August | 644.553 | 33.460 | 0.000 | 33.460 | 33.460 |
| September | 503.153 | 23.601 | 57.200 | 24.480 | 24.480 |
| October | 201.014 | 6.657 | 397.167 | 18.094 | 18.094 |
| November | 99.625 | 2.786 | 484.694 | 17.757 | 17.757 |
| December | 53.861 | 1.391 | 612.569 | 27.937 | 27.937 |
| Annual Sum or Average | 3398.625 | 152.271 | 3891.578 | 276.849 | 276.849 |
| Minimum of Months | 43.611 | 1.015 | 0.000 | 11.169 | 11.169 |
| Maximum of Months | 676.042 | 35.083 | 612.569 | 35.083 | 35.083 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 51.625 | 1.668 | 586.119 | 27.165 | 27.165 |
| February | 51.556 | 1.451 | 532.917 | 28.202 | 28.202 |
| March | 149.350 | 5.745 | 513.806 | 27.176 | 27.176 |
| April | 127.719 | 3.991 | 486.444 | 22.474 | 22.474 |
| May | 326.039 | 12.846 | 216.250 | 16.451 | 16.451 |
| June | 611.611 | 42.076 | 5.333 | 42.117 | 42.117 |
| July | 661.153 | 44.463 | 6.000 | 44.484 | 44.484 |
| August | 630.369 | 42.519 | 7.167 | 42.547 | 42.547 |
| September | 501.039 | 29.035 | 73.889 | 30.445 | 30.445 |
| October | 213.039 | 8.333 | 403.000 | 24.515 | 24.515 |
| November | 98.492 | 3.258 | 507.278 | 24.518 | 24.518 |
| December | 51.222 | 1.448 | 623.917 | 37.827 | 37.827 |
| Annual Sum or Average | 3473.214 | 196.834 | 3962.119 | 367.922 | 367.922 |
| Minimum of Months | 51.222 | 1.448 | 5.333 | 16.451 | 16.451 |
| Maximum of Months | 661.153 | 44.463 | 623.917 | 44.484 | 44.484 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 12.222 | 0.213 | 686.056 | 46.517 | 46.517 |
| February | 15.083 | 0.284 | 614.889 | 46.723 | 46.723 |
| March | 89.694 | 3.509 | 569.194 | 38.608 | 38.608 |
| April | 84.611 | 3.055 | 540.389 | 32.374 | 32.374 |
| May | 279.944 | 13.070 | 266.306 | 19.291 | 19.291 |
| June | 586.296 | 44.171 | 8.500 | 44.245 | 44.245 |
| July | 644.194 | 45.078 | 6.000 | 45.104 | 45.104 |
| August | 594.480 | 40.723 | 9.944 | 40.780 | 40.780 |
| September | 446.514 | 25.536 | 100.083 | 28.083 | 28.083 |
| October | 121.944 | 4.524 | 495.792 | 31.016 | 31.016 |
| November | 34.333 | 0.819 | 617.236 | 38.674 | 38.674 |
| December | 11.667 | 0.140 | 693.667 | 61.377 | 61.377 |
| Annual Sum or Average | 2920.984 | 181.123 | 4608.056 | 472.792 | 472.792 |
| Minimum of Months | 11.667 | 0.140 | 6.000 | 19.291 | 19.291 |
| Maximum of Months | 644.194 | 45.078 | 693.667 | 61.377 | 61.377 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 0.000 | 0.000 | 707.875 | 24.954 | 24.954 |
| February | 3.194 | 0.007 | 640.667 | 25.365 | 25.365 |
| March | 50.722 | 0.907 | 582.250 | 19.476 | 19.476 |
| April | 55.278 | 1.016 | 553.903 | 16.251 | 16.251 |
| May | 260.989 | 7.566 | 221.792 | 10.290 | 10.290 |
| June | 633.875 | 31.842 | 2.500 | 31.849 | 31.849 |
| July | 678.736 | 34.532 | 0.000 | 34.532 | 34.532 |
| August | 640.275 | 30.456 | 0.000 | 30.456 | 30.456 |
| September | 475.153 | 18.234 | 70.764 | 19.284 | 19.284 |
| October | 80.111 | 1.412 | 509.472 | 14.798 | 14.798 |
| November | 15.500 | 0.102 | 641.750 | 20.301 | 20.301 |
| December | 0.000 | 0.000 | 710.917 | 32.697 | 32.697 |
| Annual Sum or Average | 2893.833 | 126.074 | 4641.889 | 280.253 | 280.253 |
| Minimum of Months | 0.000 | 0.000 | 0.000 | 10.290 | 10.290 |
| Maximum of Months | 678.736 | 34.532 | 710.917 | 34.532 | 34.532 |
Report: FANSPLIT
For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] | AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] | AIR SYSTEM FAN ELECTRICITY ENERGY [kWh] | |
| January | 2.333 | 0.008 | 704.125 | 29.685 | 29.685 |
| February | 6.500 | 0.080 | 623.361 | 29.545 | 29.545 |
| March | 91.392 | 2.022 | 546.483 | 23.583 | 23.583 |
| April | 92.792 | 2.472 | 514.375 | 20.338 | 20.338 |
| May | 314.331 | 12.185 | 221.000 | 15.621 | 15.621 |
| June | 615.264 | 43.327 | 5.167 | 43.362 | 43.362 |
| July | 662.861 | 45.385 | 5.667 | 45.401 | 45.401 |
| August | 630.058 | 41.148 | 7.167 | 41.175 | 41.175 |
| September | 491.919 | 24.765 | 80.556 | 26.189 | 26.189 |
| October | 117.522 | 2.623 | 474.722 | 18.889 | 18.889 |
| November | 31.722 | 0.396 | 636.028 | 24.702 | 24.702 |
| December | 1.250 | 0.003 | 712.208 | 39.109 | 39.109 |
| Annual Sum or Average | 3057.944 | 174.414 | 4530.858 | 357.599 | 357.599 |
| Minimum of Months | 1.250 | 0.003 | 5.167 | 15.621 | 15.621 |
| Maximum of Months | 662.861 | 45.385 | 712.208 | 45.401 | 45.401 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3651.39 | 0.00 | 0.00 |
| February | 4285.01 | 0.00 | 0.00 |
| March | 3241.42 | 0.00 | 0.00 |
| April | 2988.27 | 0.00 | 0.00 |
| May | 810.39 | 0.00 | 0.00 |
| June | 15.75 | 0.00 | 0.00 |
| July | 8.95 | 0.00 | 0.00 |
| August | 5.59 | 0.00 | 0.00 |
| September | 202.54 | 0.00 | 0.00 |
| October | 2255.45 | 0.00 | 0.00 |
| November | 3057.06 | 0.00 | 0.00 |
| December | 5022.86 | 0.00 | 0.00 |
| Annual Sum or Average | 2117.17 | 0.00 | 0.00 |
| Minimum of Months | 5.59 | 0.00 | 0.00 |
| Maximum of Months | 5022.86 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2829.81 | 0.00 | 0.00 |
| February | 3414.35 | 0.00 | 0.00 |
| March | 2592.46 | 0.00 | 0.00 |
| April | 2390.22 | 0.00 | 0.00 |
| May | 593.86 | 0.00 | 0.00 |
| June | 5.92 | 0.00 | 0.00 |
| July | 0.85 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 115.22 | 0.00 | 0.00 |
| October | 1680.73 | 0.00 | 0.00 |
| November | 2319.27 | 0.00 | 0.00 |
| December | 3960.56 | 0.00 | 0.00 |
| Annual Sum or Average | 1649.11 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3960.56 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3654.83 | 0.00 | 0.00 |
| February | 4262.09 | 0.00 | 0.00 |
