Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:07

Tabular Output Report in Format: HTML

Building: US+MF+CZ7+hp+crawlspace+IECC_2006

Environment: ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2024-06-27 18:07:29


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 1213288.49 31.11 56.14
Net Site Energy 1213288.49 31.11 56.14
Total Source Energy 3842484.64 98.51 177.81
Net Source Energy 3842484.64 98.51 177.81


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 481895.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 30070.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 79130.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 239584.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 1213288.49 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Note: Electricity appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 481895.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 30070.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 17305.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 61824.83 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
  Water Heater 239584.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 481895.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 30070.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 60500.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 79130.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 239584.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 3.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 38.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.14
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 56.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 17.14


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 21.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50
Other 7.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 31.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 1213288.486 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 1213288.486 100.00
     
Total On-Site and Utility Electric Sources 1213288.486 100.00
Total Electricity End Uses 1213288.486 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 370400.12 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 370400.12 100.00
Total Water End Uses 370400.12 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2871.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR | SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:07
RunPeriod ANNUAL
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [ft] 1177.88
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.9113 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.9113 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.5049 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.9113 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
CRAWLSPACE 7794.39 No Yes 1.00 CRAWLSPACE GENERAL CRAWLSPACE 0.0000 0.00 0.0000  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.9113 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.9113 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.9113 600.28 2.9092  
Total 39005.22             0.5049 1083.48 1.6118  
Conditioned Total 21609.96             0.9113 600.28 2.9092  
Unconditioned Total 17395.26             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 21609.96 17395.26 0.00 0.5049 1083.48 1.6118
Total 39005.22 21609.96 17395.26 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 05-JAN-08:00 - - - - - - - - - - - 01-JAN-08:19
Heating 359.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 33.84 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 28.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 206.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 636.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 359.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 8.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 0.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 4.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 3.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 3.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 19.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 1.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 26.07 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
  Water Heater 206.50 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 1526161.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 95234.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 191605.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 250604.99 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 758764.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 3842484.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 70.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 8.87 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 11.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 35.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 177.81 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 39.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 4.91 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 6.42 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 19.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 98.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 1322.18
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 1093.88
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 1322.38
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 944.53
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 716.78
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 944.56
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 944.62
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 716.72
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 944.37
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 1335.22
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 1335.49
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 1335.79
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 1107.42
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 1107.59
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 1335.73
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96 1321.96 1321.96 1321.96 1321.96 1321.96 1.00 1.00 1321.96
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83 1093.83 1093.83 1093.83 1093.83 1093.83 1.00 1.00 1093.83
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48 1322.48 1322.48 1322.48 1322.48 1322.48 1.00 1.00 1322.48
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1322.18 1322.18 1322.18 1322.18 1322.18 1322.18 1.00 1.00 1322.18
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1093.88 1093.88 1093.88 1093.88 1093.88 1093.88 1.00 1.00 1093.88
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1322.38 1322.38 1322.38 1322.38 1322.38 1322.38 1.00 1.00 1322.38
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 944.53 944.53 944.53 944.53 944.53 944.53 1.00 1.00 944.53
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 716.78 716.78 716.78 716.78 716.78 716.78 1.00 1.00 716.78
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 944.56 944.56 944.56 944.56 944.56 944.56 1.00 1.00 944.56
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 944.62 944.62 944.62 944.62 944.62 944.62 1.00 1.00 944.62
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 716.72 716.72 716.72 716.72 716.72 716.72 1.00 1.00 716.72
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 944.37 944.37 944.37 944.37 944.37 944.37 1.00 1.00 944.37
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1335.79 1335.79 1335.79 1335.79 1335.79 1335.79 1.00 1.00 1335.79
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1107.59 1107.59 1107.59 1107.59 1107.59 1107.59 1.00 1.00 1107.59
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1335.49 1335.49 1335.49 1335.49 1335.49 1335.49 1.00 1.00 1335.49
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1335.73 1335.73 1335.73 1335.73 1335.73 1335.73 1.00 1.00 1335.73
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1107.42 1107.42 1107.42 1107.42 1107.42 1107.42 1.00 1.00 1107.42
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1335.22 1335.22 1335.22 1335.22 1335.22 1335.22 1.00 1.00 1335.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96 4.36 0.704675
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83 3.65 0.701083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48 4.41 0.701083
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1322.18 4.40 0.702589
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 1093.88 3.65 0.701083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1322.38 4.41 0.701083
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 944.53 3.04 0.711497
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 716.78 2.39 0.701083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 944.56 3.15 0.701083
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 944.62 3.06 0.710431
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 716.72 2.39 0.701083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 944.37 3.15 0.701083
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1335.79 4.38 0.706068
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1107.59 3.69 0.701083
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1335.49 4.45 0.701083
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1335.73 4.38 0.706288
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1107.42 3.69 0.701083
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1335.22 4.45 0.701083
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatPump:AirToAir

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Supplemental Heating Coil Nominal Capacity [Btu/h] Fraction of Supply Air Flow That Goes Through the Controlling Zone
HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96 1321.96 1321.96 52314.21 4.36 29309.66 1.00
HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83 1093.83 1093.83 43743.95 3.65 25047.21 1.00
HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48 1322.48 1322.48 52888.06 4.41 29319.27 1.00
HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR 1322.18 1322.18 1322.18 52767.07 4.40 29313.63 1.00
HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR 1093.88 1093.88 1093.88 43746.22 3.65 25048.27 1.00
HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR 1322.38 1322.38 1322.38 52884.29 4.41 29317.51 1.00
HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR 944.53 944.53 944.53 36519.62 3.04 22255.42 1.00
HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR 716.78 716.78 716.78 28665.16 2.39 18001.20 1.00
HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR 944.56 944.56 944.56 37774.70 3.15 22256.07 1.00
HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR 944.62 944.62 944.62 36677.22 3.06 22257.07 1.00
HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR 716.72 716.72 716.72 28662.93 2.39 18000.16 1.00
HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR 944.37 944.37 944.37 37766.75 3.15 22252.35 1.00
HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR 1335.79 1335.79 1335.79 52565.72 4.38 29567.94 1.00
HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR 1107.59 1107.59 1107.59 44294.34 3.69 25304.26 1.00
HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR 1335.49 1335.49 1335.49 53408.64 4.45 29562.42 1.00
HEAT PUMP_UNIT1_BACKROW_TOPFLOOR 1335.73 1335.73 1335.73 52516.96 4.38 29566.74 1.00
HEAT PUMP_UNIT2_BACKROW_TOPFLOOR 1107.42 1107.42 1107.42 44287.63 3.69 25301.13 1.00
HEAT PUMP_UNIT3_BACKROW_TOPFLOOR 1335.22 1335.22 1335.22 53397.82 4.45 29557.36 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 1322.18
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 1093.88
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 1322.38
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 944.53
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 716.78
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 944.56
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 944.62
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 716.72
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 944.37
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 1335.79
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 1107.59
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 1335.49
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 1335.73
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 1107.42
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 1335.22
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Heating Capacity [Btu/h]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1321.96 52867.48
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 1093.83 43743.95
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1322.48 52888.06
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1322.18 52875.98
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 1093.88 43746.22
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1322.38 52884.29
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 944.53 37773.32
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 716.78 28665.16
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 944.56 37774.70
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 944.62 37776.85
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 716.72 28662.93
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 944.37 37766.75
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 1335.79 53420.45
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 1107.59 44294.34
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 1335.49 53408.64
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 1335.73 53417.88
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 1107.42 44287.63
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 1335.22 53397.82
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Electric

Design Size Nominal Capacity [Btu/h]
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 33706.11
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 28804.29
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 33717.16
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 33710.68
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 28805.51
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 33715.14
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 25593.74
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 20701.38
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 25594.48
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 25595.63
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 20700.18
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 25590.21
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 34003.13
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 29099.90
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 33996.78
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR 34001.75
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR 29096.30
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR 33990.97
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 15354.00 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 15354.00 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 15354.00 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 10.90 8.24 12.97 20.35 39.67 54.57 64.62 67.68 62.46 50.90 35.44 21.07


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 1177.88 14. 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 37.92 65.88 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ7+hp+crawlspace+IECC_2006 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 7.7625 Rough 1.5719 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 4.5576 Rough 0.7710 5.155E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5031 Smooth 0.1189 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3300 VerySmooth 0.1230 0.114 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.911 2.909 0.000 0.000 0.000 0.000 3.821 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 875.250 0.729 128.261 0.000 0.600 0.200 0.200 0.000 General 60.174 875.250
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 9 0.167 0.0342 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.350 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 9 0.167 0.0342 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.7707 0.052 3.438 0.219 4.558
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1188 0.072 32.003 0.183 0.5031
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.7707 0.052 3.438 0.219 4.558


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 9 -0.61797381E-16 0.10275554E-15 -0.94176193E-10 0.70550100E-16
20 8 0.55018702E-09 0.40996745E-13 0.10446581E-03 -0.35964092E-09
21 7 -0.45325743E-03 0.10183730E-08 -0.10651944E-01 0.29628111E-03
22 6 0.35000963E-01 0.28248981E-06 0.18262466 -0.23007581E-01
23 5 -0.40204458 0.87190144E-05 -1.3453660 0.27251248
24 4 1.9371679 0.56641591E-04 5.2219591 -1.3641479
25 3 -4.7809977 0.95620201E-04 -11.428910 3.5178846
26 2 6.3416706 0.40914426E-04 14.116582 -4.8962826
27 1 -4.2976303 0.32019284E-05 -9.1505965 3.4916880
28 0 1.1674918 0.10995666E-07 2.4144591  
29 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
30 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
31 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
32 1 -8.0349315 0.81344511 -1.1624309 0.21506451
33 0 8.9946927 0.48845120 2.4180636  
34 12 0.94888791E-16 -0.11237443E-15 0.21480527E-09 -0.52606005E-16
35 11 -0.44509090E-09 -0.12338758E-15 -0.11566016E-03 0.28501063E-09
36 10 0.60393314E-04 0.62564840E-13 0.62960490E-02 -0.38672578E-04
37 9 -0.20055671E-02 0.85912012E-10 -0.12885789 0.13084700E-02
38 8 0.28697042E-01 0.10381403E-07 1.3966036 -0.19129448E-01
39 7 -0.23229993 0.28493476E-06 -9.1473517 0.15872626
40 6 1.1750436 0.24973161E-05 38.552224 -0.82592201
41 5 -3.8729952 0.80040830E-05 -107.65441 2.8111251
42 4 8.4143451 0.96510929E-05 200.56463 -6.3313915
43 3 -11.897084 0.41099356E-05 -245.77565 9.3152582
44 2 10.487404 0.50788650E-06 189.69676 -8.5734564
45 1 -5.2147174 0.10902359E-07 -83.415737 4.4633233
46 0 1.1135774 0.38882120E-11 15.905642  
47 12 0.21480527E-09 -0.11237443E-15 0.94888791E-16 -0.52606005E-16
48 11 -0.11566016E-03 -0.12338758E-15 -0.44509090E-09 0.28501063E-09
49 10 0.62960490E-02 0.62564840E-13 0.60393314E-04 -0.38672578E-04
50 9 -0.12885789 0.85912012E-10 -0.20055671E-02 0.13084700E-02
51 8 1.3966036 0.10381403E-07 0.28697042E-01 -0.19129448E-01
52 7 -9.1473517 0.28493476E-06 -0.23229993 0.15872626
53 6 38.552224 0.24973161E-05 1.1750436 -0.82592201
54 5 -107.65441 0.80040830E-05 -3.8729952 2.8111251
55 4 200.56463 0.96510929E-05 8.4143451 -6.3313915
56 3 -245.77565 0.41099356E-05 -11.897084 9.3152582
57 2 189.69676 0.50788650E-06 10.487404 -8.5734564
58 1 -83.415737 0.10902359E-07 -5.2147174 4.4633233
59 0 15.905642 0.38882120E-11 1.1135774  
60 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
61 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
62 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
63 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
64 1 -19.904252 0.86481321 -19.904252 0.58144210
65 0 16.688993 0.62060609E-01 16.688993  
66 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
67 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
68 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
69 1 -11.299243 2.8799011 -8.6239668 0.15905732
70 0 15.219762 1.4410112 12.640375  
71 5 -0.24423608E-08 0.10315694E-08 -0.24423608E-08 0.46347327E-11
72 4 0.46481418E-04 0.19988510E-04 0.46481418E-04 -0.22728163E-06
73 3 -0.31887091E-01 0.95525843E-02 -0.31887091E-01 0.49135354E-03
74 2 1.3495466 0.25081638 1.3495466 -0.51058024E-01
75 1 -7.0688408 0.57876498 -7.0688408 0.58136590
76 0 6.6836766 0.93387740E-01 6.6836766  
77 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
78 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
79 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
80 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
81 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
82 1 -64.420211 0.46601667 -21.697519 0.64629334
83 0 46.121323 0.20873329E-01 15.867130  
84 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
85 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
86 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
87 2 11.651569 1.6702487 11.651569 -0.78737360E-01
88 1 -51.506798 3.1050242 -51.506798 0.66829999
89 0 45.538973 0.42297268 45.538973  
90 9 -0.94176193E-10 0.10275554E-15 -0.61797381E-16 0.70550100E-16
91 8 0.10446581E-03 0.40996745E-13 0.55018702E-09 -0.35964092E-09
92 7 -0.10651944E-01 0.10183730E-08 -0.45325743E-03 0.29628111E-03
93 6 0.18262466 0.28248981E-06 0.35000963E-01 -0.23007581E-01
94 5 -1.3453660 0.87190144E-05 -0.40204458 0.27251248
95 4 5.2219591 0.56641591E-04 1.9371679 -1.3641479
96 3 -11.428910 0.95620201E-04 -4.7809977 3.5178846
97 2 14.116582 0.40914426E-04 6.3416706 -4.8962826
98 1 -9.1505965 0.32019284E-05 -4.2976303 3.4916880
99 0 2.4144591 0.10995666E-07 1.1674918  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.350 0.350 1.000 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 0.350 0.350 1.000 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.350 0.350 1.000 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
2 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
3 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.9509 15354.0 1.069 0.9773
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.9509 15354.0 1.069 0.9773
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.9509 15354.0 1.069 0.9773


