Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:34

Tabular Output Report in Format: HTML

Building: US+MF+CZ8+gasfurnace+heatedbsmt+IECC_2009

Environment: ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610

Simulation Timestamp: 2024-06-27 18:34:18


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 2372969.90 60.84 80.70
Net Site Energy 2372969.90 60.84 80.70
Total Source Energy 3583724.61 91.88 121.88
Net Source Energy 3583724.61 91.88 121.88


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 29404.35
Unconditioned Building Area 9600.87


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 1321336.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 19894.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 61803.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 334377.15 165141.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 48882.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 400929.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 485561.80 1887408.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 1321336.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 19894.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 61803.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 3888.48 79268.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 67443.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 153392.63 18429.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 120067.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 24355.55 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 24527.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
  Water Heater 0.00 400929.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 0.00 1321336.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 19894.43 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 61803.86 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 334377.15 165141.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 48882.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 0.00 400929.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 370400.12
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.80 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 2.34 58.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.60
Other 11.37 5.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 16.51 64.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 12.60


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 1.76 44.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50
Other 8.57 4.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 12.45 48.39 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 9.50


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 485561.801 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 485561.801 100.00
     
Total On-Site and Utility Electric Sources 485561.801 100.00
Total Electricity End Uses 485561.801 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00  
Air to Air Heat Recovery for Cooling 0.00  
Air to Air Heat Recovery for Heating 0.00  
High-Temperature Geothermal* 0.00  
Solar Water Thermal 0.00  
Solar Air Thermal 0.00  
Total On-Site Thermal Sources 0.00  


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 370400.12 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 370400.12 100.00
Total Water End Uses 370400.12 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 0.00
Time Setpoint Not Met During Occupied Cooling 0.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 3627.83


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNITHEATEDBSMT |

COILLOADS

| MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR | MAIN FUEL HEATING COIL_UNITHEATEDBSMT | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNITHEATEDBSMT |

WATER HEATER: LOADS

| WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR | WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR | WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR | WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR | WATER HEATER_UNIT1_FRONTROW_TOPFLOOR | WATER HEATER_UNIT2_FRONTROW_TOPFLOOR | WATER HEATER_UNIT3_FRONTROW_TOPFLOOR | WATER HEATER_UNIT1_BACKROW_TOPFLOOR | WATER HEATER_UNIT2_BACKROW_TOPFLOOR | WATER HEATER_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| HEATEDBSMT | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:34
RunPeriod ANNUAL
Weather File Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Latitude [deg] 64.82
Longitude [deg] -147.8
Elevation [ft] 436.37
Time Zone -9.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Above Ground Wall Area [ft2] 15481.63 6175.53 1565.28 6175.53 1565.28
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97
Above Ground Window-Wall Ratio [%] 13.74 8.61 33.97 8.61 33.97