| March | 3167.02 | 0.00 | 0.00 |
| April | 2894.80 | 0.00 | 0.00 |
| May | 728.79 | 0.00 | 0.00 |
| June | 12.90 | 0.00 | 0.00 |
| July | 8.32 | 0.00 | 0.00 |
| August | 4.86 | 0.00 | 0.00 |
| September | 188.37 | 0.00 | 0.00 |
| October | 2227.09 | 0.00 | 0.00 |
| November | 3064.01 | 0.00 | 0.00 |
| December | 5042.51 | 0.00 | 0.00 |
| Annual Sum or Average | 2093.09 | 0.00 | 0.00 |
| Minimum of Months | 4.86 | 0.00 | 0.00 |
| Maximum of Months | 5042.51 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 4496.83 | 0.00 | 0.00 |
| February | 5054.21 | 0.00 | 0.00 |
| March | 3555.87 | 0.00 | 0.00 |
| April | 3144.12 | 0.00 | 0.00 |
| May | 832.33 | 0.00 | 0.00 |
| June | 14.00 | 0.00 | 0.00 |
| July | 7.85 | 0.00 | 0.00 |
| August | 5.81 | 0.00 | 0.00 |
| September | 223.02 | 0.00 | 0.00 |
| October | 2479.70 | 0.00 | 0.00 |
| November | 3708.38 | 0.00 | 0.00 |
| December | 5777.13 | 0.00 | 0.00 |
| Annual Sum or Average | 2427.47 | 0.00 | 0.00 |
| Minimum of Months | 5.81 | 0.00 | 0.00 |
| Maximum of Months | 5777.13 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3763.06 | 0.00 | 0.00 |
| February | 4293.39 | 0.00 | 0.00 |
| March | 2961.38 | 0.00 | 0.00 |
| April | 2593.95 | 0.00 | 0.00 |
| May | 628.32 | 0.00 | 0.00 |
| June | 4.91 | 0.00 | 0.00 |
| July | 0.52 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 132.27 | 0.00 | 0.00 |
| October | 1942.33 | 0.00 | 0.00 |
| November | 3058.18 | 0.00 | 0.00 |
| December | 4758.91 | 0.00 | 0.00 |
| Annual Sum or Average | 1998.86 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4758.91 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 4561.22 | 0.00 | 0.00 |
| February | 5084.92 | 0.00 | 0.00 |
| March | 3476.51 | 0.00 | 0.00 |
| April | 3050.60 | 0.00 | 0.00 |
| May | 754.25 | 0.00 | 0.00 |
| June | 12.30 | 0.00 | 0.00 |
| July | 7.85 | 0.00 | 0.00 |
| August | 5.15 | 0.00 | 0.00 |
| September | 204.63 | 0.00 | 0.00 |
| October | 2425.71 | 0.00 | 0.00 |
| November | 3767.96 | 0.00 | 0.00 |
| December | 5833.77 | 0.00 | 0.00 |
| Annual Sum or Average | 2417.64 | 0.00 | 0.00 |
| Minimum of Months | 5.15 | 0.00 | 0.00 |
| Maximum of Months | 5833.77 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2299.28 | 0.00 | 0.00 |
| February | 2734.09 | 0.00 | 0.00 |
| March | 1995.30 | 0.00 | 0.00 |
| April | 1778.87 | 0.00 | 0.00 |
| May | 298.74 | 0.00 | 0.00 |
| June | 1.42 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 111.70 | 0.00 | 0.00 |
| October | 1492.49 | 0.00 | 0.00 |
| November | 1963.80 | 0.00 | 0.00 |
| December | 3333.07 | 0.00 | 0.00 |
| Annual Sum or Average | 1326.61 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3333.07 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 1471.47 | 0.00 | 0.00 |
| February | 1828.51 | 0.00 | 0.00 |
| March | 1315.66 | 0.00 | 0.00 |
| April | 1166.49 | 0.00 | 0.00 |
| May | 143.05 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 50.23 | 0.00 | 0.00 |
| October | 930.25 | 0.00 | 0.00 |
| November | 1233.72 | 0.00 | 0.00 |
| December | 2228.86 | 0.00 | 0.00 |
| Annual Sum or Average | 858.85 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 2228.86 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2288.74 | 0.00 | 0.00 |
| February | 2714.86 | 0.00 | 0.00 |
| March | 1911.95 | 0.00 | 0.00 |
| April | 1704.46 | 0.00 | 0.00 |
| May | 254.46 | 0.00 | 0.00 |
| June | 1.11 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 101.61 | 0.00 | 0.00 |
| October | 1480.65 | 0.00 | 0.00 |
| November | 1970.68 | 0.00 | 0.00 |
| December | 3347.64 | 0.00 | 0.00 |
| Annual Sum or Average | 1307.23 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3347.64 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3107.13 | 0.00 | 0.00 |
| February | 3445.29 | 0.00 | 0.00 |
| March | 2258.26 | 0.00 | 0.00 |
| April | 1886.98 | 0.00 | 0.00 |
| May | 308.60 | 0.00 | 0.00 |
| June | 1.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 129.51 | 0.00 | 0.00 |
| October | 1675.71 | 0.00 | 0.00 |
| November | 2565.57 | 0.00 | 0.00 |
| December | 4103.19 | 0.00 | 0.00 |
| Annual Sum or Average | 1613.70 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4103.19 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2327.87 | 0.00 | 0.00 |
| February | 2630.87 | 0.00 | 0.00 |
| March | 1617.04 | 0.00 | 0.00 |
| April | 1294.12 | 0.00 | 0.00 |
| May | 155.83 | 0.00 | 0.00 |
| June | 0.00 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 63.73 | 0.00 | 0.00 |
| October | 1105.44 | 0.00 | 0.00 |
| November | 1878.20 | 0.00 | 0.00 |
| December | 3022.52 | 0.00 | 0.00 |
| Annual Sum or Average | 1166.67 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 3022.52 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3164.64 | 0.00 | 0.00 |
| February | 3462.37 | 0.00 | 0.00 |
| March | 2179.35 | 0.00 | 0.00 |
| April | 1812.59 | 0.00 | 0.00 |
| May | 266.37 | 0.00 | 0.00 |
| June | 0.93 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 115.45 | 0.00 | 0.00 |
| October | 1633.34 | 0.00 | 0.00 |
| November | 2626.02 | 0.00 | 0.00 |
| December | 4150.72 | 0.00 | 0.00 |
| Annual Sum or Average | 1607.73 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4150.72 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3876.43 | 0.00 | 0.00 |
| February | 4544.74 | 0.00 | 0.00 |
| March | 3359.35 | 0.00 | 0.00 |
| April | 3018.96 | 0.00 | 0.00 |
| May | 633.02 | 0.00 | 0.00 |
| June | 9.53 | 0.00 | 0.00 |
| July | 3.58 | 0.00 | 0.00 |
| August | 5.72 | 0.00 | 0.00 |
| September | 245.21 | 0.00 | 0.00 |
| October | 2510.68 | 0.00 | 0.00 |
| November | 3344.39 | 0.00 | 0.00 |