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 45.000 0.037 22.500 0.265 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 10490.40544 10490.40544 466.14401 466.14401 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 81.19521 0.01272 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 25060.46685 25060.46685 1321.97017 1321.97017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 5299.36469 5299.36469 235.48726 235.48726 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 20734.98031 20734.98031 1093.83461 1093.83461 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 7367.78699 7367.78699 327.37284 327.37284 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 81.41841 0.01272 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 25070.22230 25070.22230 1322.47865 1322.47865 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 9763.53654 9763.53654 433.83469 433.83469 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 80.26520 0.01272 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 25064.49782 25064.49782 1322.18204 1322.18204 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4390.86977 4390.86977 195.10421 195.10421 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 77.47520 0.01272 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 20736.05963 20736.05963 1093.87698 1093.87698 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 6429.06639 6429.06639 285.65674 285.65674 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 78.81440 0.01272 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 25068.43434 25068.43434 1322.37271 1322.37271 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 10280.96542 10280.96542 456.82198 456.82198 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 80.82320 0.01272 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 17901.78673 17901.78673 944.53378 944.53378 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 5122.13814 5122.13814 227.60590 227.60590 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 13584.64349 13584.64349 716.77957 716.77957 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7497.27457 7497.27457 333.11436 333.11436 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 81.41841 0.01272 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 17902.44150 17902.44150 944.55497 944.55497 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 9598.06167 9598.06167 426.48300 426.48300 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 79.14920 0.01272 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 17903.45742 17903.45742 944.61852 944.61852 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4399.62401 4399.62401 195.48853 195.48853 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 76.65679 0.01272 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 13583.58823 13583.58823 716.71601 716.71601 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6617.63736 6617.63736 294.02539 294.02539 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 79.37240 0.01272 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 17898.67158 17898.67158 944.36429 944.36429 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6558.46595 6558.46595 291.41945 291.41945 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 79.93040 0.01272 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 25311.83209 25311.83209 1335.23288 1335.23288 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7541.69171 7541.69171 335.14826 335.14826 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 25316.96043 25316.96043 1335.48712 1335.48712 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 10734.32294 10734.32294 476.97028 476.97028 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 80.82320 0.01272 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 25322.56280 25322.56280 1335.78373 1335.78373 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5272.77064 5272.77064 234.30082 234.30082 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 77.47520 0.01272 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 20992.65980 20992.65980 1107.41511 1107.41511 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 5555.15353 5555.15353 246.86438 246.86438 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 85.95680 0.01273 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 20995.83668 20995.83668 1107.58461 1107.58461 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 10474.04094 10474.04094 465.42367 465.42367 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 79.70720 0.01272 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 25321.34362 25321.34362 1335.72017 1335.72017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 3117.35 466.14401 466.14401 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 8590.17 1321.97017 1321.97017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1684.95 235.48726 235.48726 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 7340.92 1093.83461 1093.83461 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2217.72 327.37284 327.37284 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 8592.99 1322.47865 1322.47865 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2894.51 433.83469 433.83469 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 8591.33 1322.18204 1322.18204 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1303.21 195.10421 195.10421 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 7341.23 1093.87698 1093.87698 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1910.72 285.65674 285.65674 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 8592.47 1322.37271 1322.37271 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 3051.71 456.82198 456.82198 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 6522.69 944.53378 944.53378 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1633.70 227.60590 227.60590 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 5275.85 716.77957 716.77957 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2255.14 333.11436 333.11436 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 6522.88 944.55497 944.55497 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2831.39 426.48300 426.48300 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 6523.17 944.61852 944.61852 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1294.54 195.48853 195.48853 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 5275.54 716.71601 716.71601 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1972.86 294.02539 294.02539 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 6521.79 944.36429 944.36429 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3182.77 476.97028 476.97028 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 8665.87 1335.78373 1335.78373 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1755.84 246.86438 246.86438 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 7416.26 1107.58461 1107.58461 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2333.16 335.14826 335.14826 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 8664.25 1335.48712 1335.48712 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3092.26 465.42367 465.42367 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 8665.51 1335.72017 1335.72017 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1558.15 234.30082 234.30082 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 7415.34 1107.41511 1107.41511 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 1963.40 291.41945 291.41945 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 8662.77 1335.23288 1335.23288 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1321.97017
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1093.83461
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1322.47865
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1322.18204
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1093.87698
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1322.37271
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 944.53378
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 716.77957
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 944.55497
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 944.61852
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 716.71601
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 944.36429
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1335.23288
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1335.48712
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1335.78373
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1107.41511
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1107.58461
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 1335.72017
19 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1321.97017
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1321.97017
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1321.97017
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1321.97017
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1321.97017
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1321.97017
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1093.83461
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1093.83461
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1093.83461
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1093.83461
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1093.83461
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1093.83461
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1322.47865
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1322.47865
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1322.47865
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1322.47865
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1322.47865
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1322.47865
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1322.18204
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1322.18204
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1322.18204
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1322.18204
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1322.18204
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1322.18204
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1093.87698
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1093.87698
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1093.87698
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1093.87698
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1093.87698
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1093.87698
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1322.37271
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1322.37271
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1322.37271
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1322.37271
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1322.37271
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1322.37271
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 944.53378
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 944.53378
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 944.53378
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 944.53378
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 944.53378
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 944.53378
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 716.77957
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 716.77957
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 716.77957
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 716.77957
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 716.77957
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 716.77957
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 944.55497
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 944.55497
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 944.55497
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 944.55497
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 944.55497
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 944.55497
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 944.61852
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 944.61852
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 944.61852
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 944.61852
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 944.61852
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 944.61852
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 716.71601
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 716.71601
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 716.71601
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 716.71601
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 716.71601
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 716.71601
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 944.36429
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 944.36429
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 944.36429
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 944.36429
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 944.36429
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 944.36429
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1335.78373
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1335.78373
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1335.78373
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1335.78373
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1335.78373
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1335.78373
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1107.58461
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1107.58461
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1107.58461
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1107.58461
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1107.58461
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1107.58461
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1335.48712
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1335.48712
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1335.48712
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1335.48712
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1335.48712
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1335.48712
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1335.72017
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1335.72017
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1335.72017
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1335.72017
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1335.72017
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1335.72017
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1107.41511
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1107.41511
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1107.41511
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1107.41511
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1107.41511
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1107.41511
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 1335.23288
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 1335.23288
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 1335.23288
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 1335.23288
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 1335.23288
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 1335.23288
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1321.97017
164 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1093.83461
165 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1322.47865
166 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1322.18204
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1093.87698
168 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 1322.37271
169 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 944.53378
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 716.77957
171 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 944.55497
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 944.61852
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 716.71601
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 944.36429
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1335.78373
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1107.58461
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1335.48712
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1335.72017
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1107.41511
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 1335.23288
181 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1321.97017
182 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.35952
183 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70468
184 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1321.97017
185 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1321.97017
186 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1321.97017
187 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 52314.21086
188 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 4.35952
189 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29309.65881
190 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
191 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1321.97017
192 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1321.97017
193 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 52867.47748
194 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 33706.10761
195 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1093.83461
196 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.64533
197 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
198 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1093.83461
199 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1093.83461
200 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1093.83461
201 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 43743.94814
202 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 3.64533
203 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 25047.20570
204 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
205 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1093.83461
206 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1093.83461
207 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 43743.94814
208 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 28804.28658
209 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.47865
210 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.40734
211 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
212 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1322.47865
213 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1322.47865
214 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1322.47865
215 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 52888.05836
216 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 4.40734
217 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29319.27216
218 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
219 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1322.47865
220 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.47865
221 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 52888.05836
222 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 33717.16300
223 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.18204
224 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.39726
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70259
226 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1322.18204
227 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1322.18204
228 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1322.18204
229 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 52767.07320
230 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 4.39726
231 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29313.63106
232 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
233 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1322.18204
234 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.18204
235 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 52875.98131
236 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 33710.67570
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1093.87698
238 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.64552
239 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
240 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1093.87698
241 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1093.87698
242 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1093.87698
243 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 43746.22500
244 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 3.64552
245 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 25048.26932
246 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
247 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1093.87698
248 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1093.87698
249 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 43746.22500
250 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 28805.50971
251 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.37271
252 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.40702
253 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
254 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 1322.37271
255 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1322.37271
256 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1322.37271
257 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 52884.28612
258 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 4.40702
259 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29317.51023
260 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
261 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 1322.37271
262 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 1322.37271
263 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 52884.28612
264 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 33715.13679
265 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.53378
266 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.04330
267 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71150
268 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 944.53378
269 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 944.53378
270 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 944.53378
271 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 36519.62398
272 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 3.04330
273 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 22255.42422
274 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
275 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 944.53378
276 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.53378
277 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 37773.32301
278 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 25593.73785
279 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 716.77957
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 2.38876
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
282 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 716.77957
283 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 716.77957
284 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 716.77957
285 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 28665.15839
286 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 2.38876
287 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 18001.19750
288 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
289 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 716.77957
290 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 716.77957
291 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 28665.15839
292 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 20701.37713
293 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.55497
294 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.14789
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
296 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 944.55497
297 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 944.55497
298 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 944.55497
299 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 37774.70464
300 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 3.14789
301 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 22256.06946
302 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
303 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 944.55497
304 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.55497
305 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 37774.70464
306 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 25594.47989
307 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.61852
308 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.05643
309 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.71043
310 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 944.61852
311 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 944.61852
312 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 944.61852
313 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 36677.21829
314 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 3.05643
315 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 22257.07058
316 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
317 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 944.61852
318 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.61852
319 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 37776.84829
320 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 25595.63116
321 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 716.71601
322 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 2.38858
323 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
324 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 716.71601
325 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 716.71601
326 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 716.71601
327 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 28662.93161
328 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 2.38858
329 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 18000.15760
330 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
331 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 716.71601
332 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 716.71601
333 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 28662.93161
334 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 20700.18122
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.36429
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.14723
337 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
338 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 944.36429
339 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 944.36429
340 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 944.36429
341 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 37766.74980
342 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 3.14723
343 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 22252.35444
344 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
345 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 944.36429
346 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 944.36429
347 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 37766.74980
348 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 25590.20759
349 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.78373
350 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.38048
351 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70607
352 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1335.78373
353 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1335.78373
354 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1335.78373
355 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 52565.72467
356 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 4.38048
357 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29567.93803
358 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
359 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1335.78373
360 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.78373
361 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 53420.45442
362 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 34003.12873
363 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1107.58461
364 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.69119
365 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
366 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1107.58461
367 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1107.58461
368 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1107.58461
369 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 44294.33663
370 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 3.69119
371 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 25304.26377
372 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
373 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1107.58461
374 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1107.58461
375 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 44294.33663
376 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 29099.90335
377 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.48712
378 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.45072
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
380 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1335.48712
381 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1335.48712
382 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1335.48712
383 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 53408.63522
384 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 4.45072
385 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29562.41728
386 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1335.48712
388 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.48712
389 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 53408.63522
390 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 33996.77985
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.72017
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.37641
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70629
394 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1335.72017
395 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1335.72017
396 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1335.72017
397 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 52516.96449
398 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 4.37641
399 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29566.73660
400 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
401 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1335.72017
402 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.72017
403 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 53417.88245
404 Coil:Heating:Electric SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 34001.74711
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1107.41511
406 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 3.69064
407 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
408 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1107.41511
409 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1107.41511
410 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1107.41511
411 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 44287.63420
412 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 3.69064
413 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 25301.13315
414 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
415 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1107.41511
416 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1107.41511
417 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 44287.63420
418 Coil:Heating:Electric SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 29096.30311
419 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.23288
420 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 4.44982
421 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
422 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 1335.23288
423 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 1335.23288
424 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 1335.23288
425 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 53397.81614
426 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 4.44982
427 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Supplemental Heating Coil Nominal Capacity [Btu/h] 29557.36363
428 AirLoopHVAC:UnitaryHeatPump:AirToAir HEAT PUMP_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
429 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 1335.23288
430 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 1335.23288
431 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Heating Capacity [Btu/h] 53397.81614
432 Coil:Heating:Electric SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 33990.96816
433 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
434 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
435 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
436 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
437 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
438 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
439 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
440 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
441 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
442 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
443 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
444 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
445 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
446 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
447 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
448 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
449 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
450 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
451 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
452 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
453 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
454 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
455 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
456 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
457 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
458 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
459 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
460 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
461 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
462 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
463 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
464 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
465 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
466 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
467 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
468 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
469 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
470 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
471 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
472 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
473 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
474 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
475 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
476 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
477 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
478 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
479 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
480 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
481 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
482 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
483 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
484 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
485 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
486 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
487 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
488 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
489 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
490 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
491 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
492 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
493 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
494 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
495 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
496 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
497 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
498 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
499 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
500 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
501 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
502 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
503 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
504 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
505 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
506 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
507 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
508 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
509 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
510 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
511 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
512 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
513 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
514 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
515 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
516 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
517 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
518 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
519 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
520 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
521 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 15354.00000
522 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 4.2 3.67 12.52 13.13 12.42 12.63
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 4.2 3.55 12.13 12.70 12.36 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 3.5 3.67 12.54 13.15 12.44 12.66
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 3.5 3.56 12.15 12.73 12.39 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 4.3 3.67 12.54 13.15 12.44 12.66
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 4.2 3.56 12.15 12.73 12.39 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 4.3 3.67 12.53 13.15 12.44 12.65
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 4.2 3.56 12.15 12.72 12.38 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 3.5 3.67 12.54 13.15 12.44 12.66
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 3.5 3.56 12.15 12.73 12.39 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 4.3 3.67 12.54 13.15 12.44 12.66
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 4.2 3.56 12.15 12.73 12.39 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 2.9 3.65 12.47 13.08 12.38 12.56
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 2.9 3.54 12.08 12.65 12.31 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 2.3 3.67 12.54 13.15 12.44 12.66
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 2.3 3.56 12.15 12.73 12.39 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 3.0 3.67 12.54 13.15 12.44 12.66
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 3.0 3.56 12.15 12.73 12.39 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 3.0 3.66 12.48 13.09 12.38 12.57
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 2.9 3.54 12.09 12.66 12.32 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 2.3 3.67 12.54 13.15 12.44 12.66
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 2.3 3.56 12.15 12.73 12.39 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 3.0 3.67 12.54 13.15 12.44 12.66
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 3.0 3.56 12.15 12.73 12.39 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 4.2 3.66 12.50 13.12 12.41 12.61
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 4.2 3.55 12.12 12.69 12.35 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 3.6 3.67 12.54 13.15 12.44 12.66
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 3.5 3.56 12.15 12.73 12.39 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 4.3 3.67 12.54 13.15 12.44 12.66
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 4.3 3.56 12.15 12.73 12.39 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 4.2 3.66 12.50 13.12 12.41 12.61
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 4.2 3.55 12.11 12.69 12.35 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 3.6 3.67 12.54 13.15 12.44 12.66
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 3.5 3.56 12.15 12.73 12.39 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 4.3 3.67 12.54 13.15 12.44 12.66
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 4.3 3.56 12.15 12.73 12.39 -99999.


DX Heating Coil Standard Rating Information

Component Type Component Name High Temperature Heating (net) Rating Capacity {Btu/h} Low Temperature Heating (net) Rating Capacity {Btu/h} HSPF {Btu/W-h} Region Number
1 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 54578.0 30031.7 8.38 4
2 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 54920.9 30374.6 7.36 4
3 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 45159.2 24849.3 8.29 4
4 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 45443.1 25132.8 7.36 4
5 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 54599.2 30043.7 8.38 4
6 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 54942.4 30386.6 7.36 4
7 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 54586.5 30036.5 8.38 4
8 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 54929.8 30379.8 7.36 4
9 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 45161.6 24850.3 8.29 4
10 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 45445.5 25134.2 7.36 4
11 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 54595.4 30041.3 8.38 4
12 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 54938.3 30384.5 7.36 4
13 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 38995.4 21457.4 8.32 4
14 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 39240.4 21702.4 7.36 4
15 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 29592.6 16283.4 8.33 4
16 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 29778.6 16469.4 7.36 4
17 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 38996.8 21458.4 8.32 4
18 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 39241.8 21703.4 7.36 4
19 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 38999.2 21459.4 8.32 4
20 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 39244.1 21704.4 7.36 4
21 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 29590.2 16282.1 8.33 4
22 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 29776.2 16468.0 7.36 4
23 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 38988.6 21453.6 8.32 4
24 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 39233.6 21698.6 7.36 4
25 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 55148.8 30346.0 8.30 4
26 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 55495.5 30692.6 7.36 4
27 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 45727.3 25161.8 8.29 4
28 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 46014.9 25449.1 7.36 4
29 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 55136.6 30339.2 8.30 4
30 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 55483.2 30685.8 7.36 4
31 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 55146.1 30344.6 8.30 4
32 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR 55492.8 30690.9 7.36 4
33 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 45720.5 25158.0 8.29 4
34 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR 46007.7 25445.3 7.36 4
35 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 55125.3 30333.0 8.30 4
36 Coil:Heating:DX:SingleSpeed MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR 55472.0 30679.7 7.36 4


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 8
2 6
3 7


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 -26.9 0.00 DefaultMultipliers Wetbulb -32.70 {C} 14. 210 472.5 0.00 No No
2 86.18 12.40 DefaultMultipliers Wetbulb 21.10 {C} 14. 200 925.2 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000127144 0.000110887 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000708215 0.000174012 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004280477 0.007481515 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005132369 0.008883288 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004278854 0.007478659 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004279773 0.007480260 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005132023 0.008882654 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004279054 0.007478962 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005813682 0.009909164 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.007570455 0.012885613 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005813526 0.009908907 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005813213 0.009908349 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.007571034 0.012886631 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005814697 0.009910932 Pass Pass
15 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000078601 0.000067217 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004134105 0.006620583 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004133264 0.006619205 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004132314 0.006617648 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004939375 0.007882932 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004938612 0.007881664 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004132576 0.006618080 Pass Pass
22 CRAWLSPACE SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.239487794 0.138106695 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.057462356 0.031640848 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.001650082 0.007557075 Pass Pass 0.396694432 1.145675899 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000003123 0.000009438 Pass Pass 0.176983624 0.151776582 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.002783934 0.012247341 Pass Pass 0.226007783 0.526962685 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.001142239 0.006478258 Pass Pass 0.334774471 1.071807481 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000001939 0.000004456 Pass Pass 0.154237391 0.146788067 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.002796294 0.013339211 Pass Pass 0.229549104 0.621076181 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000004506 0.000011791 Pass Pass 0.150936054 0.078964758 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000002653 0.000008237 Pass Pass 0.101364103 0.068002090 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000006643 0.000019496 Pass Pass 0.132513162 0.131704736 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000003861 0.000009075 Pass Pass 0.144843219 0.079569611 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000001634 0.000003712 Pass Pass 0.089552449 0.068643294 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000005962 0.000018637 Pass Pass 0.127985397 0.136251043 Pass Pass
36 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.511496072 0.349729455 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000005931 0.000017860 Pass Pass 0.176224371 0.225444443 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000006579 0.000018779 Pass Pass 0.181806283 0.224330956 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000004915 0.000012621 Pass Pass 0.205119520 0.155914509 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000002083 0.000004921 Pass Pass 0.118711794 0.088532652 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000002928 0.000008722 Pass Pass 0.129171231 0.092011621 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000004363 0.000010440 Pass Pass 0.190198020 0.142457187 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.269540795 0.209197777 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.024519322 0.014838398 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000052103 0.000268933 Pass Pass 0.032674412 0.029594362 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000084441 0.000356019 Pass Pass 0.030498516 0.026564013 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000087560 0.000373047 Pass Pass 0.029995101 0.029372243 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000002109 0.000006775 Pass Pass 0.023865404 0.021962431 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000001866 0.000006015 Pass Pass 0.020182488 0.019748412 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000002056 0.000006692 Pass Pass 0.020777717 0.021464077 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000036289 0.000167084 Pass Pass 0.039338669 0.034666761 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000062009 0.000252563 Pass Pass 0.037218245 0.032379396 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000071849 0.000236335 Pass Pass 0.033292810 0.034383935 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000042906 0.000186772 Pass Pass 0.023848543 0.023368501 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000001243 0.000004111 Pass Pass 0.019122404 0.020962765 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000001473 0.000004903 Pass Pass 0.020057814 0.022617874 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.322544216 0.275781144 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000002064 0.000006700 Pass Pass 0.020609019 0.019621943 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000069720 0.000296741 Pass Pass 0.028011233 0.025808664 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000087217 0.000385402 Pass Pass 0.030399522 0.026274639 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000001867 0.000006016 Pass Pass 0.019989370 0.019462927 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000057236 0.000255558 Pass Pass 0.028296182 0.024490580 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000002111 0.000006776 Pass Pass 0.023095453 0.020491820 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2216114.52 1138922.18 285163.93 0.00 0.135894E+14 0.135895E+14



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 8694.00 58.83 7.17 0.00 0.00
BREEZEWAY 8744.83 15.17 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8188.50 379.00 166.83 25.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 8188.50 0.00 0.00 0.00 0.00
Max 8760.00 379.00 166.83 25.67 0.00
Average 8728.92 21.57 8.29 1.22 0.00
Sum 183307.33 453.00 174.00 25.67 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 8485.00 274.83 0.17 0.00 0.00
BREEZEWAY 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8615.17 144.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8619.00 141.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8631.83 128.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8610.33 149.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8599.33 160.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8627.00 133.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8710.17 49.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8751.50 8.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8718.50 41.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8708.33 51.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.83 7.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8715.83 44.17 0.00 0.00 0.00
ATTIC 8085.67 574.50 84.17 15.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8665.83 94.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8667.67 92.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8647.17 112.83 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8660.00 100.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8665.67 94.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8644.33 115.67 0.00 0.00 0.00
Min 8085.67 0.00 0.00 0.00 0.00
Max 8760.00 574.50 84.17 15.67 0.00
Average 8635.29 119.94 4.02 0.75 0.00
Sum 181341.17 2518.83 84.33 15.67 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11843.41 218.97 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 11866.70 195.68 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11855.00 207.38 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11842.96 219.42 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 11852.47 209.91 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11849.51 212.87 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11988.84 73.54 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12050.96 11.42 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 11996.41 65.97 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11986.62 75.76 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12053.03 9.35 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11993.20 69.18 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11919.44 142.94 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11919.96 142.42 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11899.57 162.81 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 11944.65 117.73 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 11945.33 117.05 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11902.21 160.17 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12053.03 219.42 0.00 0.00 0.00
Average 10224.30 114.89 0.00 0.00 0.00
Sum 214710.27 2412.59 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8615.17 144.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8619.00 141.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8631.83 128.17 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8610.33 149.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8599.33 160.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8627.00 133.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8710.17 49.83 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8751.50 8.50 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8718.50 41.50 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8708.33 51.67 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8752.83 7.17 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8715.83 44.17 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8665.83 94.17 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8667.67 92.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8647.17 112.83 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8660.00 100.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8665.67 94.33 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8644.33 115.67 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8752.83 160.67 0.00 0.00 0.00
Average 7429.07 79.50 0.00 0.00 0.00
Sum 156010.50 1669.50 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.04 0.05 0.04 0.01 0.02 0.01
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.04 0.06 0.04 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.04 0.04 0.04 0.02 0.02 0.02
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.03 0.04 0.03 0.02 0.02 0.02
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.03 0.05 0.03 0.01 0.01 0.01
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.03 0.05 0.03 0.02 0.02 0.02
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.05 0.06 0.05 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.03 0.04 0.03 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.03 0.04 0.03 0.02 0.02 0.02
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.03 0.05 0.03 0.01 0.01 0.01
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.04 0.06 0.04 0.01 0.01 0.01
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.04 0.05 0.04 0.01 0.01 0.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.04 0.05 0.04 0.01 0.02 0.01
LIVING_UNIT2_BACKROW_TOPFLOOR 0.03 0.04 0.03 0.01 0.02 0.01
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.03 0.05 0.03 0.01 0.01 0.01
LIVING_UNIT1_BACKROW_TOPFLOOR 0.03 0.04 0.03 0.01 0.02 0.01
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.05 0.06 0.05 0.02 0.02 0.02
Average 0.03 0.04 0.03 0.01 0.01 0.01
Sum 0.62 0.85 0.62 0.26 0.29 0.26


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -26.9 0.00 -26.9 Wetbulb [F] 472.46 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 86.18 22.32 69.98 Wetbulb [F] 925.24 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.47 13      
Apr 0.63 23      
May 0.00 0      
Jun 7.48 53      
Jul 5.35 41      
Aug 3.43 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.022 0.022 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.033 0.034 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.022 0.022 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.350 0.335 0.883                      
North Total or Average             531.68 0.350 0.335 0.883                      
Non-North Total or Average             1595.05 0.350 0.335 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.7290 1200.55 875.25 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 787.52
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.4556 43219.92 19693.13               17719.17


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   52314.21 36864.53 15449.68 0.70 4.30    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   43743.95 30668.15 13075.80 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   52888.06 37078.93 15809.13 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   52767.07 37073.57 15693.50 0.70 4.30    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   43746.22 30669.74 13076.48 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   52884.29 37076.29 15808.00 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   36519.62 25983.60 10536.03 0.71 4.30    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   28665.16 20096.66 8568.50 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   37774.70 26483.21 11291.49 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   36677.22 26056.64 10620.58 0.71 4.30    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   28662.93 20095.10 8567.83 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   37766.75 26477.63 11289.12 0.70 4.30    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   52565.72 37114.99 15450.73 0.71 4.30    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   44294.34 31054.02 13240.32 0.70 4.30    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   53408.64 37443.90 15964.74 0.70 4.30    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   52516.96 37092.08 15424.89 0.71 4.30    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   44287.63 31049.32 13238.32 0.70 4.30    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   53397.82 37436.31 15961.50 0.70 4.30    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   4.2 3.67 12.52 13.13 12.42 12.63
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   3.5 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   4.3 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   4.3 3.67 12.53 13.15 12.44 12.65
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   3.5 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   4.3 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   2.9 3.65 12.47 13.08 12.38 12.56
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   2.3 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   3.0 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   3.0 3.66 12.48 13.09 12.38 12.57
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   2.3 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   3.0 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   4.2 3.66 12.50 13.12 12.41 12.61
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   3.6 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   4.3 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   4.2 3.66 12.50 13.12 12.41 12.61
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   3.6 3.67 12.54 13.15 12.44 12.66
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   4.3 3.67 12.54 13.15 12.44 12.66
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.55 12.13 12.70 12.36  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 3.5 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.56 12.15 12.72 12.38  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 3.5 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 2.9 3.54 12.08 12.65 12.31  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 2.3 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 3.0 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 2.9 3.54 12.09 12.66 12.32  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 2.3 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 3.0 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.55 12.12 12.69 12.35  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 3.5 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 4.3 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 4.2 3.55 12.11 12.69 12.35  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 3.5 3.56 12.15 12.73 12.39  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 4.3 3.56 12.15 12.73 12.39  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54577.9 30031.8 8.38 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 45159.2 24849.1 8.29 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54599.2 30043.5 8.38 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54586.7 30036.7 8.38 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 45161.6 24850.4 8.29 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54595.3 30041.4 8.38 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 38995.4 21457.5 8.32 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 29592.6 16283.5 8.33 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 38996.8 21458.3 8.32 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 38999.0 21459.5 8.32 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 29590.3 16282.2 8.33 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 38988.6 21453.7 8.32 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55148.8 30346.0 8.30 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 45727.4 25161.8 8.29 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55136.6 30339.2 8.30 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55146.1 30344.5 8.30 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 45720.5 25158.0 8.29 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55125.4 30333.1 8.30 4
ANSI/AHRI ratings account for supply air fan heat and electric power.

DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54920.9 30374.8 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 45443.0 25132.9 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54942.3 30386.6 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54929.7 30379.7 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 45445.4 25134.2 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed 54938.3 30384.5 7.36 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 39240.5 21702.5 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 29778.5 16469.5 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 39241.9 21703.3 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 39244.1 21704.6 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 29776.2 16468.2 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed 39233.6 21698.7 7.36 4
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55495.3 30692.5 7.36 4
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 46014.8 25449.2 7.36 4
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55483.1 30685.7 7.36 4
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55492.7 30691.1 7.36 4
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 46007.8 25445.3 7.36 4
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed 55471.8 30679.5 7.36 4
ANSI/AHRI 2023 (HSPF2) ratings account for supply air fan heat and electric power.

Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   52867.48 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   33706.11 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   43743.95 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   28804.29 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   52888.06 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric   33717.16 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   52875.98 3.84
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   33710.68 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   43746.22 3.84
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   28805.51 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed   52884.29 3.84
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric   33715.14 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   37773.32 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   25593.74 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   28665.16 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   20701.38 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   37774.70 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric   25594.48 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   37776.85 3.84
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   25595.63 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   28662.93 3.84
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   20700.18 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed   37766.75 3.84
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric   25590.21 1.00
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   53420.45 3.84
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric   34003.13 1.00
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   44294.34 3.84
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric   29099.90 1.00
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   53408.64 3.84
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric   33996.78 1.00
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   53417.88 3.84
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric   34001.75 1.00
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   44287.63 3.84
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric   29096.30 1.00
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed   53397.82 3.84
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric   33990.97 1.00
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 44.99 32.14 0.71 1.00 10.37 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1321.96 498.63 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1093.83 412.58 0.38 1.00 1.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1322.48 498.83 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1322.18 498.71 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1093.88 412.60 0.38 1.00 1.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 1322.38 498.79 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 944.53 356.27 0.38 1.00 1.68 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 716.78 270.36 0.38 1.00 1.85 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 944.56 356.28 0.38 1.00 1.68 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 944.62 356.30 0.38 1.00 1.68 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 716.72 270.34 0.38 1.00 1.85 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 944.37 356.21 0.38 1.00 1.68 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 1335.79 503.85 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 1107.59 417.77 0.38 1.00 1.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 1335.49 503.74 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 1335.73 503.83 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 1107.42 417.71 0.38 1.00 1.61 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 1335.22 503.64 0.38 1.00 1.53 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 6.95 15354.00 1.00 1.07 0.98