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
HEATEDBSMT 7794.39 Yes Yes 58539.52 1.00 185.02 0.00 0.00 0.00 0.4972   1.5385
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.7516 600.28 4.4722
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.7516 600.28 4.4722
Total 39005.22     325627.71   16363.00 0.00 2126.74 2126.74 0.5158 1083.48 2.7852
Conditioned Total 29404.35     242278.90   15481.63 0.00 2126.74 2126.74 0.6842 816.79 3.6946
Unconditioned Total 9600.87     83348.81   881.37 0.00 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
HEATEDBSMT 7794.39 Yes Yes 1.00 HEATEDBSMT GENERAL HEATEDBSMT 0.4972 0.00 1.5385  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.7516 600.28 4.4722  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.7516 600.28 4.4722  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.7516 600.28 4.4722  
Total 39005.22             0.5158 1083.48 2.7852  
Conditioned Total 29404.35             0.6842 816.79 3.6946  
Unconditioned Total 9600.87             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 29404.35 9600.87 0.00 0.5158 1083.48 2.7852
Total 39005.22 29404.35 9600.87 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 29-JUL-19:20 12-JAN-10:00 - - - - - - - - - - 01-JAN-08:19
Heating 0.00 595.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 35.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 20.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 54.92 24.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 176.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 125.05 796.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 595.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 35.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 20.13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 3.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_dryer 0.62 13.90 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_range 0.00 8.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  gas_mels 25.06 1.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 19.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 2.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  General 6.94 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.34
  Water Heater 0.00 176.23 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 1432329.01 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 63005.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 195732.82 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 1058972.43 179013.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 154811.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 434607.53 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1537774.22 2045950.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 48.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 6.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 2.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 36.01 6.09 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 5.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 14.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 52.30 69.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 36.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 1.62 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 27.15 4.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 3.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 0.00 11.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 39.42 52.45 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNITHEATEDBSMT 303.12
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 596.78
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 502.89
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 596.60
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 596.77
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 502.83
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 596.50
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 508.68
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 347.66
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 445.79
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 446.01
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 347.59
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 445.67
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 650.12
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 650.25
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 650.51
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 551.82
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 551.91
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 650.46
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 596.78 596.78 596.78 596.78 596.78 596.78 1.00 1.00 596.78
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 502.89 502.89 502.89 502.89 502.89 502.89 1.00 1.00 502.89
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 596.60 596.60 596.60 596.60 596.60 596.60 1.00 1.00 596.60
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 596.77 596.77 596.77 596.77 596.77 596.77 1.00 1.00 596.77
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 502.83 502.83 502.83 502.83 502.83 502.83 1.00 1.00 502.83
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 596.50 596.50 596.50 596.50 596.50 596.50 1.00 1.00 596.50
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.68 508.68 508.68 508.68 508.68 508.68 1.00 1.00 508.68
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 347.66 347.66 347.66 347.66 347.66 347.66 1.00 1.00 347.66
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 445.79 445.79 445.79 445.79 445.79 445.79 1.00 1.00 445.79
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 446.01 446.01 446.01 446.01 446.01 446.01 1.00 1.00 446.01
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 347.59 347.59 347.59 347.59 347.59 347.59 1.00 1.00 347.59
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 445.67 445.67 445.67 445.67 445.67 445.67 1.00 1.00 445.67
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 650.51 650.51 650.51 650.51 650.51 650.51 1.00 1.00 650.51
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 551.91 551.91 551.91 551.91 551.91 551.91 1.00 1.00 551.91
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 650.25 650.25 650.25 650.25 650.25 650.25 1.00 1.00 650.25
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 650.46 650.46 650.46 650.46 650.46 650.46 1.00 1.00 650.46
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 551.82 551.82 551.82 551.82 551.82 551.82 1.00 1.00 551.82
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 650.12 650.12 650.12 650.12 650.12 650.12 1.00 1.00 650.12
CENTRAL SYSTEM_UNITHEATEDBSMT 303.12 303.12 303.12 303.12 303.12 303.12 1.00 1.00 303.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 596.78 1.52 0.798282
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 502.89 1.37 0.769318
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 596.60 1.56 0.788153
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 596.77 1.49 0.800240
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 502.83 1.18 0.800394
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 596.50 1.51 0.800540
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 508.68 1.29 0.800088
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 347.66 0.938922 0.773432
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 445.79 1.17 0.785977
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 446.01 1.11 0.800020
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 347.59 0.819933 0.800255
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 445.67 1.13 0.798133
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 650.51 1.64 0.800083
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 551.91 1.49 0.773811
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 650.25 1.75 0.775653
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 650.46 1.63 0.800918
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 551.82 1.32 0.800865
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 650.12 1.67 0.793324
DX COOLING COIL_UNITHEATEDBSMT 303.12 0.793973 0.785828
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Heating Capacity [Btu/h] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 596.78 596.78 596.78 39200.81 1.52 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 502.89 502.89 502.89 34193.35 1.37 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 596.60 596.60 596.60 39191.69 1.56 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 596.77 596.77 596.77 39200.63 1.49 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 502.83 502.83 502.83 34190.48 1.18 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 596.50 596.50 596.50 39186.08 1.51 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 508.68 508.68 508.68 31157.05 1.29 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 347.66 347.66 347.66 25912.47 0.938922 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 445.79 445.79 445.79 31144.96 1.17 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 446.01 446.01 446.01 31156.35 1.11 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 347.59 347.59 347.59 25908.94 0.819933 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 445.67 445.67 445.67 31138.58 1.13 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 650.51 650.51 650.51 42066.11 1.64 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 551.91 551.91 551.91 36807.15 1.49 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 650.25 650.25 650.25 42051.97 1.75 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 650.46 650.46 650.46 42063.49 1.63 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 551.82 551.82 551.82 36802.44 1.32 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 650.12 650.12 650.12 42045.19 1.67 1.00
ACANDF_UNITHEATEDBSMT 303.12 303.12 303.12 23532.63 0.793973 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

Design Size Maximum Flow Rate [ft3/min]
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR 596.78
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR 502.89
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR 596.60
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR 596.77
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR 502.83
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR 596.50
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR 508.68
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR 347.66
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR 445.79
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR 446.01
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR 347.59
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR 445.67
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR 650.51
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR 551.91
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR 650.25
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR 650.46
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR 551.82
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR 650.12
SUPPLY FAN_UNITHEATEDBSMT 303.12
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Fuel

Design Size Nominal Capacity [Btu/h]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 45080.93
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 39322.36
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 45070.44
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 45080.73
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 39319.05
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 45063.99
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 35830.61
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 29799.34
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 35816.70
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 35829.81
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 29795.28
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 35809.36
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 48376.03
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 42328.22
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 48359.77
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR 48373.01
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR 42322.81
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR 48351.96
MAIN FUEL HEATING COIL_UNITHEATEDBSMT 29415.78
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Mixed