| December | 5518.69 | 0.00 | 0.00 |
| Annual Sum or Average | 2243.64 | 0.00 | 0.00 |
| Minimum of Months | 3.58 | 0.00 | 0.00 |
| Maximum of Months | 5518.69 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 2984.86 | 0.00 | 0.00 |
| February | 3596.90 | 0.00 | 0.00 |
| March | 2658.40 | 0.00 | 0.00 |
| April | 2374.05 | 0.00 | 0.00 |
| May | 418.39 | 0.00 | 0.00 |
| June | 1.83 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 149.02 | 0.00 | 0.00 |
| October | 1876.89 | 0.00 | 0.00 |
| November | 2538.62 | 0.00 | 0.00 |
| December | 4356.32 | 0.00 | 0.00 |
| Annual Sum or Average | 1736.33 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 4356.32 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 3890.07 | 0.00 | 0.00 |
| February | 4518.65 | 0.00 | 0.00 |
| March | 3269.81 | 0.00 | 0.00 |
| April | 2913.90 | 0.00 | 0.00 |
| May | 550.11 | 0.00 | 0.00 |
| June | 6.53 | 0.00 | 0.00 |
| July | 3.08 | 0.00 | 0.00 |
| August | 4.28 | 0.00 | 0.00 |
| September | 222.25 | 0.00 | 0.00 |
| October | 2468.83 | 0.00 | 0.00 |
| November | 3351.61 | 0.00 | 0.00 |
| December | 5550.14 | 0.00 | 0.00 |
| Annual Sum or Average | 2216.92 | 0.00 | 0.00 |
| Minimum of Months | 3.08 | 0.00 | 0.00 |
| Maximum of Months | 5550.14 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 4808.56 | 0.00 | 0.00 |
| February | 5339.30 | 0.00 | 0.00 |
| March | 3644.99 | 0.00 | 0.00 |
| April | 3146.28 | 0.00 | 0.00 |
| May | 646.02 | 0.00 | 0.00 |
| June | 8.00 | 0.00 | 0.00 |
| July | 2.62 | 0.00 | 0.00 |
| August | 5.93 | 0.00 | 0.00 |
| September | 273.31 | 0.00 | 0.00 |
| October | 2751.19 | 0.00 | 0.00 |
| November | 4062.31 | 0.00 | 0.00 |
| December | 6359.45 | 0.00 | 0.00 |
| Annual Sum or Average | 2572.54 | 0.00 | 0.00 |
| Minimum of Months | 2.62 | 0.00 | 0.00 |
| Maximum of Months | 6359.45 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 4022.18 | 0.00 | 0.00 |
| February | 4525.07 | 0.00 | 0.00 |
| March | 2992.90 | 0.00 | 0.00 |
| April | 2537.51 | 0.00 | 0.00 |
| May | 439.06 | 0.00 | 0.00 |
| June | 1.31 | 0.00 | 0.00 |
| July | 0.00 | 0.00 | 0.00 |
| August | 0.00 | 0.00 | 0.00 |
| September | 174.90 | 0.00 | 0.00 |
| October | 2157.49 | 0.00 | 0.00 |
| November | 3364.08 | 0.00 | 0.00 |
| December | 5270.17 | 0.00 | 0.00 |
| Annual Sum or Average | 2110.61 | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 5270.17 | 0.00 | 0.00 |
Report: COILLOADS
For: MAIN ELECTRIC HEATING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [Btu/h] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [] | |
| January | 4893.04 | 0.00 | 0.00 |
| February | 5378.53 | 0.00 | 0.00 |
| March | 3554.85 | 0.00 | 0.00 |
| April | 3043.78 | 0.00 | 0.00 |
| May | 566.42 | 0.00 | 0.00 |
| June | 6.06 | 0.00 | 0.00 |
| July | 2.71 | 0.00 | 0.00 |
| August | 4.47 | 0.00 | 0.00 |
| September | 242.68 | 0.00 | 0.00 |
| October | 2681.87 | 0.00 | 0.00 |
| November | 4141.09 | 0.00 | 0.00 |
| December | 6447.63 | 0.00 | 0.00 |
| Annual Sum or Average | 2565.17 | 0.00 | 0.00 |
| Minimum of Months | 2.71 | 0.00 | 0.00 |
| Maximum of Months | 6447.63 | 0.00 | 0.00 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.05 |
| June | 0.00 | 0.00 | 0.23 |
| July | 0.00 | 0.00 | 0.24 |
| August | 0.00 | 0.00 | 0.24 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.06 |
| November | 0.00 | 0.00 | 0.02 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.09 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.02 |
| June | 0.00 | 0.00 | 0.15 |
| July | 0.00 | 0.00 | 0.17 |
| August | 0.00 | 0.00 | 0.17 |
| September | 0.00 | 0.00 | 0.13 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.06 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.17 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.02 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.04 |
| June | 0.00 | 0.00 | 0.23 |
| July | 0.00 | 0.00 | 0.25 |
| August | 0.00 | 0.00 | 0.25 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.04 |
| November | 0.00 | 0.00 | 0.02 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.09 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.25 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.04 |
| June | 0.00 | 0.00 | 0.22 |
| July | 0.00 | 0.00 | 0.22 |
| August | 0.00 | 0.00 | 0.20 |
| September | 0.00 | 0.00 | 0.13 |
| October | 0.00 | 0.00 | 0.02 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.07 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.22 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.01 |
| June | 0.00 | 0.00 | 0.13 |
| July | 0.00 | 0.00 | 0.16 |
| August | 0.00 | 0.00 | 0.13 |
| September | 0.00 | 0.00 | 0.08 |
| October | 0.00 | 0.00 | 0.00 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.04 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.16 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.00 |
| May | 0.00 | 0.00 | 0.03 |
| June | 0.00 | 0.00 | 0.22 |
| July | 0.00 | 0.00 | 0.24 |
| August | 0.00 | 0.00 | 0.21 |
| September | 0.00 | 0.00 | 0.13 |
| October | 0.00 | 0.00 | 0.01 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.07 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.03 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.07 |
| April | 0.00 | 0.00 | 0.05 |
| May | 0.00 | 0.00 | 0.11 |
| June | 0.00 | 0.00 | 0.31 |
| July | 0.00 | 0.00 | 0.31 |
| August | 0.00 | 0.00 | 0.31 |
| September | 0.00 | 0.00 | 0.24 |
| October | 0.00 | 0.00 | 0.10 |
| November | 0.00 | 0.00 | 0.05 |
| December | 0.00 | 0.00 | 0.03 |
| Annual Sum or Average | 0.00 | 0.00 | 0.14 |
| Minimum of Months | 0.00 | 0.00 | 0.03 |