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10490.41 10490.41 8.74 466.140 466.140 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 75.00 75.00 0.00852 81.20 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5299.36 5299.36 4.41 235.492 235.492 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 75.00 74.99 0.00905 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7367.79 7367.79 6.14 327.381 327.381 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 75.00 75.00 0.00873 81.42 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9763.54 9763.54 8.13 433.843 433.843 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00859 80.27 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4390.87 4390.87 3.66 195.104 195.104 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00951 77.48 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6429.07 6429.07 5.36 285.662 285.662 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 75.00 75.00 0.00888 78.81 0.01272 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10280.97 10280.97 8.56 456.818 456.818 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00833 80.82 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5122.14 5122.14 4.27 227.605 227.605 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 75.00 75.00 0.00875 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7497.27 7497.27 6.24 333.125 333.125 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 75.00 75.00 0.00846 81.42 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9598.06 9598.06 7.99 426.476 426.476 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00841 79.15 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4399.62 4399.62 3.66 195.488 195.488 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 75.00 75.00 0.00917 76.66 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6617.64 6617.64 5.51 294.035 294.035 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.00 75.00 0.00858 79.37 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6558.47 6558.47 5.46 291.415 291.415 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 75.00 0.00885 79.93 0.01272 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7541.69 7541.69 6.28 335.142 335.142 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 75.00 74.99 0.00872 86.18 0.01273 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 10734.32 10734.32 8.94 476.980 476.980 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00850 80.82 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5272.77 5272.77 4.39 234.292 234.292 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00925 77.48 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 5555.15 5555.15 4.63 246.859 246.859 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 75.00 74.99 0.00899 85.96 0.01273 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 10474.04 10474.04 8.72 465.415 465.415 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 75.00 0.00853 79.71 0.01272 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 25060.47 25060.47 20.87 1321.963 1321.963 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 20734.98 20734.98 17.27 1093.827 1093.827 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00715 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25070.22 25070.22 20.88 1322.477 1322.477 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 25064.50 25064.50 20.88 1322.175 1322.175 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 20736.06 20736.06 17.27 1093.884 1093.884 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00715 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 25068.43 25068.43 20.88 1322.383 1322.383 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 17901.79 17901.79 14.91 944.530 944.530 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00731 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 13584.64 13584.64 11.32 716.778 716.778 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00722 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 17902.44 17902.44 14.91 944.565 944.565 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00731 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 17903.46 17903.46 14.91 944.618 944.618 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00731 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13583.59 13583.59 11.31 716.723 716.723 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00722 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 17898.67 17898.67 14.91 944.366 944.366 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00731 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 25311.83 25311.83 21.08 1335.224 1335.224 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 25316.96 25316.96 21.09 1335.494 1335.494 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 25322.56 25322.56 21.09 1335.790 1335.790 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 20992.66 20992.66 17.49 1107.422 1107.422 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00716 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 20995.84 20995.84 17.49 1107.589 1107.589 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00716 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 25321.34 25321.34 21.09 1335.726 1335.726 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00723 -26.9 0.00018 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 466.14 466.14 1321.96 1321.96 1321.9625 1321.9625 1321.9625 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 235.49 235.49 1093.83 1093.83 1093.8267 1093.8267 1093.8267 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 327.38 327.38 1322.48 1322.48 1322.4772 1322.4772 1322.4772 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 433.84 433.84 1322.18 1322.18 1322.1752 1322.1752 1322.1752 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 195.10 195.10 1093.88 1093.88 1093.8837 1093.8837 1093.8837 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 285.66 285.66 1322.38 1322.38 1322.3828 1322.3828 1322.3828 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 456.82 456.82 944.53 944.53 944.5300 944.5300 944.5300 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 227.61 227.61 716.78 716.78 716.7784 716.7784 716.7784 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 333.12 333.12 944.56 944.56 944.5645 944.5645 944.5645 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 426.48 426.48 944.62 944.62 944.6181 944.6181 944.6181 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 195.49 195.49 716.72 716.72 716.7227 716.7227 716.7227 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 294.04 294.04 944.37 944.37 944.3656 944.3656 944.3656 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 476.98 476.98 1335.79 1335.79 1335.7898 1335.7898 1335.7898 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 246.86 246.86 1107.59 1107.59 1107.5893 1107.5893 1107.5893 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 335.14 335.14 1335.49 1335.49 1335.4943 1335.4943 1335.4943 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 465.42 465.42 1335.73 1335.73 1335.7255 1335.7255 1335.7255 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 234.29 234.29 1107.42 1107.42 1107.4217 1107.4217 1107.4217 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 291.41 291.41 1335.22 1335.22 1335.2238 1335.2238 1335.2238 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 52314.211 36864.526 1321.962521 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 51489.99 42012.92 1321.962521 76.82 61.92 0.00892425 53.60 50.67 0.00750000 81.20 0.01272100 68.57 3.4037 75.00 0.00851288 44.2125 10480.25 0.00 52305.24 36181.92
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 52867.477 52867.477 1321.962521 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 52867.48 29742.89 1321.962521 68.62 55.86 0.00698541 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.4037 71.99 0.00722508 41.6005 25060.47 0.00 52936.95 52936.95
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 33706.108 33706.108 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33706.11 33706.11 -999. 68.62 55.86 0.00698541 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722508 41.6005 25060.47 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 43743.948 30668.148 1093.826728 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 43290.97 32353.26 1093.826728 78.35 63.64 0.00974848 53.60 50.67 0.00750000 86.18 0.01272586 70.04 4.1135 74.99 0.00904523 46.9396 5299.36 0.00 43736.44 30116.51
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 43743.948 43743.948 1093.826728 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 43743.95 25417.43 1093.826728 67.92 55.37 0.00686152 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.1135 71.99 0.00714801 41.1609 20734.98 0.00 43801.43 43801.43
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 28804.287 28804.287 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28804.29 28804.29 -999. 67.92 55.37 0.00686152 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00714801 41.1609 20734.98 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 52888.058 37078.930 1322.477150 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 52420.76 40986.10 1322.477150 77.10 62.54 0.00927889 53.60 50.67 0.00750000 81.42 0.01272122 68.64 3.4023 74.99 0.00875879 45.4744 7286.15 0.00 52878.99 36411.98
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 52888.058 52888.058 1322.477150 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 52888.06 29752.65 1322.477150 68.63 55.86 0.00698576 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.4023 71.99 0.00722535 41.6020 25070.22 0.00 52957.56 52957.56
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 33717.163 33717.163 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33717.16 33717.16 -999. 68.63 55.86 0.00698576 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722535 41.6020 25070.22 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 52767.073 37073.568 1322.175161 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 52156.38 42021.70 1322.175161 76.76 62.04 0.00902000 53.60 50.67 0.00750000 80.27 0.01272010 68.29 3.4031 75.00 0.00859184 44.6170 9763.54 0.00 52758.02 36397.74
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 52875.981 52875.981 1322.175161 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 52875.98 29746.92 1322.175161 68.63 55.86 0.00698555 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.4031 71.99 0.00722519 41.6011 25064.50 0.00 52945.47 52945.47
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 33710.676 33710.676 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33710.68 33710.68 -999. 68.63 55.86 0.00698555 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722519 41.6011 25064.50 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 43746.225 30669.744 1093.883662 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 44464.90 30978.68 1093.883662 76.79 63.84 0.01024587 53.60 50.67 0.00750000 77.48 0.01271739 67.44 4.1133 75.00 0.00950503 49.2869 4390.87 0.00 43738.72 30118.08
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 43746.225 43746.225 1093.883662 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 43746.22 25418.51 1093.883662 67.92 55.37 0.00686157 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.1133 71.99 0.00714805 41.1611 20736.06 0.00 43803.71 43803.71
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 28805.510 28805.510 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28805.51 28805.51 -999. 67.92 55.37 0.00686157 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00714805 41.1611 20736.06 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 52884.286 37076.286 1322.382824 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 52915.11 40273.89 1322.382824 76.82 62.74 0.00948198 53.60 50.67 0.00750000 78.81 0.01271869 67.85 3.4026 75.00 0.00887077 46.0441 6419.00 0.00 52875.21 36409.39
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 52884.286 52884.286 1322.382824 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 52884.29 29750.86 1322.382824 68.63 55.86 0.00698570 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.4026 71.99 0.00722530 41.6018 25068.43 0.00 52953.78 52953.78
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 33715.137 33715.137 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33715.14 33715.14 -999. 68.63 55.86 0.00698570 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722530 41.6018 25068.43 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 36519.624 25983.595 944.529978 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 35875.67 29879.49 944.529978 76.79 61.67 0.00876603 53.60 50.67 0.00750000 80.82 0.01272064 68.46 4.7637 75.00 0.00832942 43.2711 10263.97 0.00 36513.36 25496.25
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 37773.323 37773.323 944.529978 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 37773.32 22584.39 944.529978 67.28 55.32 0.00697349 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.7637 71.99 0.00731314 42.0963 17901.79 0.00 37822.96 37822.96
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 25593.738 25593.738 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25593.74 25593.74 -999. 67.28 55.32 0.00697349 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00731314 42.0963 17901.79 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 28665.158 20096.662 716.778384 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 28262.88 21660.65 716.778384 78.43 63.35 0.00953226 53.60 50.67 0.00750000 86.18 0.01272586 70.04 6.2774 75.00 0.00874535 45.4033 5122.14 0.00 28660.24 19735.18
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 28665.158 28665.158 716.778384 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28665.16 18267.28 716.778384 65.79 54.39 0.00677949 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 6.2774 71.99 0.00722129 41.5727 13584.64 0.00 28702.83 28702.83
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 20701.377 20701.377 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 20701.38 20701.38 -999. 65.79 54.39 0.00677949 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722129 41.5727 13584.64 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 37774.705 26483.212 944.564525 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 37273.47 30034.86 944.564525 77.08 62.18 0.00903596 53.60 50.67 0.00750000 81.42 0.01272122 68.64 4.7636 75.00 0.00848348 44.0625 7292.36 0.00 37768.22 26006.85
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 37774.705 37774.705 944.564525 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 37774.70 22585.04 944.564525 67.28 55.32 0.00697353 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.7636 71.99 0.00731316 42.0965 17902.44 0.00 37824.35 37824.35
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 25594.480 25594.480 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25594.48 25594.48 -999. 67.28 55.32 0.00697353 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00731316 42.0965 17902.44 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 36677.218 26056.638 944.618127 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 36244.25 29784.84 944.618127 76.66 61.77 0.00886168 53.60 50.67 0.00750000 79.15 0.01271901 67.95 4.7633 75.00 0.00840051 43.6357 9588.47 0.00 36670.93 25565.64
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 37776.848 37776.848 944.618127 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 37776.85 22586.06 944.618127 67.28 55.32 0.00697358 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.7633 71.99 0.00731320 42.0967 17903.46 0.00 37826.49 37826.49
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 25595.631 25595.631 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25595.63 25595.63 -999. 67.28 55.32 0.00697358 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00731320 42.0967 17903.46 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 28662.932 20095.100 716.722702 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 29038.42 20787.47 716.722702 76.60 63.40 0.00998711 53.60 50.67 0.00750000 76.66 0.01271660 67.19 6.2779 75.00 0.00919066 47.6797 4381.94 0.00 28658.01 19733.65
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 28662.932 28662.932 716.722702 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28662.93 18266.22 716.722702 65.79 54.39 0.00677941 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 6.2779 71.99 0.00722123 41.5724 13583.59 0.00 28700.60 28700.60
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 20700.181 20700.181 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 20700.18 20700.18 -999. 65.79 54.39 0.00677941 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00722123 41.5724 13583.59 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 37766.750 26477.635 944.365613 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 37567.05 29575.58 944.365613 76.89 62.37 0.00921030 53.60 50.67 0.00750000 79.37 0.01271923 68.02 4.7646 75.00 0.00857136 44.5102 6602.46 0.00 37760.27 26001.38
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 37766.750 37766.750 944.365613 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 37766.75 22581.27 944.365613 67.28 55.31 0.00697333 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.7646 71.99 0.00731303 42.0957 17898.67 0.00 37816.38 37816.38
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 25590.208 25590.208 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 25590.21 25590.21 -999. 67.28 55.31 0.00697333 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00731303 42.0957 17898.67 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 52565.725 37114.993 1335.789827 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 51762.45 42347.12 1335.789827 76.77 61.87 0.00890143 53.60 50.67 0.00750000 80.82 0.01272064 68.46 3.3684 75.00 0.00850033 44.1482 10718.11 0.00 52556.71 36431.82
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 53420.454 53420.454 1335.789827 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 53420.45 30004.99 1335.789827 68.66 55.89 0.00699463 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.3684 71.99 0.00723205 41.6402 25322.56 0.00 53490.66 53490.66
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 34003.129 34003.129 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 34003.13 34003.13 -999. 68.66 55.89 0.00699463 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00723205 41.6402 25322.56 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 44294.337 31054.016 1107.589310 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 43780.37 32971.83 1107.589310 78.21 63.48 0.00967026 53.60 50.67 0.00750000 85.96 0.01272565 69.97 4.0624 74.99 0.00899341 46.6745 5548.92 0.00 44286.74 30495.44
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 44294.337 44294.337 1107.589310 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 44294.34 25678.29 1107.589310 67.97 55.41 0.00687386 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.0624 71.99 0.00715716 41.2130 20995.84 0.00 44352.55 44352.55
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 29099.903 29099.903 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 29099.90 29099.90 -999. 67.97 55.41 0.00687386 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00715716 41.2130 20995.84 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 53408.635 37443.898 1335.494285 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 52225.80 41106.26 1335.494285 77.72 62.72 0.00926145 53.60 50.67 0.00750000 86.18 0.01272586 70.04 3.3692 74.99 0.00872420 45.2973 7541.69 0.00 53399.47 36770.39
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 53408.635 53408.635 1335.494285 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 53408.64 29999.39 1335.494285 68.66 55.89 0.00699443 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.3692 71.99 0.00723190 41.6393 25316.96 0.00 53478.82 53478.82
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 33996.780 33996.780 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33996.78 33996.78 -999. 68.66 55.89 0.00699443 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00723190 41.6393 25316.96 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 52516.964 37092.079 1335.725514 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 51894.73 42220.65 1335.725514 76.67 61.89 0.00893951 53.60 50.67 0.00750000 79.71 0.01271956 68.12 3.3686 75.00 0.00853057 44.3032 10452.75 0.00 52507.96 36409.97
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 53417.882 53417.882 1335.725514 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 53417.88 30003.77 1335.725514 68.66 55.89 0.00699458 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.3686 71.99 0.00723202 41.6400 25321.34 0.00 53488.08 53488.08
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 34001.747 34001.747 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 34001.75 34001.75 -999. 68.66 55.89 0.00699458 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00723202 41.6400 25321.34 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 44287.634 31049.317 1107.421715 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 44755.67 32330.32 1107.421715 76.69 63.33 0.00991609 53.60 50.67 0.00750000 77.48 0.01271739 67.44 4.0630 75.00 0.00925023 47.9852 5272.77 0.00 44280.04 30490.83
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 44287.634 44287.634 1107.421715 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 44287.63 25675.11 1107.421715 67.97 55.41 0.00687371 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 4.0630 71.99 0.00715705 41.2123 20992.66 0.00 44345.83 44345.83
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 29096.303 29096.303 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 29096.30 29096.30 -999. 67.97 55.41 0.00687371 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00715705 41.2123 20992.66 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 53397.816 37436.313 1335.223751 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 53280.07 40770.84 1335.223751 76.98 62.75 0.00944819 53.60 50.67 0.00750000 79.93 0.01271977 68.19 3.3698 75.00 0.00884810 45.9281 6533.46 0.00 53388.66 36762.94
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 53397.816 53397.816 1335.223751 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 53397.82 29994.26 1335.223751 68.66 55.88 0.00699424 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 3.3698 71.99 0.00723176 41.6385 25311.83 0.00 53467.99 53467.99
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 33990.968 33990.968 -999. -999. -999.00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 33990.97 33990.97 -999. 68.66 55.88 0.00699424 90.00 64.95 0.00800000 -26.9 0.00018338 -26.9 -999.000 71.99 0.00723176 41.6385 25311.83 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52314.211 36864.526 1321.962521 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 1321.962521 1.58733476   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 Sensible 51489.99 42012.92 0.9842 1.58733476 1321.962521 76.82 61.92 0.00892425 11.4 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1701.341 49788.65 81.20 0.01272100 68.57 44.99498340 3.4037 75.00 0.00851861 75.00 0.00851288 44.2125 10480.25 0.00 52305.24 36181.92 1.52464704 80.00 67.00 0.01118466 13.2 52.96 52.92 0.00850563 7.9
MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 52867.477 52867.477 1321.962521 -999. -999.00 -999.0000 1.00000 0.87876 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 1321.962521 1.58733476   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 52867.48 29742.89 1.0000 1.58733476 1321.962521 68.62 55.86 0.00698541 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 52867.48 -26.9 0.00018338 -26.9 44.99498340 3.4037 71.99 0.00722508 71.99 0.00722508 41.6005 25060.47 0.00 52936.95 52936.95 1.55928607 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33706.108 33706.108 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 1321.962521 1.58733476   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33706.11 33706.11 1.0000 -0.254140E+04 -999. 68.62 55.86 0.00698541 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33706.11 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722508 71.99 0.00722508 41.6005 25060.47 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 43743.948 30668.148 1093.826728 -999. -999.00 -999.0000 1.00000 0.86312 0.2443 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 1093.826728 1.31340274   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 43290.97 32353.26 0.9896 1.31340274 1093.826728 78.35 63.64 0.00974848 12.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1407.735 41883.23 86.18 0.01272586 70.04 44.99498340 4.1135 74.99 0.00904523 74.99 0.00904523 46.9396 5299.36 0.00 43736.44 30116.51 1.26153326 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 43743.948 43743.948 1093.826728 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 1093.826728 1.31340274   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 43743.95 25417.43 1.0000 1.31340274 1093.826728 67.92 55.37 0.00686152 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 43743.95 -26.9 0.00018338 -26.9 44.99498340 4.1135 71.99 0.00714801 71.99 0.00714801 41.1609 20734.98 0.00 43801.43 43801.43 1.29019450 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 28804.287 28804.287 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 1093.826728 1.31340274   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28804.29 28804.29 1.0000 -0.254140E+04 -999. 67.92 55.37 0.00686152 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 28804.29 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00714801 71.99 0.00714801 41.1609 20734.98 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52888.058 37078.930 1322.477150 -999. -999.00 -999.0000 1.00000 0.95693 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 1322.477150 1.58795270   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 Sensible 52420.76 40986.10 0.9912 1.58795270 1322.477150 77.10 62.54 0.00927889 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1702.004 50718.76 81.42 0.01272122 68.64 44.99498340 3.4023 75.00 0.00873039 74.99 0.00875879 45.4744 7286.15 0.00 52878.99 36411.98 1.52524057 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 52888.058 52888.058 1322.477150 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 1322.477150 1.58795270   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 52888.06 29752.65 1.0000 1.58795270 1322.477150 68.63 55.86 0.00698576 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 52888.06 -26.9 0.00018338 -26.9 44.99498340 3.4023 71.99 0.00722535 71.99 0.00722535 41.6020 25070.22 0.00 52957.56 52957.56 1.55989308 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33717.163 33717.163 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 1322.477150 1.58795270   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33717.16 33717.16 1.0000 -0.254140E+04 -999. 68.63 55.86 0.00698576 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33717.16 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722535 71.99 0.00722535 41.6020 25070.22 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52767.073 37073.568 1322.175161 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.175161 1.58759009   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 52156.38 42021.70 0.9884 1.58759009 1322.175161 76.76 62.04 0.00902000 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1701.615 50454.77 80.27 0.01272010 68.29 44.99498340 3.4031 75.00 0.00859184 75.00 0.00859184 44.6170 9763.54 0.00 52758.02 36397.74 1.52489228 80.00 67.00 0.01118466 13.2 52.80 52.79 0.00846669 7.9
MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 52875.981 52875.981 1322.175161 -999. -999.00 -999.0000 1.00000 0.87136 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.175161 1.58759009   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 52875.98 29746.92 1.0000 1.58759009 1322.175161 68.63 55.86 0.00698555 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 52875.98 -26.9 0.00018338 -26.9 44.99498340 3.4031 71.99 0.00722519 71.99 0.00722519 41.6011 25064.50 0.00 52945.47 52945.47 1.55953688 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33710.676 33710.676 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.175161 1.58759009   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33710.68 33710.68 1.0000 -0.254140E+04 -999. 68.63 55.86 0.00698555 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33710.68 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722519 71.99 0.00722519 41.6011 25064.50 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 43746.225 30669.744 1093.883662 -999. -999.00 -999.0000 1.00000 0.86984 0.2446 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 1093.883662 1.31347110   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 44464.90 30978.68 1.0164 1.31347110 1093.883662 76.79 63.84 0.01024587 12.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1407.808 43057.09 77.48 0.01271739 67.44 44.99498340 4.1133 75.00 0.00950503 75.00 0.00950503 49.2869 4390.87 0.00 43738.72 30118.08 1.26159892 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 43746.225 43746.225 1093.883662 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 1093.883662 1.31347110   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 43746.22 25418.51 1.0000 1.31347110 1093.883662 67.92 55.37 0.00686157 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 43746.22 -26.9 0.00018338 -26.9 44.99498340 4.1133 71.99 0.00714805 71.99 0.00714805 41.1611 20736.06 0.00 43803.71 43803.71 1.29026166 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 28805.510 28805.510 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 1093.883662 1.31347110   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28805.51 28805.51 1.0000 -0.254140E+04 -999. 67.92 55.37 0.00686157 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 28805.51 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00714805 71.99 0.00714805 41.1611 20736.06 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52884.286 37076.286 1322.382824 -999. -999.00 -999.0000 1.00000 0.94703 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.382824 1.58783944   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 Sensible 52915.11 40273.89 1.0006 1.58783944 1322.382824 76.82 62.74 0.00948198 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1701.882 51213.22 78.81 0.01271869 67.85 44.99498340 3.4026 75.00 0.00887685 75.00 0.00887077 46.0441 6419.00 0.00 52875.21 36409.39 1.52513178 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 52884.286 52884.286 1322.382824 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.382824 1.58783944   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 52884.29 29750.86 1.0000 1.58783944 1322.382824 68.63 55.86 0.00698570 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 52884.29 -26.9 0.00018338 -26.9 44.99498340 3.4026 71.99 0.00722530 71.99 0.00722530 41.6018 25068.43 0.00 52953.78 52953.78 1.55978182 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33715.137 33715.137 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 1322.382824 1.58783944   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33715.14 33715.14 1.0000 -0.254140E+04 -999. 68.63 55.86 0.00698570 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33715.14 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722530 71.99 0.00722530 41.6018 25068.43 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 36519.624 25983.595 944.529978 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.529978 1.13413599   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 35875.67 29879.49 0.9824 1.13413599 944.529978 76.79 61.67 0.00876603 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1215.593 34660.08 80.82 0.01272064 68.46 44.99498340 4.7637 75.00 0.00833395 75.00 0.00832942 43.2711 10263.97 0.00 36513.36 25496.25 1.08934619 80.00 67.00 0.01118466 13.2 53.34 53.29 0.00862257 8.0
MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 37773.323 37773.323 944.529978 -999. -999.00 -999.0000 1.00000 0.89942 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.529978 1.13413599   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 37773.32 22584.39 1.0000 1.13413599 944.529978 67.28 55.32 0.00697349 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 37773.32 -26.9 0.00018338 -26.9 44.99498340 4.7637 71.99 0.00731314 71.99 0.00731314 42.0963 17901.79 0.00 37822.96 37822.96 1.11409545 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 25593.738 25593.738 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.529978 1.13413599   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25593.74 25593.74 1.0000 -0.254140E+04 -999. 67.28 55.32 0.00697349 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 25593.74 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00731314 71.99 0.00731314 42.0963 17901.79 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 28665.158 20096.662 716.778384 -999. -999.00 -999.0000 1.00000 0.88264 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 716.778384 0.86066528   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 Sensible 28262.88 21660.65 0.9860 0.86066528 716.778384 78.43 63.35 0.00953226 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 922.480 27340.40 86.18 0.01272586 70.04 44.99498340 6.2774 75.00 0.00874535 75.00 0.00874535 45.4033 5122.14 0.00 28660.24 19735.18 0.82667551 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 28665.158 28665.158 716.778384 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 716.778384 0.86066528   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28665.16 18267.28 1.0000 0.86066528 716.778384 65.79 54.39 0.00677949 8.6 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 28665.16 -26.9 0.00018338 -26.9 44.99498340 6.2774 71.99 0.00722129 71.99 0.00722129 41.5727 13584.64 0.00 28702.83 28702.83 0.84545706 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 20701.377 20701.377 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 716.778384 0.86066528   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 20701.38 20701.38 1.0000 -0.254140E+04 -999. 65.79 54.39 0.00677949 8.6 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 20701.38 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722129 71.99 0.00722129 41.5727 13584.64 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 37774.705 26483.212 944.564525 -999. -999.00 -999.0000 1.00000 0.98736 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.564525 1.13417747   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 Sensible 37273.47 30034.86 0.9867 1.13417747 944.564525 77.08 62.18 0.00903596 11.5 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1215.637 36057.83 81.42 0.01272122 68.64 44.99498340 4.7636 75.00 0.00846046 75.00 0.00848348 44.0625 7292.36 0.00 37768.22 26006.85 1.08938603 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 37774.705 37774.705 944.564525 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.564525 1.13417747   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 37774.70 22585.04 1.0000 1.13417747 944.564525 67.28 55.32 0.00697353 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 37774.70 -26.9 0.00018338 -26.9 44.99498340 4.7636 71.99 0.00731316 71.99 0.00731316 42.0965 17902.44 0.00 37824.35 37824.35 1.11413620 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 25594.480 25594.480 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 944.564525 1.13417747   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25594.48 25594.48 1.0000 -0.254140E+04 -999. 67.28 55.32 0.00697353 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 25594.48 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00731316 71.99 0.00731316 42.0965 17902.44 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 36677.218 26056.638 944.618127 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 944.618127 1.13424183   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 36244.25 29784.84 0.9882 1.13424183 944.618127 76.66 61.77 0.00886168 11.3 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1215.706 35028.54 79.15 0.01271901 67.95 44.99498340 4.7633 75.00 0.00840672 75.00 0.00840051 43.6357 9588.47 0.00 36670.93 25565.64 1.08944785 80.00 67.00 0.01118466 13.2 53.26 53.23 0.00860230 8.0
MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 37776.848 37776.848 944.618127 -999. -999.00 -999.0000 1.00000 0.89564 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 944.618127 1.13424183   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 37776.85 22586.06 1.0000 1.13424183 944.618127 67.28 55.32 0.00697358 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 37776.85 -26.9 0.00018338 -26.9 44.99498340 4.7633 71.99 0.00731320 71.99 0.00731320 42.0967 17903.46 0.00 37826.49 37826.49 1.11419943 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 25595.631 25595.631 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 944.618127 1.13424183   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25595.63 25595.63 1.0000 -0.254140E+04 -999. 67.28 55.32 0.00697358 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 25595.63 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00731320 71.99 0.00731320 42.0967 17903.46 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 28662.932 20095.100 716.722702 -999. -999.00 -999.0000 1.00000 0.90133 0.2444 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 716.722702 0.86059842   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 Sensible 29038.42 20787.47 1.0131 0.86059842 716.722702 76.60 63.40 0.00998711 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 922.409 28116.01 76.66 0.01271660 67.19 44.99498340 6.2779 75.00 0.00917103 75.00 0.00919066 47.6797 4381.94 0.00 28658.01 19733.65 0.82661129 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 28662.932 28662.932 716.722702 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 716.722702 0.86059842   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28662.93 18266.22 1.0000 0.86059842 716.722702 65.79 54.39 0.00677941 8.6 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 28662.93 -26.9 0.00018338 -26.9 44.99498340 6.2779 71.99 0.00722123 71.99 0.00722123 41.5724 13583.59 0.00 28700.60 28700.60 0.84539138 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 20700.181 20700.181 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 716.722702 0.86059842   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 20700.18 20700.18 1.0000 -0.254140E+04 -999. 65.79 54.39 0.00677941 8.6 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 20700.18 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00722123 71.99 0.00722123 41.5724 13583.59 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 37766.750 26477.635 944.365613 -999. -999.00 -999.0000 1.00000 0.97651 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 944.365613 1.13393863   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 37567.05 29575.58 0.9947 1.13393863 944.365613 76.89 62.37 0.00921030 11.6 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1215.381 36351.67 79.37 0.01271923 68.02 44.99498340 4.7646 75.00 0.00857633 75.00 0.00857136 44.5102 6602.46 0.00 37760.27 26001.38 1.08915662 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 37766.750 37766.750 944.365613 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 944.365613 1.13393863   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 37766.75 22581.27 1.0000 1.13393863 944.365613 67.28 55.31 0.00697333 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 37766.75 -26.9 0.00018338 -26.9 44.99498340 4.7646 71.99 0.00731303 71.99 0.00731303 42.0957 17898.67 0.00 37816.38 37816.38 1.11390158 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 25590.208 25590.208 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 944.365613 1.13393863   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 25590.21 25590.21 1.0000 -0.254140E+04 -999. 67.28 55.31 0.00697333 8.9 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 25590.21 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00731303 71.99 0.00731303 42.0957 17898.67 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52565.725 37114.993 1335.789827 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 1335.789827 1.60393778   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 51762.45 42347.12 0.9847 1.60393778 1335.789827 76.77 61.87 0.00890143 11.4 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1719.137 50043.31 80.82 0.01272064 68.46 44.99498340 3.3684 75.00 0.00850362 75.00 0.00850033 44.1482 10718.11 0.00 52556.71 36431.82 1.54059436 80.00 67.00 0.01118466 13.2 53.05 53.01 0.00853310 7.9
MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 53420.454 53420.454 1335.789827 -999. -999.00 -999.0000 1.00000 0.88370 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 1335.789827 1.60393778   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 53420.45 30004.99 1.0000 1.60393778 1335.789827 68.66 55.89 0.00699463 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 53420.45 -26.9 0.00018338 -26.9 44.99498340 3.3684 71.99 0.00723205 71.99 0.00723205 41.6402 25322.56 0.00 53490.66 53490.66 1.57559570 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 34003.129 34003.129 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 1335.789827 1.60393778   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 34003.13 34003.13 1.0000 -0.254140E+04 -999. 68.66 55.89 0.00699463 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 34003.13 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00723205 71.99 0.00723205 41.6402 25322.56 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 44294.337 31054.016 1107.589310 -999. -999.00 -999.0000 1.00000 0.87436 0.2443 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 1107.589310 1.32992803   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 43780.37 32971.83 0.9884 1.32992803 1107.589310 78.21 63.48 0.00967026 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1425.447 42354.93 85.96 0.01272565 69.97 44.99498340 4.0624 74.99 0.00898922 74.99 0.00899341 46.6745 5548.92 0.00 44286.74 30495.44 1.27740593 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 44294.337 44294.337 1107.589310 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 1107.589310 1.32992803   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 44294.34 25678.29 1.0000 1.32992803 1107.589310 67.97 55.41 0.00687386 9.0 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 44294.34 -26.9 0.00018338 -26.9 44.99498340 4.0624 71.99 0.00715716 71.99 0.00715716 41.2130 20995.84 0.00 44352.55 44352.55 1.30642779 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 29099.903 29099.903 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 1107.589310 1.32992803   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 29099.90 29099.90 1.0000 -0.254140E+04 -999. 67.97 55.41 0.00687386 9.0 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 29099.90 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00715716 71.99 0.00715716 41.2130 20995.84 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 53408.635 37443.898 1335.494285 -999. -999.00 -999.0000 1.00000 0.92815 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 1335.494285 1.60358291   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:20:00 Sensible 52225.80 41106.26 0.9779 1.60358291 1335.494285 77.72 62.72 0.00926145 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1718.756 50507.05 86.18 0.01272586 70.04 44.99498340 3.3692 74.99 0.00872420 74.99 0.00872420 45.2973 7541.69 0.00 53399.47 36770.39 1.54025351 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 53408.635 53408.635 1335.494285 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 1335.494285 1.60358291   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 53408.64 29999.39 1.0000 1.60358291 1335.494285 68.66 55.89 0.00699443 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 53408.64 -26.9 0.00018338 -26.9 44.99498340 3.3692 71.99 0.00723190 71.99 0.00723190 41.6393 25316.96 0.00 53478.82 53478.82 1.57524710 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33996.780 33996.780 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 1335.494285 1.60358291   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33996.78 33996.78 1.0000 -0.254140E+04 -999. 68.66 55.89 0.00699443 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33996.78 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00723190 71.99 0.00723190 41.6393 25316.96 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 52516.964 37092.079 1335.725514 -999. -999.00 -999.0000 1.00000 1.00000 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 1335.725514 1.60386056   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 51894.73 42220.65 0.9882 1.60386056 1335.725514 76.67 61.89 0.00893951 11.4 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1719.054 50175.68 79.71 0.01271956 68.12 44.99498340 3.3686 75.00 0.00853495 75.00 0.00853057 44.3032 10452.75 0.00 52507.96 36409.97 1.54052019 80.00 67.00 0.01118466 13.2 53.07 53.03 0.00853740 8.0
MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 53417.882 53417.882 1335.725514 -999. -999.00 -999.0000 1.00000 0.88448 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 1335.725514 1.60386056   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 53417.88 30003.77 1.0000 1.60386056 1335.725514 68.66 55.89 0.00699458 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 53417.88 -26.9 0.00018338 -26.9 44.99498340 3.3686 71.99 0.00723202 71.99 0.00723202 41.6400 25321.34 0.00 53488.08 53488.08 1.57551984 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 34001.747 34001.747 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 1335.725514 1.60386056   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 34001.75 34001.75 1.0000 -0.254140E+04 -999. 68.66 55.89 0.00699458 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 34001.75 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00723202 71.99 0.00723202 41.6400 25321.34 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 44287.634 31049.317 1107.421715 -999. -999.00 -999.0000 1.00000 0.90505 0.2444 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 1107.421715 1.32972679   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 44755.67 32330.32 1.0106 1.32972679 1107.421715 76.69 63.33 0.00991609 12.0 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1425.231 43330.44 77.48 0.01271739 67.44 44.99498340 4.0630 75.00 0.00925023 75.00 0.00925023 47.9852 5272.77 0.00 44280.04 30490.83 1.27721264 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 44287.634 44287.634 1107.421715 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 1107.421715 1.32972679   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 44287.63 25675.11 1.0000 1.32972679 1107.421715 67.97 55.41 0.00687371 9.0 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 44287.63 -26.9 0.00018338 -26.9 44.99498340 4.0630 71.99 0.00715705 71.99 0.00715705 41.2123 20992.66 0.00 44345.83 44345.83 1.30623011 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 29096.303 29096.303 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 1107.421715 1.32972679   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 29096.30 29096.30 1.0000 -0.254140E+04 -999. 67.97 55.41 0.00687371 9.0 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 29096.30 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00715705 71.99 0.00715705 41.2123 20992.66 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 53397.816 37436.313 1335.223751 -999. -999.00 -999.0000 1.00000 0.94413 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 1335.223751 1.60325807   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 53280.07 40770.84 0.9978 1.60325807 1335.223751 76.98 62.75 0.00944819 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 1718.408 51561.66 79.93 0.01271977 68.19 44.99498340 3.3698 75.00 0.00885081 75.00 0.00884810 45.9281 6533.46 0.00 53388.66 36762.94 1.53994149 80.00 67.00 0.01118466 13.2 52.79 52.75 0.00844959 7.9
MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes unknown No 53397.816 53397.816 1335.223751 -999. -999.00 -999.0000 1.00000 0.86957 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 1335.223751 1.60325807   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 53397.82 29994.26 1.0000 1.60325807 1335.223751 68.66 55.88 0.00699424 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 53397.82 -26.9 0.00018338 -26.9 44.99498340 3.3698 71.99 0.00723176 71.99 0.00723176 41.6385 25311.83 0.00 53467.99 53467.99 1.57492800 70.00 60.00 0.00875166 10.4 108.67 72.43 0.00875166 15.6
SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Electric AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 33990.968 33990.968 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 1335.223751 1.60325807   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 33990.97 33990.97 1.0000 -0.254140E+04 -999. 68.66 55.88 0.00699424 9.1 90.00 64.95 0.00800000 12.6 -999. -999.0 -999.0 -999.0 0.000 33990.97 -26.9 0.00018338 -26.9 44.99498340 -999.000 71.99 0.00723176 71.99 0.00723176 41.6385 25311.83 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3549.67 6874.50 2347.67
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2602.83 6931.50 1652.50
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3550.00 6744.17 2279.67
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3726.17 7104.00 2681.50
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2900.83 7226.17 2111.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3699.17 6993.50 2631.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3101.50 6456.83 1681.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1891.83 6335.50 681.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3061.83 6347.33 1610.83
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3267.33 6684.33 2003.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2175.33 6629.00 1118.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3241.00 6597.00 1976.00
LIVING_UNIT3_BACKROW_TOPFLOOR 3798.50 6834.33 2524.17
LIVING_UNIT3_FRONTROW_TOPFLOOR 3619.83 6637.67 2234.33
LIVING_UNIT1_FRONTROW_TOPFLOOR 3604.67 6765.67 2289.67
LIVING_UNIT2_BACKROW_TOPFLOOR 2969.17 6973.17 1947.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 2695.00 6750.33 1544.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3791.50 6943.17 2586.17
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4347.17 7407.67 2871.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.372 0.000 0.284
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.327 0.000 0.284
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.372 0.000 0.284
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.371 0.000 0.284
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.327 0.000 0.284
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.371 0.000 0.284
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.163 0.000 0.284
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.119 0.000 0.284
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.163 0.000 0.284
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.163 0.000 0.284
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.119 0.000 0.284
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.163 0.000 0.284
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.372 0.000 0.284
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.372 0.000 0.284
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.372 0.000 0.284
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.327 0.000 0.284
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.328 0.000 0.284
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.372 0.000 0.284
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.006
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.006
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.006
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 32970261.31 58117088.29 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 29042908.28 54189735.26 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 32984011.27 58130838.25 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 32949058.93 58095885.91 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 29015330.44 54162157.42 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 32963381.98 58110208.96 23785081.69 1454.17 1131.50 6222.33 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 14467399.89 39615767.20 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 10528686.52 35677053.84 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 14471746.03 39620113.35 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 14457163.48 39605530.80 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 10517534.22 35665901.54 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 14462078.69 39610446.00 23785081.69 1449.83 1132.00 6226.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 32998469.63 58148378.92 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 33014748.63 58164657.92 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 33001678.61 58151587.90 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 29050924.30 54200833.59 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 29071841.89 54221751.17 23785081.69 1446.33 1131.00 6230.67 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 32985522.73 58135432.02 23785081.69 1446.33 1131.00 6230.67 0.00
Total Facility 0.00 0.452671E+09 0.452671E+09 0.458953E+09 0.911623E+09 0.428131E+09 1454.17 1139.33 6230.67 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 62.3709 109.9419 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 54.9414 102.5124 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 62.3969 109.9679 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 62.3308 109.9018 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 54.8892 102.4602 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 62.3579 109.9289 44.9950 1454.17 1131.50 6222.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 27.3684 74.9424 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 19.9174 67.4914 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 27.3767 74.9506 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 27.3491 74.9230 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 19.8963 67.4703 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 27.3584 74.9323 44.9950 1449.83 1132.00 6226.17
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 62.4242 110.0011 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 62.4550 110.0319 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 62.4303 110.0072 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 54.9565 102.5334 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 54.9961 102.5730 44.9950 1446.33 1131.00 6230.67
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 62.3997 109.9766 44.9950 1446.33 1131.00 6230.67
Total Facility 0.0000 856.3312 856.3312 868.2153 1724.5465 809.9097 1454.17 1139.33 6230.67