Maximum Heater Capacity [Btu/h] Use Side Design Flow Rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 36002.06 1.04
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 36002.06 1.04
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 36002.06 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 2.59 -0.0 4.60 11.91 30.97 45.70 55.63 58.66 53.51 42.08 26.80 12.63


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 Fairbanks Intl Arpt AK USA TMY3 WMO#=702610 64.82 -147.85 -9.00 436.37 14. 1.1854


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 29.25 65.16 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ8+gasfurnace+heatedbsmt+IECC_2009 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.1351 Rough 0.0417 9.402E-002 42.764 0.280 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 7.7625 Rough 1.5719 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 1.9554E-005 Rough 0.0008 12.990 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3227 Rough 0.4584 6.015E-002 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5031 Smooth 0.1189 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.3300 VerySmooth 0.1230 0.114 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFBASEMENTAVGWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTWALLSURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFBASEMENTAVGFLOOR N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTFLOORTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFBASEMENTUPPERWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTUPPERWALLTEMP NO 24.000 0.000 N/A N/A
4 SURFPROPOTHSDCOEFBASEMENTLOWERWALL N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCBASEMENTLOWERWALLTEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 HEATEDBSMT 0.0 0.00 0.00 0.00 59.94 32.51 -3.4 1 1 1 0.00 119.89 0.00 65.10 -7.0 0.49 7.51 58539.45 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 HEATEDBSMT 7794.37 0.0 N/A 0.000 0.497 1.538 0.000 0.000 0.000 0.000 2.036 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.751 2.110 2.363 0.000 0.000 0.000 5.224 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 683.529 0.569 100.165 0.000 0.600 0.200 0.200 0.000 General 46.993 683.529
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
37 BASEMENT HARDWIRED LIGHTING INTERIORLIGHTINGHE HEATEDBSMT 7794.37 0.0 2935.480 0.377 N/A 0.000 0.600 0.200 0.200 0.000 General 201.813 2935.480
38 BASEMENT PLUG-IN LIGHTING INTERIORLIGHTINGHE HEATEDBSMT 7794.37 0.0 939.713 0.120 N/A 0.000 0.600 0.200 0.200 0.000 General 64.606 939.713


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 GAS_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
5 GAS_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 GAS_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 GAS_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
13 GAS_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 GAS_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 GAS_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
21 GAS_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 GAS_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 GAS_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
29 GAS_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 GAS_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 GAS_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
37 GAS_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 GAS_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 GAS_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
45 GAS_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 GAS_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 GAS_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
53 GAS_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 GAS_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 GAS_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
61 GAS_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 GAS_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 GAS_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
69 GAS_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 GAS_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 GAS_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
77 GAS_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 GAS_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 GAS_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
85 GAS_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 GAS_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 GAS_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
93 GAS_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 GAS_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 GAS_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
101 GAS_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 GAS_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 GAS_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
109 GAS_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 GAS_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 GAS_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
117 GAS_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 GAS_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 GAS_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
125 GAS_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 GAS_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 GAS_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
133 GAS_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 GAS_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 GAS_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 55.199 0.046 8.089 0.000 1.000 0.000 0.000 gas_dryer 0.000 55.199
141 GAS_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 gas_range 0.000 0.000
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 GAS_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1439.049 1.199 210.881 6.000E-002 0.690 0.250 0.000 gas_mels 744.021 1439.049
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 460.217 0.383 67.441 6.244E-002 0.412 0.251 0.275 IECC_adj 237.943 460.217
145 IECC_ADJ_HEATEDBSMT MISCPLUGLOAD HEATEDBSMT 7794.37 0.0 11991.491 1.538 N/A 6.244E-002 0.412 0.251 0.275 IECC_adj 6199.880 11991.491


GasEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 GAS_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
2 GAS_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
3 GAS_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
4 GAS_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
5 GAS_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
6 GAS_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
7 GAS_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
8 GAS_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
9 GAS_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
10 GAS_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
11 GAS_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
12 GAS_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
13 GAS_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
14 GAS_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
15 GAS_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
16 GAS_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
17 GAS_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
18 GAS_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
19 GAS_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
20 GAS_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
21 GAS_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
22 GAS_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
23 GAS_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
24 GAS_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
25 GAS_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
26 GAS_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
27 GAS_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
28 GAS_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
29 GAS_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
30 GAS_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
31 GAS_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
32 GAS_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
33 GAS_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
34 GAS_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
35 GAS_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
36 GAS_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
37 GAS_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
38 GAS_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
39 GAS_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
40 GAS_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
41 GAS_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
42 GAS_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
43 GAS_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
44 GAS_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
45 GAS_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
46 GAS_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
47 GAS_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
48 GAS_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
49 GAS_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
50 GAS_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
51 GAS_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900
52 GAS_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1125.237 0.937 164.894 5.000E-002 0.100 0.850 0.000 gas_dryer 0.000 1125.237
53 GAS_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1538.075 1.281 225.392 6.000E-002 0.690 0.250 0.000 gas_range 36.215 1538.075
54 GAS_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 172.900 0.144 25.337 6.000E-002 0.690 0.250 0.000 gas_mels 89.394 172.900