| Maximum of Months | 0.00 | 0.00 | 0.31 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.02 |
| March | 0.00 | 0.00 | 0.04 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.06 |
| June | 0.00 | 0.00 | 0.23 |
| July | 0.00 | 0.00 | 0.24 |
| August | 0.00 | 0.00 | 0.24 |
| September | 0.00 | 0.00 | 0.19 |
| October | 0.00 | 0.00 | 0.07 |
| November | 0.00 | 0.00 | 0.04 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.10 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.24 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.03 |
| March | 0.00 | 0.00 | 0.06 |
| April | 0.00 | 0.00 | 0.04 |
| May | 0.00 | 0.00 | 0.11 |
| June | 0.00 | 0.00 | 0.33 |
| July | 0.00 | 0.00 | 0.34 |
| August | 0.00 | 0.00 | 0.33 |
| September | 0.00 | 0.00 | 0.25 |
| October | 0.00 | 0.00 | 0.09 |
| November | 0.00 | 0.00 | 0.04 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.14 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.02 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.09 |
| June | 0.00 | 0.00 | 0.30 |
| July | 0.00 | 0.00 | 0.30 |
| August | 0.00 | 0.00 | 0.27 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.10 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.30 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.00 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.05 |
| June | 0.00 | 0.00 | 0.22 |
| July | 0.00 | 0.00 | 0.23 |
| August | 0.00 | 0.00 | 0.20 |
| September | 0.00 | 0.00 | 0.12 |
| October | 0.00 | 0.00 | 0.01 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.07 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.23 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.09 |
| June | 0.00 | 0.00 | 0.32 |
| July | 0.00 | 0.00 | 0.32 |
| August | 0.00 | 0.00 | 0.29 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.02 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.32 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.02 |
| February | 0.00 | 0.00 | 0.02 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.04 |
| May | 0.00 | 0.00 | 0.11 |
| June | 0.00 | 0.00 | 0.34 |
| July | 0.00 | 0.00 | 0.34 |
| August | 0.00 | 0.00 | 0.32 |
| September | 0.00 | 0.00 | 0.24 |
| October | 0.00 | 0.00 | 0.08 |
| November | 0.00 | 0.00 | 0.03 |
| December | 0.00 | 0.00 | 0.02 |
| Annual Sum or Average | 0.00 | 0.00 | 0.13 |
| Minimum of Months | 0.00 | 0.00 | 0.02 |
| Maximum of Months | 0.00 | 0.00 | 0.34 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.06 |
| June | 0.00 | 0.00 | 0.25 |
| July | 0.00 | 0.00 | 0.26 |
| August | 0.00 | 0.00 | 0.25 |
| September | 0.00 | 0.00 | 0.18 |
| October | 0.00 | 0.00 | 0.05 |
| November | 0.00 | 0.00 | 0.02 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.10 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.01 |
| February | 0.00 | 0.00 | 0.01 |
| March | 0.00 | 0.00 | 0.05 |
| April | 0.00 | 0.00 | 0.03 |
| May | 0.00 | 0.00 | 0.10 |
| June | 0.00 | 0.00 | 0.35 |
| July | 0.00 | 0.00 | 0.36 |
| August | 0.00 | 0.00 | 0.34 |
| September | 0.00 | 0.00 | 0.24 |
| October | 0.00 | 0.00 | 0.07 |
| November | 0.00 | 0.00 | 0.03 |
| December | 0.00 | 0.00 | 0.01 |
| Annual Sum or Average | 0.00 | 0.00 | 0.13 |
| Minimum of Months | 0.00 | 0.00 | 0.01 |
| Maximum of Months | 0.00 | 0.00 | 0.36 |
Report: COILLOADS
For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.03 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.10 |
| June | 0.00 | 0.00 | 0.33 |
| July | 0.00 | 0.00 | 0.33 |
| August | 0.00 | 0.00 | 0.30 |
| September | 0.00 | 0.00 | 0.19 |
| October | 0.00 | 0.00 | 0.03 |
| November | 0.00 | 0.00 | 0.01 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.33 |
Report: COILLOADS
For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.01 |
| May | 0.00 | 0.00 | 0.06 |
| June | 0.00 | 0.00 | 0.24 |
| July | 0.00 | 0.00 | 0.26 |
| August | 0.00 | 0.00 | 0.23 |
| September | 0.00 | 0.00 | 0.14 |
| October | 0.00 | 0.00 | 0.01 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.08 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.26 |
Report: COILLOADS
For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| HEATING COIL HEATING RATE [] | HEATING COIL AIR HEATING RATE [] | COOLING COIL TOTAL COOLING RATE [ton] | |
| January | 0.00 | 0.00 | 0.00 |
| February | 0.00 | 0.00 | 0.00 |
| March | 0.00 | 0.00 | 0.01 |
| April | 0.00 | 0.00 | 0.02 |
| May | 0.00 | 0.00 | 0.09 |
| June | 0.00 | 0.00 | 0.34 |
| July | 0.00 | 0.00 | 0.35 |
| August | 0.00 | 0.00 | 0.31 |
| September | 0.00 | 0.00 | 0.19 |
| October | 0.00 | 0.00 | 0.02 |
| November | 0.00 | 0.00 | 0.00 |
| December | 0.00 | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 | 0.11 |
| Minimum of Months | 0.00 | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 | 0.35 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.58 | 1080.74 |
| February | 0.00 | 0.00 | 1474.49 | 991.56 |
| March | 0.00 | 0.00 | 1445.83 | 1076.46 |
| April | 0.00 | 0.00 | 1381.26 | 995.21 |
| May | 0.00 | 0.00 | 1280.31 | 953.23 |
| June | 0.00 | 0.00 | 1183.43 | 852.68 |
| July | 0.00 | 0.00 | 1115.49 | 830.51 |
| August | 0.00 | 0.00 | 1089.44 | 811.12 |
| September | 0.00 | 0.00 | 1118.76 | 806.08 |
| October | 0.00 | 0.00 | 1192.37 | 887.75 |
| November | 0.00 | 0.00 | 1287.80 | 927.87 |
| December | 0.00 | 0.00 | 1386.45 | 1032.25 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.82 | 11245.46 |
| Minimum of Months | 0.00 | 0.00 | 1089.44 | 806.08 |
| Maximum of Months | 0.00 | 0.00 | 1474.49 | 1080.74 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.64 | 1080.78 |
| February | 0.00 | 0.00 | 1474.08 | 991.29 |
| March | 0.00 | 0.00 | 1448.09 | 1078.14 |