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 25146826.98 25146826.98 23785081.69 1454.17 1131.50 6222.33 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 25148367.32 25148367.32 23785081.69 1449.83 1132.00 6226.17 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 25149909.29 25149909.29 23785081.69 1446.33 1131.00 6230.67 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 47.5710 47.5710 44.9950 1454.17 1131.50 6222.33
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 47.5740 47.5740 44.9950 1449.83 1132.00 6226.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 47.5769 47.5769 44.9950 1446.33 1131.00 6230.67


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 1940
Defaulted Fields 1825
Fields with Defaults 6415
Autosized Fields 378
Autosizable Fields 576
Autocalculated Fields 161
Autocalculatable Fields 349



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
Electricity:Building 106022.24 6418.34 02-JAN-03:10 20705.41 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
Electricity:SpaceType:GENERAL 106022.24 6418.34 02-JAN-03:10 20705.41 01-JAN-18:10
InteriorLights:Electricity 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
General:InteriorLights:Electricity 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 17719.17 396.81 01-JAN-00:10 5771.73 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5890.12 356.57 02-JAN-03:10 1150.30 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 984.40 22.04 01-JAN-00:10 320.65 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Fans:Electricity 23175.28 578.57 24-APR-01:20 8215.04 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
ElectricityPurchased:Plant 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
Cogeneration:ElectricityPurchased 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
General:Cogeneration:ElectricityPurchased 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
ElectricityNet:Plant 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
Cogeneration:ElectricityNet 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
General:Cogeneration:ElectricityNet 355342.77 8374.61 11-MAY-03:30 186479.46 05-JAN-07:50
Electricity:HVAC 173117.65 578.57 24-APR-01:20 120882.33 06-JAN-05:00
Ventilation:Fans:Electricity 5068.29 578.57 01-JAN-00:10 578.57 01-JAN-00:10
General:Fans:Electricity 18106.99 0.00 24-APR-01:20 7636.47 01-JAN-00:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 8807.00 0.00 01-JAN-00:10 16255.13 29-JUN-16:10
General:Cooling:Electricity 8807.00 0.00 01-JAN-00:10 16255.13 29-JUN-16:10
Heating:Electricity 141135.36 0.00 11-APR-15:40 112667.29 06-JAN-05:00
General:Heating:Electricity 141135.36 0.00 11-APR-15:40 112667.29 06-JAN-05:00
Electricity:Plant 70168.57 0.00 01-JAN-00:10 61568.92 05-MAR-07:20
WaterSystems:Electricity 70168.57 0.00 01-JAN-00:10 61568.92 05-MAR-07:20
Water Heater:WaterSystems:Electricity 70168.57 0.00 01-JAN-00:10 61568.92 05-MAR-07:20
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1790064.52 1194.46 08-SEP-03:00 788035.13 06-JAN-08:10
EnergyTransfer:Building 825847.23 0.00 24-APR-01:20 398191.35 06-JAN-05:00
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 725252.64 0.00 11-APR-15:40 398191.35 06-JAN-05:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 725252.64 0.00 11-APR-15:40 398191.35 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 100594.58 0.00 01-JAN-00:10 151794.50 29-JUN-18:10
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 100594.58 0.00 01-JAN-00:10 151794.50 29-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 53745.40 0.00 04-FEB-15:00 26150.15 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 47072.66 0.00 04-FEB-15:00 26150.15 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 47072.66 0.00 04-FEB-15:00 26150.15 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6672.75 0.00 01-JAN-00:10 11969.90 29-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 6672.75 0.00 01-JAN-00:10 11969.90 29-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 42216.63 0.00 08-FEB-14:00 21599.50 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 37968.01 0.00 08-FEB-14:00 21599.50 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 37968.01 0.00 08-FEB-14:00 21599.50 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4248.62 0.00 01-JAN-00:10 6501.35 30-JUN-15:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4248.62 0.00 01-JAN-00:10 6501.35 30-JUN-15:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 53016.97 0.00 26-MAR-12:20 26172.29 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 46734.64 0.00 26-MAR-12:20 26172.29 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 46734.64 0.00 26-MAR-12:20 26172.29 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6282.34 0.00 01-JAN-00:10 8471.04 30-JUN-10:50
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 6282.34 0.00 01-JAN-00:10 8471.04 30-JUN-10:50
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 55497.33 0.00 19-MAR-16:20 26219.87 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 50285.86 0.00 19-MAR-16:20 26219.87 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 50285.86 0.00 19-MAR-16:20 26219.87 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5211.47 0.00 01-JAN-00:10 11537.89 29-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5211.47 0.00 01-JAN-00:10 11537.89 29-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44373.96 0.00 11-APR-15:40 21679.04 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 41385.99 0.00 11-APR-15:40 21679.04 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 41385.99 0.00 11-APR-15:40 21679.04 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2987.98 0.00 01-JAN-00:10 6304.21 29-JUN-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2987.98 0.00 01-JAN-00:10 6304.21 29-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 54791.87 0.00 11-APR-09:00 26234.62 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 49988.31 0.00 11-APR-09:00 26234.62 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 49988.31 0.00 11-APR-09:00 26234.62 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4803.56 0.00 01-JAN-00:10 7360.44 29-JUN-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4803.56 0.00 01-JAN-00:10 7360.44 29-JUN-18:20
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 38704.85 0.00 04-FEB-14:00 18324.33 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 31003.26 0.00 04-FEB-14:00 18324.33 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 31003.26 0.00 04-FEB-14:00 18324.33 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7701.59 0.00 01-JAN-00:10 11308.44 29-JUN-17:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 7701.59 0.00 01-JAN-00:10 11308.44 29-JUN-17:20
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 27417.13 0.00 04-FEB-13:50 13781.92 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 22081.62 0.00 04-FEB-13:50 13781.92 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 22081.62 0.00 04-FEB-13:50 13781.92 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5335.51 0.00 01-JAN-00:10 5957.57 29-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5335.51 0.00 01-JAN-00:10 5957.57 29-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 38164.86 0.00 04-FEB-14:30 18336.42 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 30718.74 0.00 04-FEB-14:30 18336.42 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 30718.74 0.00 04-FEB-14:30 18336.42 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7446.12 0.00 01-JAN-00:10 8235.64 29-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7446.12 0.00 01-JAN-00:10 8235.64 29-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 39937.80 0.00 19-MAR-15:40 18387.33 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 33856.51 0.00 19-MAR-15:40 18387.33 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 33856.51 0.00 19-MAR-15:40 18387.33 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6081.29 0.00 01-JAN-00:10 10969.14 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 6081.29 0.00 01-JAN-00:10 10969.14 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 28912.78 0.00 10-APR-17:30 13856.25 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 25040.93 0.00 10-APR-17:30 13856.25 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 25040.93 0.00 10-APR-17:30 13856.25 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3871.85 0.00 01-JAN-00:10 5777.93 29-JUN-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3871.85 0.00 01-JAN-00:10 5777.93 29-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 39434.86 0.00 10-APR-09:00 18392.08 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 33617.02 0.00 10-APR-09:00 18392.08 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 33617.02 0.00 10-APR-09:00 18392.08 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5817.83 0.00 01-JAN-00:10 7318.70 28-JUN-10:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5817.83 0.00 01-JAN-00:10 7318.70 28-JUN-10:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 55772.71 0.00 11-APR-10:20 26380.19 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 50126.57 0.00 11-APR-10:20 26380.19 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 50126.57 0.00 11-APR-10:20 26380.19 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5646.14 0.00 01-JAN-00:10 8068.57 29-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5646.14 0.00 01-JAN-00:10 8068.57 29-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 54071.92 0.00 26-MAR-13:00 26335.85 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 47360.91 0.00 26-MAR-13:00 26335.85 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 47360.91 0.00 26-MAR-13:00 26335.85 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 6711.01 0.00 01-JAN-00:10 8706.43 30-JUN-15:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 6711.01 0.00 01-JAN-00:10 8706.43 30-JUN-15:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 54767.47 0.00 08-FEB-14:40 26331.29 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 47692.51 0.00 08-FEB-14:40 26331.29 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 47692.51 0.00 08-FEB-14:40 26331.29 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 7074.96 0.00 01-JAN-00:10 12159.32 29-JUN-17:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 7074.96 0.00 01-JAN-00:10 12159.32 29-JUN-17:30
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 45275.23 0.00 11-APR-15:10 21844.68 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 41397.12 0.00 11-APR-15:10 21844.68 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 41397.12 0.00 11-APR-15:10 21844.68 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3878.11 0.00 01-JAN-00:10 6941.99 29-JUN-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 3878.11 0.00 01-JAN-00:10 6941.99 29-JUN-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 43274.22 0.00 26-MAR-13:40 21784.38 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 38479.28 0.00 26-MAR-13:40 21784.38 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 38479.28 0.00 26-MAR-13:40 21784.38 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4794.94 0.00 01-JAN-00:10 6912.83 29-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4794.94 0.00 01-JAN-00:10 6912.83 29-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 56471.24 0.00 19-MAR-16:30 26381.15 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 50442.72 0.00 19-MAR-16:30 26381.15 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 50442.72 0.00 19-MAR-16:30 26381.15 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 6028.52 0.00 01-JAN-00:10 12001.75 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 6028.52 0.00 01-JAN-00:10 12001.75 30-JUN-18:10
PlantLoopHeatingDemand:Facility 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
PlantLoopHeatingDemand:Plant 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
EnergyTransfer:HVAC 802339.69 0.00 24-APR-01:20 372137.61 06-JAN-05:00
CoolingCoils:EnergyTransfer 133923.06 0.00 01-JAN-00:10 211452.60 29-JUN-18:10
HeatingCoils:EnergyTransfer 668416.62 0.00 11-APR-15:40 372137.61 06-JAN-05:00
EnergyTransfer:Plant 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
WaterSystems:EnergyTransfer 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 161877.61 1136.34 18-AUG-03:00 42374.11 26-FEB-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 47072.516 -555.68 0.000 0.000 3094.807 3361.146 10464.601 8589.652 0.000 191.932 0.000 0.000 -9837.01 0.000 -39646.30 -16618.76
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 37967.899 -353.81 0.000 0.000 3089.975 3361.146 10464.601 4319.195 0.000 180.173 0.000 0.000 -3916.70 0.000 -36827.69 -14390.03
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 46734.502 -523.18 0.000 0.000 3094.159 3361.146 10464.601 8438.919 0.000 191.932 0.000 0.000 -9663.91 0.000 -39675.94 -16663.10
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 50285.720 -433.99 0.000 0.000 3098.960 3361.146 10464.601 5529.520 0.000 191.936 0.000 0.000 -10600.74 0.000 -39577.48 -17542.33
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 41385.883 -248.83 0.000 0.000 3096.384 3361.146 10464.601 1001.093 0.000 180.180 0.000 0.000 -4512.65 0.000 -36739.96 -15248.73
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 49988.180 -400.03 0.000 0.000 3098.387 3361.146 10464.601 5324.473 0.000 191.932 0.000 0.000 -10372.63 0.000 -39612.24 -17640.31
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 31003.155 -641.36 0.000 0.000 3076.596 3361.146 10464.601 8474.785 0.000 135.732 0.000 0.000 -10106.92 0.000 -26427.40 -12280.25
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 22081.543 -444.32 0.000 0.000 3068.122 3361.146 10464.601 4262.267 0.000 124.046 0.000 0.000 -4025.17 0.000 -23611.91 -10389.19
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 30718.639 -620.09 0.000 0.000 3077.191 3361.146 10464.601 8323.451 0.000 135.732 0.000 0.000 -9918.80 0.000 -26443.53 -12272.34
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 33856.409 -506.43 0.000 0.000 3081.456 3361.146 10464.601 5451.988 0.000 135.732 0.000 0.000 -10890.50 0.000 -26373.35 -13006.31
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 25040.863 -322.44 0.000 0.000 3076.100 3361.146 10464.601 977.433 0.000 124.046 0.000 0.000 -4637.04 0.000 -23542.67 -10992.66
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 33616.932 -484.49 0.000 0.000 3082.353 3361.146 10464.601 5245.520 0.000 135.732 0.000 0.000 -10646.73 0.000 -26392.19 -13049.55
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 50126.449 -470.20 0.000 0.000 3092.937 3361.146 10464.601 5257.113 0.000 189.561 0.000 0.000 -10614.10 0.000 -39722.41 -16509.18
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 47360.778 -558.87 0.000 0.000 3089.690 3361.146 10464.601 8347.426 0.000 189.561 0.000 0.000 -9871.81 0.000 -39773.36 -16457.05
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 47692.374 -589.17 0.000 0.000 3090.040 3361.146 10464.601 8491.599 0.000 189.561 0.000 0.000 -10057.22 0.000 -39744.92 -16412.36
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 41397.027 -322.96 0.000 0.000 3089.609 3361.146 10464.601 981.615 0.000 177.954 0.000 0.000 -4618.34 0.000 -36858.17 -14117.37
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 38479.174 -399.31 0.000 0.000 3084.721 3361.146 10464.601 4269.726 0.000 177.946 0.000 0.000 -4000.07 0.000 -36926.20 -14116.16
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 50442.592 -502.03 0.000 0.000 3093.152 3361.146 10464.601 5455.464 0.000 189.568 0.000 0.000 -10853.87 0.000 -39692.07 -16432.20
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12109.270 388783.085 0.000 0.000 0.000 -400892.36 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 18785.464 113211.925 0.000 0.000 0.000 -131997.39 -0.10
Total Facility 0.000 0.000 725250.636 -8377.18 0.000 0.000 55574.640 60500.637 188362.826 98741.239 0.000 33927.992 501995.010 0.000 -149144.18 0.000 -1150477.52 -264137.98