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 11 0.167 0.0631 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
4 INTERIOR CEILING 6 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 Rough
5 ATTIC FLOOR 7 2 12 0.167 0.0225 0.900 0.900 0.700 0.700 MediumSmooth
6 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
7 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
8 EXTERIOR DOOR 14 1 5 0.167 0.350 0.900 0.900 0.700 0.700 Smooth
9 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
10 BASEMENT WALL 24 3 10 0.167 0.0664 0.900 0.900 0.700 0.700 Rough
11 iz-EXTERIOR FLOOR 25 3 4 0.167 0.300 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.0417 0.094 42.764 0.280 0.1351
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
11 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
12 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
13 CEIL_CONSOL_LAYER 1.5719 0.062 2.618 0.185 7.762
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
18 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
19 DOOR_CONST 0.1188 0.072 32.003 0.183 0.5031
20 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
21 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
22 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
23 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
24 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
25 BSMTWALL_CONSOL_LAYER 0.4584 0.060 7.541 0.248 2.323
26 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.0010 12.990 3.438 0.219 0.1955E-04


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 11 -0.54724946E-11 -0.29353179E-14 -0.58361936E-11 0.17617726E-15
2 10 0.24755928E-06 0.16971160E-13 0.58954555E-06 -0.42317085E-11
3 9 -0.21700660E-03 0.26282512E-10 -0.34360792E-03 0.18634160E-06
4 8 0.10400975E-01 0.16063655E-07 0.16710006E-01 -0.10459154E-03
5 7 -0.18466841 0.14497582E-05 -0.31678806 0.33996447E-02
6 6 1.6813335 0.30890211E-04 3.0392820 -0.45644738E-01
7 5 -8.8640021 0.19737274E-03 -16.399456 0.32465800
8 4 28.400945 0.41196590E-03 52.185337 -1.3315683
9 3 -55.684303 0.27160336E-03 -99.213599 3.2198962
10 2 64.740984 0.46773103E-04 110.17164 -4.4902555
11 1 -40.701741 0.11975386E-05 -65.686261 3.3169381
12 0 10.602230 0.29970883E-09 16.204438  
13 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
14 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
15 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
16 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
17 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
18 0 6.2472388 0.62260140E-03 6.2472388  
19 4 0.29631924E-13 -0.40788276E-14 0.60443234E-14 -0.77798347E-16
20 3 -0.11254351E-04 0.79669069E-06 -0.23145793E-05 0.39394231E-13
21 2 0.49771861 0.29587917E-01 0.78801895E-01 -0.76025120E-05
22 1 -8.3915550 0.80192706 -1.1535996 0.21114735
23 0 9.2367617 0.51139848 2.4177143  
24 12 0.94888791E-16 -0.11237443E-15 0.21480527E-09 -0.52606005E-16
25 11 -0.44509090E-09 -0.12338758E-15 -0.11566016E-03 0.28501063E-09
26 10 0.60393314E-04 0.62564840E-13 0.62960490E-02 -0.38672578E-04
27 9 -0.20055671E-02 0.85912012E-10 -0.12885789 0.13084700E-02
28 8 0.28697042E-01 0.10381403E-07 1.3966036 -0.19129448E-01
29 7 -0.23229993 0.28493476E-06 -9.1473517 0.15872626
30 6 1.1750436 0.24973161E-05 38.552224 -0.82592201
31 5 -3.8729952 0.80040830E-05 -107.65441 2.8111251
32 4 8.4143451 0.96510929E-05 200.56463 -6.3313915
33 3 -11.897084 0.41099356E-05 -245.77565 9.3152582
34 2 10.487404 0.50788650E-06 189.69676 -8.5734564
35 1 -5.2147174 0.10902359E-07 -83.415737 4.4633233
36 0 1.1135774 0.38882120E-11 15.905642  
37 12 0.21480527E-09 -0.11237443E-15 0.94888791E-16 -0.52606005E-16
38 11 -0.11566016E-03 -0.12338758E-15 -0.44509090E-09 0.28501063E-09
39 10 0.62960490E-02 0.62564840E-13 0.60393314E-04 -0.38672578E-04
40 9 -0.12885789 0.85912012E-10 -0.20055671E-02 0.13084700E-02
41 8 1.3966036 0.10381403E-07 0.28697042E-01 -0.19129448E-01
42 7 -9.1473517 0.28493476E-06 -0.23229993 0.15872626
43 6 38.552224 0.24973161E-05 1.1750436 -0.82592201
44 5 -107.65441 0.80040830E-05 -3.8729952 2.8111251