| April | 0.00 | 0.00 | 1380.90 | 994.95 |
| May | 0.00 | 0.00 | 1279.96 | 952.97 |
| June | 0.00 | 0.00 | 1180.65 | 850.67 |
| July | 0.00 | 0.00 | 1117.43 | 831.96 |
| August | 0.00 | 0.00 | 1087.22 | 809.47 |
| September | 0.00 | 0.00 | 1119.71 | 806.76 |
| October | 0.00 | 0.00 | 1193.43 | 888.54 |
| November | 0.00 | 0.00 | 1287.97 | 928.00 |
| December | 0.00 | 0.00 | 1386.47 | 1032.26 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.86 | 11245.79 |
| Minimum of Months | 0.00 | 0.00 | 1087.22 | 806.76 |
| Maximum of Months | 0.00 | 0.00 | 1474.08 | 1080.78 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.64 | 1080.79 |
| February | 0.00 | 0.00 | 1474.27 | 991.41 |
| March | 0.00 | 0.00 | 1445.91 | 1076.52 |
| April | 0.00 | 0.00 | 1381.41 | 995.32 |
| May | 0.00 | 0.00 | 1280.23 | 953.17 |
| June | 0.00 | 0.00 | 1180.89 | 850.84 |
| July | 0.00 | 0.00 | 1117.45 | 831.97 |
| August | 0.00 | 0.00 | 1089.45 | 811.13 |
| September | 0.00 | 0.00 | 1118.49 | 805.88 |
| October | 0.00 | 0.00 | 1192.12 | 887.57 |
| November | 0.00 | 0.00 | 1287.73 | 927.83 |
| December | 0.00 | 0.00 | 1386.45 | 1032.25 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.73 | 11244.67 |
| Minimum of Months | 0.00 | 0.00 | 1089.45 | 805.88 |
| Maximum of Months | 0.00 | 0.00 | 1474.27 | 1080.79 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.68 | 1080.82 |
| February | 0.00 | 0.00 | 1476.90 | 993.18 |
| March | 0.00 | 0.00 | 1445.92 | 1076.53 |
| April | 0.00 | 0.00 | 1381.07 | 995.08 |
| May | 0.00 | 0.00 | 1280.30 | 953.22 |
| June | 0.00 | 0.00 | 1183.42 | 852.66 |
| July | 0.00 | 0.00 | 1115.47 | 830.50 |
| August | 0.00 | 0.00 | 1089.43 | 811.11 |
| September | 0.00 | 0.00 | 1118.90 | 806.18 |
| October | 0.00 | 0.00 | 1193.25 | 888.41 |
| November | 0.00 | 0.00 | 1288.28 | 928.22 |
| December | 0.00 | 0.00 | 1387.13 | 1032.76 |
| Annual Sum or Average | 0.00 | 0.00 | 1283.18 | 11248.66 |
| Minimum of Months | 0.00 | 0.00 | 1089.43 | 806.18 |
| Maximum of Months | 0.00 | 0.00 | 1476.90 | 1080.82 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.53 | 1080.70 |
| February | 0.00 | 0.00 | 1477.27 | 993.43 |
| March | 0.00 | 0.00 | 1446.36 | 1076.85 |
| April | 0.00 | 0.00 | 1381.25 | 995.21 |
| May | 0.00 | 0.00 | 1280.07 | 953.05 |
| June | 0.00 | 0.00 | 1181.96 | 851.62 |
| July | 0.00 | 0.00 | 1117.36 | 831.91 |
| August | 0.00 | 0.00 | 1087.24 | 809.48 |
| September | 0.00 | 0.00 | 1119.79 | 806.82 |
| October | 0.00 | 0.00 | 1194.19 | 889.10 |
| November | 0.00 | 0.00 | 1288.27 | 928.21 |
| December | 0.00 | 0.00 | 1388.45 | 1033.74 |
| Annual Sum or Average | 0.00 | 0.00 | 1283.35 | 11250.11 |
| Minimum of Months | 0.00 | 0.00 | 1087.24 | 806.82 |
| Maximum of Months | 0.00 | 0.00 | 1477.27 | 1080.70 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.67 | 1080.81 |
| February | 0.00 | 0.00 | 1477.06 | 993.29 |
| March | 0.00 | 0.00 | 1445.93 | 1076.54 |
| April | 0.00 | 0.00 | 1380.99 | 995.02 |
| May | 0.00 | 0.00 | 1280.19 | 953.13 |
| June | 0.00 | 0.00 | 1181.26 | 851.11 |
| July | 0.00 | 0.00 | 1117.23 | 831.81 |
| August | 0.00 | 0.00 | 1089.44 | 811.12 |
| September | 0.00 | 0.00 | 1118.54 | 805.92 |
| October | 0.00 | 0.00 | 1192.62 | 887.94 |
| November | 0.00 | 0.00 | 1290.49 | 929.81 |
| December | 0.00 | 0.00 | 1386.59 | 1032.36 |
| Annual Sum or Average | 0.00 | 0.00 | 1283.20 | 11248.85 |
| Minimum of Months | 0.00 | 0.00 | 1089.44 | 805.92 |
| Maximum of Months | 0.00 | 0.00 | 1477.06 | 1080.81 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.27 | 1080.51 |
| February | 0.00 | 0.00 | 1474.57 | 991.61 |
| March | 0.00 | 0.00 | 1445.72 | 1076.38 |
| April | 0.00 | 0.00 | 1378.87 | 993.49 |
| May | 0.00 | 0.00 | 1279.25 | 952.44 |
| June | 0.00 | 0.00 | 1180.39 | 850.49 |
| July | 0.00 | 0.00 | 1117.20 | 831.79 |
| August | 0.00 | 0.00 | 1087.23 | 809.47 |
| September | 0.00 | 0.00 | 1119.31 | 806.48 |
| October | 0.00 | 0.00 | 1192.09 | 887.55 |
| November | 0.00 | 0.00 | 1287.30 | 927.51 |
| December | 0.00 | 0.00 | 1386.47 | 1032.27 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.19 | 11239.98 |
| Minimum of Months | 0.00 | 0.00 | 1087.23 | 806.48 |
| Maximum of Months | 0.00 | 0.00 | 1474.57 | 1080.51 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.43 | 1080.63 |
| February | 0.00 | 0.00 | 1471.89 | 989.81 |
| March | 0.00 | 0.00 | 1446.28 | 1076.79 |
| April | 0.00 | 0.00 | 1381.18 | 995.15 |
| May | 0.00 | 0.00 | 1278.04 | 951.53 |
| June | 0.00 | 0.00 | 1180.07 | 850.25 |
| July | 0.00 | 0.00 | 1117.07 | 831.69 |
| August | 0.00 | 0.00 | 1087.41 | 809.61 |
| September | 0.00 | 0.00 | 1119.53 | 806.63 |
| October | 0.00 | 0.00 | 1191.44 | 887.06 |
| November | 0.00 | 0.00 | 1285.95 | 926.54 |
| December | 0.00 | 0.00 | 1386.53 | 1032.31 |
| Annual Sum or Average | 0.00 | 0.00 | 1281.97 | 11238.02 |
| Minimum of Months | 0.00 | 0.00 | 1087.41 | 806.63 |
| Maximum of Months | 0.00 | 0.00 | 1471.89 | 1080.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.28 | 1080.52 |
| February | 0.00 | 0.00 | 1474.57 | 991.62 |
| March | 0.00 | 0.00 | 1445.53 | 1076.24 |
| April | 0.00 | 0.00 | 1378.72 | 993.38 |
| May | 0.00 | 0.00 | 1277.36 | 951.03 |
| June | 0.00 | 0.00 | 1182.67 | 852.13 |
| July | 0.00 | 0.00 | 1115.24 | 830.33 |
| August | 0.00 | 0.00 | 1089.31 | 811.02 |
| September | 0.00 | 0.00 | 1117.06 | 804.85 |
| October | 0.00 | 0.00 | 1193.41 | 888.53 |
| November | 0.00 | 0.00 | 1286.02 | 926.59 |
| December | 0.00 | 0.00 | 1386.60 | 1032.36 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.04 | 11238.60 |