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 29-JUN-17:19 0.00 0.00 0.00 -1.0 0.00 0.00 263.17 733.36 1664.02 7447.69 0.00 1754.76 107.37 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 30-JUN-14:00 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 141.03 1091.85 1913.14 0.00 1736.47 1504.32 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 30-JUN-10:00 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 141.03 1089.80 5914.71 0.00 1515.39 0.00 0.00 0.00 0.00 0.00 -305.1
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 29-JUN-17:30 0.00 0.00 0.00 -1.0 0.00 0.00 263.17 733.36 1664.02 7434.43 0.00 1738.63 0.00 0.00 0.00 0.00 0.00 -295.9
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUN-18:34 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 987.22 1724.99 1091.16 0.00 1441.14 633.07 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUN-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 987.22 1724.99 1916.95 0.00 1640.02 666.17 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 29-JUN-17:19 0.00 0.00 0.00 -0.9 0.00 0.00 263.17 733.36 1664.02 7435.39 0.00 1215.80 0.00 0.00 0.00 0.00 0.00 -2.8
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUN-18:10 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 987.22 1724.99 591.73 0.00 993.33 1234.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-10:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 141.03 1121.12 6897.94 0.00 374.59 0.00 0.00 0.00 0.00 0.00 -413.0
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 30-JUN-18:15 0.00 0.00 0.00 -0.9 0.00 0.00 426.77 987.22 1724.99 7322.57 0.00 721.16 0.00 0.00 0.00 0.00 0.00 -212.6
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUN-18:30 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 987.22 1724.99 1092.26 0.00 934.19 612.51 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 28-JUN-09:05 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 141.03 1096.02 5357.77 0.00 570.75 38.38 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUN-18:10 0.00 0.00 0.00 -0.7 0.00 0.00 426.77 987.22 1724.99 1907.78 0.00 1633.35 1389.86 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 30-JUN-14:00 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 141.03 1091.85 3369.83 0.00 1873.32 2116.24 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 29-JUN-17:30 0.00 0.00 0.00 -1.0 0.00 0.00 263.17 733.36 1664.02 7175.04 0.00 1732.24 591.54 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUN-18:34 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 987.22 1724.99 1085.40 0.00 1434.91 1282.73 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUN-18:10 0.00 0.00 0.00 -0.6 0.00 0.00 426.77 987.22 1724.99 589.32 0.00 1520.83 1664.97 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 30-JUN-18:15 0.00 0.00 0.00 -1.0 0.00 0.00 426.77 987.22 1724.99 7293.98 0.00 1046.51 522.30 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 29-JUN-18:10 0.00 0.00 0.00 -12.7 0.00 0.00 7681.78 17769.97 31049.73 49349.46 0.00 59381.44 28927.08 0.00 0.00 0.00 -42340.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 26150.29 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4482.2 0.00 -17210.6 -6041.3
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 21599.66 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1813.4 0.00 -15876.5 -5493.5
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 26172.43 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4476.4 0.00 -17210.6 -6069.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 26220.02 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4477.2 0.00 -17210.6 -6116.0
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 21679.20 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1809.1 0.00 -15876.5 -5577.3
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 06-JAN-04:00 0.00 0.00 26234.76 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4471.6 0.00 -17210.6 -6136.4
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 18324.49 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4588.8 0.00 -10937.3 -4382.1
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 13782.10 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1858.0 0.00 -9602.6 -3905.3
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 18336.58 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4568.9 0.00 -10937.3 -4414.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 18387.49 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4574.2 0.00 -10937.3 -4459.7
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 13856.43 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1843.9 0.00 -9602.6 -3993.7
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 06-JAN-04:00 0.00 0.00 18392.24 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4554.4 0.00 -10937.3 -4484.3
LIVING_UNIT3_BACKROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 26380.34 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4549.0 0.00 -17226.0 -6189.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 26335.99 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4568.7 0.00 -17226.0 -6125.1
LIVING_UNIT1_FRONTROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 26331.44 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4595.8 0.00 -17226.0 -6093.4
LIVING_UNIT2_BACKROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 21844.84 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1840.2 0.00 -15890.7 -5697.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 21784.54 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -1859.5 0.00 -15890.7 -5618.1
LIVING_UNIT1_BACKROW_TOPFLOOR 06-JAN-04:00 0.00 0.00 26381.30 0.00 0.00 0.00 526.24 225.65 831.88 0.00 0.00 0.00 0.00 0.00 -4576.1 0.00 -17226.0 -6163.0
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JAN-04:00 0.00 0.00 398194.14 0.00 0.00 0.00 9472.36 4061.71 14973.78 0.00 0.00 10869.17 73160.17 0.00 -65507.3 0.00 -445224.1 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1321.9625 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1321.9625 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1093.8267 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1093.8267 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1322.4772 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.4772 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1322.1752 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.1752 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1093.8837 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1093.8837 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1322.3828 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.3828 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 944.5300 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.5300 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 716.7784 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 716.7784 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 944.5645 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.5645 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 944.6181 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.6181 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 716.7227 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 716.7227 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 944.3656 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.3656 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1335.7898 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.7898 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1107.5893 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1107.5893 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1335.4943 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.4943 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1335.7255 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.7255 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1107.4217 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1107.4217 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1335.2238 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.2238 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1321.9625 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1321.9625 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1093.8267 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1093.8267 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1322.4772 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.4772 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1322.1752 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.1752 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1093.8837 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1093.8837 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1322.3828 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1322.3828 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 944.5300 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.5300 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 716.7784 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 716.7784 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 944.5645 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.5645 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 944.6181 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.6181 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 716.7227 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 716.7227 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 944.3656 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 944.3656 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1335.7898 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.7898 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1107.5893 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1107.5893 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1335.4943 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.4943 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1335.7255 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.7255 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1107.4217 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1107.4217 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1335.2238 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 1335.2238 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1321.9625 1321.9625 1321.9625 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1093.8267 1093.8267 1093.8267 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.4772 1322.4772 1322.4772 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.1752 1322.1752 1322.1752 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1093.8837 1093.8837 1093.8837 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.3828 1322.3828 1322.3828 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.5300 944.5300 944.5300 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 716.7784 716.7784 716.7784 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.5645 944.5645 944.5645 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.6181 944.6181 944.6181 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 716.7227 716.7227 716.7227 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.3656 944.3656 944.3656 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.2238 1335.2238 1335.2238 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.4943 1335.4943 1335.4943 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.7898 1335.7898 1335.7898 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1107.4217 1107.4217 1107.4217 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1107.5893 1107.5893 1107.5893 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.7255 1335.7255 1335.7255 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1321.9625 1321.9625 1321.9625 1321.9625 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1093.8267 1093.8267 1093.8267 1093.8267 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1322.4772 1322.4772 1322.4772 1322.4772 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1322.1752 1322.1752 1322.1752 1322.1752 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1093.8837 1093.8837 1093.8837 1093.8837 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1322.3828 1322.3828 1322.3828 1322.3828 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 944.5300 944.5300 944.5300 944.5300 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 716.7784 716.7784 716.7784 716.7784 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 944.5645 944.5645 944.5645 944.5645 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 944.6181 944.6181 944.6181 944.6181 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 716.7227 716.7227 716.7227 716.7227 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 944.3656 944.3656 944.3656 944.3656 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1335.7898 1335.7898 1335.7898 1335.7898 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1107.5893 1107.5893 1107.5893 1107.5893 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1335.4943 1335.4943 1335.4943 1335.4943 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1335.7255 1335.7255 1335.7255 1335.7255 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1107.4217 1107.4217 1107.4217 1107.4217 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1335.2238 1335.2238 1335.2238 1335.2238 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1321.9625 1321.9625 1321.9625 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1093.8267 1093.8267 1093.8267 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.4772 1322.4772 1322.4772 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.1752 1322.1752 1322.1752 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1093.8837 1093.8837 1093.8837 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1322.3828 1322.3828 1322.3828 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.5300 944.5300 944.5300 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 716.7784 716.7784 716.7784 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.5645 944.5645 944.5645 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.6181 944.6181 944.6181 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 716.7227 716.7227 716.7227 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 944.3656 944.3656 944.3656 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.2238 1335.2238 1335.2238 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.4943 1335.4943 1335.4943 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.7898 1335.7898 1335.7898 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1107.4217 1107.4217 1107.4217 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1107.5893 1107.5893 1107.5893 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 1335.7255 1335.7255 1335.7255 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1321.9625 1321.9625 1321.9625 1321.9625 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1093.8267 1093.8267 1093.8267 1093.8267 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1322.4772 1322.4772 1322.4772 1322.4772 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1322.1752 1322.1752 1322.1752 1322.1752 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1093.8837 1093.8837 1093.8837 1093.8837 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1322.3828 1322.3828 1322.3828 1322.3828 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 944.5300 944.5300 944.5300 944.5300 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 716.7784 716.7784 716.7784 716.7784 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 944.5645 944.5645 944.5645 944.5645 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 944.6181 944.6181 944.6181 944.6181 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 716.7227 716.7227 716.7227 716.7227 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 944.3656 944.3656 944.3656 944.3656 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1335.7898 1335.7898 1335.7898 1335.7898 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1107.5893 1107.5893 1107.5893 1107.5893 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1335.4943 1335.4943 1335.4943 1335.4943 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1335.7255 1335.7255 1335.7255 1335.7255 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1107.4217 1107.4217 1107.4217 1107.4217 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1335.2238 1335.2238 1335.2238 1335.2238 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Sec1.1A-General Information

Data
Weather File ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [ft2] 39005.22
Principal Heating Source Electricity


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 141135.36 112667.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 8807.00 16255.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 17719.17 5771.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 5068.29 578.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 18106.99 7636.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 70168.57 61568.92 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 1213288.49
Natural Gas 0.00 0.00
Additional 0.00 0.00
Total 301503.54 1213288.49


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.45
Space Heating 3.62
Space Cooling 0.23
Fans (All) 0.59
Service Water Heating 1.80
Receptacle Equipment 2.26
Miscellaneous (All) 9.11
Subtotal 9.11


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 0.00
Service Water Heating 0.00
Miscellaneous (All) 0.00
Subtotal 0.00


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 4.99
Space Heating 39.72
Space Cooling 2.48
Fans (All) 6.52
Service Water Heating 19.75
Receptacle Equipment 24.85
Miscellaneous 1.70


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 3134. 8760.
CLOTHESWASHER_FLOW_SCH 3692. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:07:29

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 281.802 281.802
February 0.000 0.000 660.833 194.436 194.436
March 10.667 0.192 709.806 138.679 138.679
April 74.083 2.962 571.333 50.511 50.511
May 281.244 12.554 283.750 21.319 21.319
June 411.389 21.162 131.306 22.892 22.892
July 535.986 28.922 56.722 29.421 29.421
August 415.708 20.581 84.417 21.579 21.579
September 198.383 6.884 357.000 15.329 15.329
October 56.472 1.810 629.667 40.555 40.555
November 0.000 0.000 706.667 100.166 100.166
December 0.000 0.000 744.000 260.255 260.255
           
Annual Sum or Average 1983.933 95.068 5679.500 1176.945 1176.945
Minimum of Months 0.000 0.000 56.722 15.329 15.329
Maximum of Months 535.986 28.922 744.000 281.802 281.802



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 232.033 232.033
February 0.000 0.000 671.333 160.232 160.232
March 0.000 0.000 730.667 114.308 114.308
April 53.000 1.030 587.944 39.466 39.466
May 268.947 7.169 274.917 13.779 13.779
June 427.275 14.496 94.556 15.456 15.456
July 562.142 20.623 40.917 20.852 20.852
August 457.917 14.737 58.000 15.257 15.257
September 206.553 4.275 315.667 10.120 10.120
October 56.528 1.142 623.556 31.043 31.043
November 0.000 0.000 705.250 79.823 79.823
December 0.000 0.000 744.000 213.197 213.197
           
Annual Sum or Average 2032.361 63.472 5590.806 945.566 945.566
Minimum of Months 0.000 0.000 40.917 10.120 10.120
Maximum of Months 562.142 20.623 744.000 232.033 232.033



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 282.400 282.400
February 0.000 0.000 672.000 194.941 194.941
March 0.000 0.000 733.917 137.758 137.758
April 83.458 1.933 565.319 47.698 47.698
May 293.444 10.695 260.611 18.681 18.681
June 455.564 21.387 100.417 22.803 22.803
July 568.172 28.921 52.167 29.411 29.411
August 446.153 19.744 75.250 20.680 20.680
September 221.319 6.169 346.750 14.362 14.362
October 56.931 1.452 632.444 40.081 40.081
November 0.000 0.000 708.167 100.120 100.120
December 0.000 0.000 744.000 260.935 260.935
           
Annual Sum or Average 2125.042 90.301 5635.042 1169.869 1169.869
Minimum of Months 0.000 0.000 52.167 14.362 14.362
Maximum of Months 568.172 28.921 744.000 282.400 282.400



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 288.681 288.681
February 0.000 0.000 672.000 204.171 204.171
March 0.500 0.001 731.917 148.042 148.042
April 44.139 1.351 617.250 52.564 52.564
May 257.139 9.995 308.333 19.193 19.193
June 406.347 19.062 128.694 20.707 20.707
July 534.522 25.645 53.056 26.106 26.106
August 395.028 16.230 88.264 17.261 17.261
September 134.444 3.342 400.333 12.669 12.669
October 16.944 0.214 679.944 41.877 41.877
November 0.000 0.000 711.500 105.836 105.836
December 0.000 0.000 744.000 264.924 264.924
           
Annual Sum or Average 1789.064 75.840 5879.292 1202.032 1202.032
Minimum of Months 0.000 0.000 53.056 12.669 12.669
Maximum of Months 534.522 25.645 744.000 288.681 288.681



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 238.574 238.574
February 0.000 0.000 672.000 169.894 169.894
March 0.000 0.000 744.000 124.417 124.417
April 10.833 0.235 651.667 42.941 42.941
May 228.122 5.104 317.556 12.353 12.353
June 421.958 12.528 90.750 13.420 13.420
July 562.606 17.418 39.000 17.618 17.618
August 432.181 10.291 61.833 10.838 10.838
September 89.778 1.232 384.194 8.077 8.077
October 0.000 0.000 696.500 33.099 33.099
November 0.000 0.000 711.333 85.587 85.587
December 0.000 0.000 744.000 217.637 217.637
           
Annual Sum or Average 1745.478 46.808 5856.833 974.456 974.456
Minimum of Months 0.000 0.000 39.000 8.077 8.077
Maximum of Months 562.606 17.418 744.000 238.574 238.574



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 289.144 289.144
February 0.000 0.000 672.000 204.772 204.772
March 0.000 0.000 744.000 147.694 147.694
April 34.833 0.447 614.289 50.011 50.011
May 274.125 8.142 288.500 16.573 16.573
June 453.464 19.394 98.500 20.767 20.767
July 568.803 25.823 50.833 26.291 26.291
August 438.222 15.373 78.000 16.338 16.338
September 144.556 2.253 380.278 11.186 11.186
October 4.500 0.015 683.250 41.630 41.630
November 0.000 0.000 712.000 105.826 105.826
December 0.000 0.000 744.000 265.383 265.383
           
Annual Sum or Average 1918.503 71.447 5809.650 1195.615 1195.615
Minimum of Months 0.000 0.000 50.833 11.186 11.186
Maximum of Months 568.803 25.823 744.000 289.144 289.144



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 196.960 196.960
February 5.000 0.038 645.417 132.481 132.481
March 22.000 0.489 680.389 93.130 93.130
April 107.056 4.023 513.833 33.452 33.452
May 340.061 14.678 204.806 19.130 19.130
June 483.611 23.433 56.889 23.988 23.988
July 599.731 31.566 23.333 31.631 31.631
August 518.181 23.424 34.667 23.717 23.717
September 250.347 8.793 263.500 12.974 12.974
October 79.056 2.430 591.583 27.043 27.043
November 0.667 0.002 695.167 67.410 67.410
December 0.000 0.000 744.000 182.107 182.107
           
Annual Sum or Average 2405.708 108.876 5197.583 844.021 844.021
Minimum of Months 0.000 0.000 23.333 12.974 12.974
Maximum of Months 599.731 31.566 744.000 196.960 196.960



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 147.233 147.233
February 0.000 0.000 642.750 98.208 98.208
March 3.833 0.012 691.389 68.222 68.222
April 96.444 1.727 494.417 22.005 22.005
May 361.639 9.083 172.222 11.607 11.607
June 511.469 16.762 16.278 16.937 16.937
July 640.958 23.249 0.000 23.249 23.249
August 579.014 17.882 17.000 17.980 17.980
September 272.875 6.336 196.583 8.436 8.436
October 81.028 1.815 559.000 17.823 17.823
November 0.000 0.000 687.667 47.217 47.217
December 0.000 0.000 744.000 135.160 135.160
           
Annual Sum or Average 2547.261 76.866 4965.306 614.075 614.075
Minimum of Months 0.000 0.000 0.000 8.436 8.436
Maximum of Months 640.958 23.249 744.000 147.233 147.233



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 197.429 197.429
February 0.000 0.000 658.083 132.686 132.686
March 3.500 0.018 698.239 91.569 91.569
April 114.894 2.982 487.833 30.911 30.911
May 373.747 12.933 178.056 16.912 16.912
June 537.169 23.806 40.833 24.248 24.248
July 620.461 31.308 22.333 31.392 31.392
August 537.097 22.458 33.917 22.720 22.720
September 269.514 8.234 249.500 12.317 12.317
October 81.389 2.092 592.936 26.644 26.644
November 0.000 0.000 696.056 67.356 67.356
December 0.000 0.000 744.000 182.720 182.720
           
Annual Sum or Average 2537.772 103.832 5145.786 836.902 836.902
Minimum of Months 0.000 0.000 22.333 12.317 12.317
Maximum of Months 620.461 31.308 744.000 197.429 197.429



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 204.241 204.241
February 0.000 0.000 672.000 142.119 142.119
March 2.417 0.024 716.694 101.436 101.436
April 65.889 1.844 566.917 34.331 34.331
May 315.022 11.949 224.694 16.660 16.660
June 484.717 21.477 52.389 21.978 21.978
July 605.522 28.565 18.250 28.615 28.615
August 503.819 19.153 37.000 19.462 19.462
September 192.972 4.692 300.417 9.443 9.443
October 29.333 0.347 646.306 27.369 27.369
November 0.000 0.000 708.667 72.756 72.756
December 0.000 0.000 744.000 187.296 187.296
           
Annual Sum or Average 2199.692 88.050 5431.333 865.708 865.708
Minimum of Months 0.000 0.000 18.250 9.443 9.443
Maximum of Months 605.522 28.565 744.000 204.241 204.241



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 154.198 154.198
February 0.000 0.000 672.000 107.798 107.798
March 0.000 0.000 744.000 77.604 77.604
April 25.250 0.350 590.250 24.101 24.101
May 310.292 6.727 201.639 9.573 9.573
June 510.597 14.906 13.736 15.052 15.052
July 643.772 20.334 0.000 20.334 20.334
August 562.944 13.550 18.333 13.658 13.658
September 173.333 2.357 243.000 4.987 4.987
October 6.667 0.036 652.111 18.577 18.577
November 0.000 0.000 707.083 52.595 52.595
December 0.000 0.000 744.000 140.123 140.123
           
Annual Sum or Average 2232.856 58.261 5330.153 638.600 638.600
Minimum of Months 0.000 0.000 0.000 4.987 4.987
Maximum of Months 643.772 20.334 744.000 154.198 154.198



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 204.589 204.589
February 0.000 0.000 672.000 142.520 142.520
March 0.000 0.000 744.000 101.015 101.015
April 61.917 0.846 555.472 31.822 31.822
May 345.969 10.208 190.194 14.420 14.420
June 539.658 21.955 39.250 22.375 22.375
July 622.992 28.447 21.667 28.523 28.523
August 530.333 18.293 35.167 18.569 18.569
September 220.736 3.838 270.500 8.390 8.390
October 14.917 0.086 655.250 27.123 27.123
November 0.000 0.000 708.583 72.725 72.725
December 0.000 0.000 744.000 187.706 187.706
           
Annual Sum or Average 2336.522 83.673 5380.083 859.778 859.778
Minimum of Months 0.000 0.000 21.667 8.390 8.390
Maximum of Months 622.992 28.447 744.000 204.589 204.589



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 285.827 285.827
February 0.000 0.000 664.917 197.681 197.681
March 7.500 0.109 712.167 140.768 140.768
April 69.917 2.749 569.083 50.500 50.500
May 291.250 13.352 268.625 21.670 21.670
June 432.458 22.964 112.083 24.417 24.417
July 561.403 31.482 47.639 31.860 31.860
August 443.903 22.114 69.833 22.972 22.972
September 201.247 6.901 342.083 15.071 15.071
October 53.028 1.563 628.333 40.891 40.891
November 0.000 0.000 708.000 102.151 102.151
December 0.000 0.000 744.000 263.890 263.890
           