45 4 200.56463 0.96510929E-05 8.4143451 -6.3313915
46 3 -245.77565 0.41099356E-05 -11.897084 9.3152582
47 2 189.69676 0.50788650E-06 10.487404 -8.5734564
48 1 -83.415737 0.10902359E-07 -5.2147174 4.4633233
49 0 15.905642 0.38882120E-11 1.1135774  
50 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
51 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
52 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
53 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
54 1 -19.904252 0.86481321 -19.904252 0.58144210
55 0 16.688993 0.62060609E-01 16.688993  
56 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
57 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
58 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
59 1 -11.299243 2.8799011 -8.6239668 0.15905732
60 0 15.219762 1.4410112 12.640375  
61 5 -0.24423608E-08 0.10315694E-08 -0.24423608E-08 0.46347327E-11
62 4 0.46481418E-04 0.19988510E-04 0.46481418E-04 -0.22728163E-06
63 3 -0.31887091E-01 0.95525843E-02 -0.31887091E-01 0.49135354E-03
64 2 1.3495466 0.25081638 1.3495466 -0.51058024E-01
65 1 -7.0688408 0.57876498 -7.0688408 0.58136590
66 0 6.6836766 0.93387740E-01 6.6836766  
67 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
68 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
69 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
70 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
71 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
72 1 -64.420211 0.46601667 -21.697519 0.64629334
73 0 46.121323 0.20873329E-01 15.867130  
74 10 0.50442590E-10 0.37421431E-14 0.50442587E-10 -0.86521684E-16
75 9 -0.53972773E-06 0.41502128E-13 -0.53972773E-06 0.83963618E-10
76 8 0.10045687E-02 0.32837718E-09 0.10045687E-02 -0.39657273E-06
77 7 -0.35699803E-01 0.19108467E-06 -0.35699803E-01 0.47332591E-03
78 6 0.49910094 0.13935795E-04 0.49910094 -0.11937255E-01
79 5 -3.5897715 0.21519702E-03 -3.5897715 0.12239145
80 4 14.570676 0.91210570E-03 14.570676 -0.65483682
81 3 -34.297718 0.11291753E-02 -34.297718 1.9662386
82 2 45.961246 0.36528821E-03 45.961246 -3.3045605
83 1 -32.291846 0.20188525E-04 -32.291846 2.8751859
84 0 9.1856636 0.31580648E-07 9.1856636  
85 4 0.60443234E-14 -0.40788276E-14 0.29631924E-13 -0.77798347E-16
86 3 -0.23145793E-05 0.79669069E-06 -0.11254351E-04 0.39394231E-13
87 2 0.78801895E-01 0.29587917E-01 0.49771861 -0.76025120E-05
88 1 -1.1535996 0.80192706 -8.3915550 0.21114735
89 0 2.4177143 0.51139848 9.2367617  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.350 0.350 1.000 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 0.350 0.350 1.000 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.350 0.350 1.000 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
2 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
3 GLASS SpectralAverage   0.12304 0.24698 0.54587 0.54587 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.11365 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor
1 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
2 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
3 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
4 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
5 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
6 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 5.3474 36002.1 0.823 0.5744
7 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
8 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
9 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
10 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
11 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
12 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 5.3474 36002.1 0.823 0.5744
13 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
14 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
15 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
16 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
17 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744
18 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR 5.3474 36002.1 0.823 0.5744