| Minimum of Months | 0.00 | 0.00 | 1089.31 | 804.85 |
| Maximum of Months | 0.00 | 0.00 | 1474.57 | 1080.52 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.48 | 1080.67 |
| February | 0.00 | 0.00 | 1474.54 | 991.59 |
| March | 0.00 | 0.00 | 1447.98 | 1078.06 |
| April | 0.00 | 0.00 | 1380.65 | 994.77 |
| May | 0.00 | 0.00 | 1278.39 | 951.80 |
| June | 0.00 | 0.00 | 1180.31 | 850.42 |
| July | 0.00 | 0.00 | 1117.20 | 831.79 |
| August | 0.00 | 0.00 | 1087.23 | 809.47 |
| September | 0.00 | 0.00 | 1119.41 | 806.55 |
| October | 0.00 | 0.00 | 1193.48 | 888.58 |
| November | 0.00 | 0.00 | 1287.67 | 927.78 |
| December | 0.00 | 0.00 | 1386.67 | 1032.41 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.64 | 11243.89 |
| Minimum of Months | 0.00 | 0.00 | 1087.23 | 806.55 |
| Maximum of Months | 0.00 | 0.00 | 1474.54 | 1080.67 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.69 | 1080.82 |
| February | 0.00 | 0.00 | 1476.89 | 993.17 |
| March | 0.00 | 0.00 | 1446.14 | 1076.69 |
| April | 0.00 | 0.00 | 1380.98 | 995.01 |
| May | 0.00 | 0.00 | 1278.34 | 951.76 |
| June | 0.00 | 0.00 | 1180.15 | 850.31 |
| July | 0.00 | 0.00 | 1117.07 | 831.69 |
| August | 0.00 | 0.00 | 1087.42 | 809.61 |
| September | 0.00 | 0.00 | 1119.17 | 806.38 |
| October | 0.00 | 0.00 | 1192.60 | 887.92 |
| November | 0.00 | 0.00 | 1288.23 | 928.18 |
| December | 0.00 | 0.00 | 1387.15 | 1032.77 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.69 | 11244.33 |
| Minimum of Months | 0.00 | 0.00 | 1087.42 | 806.38 |
| Maximum of Months | 0.00 | 0.00 | 1476.89 | 1080.82 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.63 | 1080.78 |
| February | 0.00 | 0.00 | 1474.63 | 991.65 |
| March | 0.00 | 0.00 | 1447.87 | 1077.98 |
| April | 0.00 | 0.00 | 1378.30 | 993.08 |
| May | 0.00 | 0.00 | 1280.11 | 953.07 |
| June | 0.00 | 0.00 | 1180.00 | 850.20 |
| July | 0.00 | 0.00 | 1117.15 | 831.75 |
| August | 0.00 | 0.00 | 1087.28 | 809.51 |
| September | 0.00 | 0.00 | 1119.23 | 806.42 |
| October | 0.00 | 0.00 | 1192.53 | 887.87 |
| November | 0.00 | 0.00 | 1288.24 | 928.19 |
| December | 0.00 | 0.00 | 1386.98 | 1032.65 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.55 | 11243.15 |
| Minimum of Months | 0.00 | 0.00 | 1087.28 | 806.42 |
| Maximum of Months | 0.00 | 0.00 | 1474.63 | 1080.78 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.43 | 1080.63 |
| February | 0.00 | 0.00 | 1474.43 | 991.52 |
| March | 0.00 | 0.00 | 1445.84 | 1076.47 |
| April | 0.00 | 0.00 | 1381.40 | 995.31 |
| May | 0.00 | 0.00 | 1279.34 | 952.50 |
| June | 0.00 | 0.00 | 1180.24 | 850.38 |
| July | 0.00 | 0.00 | 1117.40 | 831.93 |
| August | 0.00 | 0.00 | 1087.23 | 809.47 |
| September | 0.00 | 0.00 | 1119.78 | 806.81 |
| October | 0.00 | 0.00 | 1193.36 | 888.49 |
| November | 0.00 | 0.00 | 1288.22 | 928.17 |
| December | 0.00 | 0.00 | 1386.11 | 1032.00 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.62 | 11243.69 |
| Minimum of Months | 0.00 | 0.00 | 1087.23 | 806.81 |
| Maximum of Months | 0.00 | 0.00 | 1474.43 | 1080.63 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.47 | 1080.66 |
| February | 0.00 | 0.00 | 1474.53 | 991.59 |
| March | 0.00 | 0.00 | 1445.91 | 1076.52 |
| April | 0.00 | 0.00 | 1381.37 | 995.29 |
| May | 0.00 | 0.00 | 1277.43 | 951.08 |
| June | 0.00 | 0.00 | 1182.06 | 851.69 |
| July | 0.00 | 0.00 | 1117.23 | 831.81 |
| August | 0.00 | 0.00 | 1087.23 | 809.47 |
| September | 0.00 | 0.00 | 1119.40 | 806.54 |
| October | 0.00 | 0.00 | 1191.62 | 887.20 |
| November | 0.00 | 0.00 | 1288.08 | 928.08 |
| December | 0.00 | 0.00 | 1386.49 | 1032.28 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.45 | 11242.19 |
| Minimum of Months | 0.00 | 0.00 | 1087.23 | 806.54 |
| Maximum of Months | 0.00 | 0.00 | 1474.53 | 1080.66 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.54 | 1080.71 |
| February | 0.00 | 0.00 | 1474.53 | 991.59 |
| March | 0.00 | 0.00 | 1445.82 | 1076.45 |
| April | 0.00 | 0.00 | 1381.24 | 995.20 |
| May | 0.00 | 0.00 | 1278.29 | 951.72 |
| June | 0.00 | 0.00 | 1180.67 | 850.69 |
| July | 0.00 | 0.00 | 1117.32 | 831.87 |
| August | 0.00 | 0.00 | 1087.25 | 809.49 |
| September | 0.00 | 0.00 | 1119.60 | 806.68 |
| October | 0.00 | 0.00 | 1192.70 | 888.00 |
| November | 0.00 | 0.00 | 1286.90 | 927.23 |
| December | 0.00 | 0.00 | 1386.68 | 1032.42 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.43 | 11242.05 |
| Minimum of Months | 0.00 | 0.00 | 1087.25 | 806.68 |
| Maximum of Months | 0.00 | 0.00 | 1474.53 | 1080.71 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.57 | 1080.73 |
| February | 0.00 | 0.00 | 1476.29 | 992.77 |
| March | 0.00 | 0.00 | 1446.36 | 1076.86 |
| April | 0.00 | 0.00 | 1381.06 | 995.07 |
| May | 0.00 | 0.00 | 1278.21 | 951.67 |
| June | 0.00 | 0.00 | 1183.35 | 852.62 |
| July | 0.00 | 0.00 | 1115.41 | 830.46 |
| August | 0.00 | 0.00 | 1088.27 | 810.25 |
| September | 0.00 | 0.00 | 1118.65 | 806.00 |
| October | 0.00 | 0.00 | 1193.75 | 888.78 |
| November | 0.00 | 0.00 | 1288.26 | 928.20 |
| December | 0.00 | 0.00 | 1386.87 | 1032.56 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.87 | 11245.95 |
| Minimum of Months | 0.00 | 0.00 | 1088.27 | 806.00 |
| Maximum of Months | 0.00 | 0.00 | 1476.29 | 1080.73 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.70 | 1080.83 |
| February | 0.00 | 0.00 | 1476.96 | 993.22 |
| March | 0.00 | 0.00 | 1446.12 | 1076.67 |
| April | 0.00 | 0.00 | 1381.29 | 995.23 |
| May | 0.00 | 0.00 | 1279.40 | 952.55 |
| June | 0.00 | 0.00 | 1180.09 | 850.27 |
| July | 0.00 | 0.00 | 1117.20 | 831.79 |