Annual Sum or Average 2060.706 101.234 5610.764 1197.699 1197.699
Minimum of Months 0.000 0.000 47.639 15.071 15.071
Maximum of Months 561.403 31.482 744.000 285.827 285.827



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 235.772 235.772
February 0.000 0.000 672.000 163.088 163.088
March 0.000 0.000 735.917 116.124 116.124
April 50.500 0.982 583.556 39.432 39.432
May 283.728 8.171 259.639 14.283 14.283
June 455.014 16.504 73.306 17.227 17.227
July 586.636 23.425 32.500 23.571 23.571
August 492.083 16.588 44.875 17.009 17.009
September 211.514 4.489 298.222 10.025 10.025
October 55.278 0.992 625.222 31.319 31.319
November 0.000 0.000 709.667 81.542 81.542
December 0.000 0.000 744.000 216.623 216.623
           
Annual Sum or Average 2134.753 71.150 5522.903 966.015 966.015
Minimum of Months 0.000 0.000 32.500 10.025 10.025
Maximum of Months 586.636 23.425 744.000 235.772 235.772



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 286.309 286.309
February 0.000 0.000 672.000 198.134 198.134
March 0.000 0.000 735.833 140.066 140.066
April 79.028 1.753 565.528 47.849 47.849
May 303.722 11.491 249.722 19.070 19.070
June 475.314 23.088 82.917 24.239 24.239
July 593.144 31.395 44.667 31.770 31.770
August 472.731 21.212 64.083 22.004 22.004
September 225.106 6.150 328.417 14.059 14.059
October 54.319 1.251 632.667 40.507 40.507
November 0.000 0.000 710.333 102.074 102.074
December 0.000 0.000 744.000 264.425 264.425
           
Annual Sum or Average 2203.364 96.341 5574.167 1190.507 1190.507
Minimum of Months 0.000 0.000 44.667 14.059 14.059
Maximum of Months 593.144 31.395 744.000 286.309 286.309



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 291.672 291.672
February 0.000 0.000 672.000 206.030 206.030
March 0.000 0.000 730.000 148.509 148.509
April 48.000 1.557 601.750 52.205 52.205
May 275.167 11.720 287.208 20.354 20.354
June 431.111 21.783 109.778 23.157 23.157
July 562.017 29.533 45.250 29.878 29.878
August 429.778 19.060 71.778 19.941 19.941
September 152.583 4.001 375.556 12.910 12.910
October 17.750 0.221 675.639 42.201 42.201
November 0.000 0.000 711.667 107.150 107.150
December 0.000 0.000 744.000 267.881 267.881
           
Annual Sum or Average 1916.406 87.875 5768.625 1221.888 1221.888
Minimum of Months 0.000 0.000 45.250 12.910 12.910
Maximum of Months 562.017 29.533 744.000 291.672 291.672



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 241.411 241.411
February 0.000 0.000 672.000 171.380 171.380
March 0.000 0.000 744.000 124.406 124.406
April 21.000 0.335 631.333 42.146 42.146
May 258.883 6.765 287.417 13.327 13.327
June 453.500 15.320 69.667 15.987 15.987
July 590.397 21.428 29.167 21.551 21.551
August 475.778 13.415 47.417 13.858 13.858
September 126.000 1.877 349.500 8.243 8.243
October 3.167 0.005 685.472 33.252 33.252
November 0.000 0.000 711.333 86.683 86.683
December 0.000 0.000 744.000 220.478 220.478
           
Annual Sum or Average 1928.725 59.145 5715.306 992.722 992.722
Minimum of Months 0.000 0.000 29.167 8.243 8.243
Maximum of Months 590.397 21.428 744.000 241.411 241.411



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 291.991 291.991
February 0.000 0.000 672.000 206.494 206.494
March 0.000 0.000 744.000 148.245 148.245
April 36.861 0.622 602.972 49.706 49.706
May 291.611 9.801 267.000 17.672 17.672
June 477.636 21.885 81.167 22.991 22.991
July 594.444 29.466 43.333 29.819 29.819
August 466.300 18.093 65.125 18.903 18.903
September 165.083 2.961 356.833 11.467 11.467
October 6.500 0.028 680.917 41.995 41.995
November 0.000 0.000 712.167 107.098 107.098
December 0.000 0.000 744.000 268.215 268.215
           
Annual Sum or Average 2038.436 82.856 5713.514 1214.596 1214.596
Minimum of Months 0.000 0.000 43.333 11.467 11.467
Maximum of Months 594.444 29.466 744.000 291.991 291.991



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7904.06 0.00 0.00
February 8102.22 0.00 0.00
March 6915.79 0.00 0.00
April 3792.92 0.00 0.00
May 882.76 0.00 0.00
June 205.26 0.00 0.00
July 65.60 0.00 0.00
August 124.51 0.00 0.00
September 977.46 0.00 0.00
October 3327.49 0.00 0.00
November 6705.54 0.00 0.00
December 8357.02 0.00 0.00
       
Annual Sum or Average 3923.81 0.00 0.00
Minimum of Months 65.60 0.00 0.00
Maximum of Months 8357.02 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6465.92 0.00 0.00
February 6665.39 0.00 0.00
March 5720.65 0.00 0.00
April 3069.74 0.00 0.00
May 663.26 0.00 0.00
June 109.41 0.00 0.00
July 30.37 0.00 0.00
August 63.36 0.00 0.00
September 671.94 0.00 0.00
October 2561.70 0.00 0.00
November 5313.43 0.00 0.00
December 6785.04 0.00 0.00
       
Annual Sum or Average 3157.72 0.00 0.00
Minimum of Months 30.37 0.00 0.00
Maximum of Months 6785.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7928.97 0.00 0.00
February 8154.23 0.00 0.00
March 6897.00 0.00 0.00
April 3614.91 0.00 0.00
May 787.40 0.00 0.00
June 163.18 0.00 0.00
July 64.00 0.00 0.00
August 116.14 0.00 0.00
September 938.28 0.00 0.00
October 3318.84 0.00 0.00
November 6702.45 0.00 0.00
December 8384.08 0.00 0.00
       
Annual Sum or Average 3899.38 0.00 0.00
Minimum of Months 64.00 0.00 0.00
Maximum of Months 8384.08 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8247.54 0.00 0.00
February 8798.72 0.00 0.00
March 7580.17 0.00 0.00
April 4159.26 0.00 0.00
May 937.41 0.00 0.00
June 194.18 0.00 0.00
July 60.64 0.00 0.00
August 128.75 0.00 0.00
September 1092.32 0.00 0.00
October 3635.84 0.00 0.00
November 7177.74 0.00 0.00
December 8594.82 0.00 0.00
       
Annual Sum or Average 4191.26 0.00 0.00
Minimum of Months 60.64 0.00 0.00
Maximum of Months 8798.72 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6801.42 0.00 0.00
February 7372.83 0.00 0.00
March 6442.24 0.00 0.00
April 3508.56 0.00 0.00
May 741.07 0.00 0.00
June 100.96 0.00 0.00
July 26.54 0.00 0.00
August 66.90 0.00 0.00
September 797.98 0.00 0.00
October 2904.57 0.00 0.00
November 5793.83 0.00 0.00
December 7016.56 0.00 0.00
       
Annual Sum or Average 3442.35 0.00 0.00
Minimum of Months 26.54 0.00 0.00
Maximum of Months 7372.83 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8271.97 0.00 0.00
February 8862.30 0.00 0.00
March 7599.59 0.00 0.00
April 3989.19 0.00 0.00
May 838.99 0.00 0.00
June 158.12 0.00 0.00
July 61.25 0.00 0.00
August 119.69 0.00 0.00
September 1027.51 0.00 0.00
October 3634.56 0.00 0.00
November 7178.41 0.00 0.00
December 8615.86 0.00 0.00
       
Annual Sum or Average 4170.25 0.00 0.00
Minimum of Months 61.25 0.00 0.00
Maximum of Months 8862.30 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5429.77 0.00 0.00
February 5364.66 0.00 0.00
March 4520.28 0.00 0.00
April 2299.48 0.00 0.00
May 432.22 0.00 0.00
June 59.22 0.00 0.00
July 8.50 0.00 0.00
August 33.49 0.00 0.00
September 471.84 0.00 0.00
October 2074.94 0.00 0.00
November 4454.75 0.00 0.00
December 5774.44 0.00 0.00
       
Annual Sum or Average 2562.33 0.00 0.00
Minimum of Months 8.50 0.00 0.00
Maximum of Months 5774.44 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3994.75 0.00 0.00
February 3915.96 0.00 0.00
March 3294.35 0.00 0.00
April 1568.16 0.00 0.00
May 239.38 0.00 0.00
June 16.35 0.00 0.00
July 0.00 0.00 0.00
August 10.15 0.00 0.00
September 235.24 0.00 0.00
October 1333.15 0.00 0.00
November 3076.77 0.00 0.00
December 4208.71 0.00 0.00
       
Annual Sum or Average 1813.80 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4208.71 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5449.40 0.00 0.00
February 5386.33 0.00 0.00
March 4462.09 0.00 0.00
April 2150.21 0.00 0.00
May 372.68 0.00 0.00
June 45.55 0.00 0.00
July 10.93 0.00 0.00
August 29.50 0.00 0.00
September 453.97 0.00 0.00
October 2068.76 0.00 0.00
November 4449.39 0.00 0.00
December 5798.66 0.00 0.00
       
Annual Sum or Average 2541.76 0.00 0.00
Minimum of Months 10.93 0.00 0.00
Maximum of Months 5798.66 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5778.57 0.00 0.00
February 6022.06 0.00 0.00
March 5112.14 0.00 0.00
April 2590.49 0.00 0.00
May 462.88 0.00 0.00
June 52.64 0.00 0.00
July 6.57 0.00 0.00
August 35.63 0.00 0.00
September 543.00 0.00 0.00
October 2320.12 0.00 0.00
November 4894.49 0.00 0.00
December 6025.18 0.00 0.00
       
Annual Sum or Average 2802.77 0.00 0.00
Minimum of Months 6.57 0.00 0.00
Maximum of Months 6025.18 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4333.45 0.00 0.00
February 4587.04 0.00 0.00
March 3947.44 0.00 0.00
April 1900.57 0.00 0.00
May 274.96 0.00 0.00
June 13.15 0.00 0.00
July 0.00 0.00 0.00
August 11.25 0.00 0.00
September 297.10 0.00 0.00
October 1591.44 0.00 0.00
November 3517.17 0.00 0.00
December 4452.15 0.00 0.00
       
Annual Sum or Average 2063.59 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4587.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5798.00 0.00 0.00
February 6069.87 0.00 0.00
March 5113.09 0.00 0.00
April 2426.39 0.00 0.00
May 395.83 0.00 0.00
June 43.15 0.00 0.00
July 9.96 0.00 0.00
August 31.13 0.00 0.00
September 506.86 0.00 0.00
October 2321.63 0.00 0.00
November 4891.62 0.00 0.00
December 6044.94 0.00 0.00
       
Annual Sum or Average 2786.71 0.00 0.00
Minimum of Months 9.96 0.00 0.00
Maximum of Months 6069.87 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8041.57 0.00 0.00
February 8275.09 0.00 0.00
March 7041.12 0.00 0.00
April 3811.83 0.00 0.00
May 836.45 0.00 0.00
June 170.28 0.00 0.00
July 50.32 0.00 0.00
August 106.23 0.00 0.00
September 946.12 0.00 0.00
October 3381.36 0.00 0.00
November 6854.99 0.00 0.00
December 8492.30 0.00 0.00
       
Annual Sum or Average 3977.07 0.00 0.00
Minimum of Months 50.32 0.00 0.00
Maximum of Months 8492.30 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6590.13 0.00 0.00
February 6813.93 0.00 0.00
March 5822.26 0.00 0.00
April 3070.59 0.00 0.00
May 611.69 0.00 0.00
June 80.61 0.00 0.00
July 19.84 0.00 0.00
August 50.62 0.00 0.00
September 637.26 0.00 0.00
October 2599.69 0.00 0.00
November 5441.14 0.00 0.00
December 6910.13 0.00 0.00
       
Annual Sum or Average 3201.13 0.00 0.00
Minimum of Months 19.84 0.00 0.00
Maximum of Months 6910.13 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8064.36 0.00 0.00
February 8324.60 0.00 0.00
March 7027.55 0.00 0.00
April 3637.12 0.00 0.00
May 741.35 0.00 0.00
June 130.17 0.00 0.00
July 49.55 0.00 0.00
August 97.35 0.00 0.00
September 903.97 0.00 0.00
October 3374.53 0.00 0.00
November 6849.46 0.00 0.00
December 8515.52 0.00 0.00
       
Annual Sum or Average 3952.57 0.00 0.00
Minimum of Months 49.55 0.00 0.00
Maximum of Months 8515.52 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8337.03 0.00 0.00
February 8881.27 0.00 0.00
March 7589.19 0.00 0.00
April 4102.22 0.00 0.00
May 876.81 0.00 0.00
June 160.11 0.00 0.00
July 45.92 0.00 0.00
August 109.16 0.00 0.00
September 1042.84 0.00 0.00
October 3662.63 0.00 0.00
November 7273.69 0.00 0.00
December 8698.49 0.00 0.00
       
Annual Sum or Average 4205.31 0.00 0.00
Minimum of Months 45.92 0.00 0.00
Maximum of Months 8881.27 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6881.95 0.00 0.00
February 7426.86 0.00 0.00
March 6415.03 0.00 0.00
April 3413.30 0.00 0.00
May 665.79 0.00 0.00
June 73.78 0.00 0.00
July 16.77 0.00 0.00
August 53.48 0.00 0.00
September 741.53 0.00 0.00
October 2912.77 0.00 0.00
November 5871.51 0.00 0.00
December 7113.50 0.00 0.00
       
Annual Sum or Average 3443.27 0.00 0.00
Minimum of Months 16.77 0.00 0.00
Maximum of Months 7426.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN DX HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8357.04 0.00 0.00
February 8934.20 0.00 0.00
March 7607.37 0.00 0.00
April 3929.39 0.00 0.00
May 773.81 0.00 0.00
June 124.92 0.00 0.00
July 46.74 0.00 0.00
August 99.40 0.00 0.00
September 975.29 0.00 0.00
October 3661.97 0.00 0.00
November 7270.61 0.00 0.00
December 8716.08 0.00 0.00
       
Annual Sum or Average 4181.64 0.00 0.00
Minimum of Months 46.74 0.00 0.00
Maximum of Months 8934.20 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5248.06 0.00 0.00
February 2328.34 0.00 0.00
March 637.54 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 33.55 0.00 0.00
December 4042.54 0.00 0.00
       
Annual Sum or Average 1024.58 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5248.06 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4262.83 0.00 0.00
February 1880.65 0.00 0.00
March 509.63 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 23.40 0.00 0.00
December 3277.47 0.00 0.00
       
Annual Sum or Average 829.89 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4262.83 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5209.16 0.00 0.00
February 2270.28 0.00 0.00
March 617.57 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 33.10 0.00 0.00
December 3998.60 0.00 0.00
       
Annual Sum or Average 1011.36 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5209.16 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5679.26 0.00 0.00
February 2505.46 0.00 0.00
March 656.19 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 34.40 0.00 0.00
December 4395.46 0.00 0.00
       
Annual Sum or Average 1106.42 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5679.26 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4722.78 0.00 0.00
February 2077.56 0.00 0.00
March 529.18 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 24.21 0.00 0.00
December 3649.90 0.00 0.00
       
Annual Sum or Average 917.41 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4722.78 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5649.79 0.00 0.00
February 2444.25 0.00 0.00
March 630.97 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 33.83 0.00 0.00
December 4362.98 0.00 0.00
       
Annual Sum or Average 1094.27 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5649.79 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3510.71 0.00 0.00
February 1563.18 0.00 0.00
March 438.55 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 22.74 0.00 0.00
December 2717.54 0.00 0.00
       
Annual Sum or Average 688.01 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3510.71 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2539.86 0.00 0.00
February 1121.48 0.00 0.00
March 312.62 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 12.87 0.00 0.00
December 1960.97 0.00 0.00
       
Annual Sum or Average 495.90 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2539.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3478.78 0.00 0.00
February 1515.45 0.00 0.00
March 425.63 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 22.39 0.00 0.00
December 2675.44 0.00 0.00
       
Annual Sum or Average 676.93 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3478.78 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3880.08 0.00 0.00
February 1700.05 0.00 0.00
March 455.22 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 23.50 0.00 0.00
December 3013.57 0.00 0.00
       
Annual Sum or Average 756.50 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3880.08 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 2920.32 0.00 0.00
February 1270.20 0.00 0.00
March 329.66 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 13.56 0.00 0.00
December 2264.44 0.00 0.00
       
Annual Sum or Average 566.90 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 2920.32 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3851.89 0.00 0.00
February 1650.86 0.00 0.00
March 437.11 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 23.04 0.00 0.00
December 2979.28 0.00 0.00
       
Annual Sum or Average 745.84 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3851.89 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5318.80 0.00 0.00
February 2344.98 0.00 0.00
March 638.37 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 32.58 0.00 0.00
December 4095.48 0.00 0.00
       
Annual Sum or Average 1036.35 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5318.80 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4324.05 0.00 0.00
February 1893.90 0.00 0.00
March 510.21 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 22.49 0.00 0.00
December 3321.56 0.00 0.00
       
Annual Sum or Average 839.82 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4324.05 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5281.04 0.00 0.00
February 2292.07 0.00 0.00
March 620.61 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 32.18 0.00 0.00
December 4052.82 0.00 0.00
       
Annual Sum or Average 1023.92 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5281.04 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5692.53 0.00 0.00
February 2496.48 0.00 0.00
March 653.74 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 33.31 0.00 0.00
December 4403.17 0.00 0.00
       
Annual Sum or Average 1107.22 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5692.53 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4721.80 0.00 0.00
February 2061.18 0.00 0.00
March 526.32 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 23.19 0.00 0.00
December 3646.43 0.00 0.00
       
Annual Sum or Average 915.45 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4721.80 0.00 0.00



Table of Contents

Report: COILLOADS

For: SUPP HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5662.74 0.00 0.00
February 2440.89 0.00 0.00
March 631.60 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.00
June 0.00 0.00 0.00
July 0.00 0.00 0.00
August 0.00 0.00 0.00
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 32.83 0.00 0.00
December 4370.28 0.00 0.00
       
Annual Sum or Average 1095.71 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 5662.74 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.12
June 0.00 0.00 0.22
July 0.00 0.00 0.30
August 0.00 0.00 0.21
September 0.00 0.00 0.07
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.22
August 0.00 0.00 0.15
September 0.00 0.00 0.04
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.11
June 0.00 0.00 0.23
July 0.00 0.00 0.30
August 0.00 0.00 0.20
September 0.00 0.00 0.06
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.10
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.17
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.05
June 0.00 0.00 0.14
July 0.00 0.00 0.18
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.18



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.08
June 0.00 0.00 0.21
July 0.00 0.00 0.27
August 0.00 0.00 0.16
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.14
June 0.00 0.00 0.24
July 0.00 0.00 0.32
August 0.00 0.00 0.24
September 0.00 0.00 0.09
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.09
June 0.00 0.00 0.18
July 0.00 0.00 0.24
August 0.00 0.00 0.19
September 0.00 0.00 0.07
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.13
June 0.00 0.00 0.25
July 0.00 0.00 0.33
August 0.00 0.00 0.23
September 0.00 0.00 0.09
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.12
June 0.00 0.00 0.22
July 0.00 0.00 0.29
August 0.00 0.00 0.19
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.21
August 0.00 0.00 0.14
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.30
August 0.00 0.00 0.19
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.13
June 0.00 0.00 0.24
July 0.00 0.00 0.32
August 0.00 0.00 0.23
September 0.00 0.00 0.07
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.32