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 60.000 0.050 30.000 0.353 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
19 VENTILATION_UNITHEATEDBSMT ALWAYS_OFF HEATEDBSMT 7794.37 0.0 60.000 0.008 N/A 6.151E-002 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 HEATEDBSMT Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 HEATEDBSMT Cooling 4487.46441 4487.46441 194.07137 194.07137 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 71.03840 0.00700 7794.38637 0.00000 59.99321 0.00000
2 HEATEDBSMT Heating 16391.49834 16391.49834 303.11437 303.11437 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 -43.4200 0.00006 7794.38637 0.00000 59.99321 0.00000
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 10645.90413 10645.90413 460.40248 460.40248 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 76.45460 0.00700 1200.55323 2.00000 59.99321 0.00000
4 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 32293.56524 32293.56524 596.77959 596.77959 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
5 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 6287.91748 6287.91748 271.92793 271.92793 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 81.13640 0.00701 1200.55323 2.00000 59.99321 0.00000
6 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 27211.96650 27211.96650 502.88129 502.88129 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
7 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 8047.29208 8047.29208 348.00843 348.00843 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 78.32120 0.00700 1200.55323 2.00000 59.99321 0.00000
8 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 32284.30688 32284.30688 596.61009 596.61009 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
9 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 9363.73387 9363.73387 404.95758 404.95758 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.15960 0.00700 1200.55323 2.00000 59.99321 0.00000
10 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 32293.38744 32293.38744 596.77959 596.77959 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
11 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 4248.04591 4248.04591 183.71438 183.71438 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 71.58920 0.00700 1200.55323 2.00000 59.99321 0.00000
12 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 27209.05030 27209.05030 502.83892 502.83892 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
13 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 6477.93009 6477.93009 280.14827 280.14827 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.72020 0.00700 1200.55323 2.00000 59.99321 0.00000
14 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 32278.61385 32278.61385 596.50416 596.50416 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
15 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 11762.26625 11762.26625 508.68638 508.68638 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.53660 0.00700 1200.55323 2.00000 59.99321 0.00000
16 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 24130.17812 24130.17812 446.01689 446.01689 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
17 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 6978.09489 6978.09489 301.77962 301.77962 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 80.76920 0.00701 1200.55323 2.00000 59.99321 0.00000
18 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 18807.91239 18807.91239 347.66945 347.66945 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
19 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 9110.11346 9110.11346 393.98300 393.98300 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 78.93320 0.00701 1200.55323 2.00000 59.99321 0.00000
20 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 24117.90236 24117.90236 445.78384 445.78384 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
21 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 10286.20611 10286.20611 444.85164 444.85164 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 73.82300 0.00700 1200.55323 2.00000 59.99321 0.00000
22 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 24129.46737 24129.46737 446.01689 446.01689 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
23 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 4926.27201 4926.27201 213.05082 213.05082 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 71.03840 0.00700 1200.55323 2.00000 59.99321 0.00000
24 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 18804.33580 18804.33580 347.58470 347.58470 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
25 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 7496.00237 7496.00237 324.17369 324.17369 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 76.17920 0.00700 1200.55323 2.00000 59.99321 0.00000
26 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 24111.42891 24111.42891 445.67791 445.67791 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
27 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 7403.11098 7403.11098 320.14826 320.14826 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 77.09720 0.00700 1200.55323 2.00000 59.99321 0.00000
28 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 35179.95660 35179.95660 650.12704 650.12704 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
29 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 9082.84691 9082.84691 392.79656 392.79656 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 81.32000 0.00701 1200.55323 2.00000 59.99321 0.00000
30 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 35186.84229 35186.84229 650.25416 650.25416 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
31 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 12073.96586 12073.96586 522.16095 522.16095 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.53660 0.00700 1200.55323 2.00000 59.99321 0.00000
32 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 35201.19234 35201.19234 650.50839 650.50839 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
33 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 5751.48591 5751.48591 248.72878 248.72878 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 71.86460 0.00700 1200.55323 2.00000 59.99321 0.00000
34 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 29859.58020 29859.58020 551.82196 551.82196 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
35 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 7233.98575 7233.98575 312.83894 312.83894 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 80.76920 0.00701 1200.55323 2.00000 59.99321 0.00000
36 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 29864.35304 29864.35304 551.90671 551.90671 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000
37 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 11155.89513 11155.89513 482.45757 482.45757 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 74.15960 0.00700 1200.55323 2.00000 59.99321 0.00000
38 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 35198.52856 35198.52856 650.46602 650.46602 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -43.4200 0.00006 1200.55323 2.00000 59.99321 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 3104.76 460.40248 460.40248 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 11489.10 596.77959 596.77959 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1932.69 271.92793 271.92793 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 10021.50 502.88129 502.88129 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2388.53 348.00843 348.00843 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 11486.43 596.61009 596.61009 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2691.10 404.95758 404.95758 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 11489.05 596.77959 596.77959 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1164.11 183.71438 183.71438 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 10020.66 502.83892 502.83892 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1886.12 280.14827 280.14827 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 11484.78 596.50416 596.50416 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 3410.27 508.68638 508.68638 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 9131.61 446.01689 446.01689 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 2125.33 301.77962 301.77962 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 7594.51 347.66945 347.66945 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2707.24 393.98300 393.98300 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 9128.06 445.78384 445.78384 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2951.47 444.85164 444.85164 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 9131.41 446.01689 446.01689 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1349.85 213.05082 213.05082 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 7593.48 347.58470 347.58470 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 2189.03 324.17369 324.17369 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 9126.20 445.67791 445.67791 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 3500.38 522.16095 522.16095 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 12328.87 650.50839 650.50839 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 2199.30 312.83894 312.83894 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 10787.56 551.90671 551.90671 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2744.08 392.79656 392.79656 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 12324.73 650.25416 650.25416 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 3209.18 482.45757 482.45757 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 12328.10 650.46602 650.46602 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1603.88 248.72878 248.72878 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 10786.18 551.82196 551.82196 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 2179.38 320.14826 320.14826 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 12322.74 650.12704 650.12704 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
37 CENTRAL SYSTEM_UNITHEATEDBSMT Cooling Sensible 1223.00 194.07137 194.07137 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
38 CENTRAL SYSTEM_UNITHEATEDBSMT Heating Sensible 6897.02 303.11437 303.11437 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNITHEATEDBSMT Design Size Maximum Air Flow Rate [ft3/min] 303.11437
2 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 596.77959
3 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 502.88129
4 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 596.61009
5 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 596.77959
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 502.83892
7 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 596.50416
8 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 508.68638
9 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 347.66945
10 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 445.78384
11 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 446.01689
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 347.58470
13 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 445.67791
14 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 650.12704
15 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 650.25416
16 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 650.50839
17 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 551.82196
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 551.90671
19 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 650.46602
20 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 596.77959
21 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 596.77959
22 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 596.77959
23 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 596.77959
24 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 596.77959
25 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 596.77959
26 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
27 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
28 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 502.88129
29 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 502.88129