| August | 0.00 | 0.00 | 1087.23 | 809.47 |
| September | 0.00 | 0.00 | 1119.47 | 806.59 |
| October | 0.00 | 0.00 | 1193.57 | 888.64 |
| November | 0.00 | 0.00 | 1288.20 | 928.16 |
| December | 0.00 | 0.00 | 1387.26 | 1032.85 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.91 | 11246.28 |
| Minimum of Months | 0.00 | 0.00 | 1087.23 | 806.59 |
| Maximum of Months | 0.00 | 0.00 | 1476.96 | 1080.83 |
Report: WATER HEATER: LOADS
For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| WATER HEATER TOTAL DEMAND RATE [] | WATER HEATER TOTAL DEMAND ENERGY [] | WATER HEATER HEATING RATE [Btu/h] | WATER HEATER HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 | 1451.69 | 1080.82 |
| February | 0.00 | 0.00 | 1476.88 | 993.17 |
| March | 0.00 | 0.00 | 1445.93 | 1076.53 |
| April | 0.00 | 0.00 | 1380.80 | 994.88 |
| May | 0.00 | 0.00 | 1278.29 | 951.72 |
| June | 0.00 | 0.00 | 1180.68 | 850.70 |
| July | 0.00 | 0.00 | 1117.31 | 831.87 |
| August | 0.00 | 0.00 | 1087.25 | 809.48 |
| September | 0.00 | 0.00 | 1119.61 | 806.69 |
| October | 0.00 | 0.00 | 1193.31 | 888.45 |
| November | 0.00 | 0.00 | 1288.19 | 928.15 |
| December | 0.00 | 0.00 | 1387.15 | 1032.77 |
| Annual Sum or Average | 0.00 | 0.00 | 1282.79 | 11245.23 |
| Minimum of Months | 0.00 | 0.00 | 1087.25 | 806.69 |
| Maximum of Months | 0.00 | 0.00 | 1476.88 | 1080.82 |
Report: HEATING AND COOLING LOADS
For: BREEZEWAY
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 8.44 | 2824.63 |
| February | 6.78 | 2993.99 |
| March | 21.96 | 2507.48 |
| April | 12.24 | 2237.09 |
| May | 34.68 | 626.90 |
| June | 147.58 | 11.79 |
| July | 155.56 | 6.93 |
| August | 157.42 | 4.32 |
| September | 120.74 | 151.62 |
| October | 39.45 | 1744.76 |
| November | 16.75 | 2288.58 |
| December | 8.46 | 3885.56 |
| Annual Sum or Average | 730.06 | 19283.64 |
| Minimum of Months | 6.78 | 4.32 |
| Maximum of Months | 157.42 | 3885.56 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 4.11 | 2155.57 |
| February | 2.06 | 2349.14 |
| March | 8.03 | 1974.77 |
| April | 2.52 | 1761.99 |
| May | 13.44 | 452.36 |
| June | 93.80 | 4.36 |
| July | 111.56 | 0.65 |
| August | 112.52 | 0.00 |
| September | 87.63 | 84.94 |
| October | 20.62 | 1280.28 |
| November | 8.37 | 1709.68 |
| December | 4.29 | 3016.90 |
| Annual Sum or Average | 468.94 | 14790.62 |
| Minimum of Months | 2.06 | 0.00 |
| Maximum of Months | 112.52 | 3016.90 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 5.42 | 2791.48 |
| February | 4.06 | 2940.26 |
| March | 16.39 | 2418.90 |
| April | 9.24 | 2139.66 |
| May | 31.05 | 556.63 |
| June | 150.75 | 9.53 |
| July | 167.05 | 6.36 |
| August | 166.71 | 3.71 |
| September | 122.45 | 139.23 |
| October | 31.55 | 1701.01 |
| November | 11.90 | 2264.74 |
| December | 5.11 | 3851.36 |
| Annual Sum or Average | 721.69 | 18822.88 |
| Minimum of Months | 4.06 | 3.71 |
| Maximum of Months | 167.05 | 3851.36 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.40 | 3473.22 |
| February | 0.23 | 3525.94 |
| March | 6.31 | 2746.45 |
| April | 4.74 | 2350.09 |
| May | 27.05 | 642.87 |
| June | 139.98 | 10.47 |
| July | 145.91 | 6.06 |
| August | 132.18 | 4.49 |
| September | 85.82 | 166.70 |
| October | 11.47 | 1915.25 |
| November | 1.56 | 2771.85 |
| December | 0.33 | 4462.08 |
| Annual Sum or Average | 555.98 | 22075.46 |
| Minimum of Months | 0.23 | 4.49 |
| Maximum of Months | 145.91 | 4462.08 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 2866.46 |
| February | 0.00 | 2953.94 |
| March | 0.16 | 2255.79 |
| April | 0.10 | 1912.16 |
| May | 8.42 | 478.61 |
| June | 86.60 | 3.62 |
| July | 102.13 | 0.40 |
| August | 87.46 | 0.00 |
| September | 52.74 | 97.51 |
| October | 1.26 | 1479.54 |
| November | 0.00 | 2254.38 |
| December | 0.00 | 3625.04 |
| Annual Sum or Average | 338.88 | 17927.45 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 102.13 | 3625.04 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 3477.87 |
| February | 0.00 | 3501.97 |
| March | 1.70 | 2650.79 |
| April | 2.36 | 2251.01 |
| May | 23.13 | 575.10 |
| June | 143.32 | 9.08 |
| July | 157.24 | 5.98 |
| August | 140.93 | 3.93 |
| September | 85.65 | 150.99 |
| October | 4.32 | 1849.57 |
| November | 0.14 | 2780.34 |
| December | 0.00 | 4448.17 |
| Annual Sum or Average | 558.81 | 21704.79 |
| Minimum of Months | 0.00 | 3.93 |
| Maximum of Months | 157.24 | 4448.17 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 21.98 | 1802.38 |
| February | 20.85 | 1935.81 |
| March | 46.52 | 1564.09 |
| April | 30.73 | 1349.45 |
| May | 74.31 | 234.18 |
| June | 203.03 | 1.08 |
| July | 205.97 | 0.00 |
| August | 205.86 | 0.00 |
| September | 159.42 | 84.74 |
| October | 67.23 | 1169.95 |
| November | 33.89 | 1489.75 |
| December | 18.21 | 2612.76 |
| Annual Sum or Average | 1088.02 | 12244.18 |
| Minimum of Months | 18.21 | 0.00 |
| Maximum of Months | 205.97 | 2612.76 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 14.98 | 1130.36 |
| February | 11.41 | 1268.70 |
| March | 27.41 | 1010.68 |
| April | 14.70 | 867.18 |
| May | 44.14 | 109.89 |
| June | 143.83 | 0.00 |
| July | 157.60 | 0.00 |
| August | 157.91 | 0.00 |
| September | 125.18 | 37.34 |
| October | 47.11 | 714.61 |
| November | 24.41 | 917.15 |
| December | 14.24 | 1712.18 |
| Annual Sum or Average | 782.93 | 7768.09 |
| Minimum of Months | 11.41 | 0.00 |
| Maximum of Months | 157.91 | 1712.18 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 16.00 | 1766.14 |
| February | 16.50 | 1892.23 |
| March | 41.60 | 1475.38 |
| April | 29.98 | 1272.84 |
| May | 74.67 | 196.36 |
| June | 211.66 | 0.83 |
| July | 222.38 | 0.00 |