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.18
July 0.00 0.00 0.25
August 0.00 0.00 0.17
September 0.00 0.00 0.05
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.25



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.11
June 0.00 0.00 0.25
July 0.00 0.00 0.33
August 0.00 0.00 0.22
September 0.00 0.00 0.06
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.33



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.12
June 0.00 0.00 0.23
July 0.00 0.00 0.30
August 0.00 0.00 0.20
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.30



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.23
August 0.00 0.00 0.14
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.10
June 0.00 0.00 0.23
July 0.00 0.00 0.31
August 0.00 0.00 0.19
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.31



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.56 1165.78
March 0.00 0.00 1724.30 1283.79
April 0.00 0.00 1664.29 1199.14
May 0.00 0.00 1557.57 1159.66
June 0.00 0.00 1445.20 1041.28
July 0.00 0.00 1354.26 1008.28
August 0.00 0.00 1301.75 969.19
September 0.00 0.00 1315.27 947.66
October 0.00 0.00 1378.72 1026.50
November 0.00 0.00 1480.96 1067.05
December 0.00 0.00 1595.63 1187.99
         
Annual Sum or Average 0.00 0.00 1518.48 13311.30
Minimum of Months 0.00 0.00 1301.75 947.66
Maximum of Months 0.00 0.00 1733.56 1283.79



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.52 1283.95
April 0.00 0.00 1664.51 1199.30
May 0.00 0.00 1557.61 1159.68
June 0.00 0.00 1445.90 1041.79
July 0.00 0.00 1354.18 1008.22
August 0.00 0.00 1301.00 968.63
September 0.00 0.00 1312.80 945.89
October 0.00 0.00 1380.91 1028.13
November 0.00 0.00 1479.85 1066.25
December 0.00 0.00 1595.84 1188.15
         
Annual Sum or Average 0.00 0.00 1518.40 13310.65
Minimum of Months 0.00 0.00 1301.00 945.89
Maximum of Months 0.00 0.00 1733.42 1283.95



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.52 1283.95
April 0.00 0.00 1664.33 1199.17
May 0.00 0.00 1557.35 1159.49
June 0.00 0.00 1445.83 1041.74
July 0.00 0.00 1354.40 1008.39
August 0.00 0.00 1300.76 968.45
September 0.00 0.00 1312.97 946.01
October 0.00 0.00 1380.89 1028.11
November 0.00 0.00 1479.95 1066.32
December 0.00 0.00 1595.85 1188.15
         
Annual Sum or Average 0.00 0.00 1518.38 13310.45
Minimum of Months 0.00 0.00 1300.76 946.01
Maximum of Months 0.00 0.00 1733.42 1283.95



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.70 1199.43
May 0.00 0.00 1557.83 1159.85
June 0.00 0.00 1444.86 1041.04
July 0.00 0.00 1354.48 1008.44
August 0.00 0.00 1301.94 969.33
September 0.00 0.00 1315.16 947.58
October 0.00 0.00 1380.80 1028.04
November 0.00 0.00 1479.52 1066.01
December 0.00 0.00 1595.81 1188.13
         
Annual Sum or Average 0.00 0.00 1518.61 13312.47
Minimum of Months 0.00 0.00 1301.94 947.58
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1665.01 1199.66
May 0.00 0.00 1558.05 1160.01
June 0.00 0.00 1445.13 1041.23
July 0.00 0.00 1354.31 1008.32
August 0.00 0.00 1301.33 968.87
September 0.00 0.00 1315.65 947.94
October 0.00 0.00 1378.77 1026.53
November 0.00 0.00 1481.54 1067.46
December 0.00 0.00 1595.66 1188.01
         
Annual Sum or Average 0.00 0.00 1518.63 13312.66
Minimum of Months 0.00 0.00 1301.33 947.94
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.74 1199.47
May 0.00 0.00 1557.62 1159.69
June 0.00 0.00 1445.84 1041.74
July 0.00 0.00 1354.39 1008.38
August 0.00 0.00 1300.76 968.45
September 0.00 0.00 1315.33 947.71
October 0.00 0.00 1378.82 1026.57
November 0.00 0.00 1481.18 1067.21
December 0.00 0.00 1595.63 1187.99
         
Annual Sum or Average 0.00 0.00 1518.54 13311.83
Minimum of Months 0.00 0.00 1300.76 947.71
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.97 1166.05
March 0.00 0.00 1723.79 1283.41
April 0.00 0.00 1663.43 1198.52
May 0.00 0.00 1557.33 1159.48
June 0.00 0.00 1445.49 1041.49
July 0.00 0.00 1352.23 1006.77
August 0.00 0.00 1301.62 969.09
September 0.00 0.00 1312.98 946.01
October 0.00 0.00 1380.99 1028.19
November 0.00 0.00 1479.43 1065.94
December 0.00 0.00 1595.81 1188.13
         
Annual Sum or Average 0.00 0.00 1518.11 13308.07
Minimum of Months 0.00 0.00 1301.62 946.01
Maximum of Months 0.00 0.00 1733.97 1283.41



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1734.01 1166.08
March 0.00 0.00 1723.90 1283.49
April 0.00 0.00 1663.43 1198.52
May 0.00 0.00 1557.45 1159.56
June 0.00 0.00 1445.38 1041.41
July 0.00 0.00 1352.06 1006.65
August 0.00 0.00 1301.36 968.90
September 0.00 0.00 1312.16 945.42
October 0.00 0.00 1380.17 1027.57
November 0.00 0.00 1479.77 1066.19
December 0.00 0.00 1595.81 1188.13
         
Annual Sum or Average 0.00 0.00 1517.98 13306.92
Minimum of Months 0.00 0.00 1301.36 945.42
Maximum of Months 0.00 0.00 1734.01 1283.49



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.50 1165.74
March 0.00 0.00 1724.37 1283.84
April 0.00 0.00 1664.06 1198.98
May 0.00 0.00 1556.44 1158.81
June 0.00 0.00 1445.20 1041.28
July 0.00 0.00 1352.33 1006.85
August 0.00 0.00 1301.59 969.07
September 0.00 0.00 1312.80 945.88
October 0.00 0.00 1380.79 1028.04
November 0.00 0.00 1479.44 1065.96
December 0.00 0.00 1595.81 1188.13
         
Annual Sum or Average 0.00 0.00 1518.05 13307.56
Minimum of Months 0.00 0.00 1301.59 945.88
Maximum of Months 0.00 0.00 1733.50 1283.84



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.48 1283.92
April 0.00 0.00 1664.41 1199.22
May 0.00 0.00 1557.22 1159.39
June 0.00 0.00 1445.48 1041.49
July 0.00 0.00 1352.31 1006.83
August 0.00 0.00 1301.73 969.17
September 0.00 0.00 1313.17 946.16
October 0.00 0.00 1380.98 1028.18
November 0.00 0.00 1480.04 1066.38
December 0.00 0.00 1595.85 1188.15
         
Annual Sum or Average 0.00 0.00 1518.28 13309.57
Minimum of Months 0.00 0.00 1301.73 946.16
Maximum of Months 0.00 0.00 1733.42 1283.92



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.76 1199.48
May 0.00 0.00 1557.35 1159.49
June 0.00 0.00 1445.10 1041.21
July 0.00 0.00 1352.32 1006.84
August 0.00 0.00 1301.49 969.00
September 0.00 0.00 1312.53 945.69
October 0.00 0.00 1380.84 1028.08
November 0.00 0.00 1479.64 1066.10
December 0.00 0.00 1596.64 1188.74
         
Annual Sum or Average 0.00 0.00 1518.24 13309.24
Minimum of Months 0.00 0.00 1301.49 945.69
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.45 1199.25
May 0.00 0.00 1556.97 1159.21
June 0.00 0.00 1445.18 1041.26
July 0.00 0.00 1352.32 1006.84
August 0.00 0.00 1301.59 969.07
September 0.00 0.00 1312.93 945.98
October 0.00 0.00 1380.92 1028.13
November 0.00 0.00 1480.07 1066.40
December 0.00 0.00 1595.85 1188.15
         
Annual Sum or Average 0.00 0.00 1518.21 13308.92
Minimum of Months 0.00 0.00 1301.59 945.98
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.47 1165.72
March 0.00 0.00 1724.40 1283.86
April 0.00 0.00 1664.32 1199.16
May 0.00 0.00 1557.48 1159.59
June 0.00 0.00 1445.99 1041.85
July 0.00 0.00 1354.39 1008.38
August 0.00 0.00 1300.86 968.53
September 0.00 0.00 1312.93 945.98
October 0.00 0.00 1380.87 1028.09
November 0.00 0.00 1479.97 1066.33
December 0.00 0.00 1595.85 1188.15
         
Annual Sum or Average 0.00 0.00 1518.40 13310.65
Minimum of Months 0.00 0.00 1300.86 945.98
Maximum of Months 0.00 0.00 1733.47 1283.86



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.95
April 0.00 0.00 1664.52 1199.31
May 0.00 0.00 1557.48 1159.59
June 0.00 0.00 1445.78 1041.70
July 0.00 0.00 1352.16 1006.72
August 0.00 0.00 1302.58 969.81
September 0.00 0.00 1312.66 945.79
October 0.00 0.00 1380.84 1028.08
November 0.00 0.00 1479.86 1066.25
December 0.00 0.00 1595.84 1188.15
         
Annual Sum or Average 0.00 0.00 1518.33 13310.02
Minimum of Months 0.00 0.00 1302.58 945.79
Maximum of Months 0.00 0.00 1733.42 1283.95



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.95
April 0.00 0.00 1664.36 1199.19
May 0.00 0.00 1557.28 1159.44
June 0.00 0.00 1445.65 1041.60
July 0.00 0.00 1352.76 1007.17
August 0.00 0.00 1302.18 969.51
September 0.00 0.00 1312.75 945.85
October 0.00 0.00 1380.91 1028.12
November 0.00 0.00 1479.92 1066.30
December 0.00 0.00 1595.85 1188.15
         
Annual Sum or Average 0.00 0.00 1518.32 13309.96
Minimum of Months 0.00 0.00 1302.18 945.85
Maximum of Months 0.00 0.00 1733.42 1283.95



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.63 1199.39
May 0.00 0.00 1557.66 1159.72
June 0.00 0.00 1445.94 1041.81
July 0.00 0.00 1354.40 1008.39
August 0.00 0.00 1300.86 968.53
September 0.00 0.00 1313.70 946.53
October 0.00 0.00 1380.39 1027.74
November 0.00 0.00 1481.02 1067.09
December 0.00 0.00 1595.63 1187.99
         
Annual Sum or Average 0.00 0.00 1518.54 13311.80
Minimum of Months 0.00 0.00 1300.86 946.53
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.91 1199.59
May 0.00 0.00 1557.79 1159.82
June 0.00 0.00 1445.81 1041.72
July 0.00 0.00 1352.17 1006.73
August 0.00 0.00 1302.59 969.81
September 0.00 0.00 1313.57 946.44
October 0.00 0.00 1380.44 1027.78
November 0.00 0.00 1481.05 1067.11
December 0.00 0.00 1595.63 1187.99
         
Annual Sum or Average 0.00 0.00 1518.51 13311.60
Minimum of Months 0.00 0.00 1302.59 946.44
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 1685.62 1254.99
February 0.00 0.00 1733.42 1165.68
March 0.00 0.00 1724.51 1283.94
April 0.00 0.00 1664.68 1199.42
May 0.00 0.00 1557.49 1159.59
June 0.00 0.00 1445.65 1041.61
July 0.00 0.00 1352.32 1006.84
August 0.00 0.00 1302.63 969.85
September 0.00 0.00 1313.82 946.62
October 0.00 0.00 1380.01 1027.45
November 0.00 0.00 1481.04 1067.11
December 0.00 0.00 1595.63 1187.99
         
Annual Sum or Average 0.00 0.00 1518.45 13311.08
Minimum of Months 0.00 0.00 1302.63 946.62
Maximum of Months 0.00 0.00 1733.42 1283.94



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10754.32
February 0.00 7678.19
March 1.30 6096.51
April 19.74 2895.19
May 80.17 687.17
June 121.51 153.80
July 160.57 50.54
August 117.09 96.11
September 43.29 733.10
October 12.02 2609.71
November 0.00 5197.60
December 0.00 10120.43
     
Annual Sum or Average 555.69 47072.66
Minimum of Months 0.00 50.54
Maximum of Months 160.57 10754.32



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8780.12
February 0.00 6294.11
March 0.00 5028.91
April 6.71 2343.02
May 44.27 516.39
June 79.44 82.11
July 109.36 23.39
August 80.51 48.95
September 26.01 504.10
October 7.51 2009.35
November 0.00 4117.79
December 0.00 8219.76
     
Annual Sum or Average 353.82 37968.01
Minimum of Months 0.00 23.39
Maximum of Months 109.36 8780.12



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10745.94
February 0.00 7675.85
March 0.00 6065.17
April 12.85 2760.84
May 67.59 613.51
June 122.77 122.41
July 160.22 49.32
August 111.56 89.67
September 38.59 704.02
October 9.60 2602.86
November 0.00 5194.88
December 0.00 10110.18
     
Annual Sum or Average 523.18 46734.64
Minimum of Months 0.00 49.32
Maximum of Months 160.22 10745.94



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11354.57
February 0.00 8298.92
March 0.01 6637.67
April 8.85 3171.66
May 63.39 729.34
June 108.63 145.53
July 140.91 46.72
August 90.61 99.38
September 20.23 818.88
October 1.37 2849.24
November 0.00 5557.79
December 0.00 10576.18
     
Annual Sum or Average 434.00 50285.86
Minimum of Months 0.00 46.72
Maximum of Months 140.91 11354.57



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 9394.68
February 0.00 6935.26
March 0.00 5615.23
April 1.39 2673.77
May 30.61 576.49
June 66.84 75.79
July 89.69 20.44
August 53.66 51.68
September 6.64 598.32
October 0.00 2275.55
November 0.00 4484.18
December 0.00 8684.58
     
Annual Sum or Average 248.83 41385.99
Minimum of Months 0.00 20.44
Maximum of Months 89.69 9394.68



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11352.40
February 0.00 8302.57
March 0.00 6632.17
April 2.79 3043.49
May 50.30 653.44
June 109.51 118.61
July 140.29 47.20
August 83.99 92.41
September 13.05 770.84
October 0.09 2848.12
November 0.00 5557.83
December 0.00 10569.23
     
Annual Sum or Average 400.03 49988.31
Minimum of Months 0.00 47.20
Maximum of Months 140.29 11352.40



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7328.94
February 0.25 5111.02
March 3.26 4008.30
April 26.61 1757.29
May 93.32 337.01
June 135.75 44.56
July 177.57 6.56
August 133.96 25.93
September 54.69 354.24
October 15.94 1628.88
November 0.01 3456.23
December 0.00 6944.30
     
Annual Sum or Average 641.37 31003.26
Minimum of Months 0.00 6.56
Maximum of Months 177.57 7328.94



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5367.91
February 0.00 3722.88
March 0.08 2918.38
April 11.53 1199.11
May 57.19 186.85
June 95.27 12.38
July 128.43 0.00
August 100.73 7.89
September 39.08 176.67
October 12.00 1047.23
November 0.00 2387.34
December 0.00 5054.99
     
Annual Sum or Average 444.33 22081.62
Minimum of Months 0.00 0.00
Maximum of Months 128.43 5367.91



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7321.38
February 0.00 5094.32
March 0.13 3951.63
April 20.15 1644.61
May 83.18 291.06
June 140.91 34.33
July 179.47 8.42
August 130.27 22.86
September 52.07 341.03
October 13.91 1624.08
November 0.00 3451.94
December 0.00 6933.08
     
Annual Sum or Average 620.10 30718.74
Minimum of Months 0.00 8.42
Maximum of Months 179.47 7321.38



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7888.50
February 0.00 5678.19
March 0.16 4491.32
April 12.01 1977.41
May 75.17 360.71
June 123.20 39.64
July 158.60 5.06
August 107.11 27.58
September 27.99 407.47
October 2.18 1819.66
November 0.00 3791.88
December 0.00 7369.10
     
Annual Sum or Average 506.44 33856.51
Minimum of Months 0.00 5.06
Maximum of Months 158.60 7888.50



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 5927.13
February 0.00 4306.93
March 0.00 3449.39
April 2.17 1450.48
May 41.20 214.43
June 82.95 9.98
July 109.51 0.00
August 73.24 8.74
September 13.17 223.05
October 0.22 1248.18
November 0.00 2723.51
December 0.00 5479.13
     
Annual Sum or Average 322.44 25040.93
Minimum of Months 0.00 0.00
Maximum of Months 109.51 5927.13



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 7883.16
February 0.00 5678.63
March 0.00 4477.18
April 5.51 1854.00
May 64.36 309.09
June 128.16 32.52
July 160.21 7.67
August 102.87 24.12
September 22.86 380.74
October 0.52 1820.84
November 0.00 3789.38
December 0.00 7359.69
     
Annual Sum or Average 484.50 33617.02
Minimum of Months 0.00 7.67
Maximum of Months 160.21 7883.16



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11435.10
February 0.00 8354.54
March 0.00 6640.31
April 3.96 2998.76
May 61.14 603.00
June 124.96 93.78
July 162.34 36.00
August 100.27 76.77
September 17.37 731.75
October 0.17 2869.74
November 0.00 5627.88
December 0.00 10658.95
     
Annual Sum or Average 470.20 50126.57
Minimum of Months 0.00 36.00
Maximum of Months 162.34 11435.10



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10913.60
February 0.00 7815.97
March 0.00 6172.51
April 11.62 2777.98
May 72.63 577.84
June 133.08 97.72
July 174.96 38.17
August 120.14 75.19
September 38.22 678.32
October 8.24 2646.47
November 0.00 5306.82
December 0.00 10260.33
     
Annual Sum or Average 558.88 47360.91
Minimum of Months 0.00 38.17
Maximum of Months 174.96 10913.60



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10923.11
February 0.00 7816.71
March 0.73 6197.86
April 18.18 2909.51
May 84.82 651.17
June 131.79 127.65
July 174.96 38.76
August 125.48 82.02
September 42.93 709.59
October 10.30 2651.80
November 0.00 5311.35
December 0.00 10272.98
     
Annual Sum or Average 589.19 47692.51
Minimum of Months 0.00 38.76
Maximum of Months 174.96 10923.11



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 9463.60
February 0.00 6965.65
March 0.00 5592.81
April 2.05 2602.08
May 41.30 518.11
June 83.82 55.44
July 113.48 12.91
August 71.88 41.33
September 10.40 556.02
October 0.03 2282.16
November 0.00 4543.16
December 0.00 8763.87
     
Annual Sum or Average 322.96 41397.12
Minimum of Months 0.00 12.91
Maximum of Months 113.48 9463.60



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8930.94
February 0.00 6412.65
March 0.00 5111.19
April 6.38 2343.67
May 50.66 476.29
June 91.47 60.55
July 125.91 15.27
August 91.27 39.12
September 27.13 478.06
October 6.50 2039.09
November 0.00 4215.02
December 0.00 8357.41
     
Annual Sum or Average 399.31 38479.28
Minimum of Months 0.00 15.27
Maximum of Months 125.91 8930.94



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:07:29

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11441.29
February 0.00 8354.74
March 0.00 6644.16
April 10.12 3128.63
May 73.82 682.29
June 123.95 120.05
July 162.45 35.37
August 106.33 84.28
September 23.97 781.80
October 1.40 2870.27
November 0.00 5630.62
December 0.00 10669.21
     
Annual Sum or Average 502.04 50442.72