30 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 502.88129
31 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 502.88129
32 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 502.88129
33 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 502.88129
34 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
35 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
36 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 596.61009
37 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 596.61009
38 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 596.61009
39 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 596.61009
40 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 596.61009
41 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 596.61009
42 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
43 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
44 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 596.77959
45 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 596.77959
46 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 596.77959
47 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 596.77959
48 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 596.77959
49 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 596.77959
50 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
51 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
52 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 502.83892
53 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 502.83892
54 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 502.83892
55 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 502.83892
56 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 502.83892
57 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 502.83892
58 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
59 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
60 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 596.50416
61 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 596.50416
62 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 596.50416
63 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 596.50416
64 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 596.50416
65 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 596.50416
66 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
67 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
68 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 508.68638
69 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 508.68638
70 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 508.68638
71 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 508.68638
72 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 508.68638
73 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 508.68638
74 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
75 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
76 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 347.66945
77 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 347.66945
78 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 347.66945
79 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 347.66945
80 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 347.66945
81 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 347.66945
82 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
83 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
84 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 445.78384
85 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 445.78384
86 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 445.78384
87 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 445.78384
88 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 445.78384
89 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 445.78384
90 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
91 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
92 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 446.01689
93 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 446.01689
94 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 446.01689
95 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 446.01689
96 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 446.01689
97 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 446.01689
98 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
99 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
100 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 347.58470
101 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 347.58470
102 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 347.58470
103 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 347.58470
104 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 347.58470
105 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 347.58470
106 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
107 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
108 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 445.67791
109 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 445.67791
110 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 445.67791
111 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 445.67791
112 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 445.67791
113 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 445.67791
114 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
115 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 650.50839
117 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 650.50839
118 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 650.50839
119 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 650.50839
120 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 650.50839
121 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 650.50839
122 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
123 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 551.90671
125 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 551.90671
126 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 551.90671
127 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 551.90671
128 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 551.90671
129 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 551.90671
130 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
131 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 650.25416
133 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 650.25416
134 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 650.25416
135 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 650.25416
136 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 650.25416
137 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 650.25416
138 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
139 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 650.46602
141 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 650.46602
142 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 650.46602
143 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 650.46602
144 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 650.46602
145 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 650.46602
146 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
147 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 551.82196
149 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 551.82196
150 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 551.82196
151 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 551.82196
152 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 551.82196
153 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 551.82196
154 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
155 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 650.12704
157 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 650.12704
158 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 650.12704
159 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 650.12704
160 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 650.12704
161 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 650.12704
162 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
163 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 303.11437
165 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 303.11437
166 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Sum of Air Terminal Maximum Flow Rates [ft3/min] 303.11437
167 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Heating Design Air Flow Rate [ft3/min] 303.11437
168 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Cooling Design Air Flow Rate [ft3/min] 303.11437
169 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Adjusted Main Design Air Flow Rate [ft3/min] 303.11437
170 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT User Heating Air Flow Ratio [] 1.00000
171 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Calculated Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 596.77959
173 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 502.88129
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 596.61009
175 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 596.77959
176 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 502.83892
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 596.50416
178 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 508.68638
179 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 347.66945
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 445.78384
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 446.01689
182 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 347.58470
183 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 445.67791
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 650.50839
185 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 551.90671
186 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 650.25416
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 650.46602
188 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 551.82196
189 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 650.12704
190 AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT Design Supply Air Flow Rate [ft3/min] 303.11437
191 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 596.77959
192 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.51714
193 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.79828
194 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 596.77959
195 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 596.77959
196 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 596.77959
197 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 39200.80913
198 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.51714
199 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
200 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 596.77959
201 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 45080.93051
202 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 502.88129
203 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.37228
204 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.76932
205 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 502.88129
206 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 502.88129
207 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 502.88129
208 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 34193.35462
209 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.37228
210 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
211 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 502.88129
212 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 39322.35781
213 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 596.61009
214 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.55608
215 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.78815
216 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 596.61009
217 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 596.61009
218 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 596.61009
219 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 39191.68561
220 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.55608
221 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
222 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 596.61009