| August | 219.96 | 0.00 |
| September | 164.57 | 75.88 |
| October | 60.90 | 1142.57 |
| November | 27.98 | 1471.65 |
| December | 14.49 | 2583.26 |
| Annual Sum or Average | 1100.69 | 11877.13 |
| Minimum of Months | 14.49 | 0.00 |
| Maximum of Months | 222.38 | 2583.26 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 1.25 | 2430.93 |
| February | 1.60 | 2434.63 |
| March | 17.02 | 1766.79 |
| April | 15.68 | 1428.69 |
| May | 62.17 | 241.44 |
| June | 195.39 | 0.75 |
| July | 195.38 | 0.00 |
| August | 176.60 | 0.00 |
| September | 117.12 | 98.06 |
| October | 22.48 | 1311.03 |
| November | 3.92 | 1942.48 |
| December | 1.03 | 3210.21 |
| Annual Sum or Average | 809.64 | 14865.01 |
| Minimum of Months | 1.03 | 0.00 |
| Maximum of Months | 195.39 | 3210.21 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 1786.81 |
| February | 0.03 | 1823.96 |
| March | 3.01 | 1241.19 |
| April | 4.15 | 961.29 |
| May | 33.36 | 119.61 |
| June | 136.53 | 0.00 |
| July | 147.10 | 0.00 |
| August | 128.40 | 0.00 |
| September | 81.75 | 47.34 |
| October | 5.88 | 848.51 |
| November | 0.35 | 1395.15 |
| December | 0.00 | 2320.00 |
| Annual Sum or Average | 540.57 | 10543.84 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 147.10 | 2320.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.07 | 2436.84 |
| February | 0.51 | 2408.09 |
| March | 10.54 | 1678.14 |
| April | 14.01 | 1350.70 |
| May | 62.07 | 205.11 |
| June | 203.76 | 0.69 |
| July | 211.45 | 0.00 |
| August | 190.39 | 0.00 |
| September | 120.80 | 86.03 |
| October | 13.17 | 1257.71 |
| November | 1.98 | 1956.86 |
| December | 0.04 | 3196.14 |
| Annual Sum or Average | 828.78 | 14576.31 |
| Minimum of Months | 0.04 | 0.00 |
| Maximum of Months | 211.45 | 3196.14 |
Report: HEATING AND COOLING LOADS
For: ATTIC
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 0.00 |
| February | 0.00 | 0.00 |
| March | 0.00 | 0.00 |
| April | 0.00 | 0.00 |
| May | 0.00 | 0.00 |
| June | 0.00 | 0.00 |
| July | 0.00 | 0.00 |
| August | 0.00 | 0.00 |
| September | 0.00 | 0.00 |
| October | 0.00 | 0.00 |
| November | 0.00 | 0.00 |
| December | 0.00 | 0.00 |
| Annual Sum or Average | 0.00 | 0.00 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 0.00 | 0.00 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.04 | 3744.34 |
| February | 0.40 | 3717.55 |
| March | 10.41 | 2720.30 |
| April | 12.82 | 2254.08 |
| May | 62.92 | 433.45 |
| June | 221.73 | 4.49 |
| July | 229.54 | 2.07 |
| August | 208.19 | 3.42 |
| September | 127.75 | 179.72 |
| October | 13.41 | 2052.26 |
| November | 1.98 | 3066.70 |
| December | 0.01 | 4933.96 |
| Annual Sum or Average | 889.21 | 23112.34 |
| Minimum of Months | 0.01 | 2.07 |
| Maximum of Months | 229.54 | 4933.96 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT3_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 9.39 | 2983.32 |
| February | 8.20 | 3130.03 |
| March | 32.50 | 2507.64 |
| April | 22.17 | 2162.61 |
| May | 70.13 | 421.88 |
| June | 225.52 | 4.85 |
| July | 235.87 | 2.36 |
| August | 227.72 | 3.28 |
| September | 160.31 | 164.94 |
| October | 47.00 | 1893.37 |
| November | 18.39 | 2487.46 |
| December | 8.03 | 4256.45 |
| Annual Sum or Average | 1065.22 | 20018.19 |
| Minimum of Months | 8.03 | 2.36 |
| Maximum of Months | 235.87 | 4256.45 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 12.93 | 3014.14 |
| February | 11.63 | 3191.82 |
| March | 38.36 | 2612.09 |
| April | 24.77 | 2271.69 |
| May | 72.45 | 492.21 |
| June | 219.23 | 7.17 |
| July | 221.37 | 2.78 |
| August | 215.71 | 4.45 |
| September | 157.86 | 184.52 |
| October | 55.70 | 1952.20 |
| November | 23.66 | 2516.57 |
| December | 11.53 | 4291.10 |
| Annual Sum or Average | 1065.20 | 20540.74 |
| Minimum of Months | 11.53 | 2.78 |
| Maximum of Months | 221.37 | 4291.10 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 0.00 | 3079.83 |
| February | 0.04 | 3129.59 |
| March | 4.58 | 2291.70 |
| April | 5.13 | 1880.32 |
| May | 37.69 | 336.20 |
| June | 155.58 | 0.97 |
| July | 166.08 | 0.00 |
| August | 146.92 | 0.00 |
| September | 90.91 | 129.60 |
| October | 7.09 | 1652.02 |
| November | 0.51 | 2492.83 |
| December | 0.00 | 4035.43 |
| Annual Sum or Average | 614.50 | 19028.49 |
| Minimum of Months | 0.00 | 0.00 |
| Maximum of Months | 166.08 | 4035.43 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT2_FRONTROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 8.14 | 2284.41 |
| February | 5.38 | 2486.43 |
| March | 21.36 | 2034.56 |
| April | 11.12 | 1758.33 |
| May | 43.85 | 320.21 |
| June | 159.13 | 1.35 |
| July | 172.23 | 0.00 |
| August | 166.31 | 0.00 |
| September | 122.15 | 110.37 |
| October | 35.40 | 1436.45 |
| November | 14.86 | 1880.22 |
| December | 7.31 | 3334.04 |
| Annual Sum or Average | 767.22 | 15646.37 |
| Minimum of Months | 5.38 | 0.00 |
| Maximum of Months | 172.23 | 3334.04 |
Report: HEATING AND COOLING LOADS
For: LIVING_UNIT1_BACKROW_TOPFLOOR
Timestamp: 2024-06-27 17:41:15
Custom Monthly Report| ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] | ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu] | |
| January | 1.07 | 3738.21 |
| February | 1.44 | 3749.11 |
| March | 18.14 | 2833.64 |
| April | 15.67 | 2367.04 |
| May | 65.56 | 502.22 |
| June | 215.48 | 6.02 |
| July | 215.21 | 2.04 |
| August | 196.53 | 4.61 |
| September | 126.97 | 205.62 |
| October | 23.07 | 2138.79 |
| November | 4.11 | 3056.20 |
| December | 0.68 | 4943.88 |
| Annual Sum or Average | 883.95 | 23547.37 |
| Minimum of Months | 0.68 | 2.04 |
| Maximum of Months | 215.48 | 4943.88 |