223 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 45070.43844
224 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 596.77959
225 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.48951
226 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80024
227 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 596.77959
228 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 596.77959
229 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 596.77959
230 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 39200.63396
231 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.48951
232 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
233 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 596.77959
234 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 45080.72903
235 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 502.83892
236 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.18224
237 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80039
238 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 502.83892
239 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 502.83892
240 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 502.83892
241 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 34190.48093
242 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.18224
243 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
244 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 502.83892
245 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 39319.05308
246 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 596.50416
247 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.51053
248 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80054
249 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 596.50416
250 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 596.50416
251 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 596.50416
252 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Heating Capacity [Btu/h] 39186.07554
253 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.51053
254 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
255 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 596.50416
256 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Nominal Capacity [Btu/h] 45063.98686
257 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 508.68638
258 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.28995
259 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80009
260 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 508.68638
261 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 508.68638
262 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 508.68638
263 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 31157.05424
264 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.28995
265 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
266 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 508.68638
267 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 35830.61241
268 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 347.66945
269 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.93892
270 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77343
271 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 347.66945
272 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 347.66945
273 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 347.66945
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 25912.46682
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.93892
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
277 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 347.66945
278 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 29799.33687
279 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 445.78384
280 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.16711
281 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.78598
282 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 445.78384
283 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 445.78384
284 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 445.78384
285 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 31144.95730
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.16711
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
288 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 445.78384
289 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 35816.70090
290 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 446.01689
291 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.11396
292 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80002
293 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 446.01689
294 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 446.01689
295 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 446.01689
296 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 31156.35386
297 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.11396
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
299 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 446.01689
300 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 35829.80694
301 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 347.58470
302 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.81993
303 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80025
304 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 347.58470
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 347.58470
306 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 347.58470
307 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 25908.94240
308 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.81993
309 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
310 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 347.58470
311 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 29795.28376
312 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 445.67791
313 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.13353
314 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.79813
315 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 445.67791
316 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 445.67791
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 445.67791
318 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Heating Capacity [Btu/h] 31138.57819
319 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.13353
320 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
321 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 445.67791
322 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Nominal Capacity [Btu/h] 35809.36493
323 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 650.50839
324 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.64454
325 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80008
326 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 650.50839
327 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 650.50839
328 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 650.50839
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 42066.11266
330 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.64454
331 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
332 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 650.50839
333 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 48376.02959
334 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 551.90671
335 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.48868
336 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77381
337 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 551.90671
338 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 551.90671
339 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 551.90671
340 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 36807.14728
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.48868
342 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
343 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 551.90671
344 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 42328.21936
345 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 650.25416
346 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.74905
347 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.77565
348 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 650.25416
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 650.25416
350 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 650.25416
351 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 42051.97166
352 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.74905
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
354 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 650.25416
355 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 48359.76742
356 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 650.46602
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.62512
358 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80092
359 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 650.46602
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 650.46602
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 650.46602
362 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 42063.48771
363 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.62512
364 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
365 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 650.46602
366 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 48373.01086
367 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 551.82196
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.32227
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.80087
370 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 551.82196
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 551.82196
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 551.82196
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 36802.44398
374 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.32227
375 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
376 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 551.82196
377 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 42322.81056
378 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 650.12704
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.67338
380 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.79332
381 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 650.12704
382 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 650.12704
383 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 650.12704
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Heating Capacity [Btu/h] 42045.18632
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.67338
386 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
387 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 650.12704
388 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Nominal Capacity [Btu/h] 48351.96424
389 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Rated Air Flow Rate [ft3/min] 303.11437
390 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Gross Rated Total Cooling Capacity [ton] 0.79397
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT Design Size Gross Rated Sensible Heat Ratio 0.78583
392 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate [ft3/min] 303.11437
393 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate During Heating Operation [ft3/min] 303.11437
394 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Supply Air Flow Rate During Cooling Operation [ft3/min] 303.11437
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Nominal Heating Capacity [Btu/h] 23532.62504
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Nominal Cooling Capacity [ton] 0.79397
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNITHEATEDBSMT Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
398 Fan:OnOff SUPPLY FAN_UNITHEATEDBSMT Design Size Maximum Flow Rate [ft3/min] 303.11437
399 Coil:Heating:Fuel MAIN FUEL HEATING COIL_UNITHEATEDBSMT Design Size Nominal Capacity [Btu/h] 29415.78133
400 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
401 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
402 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
403 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
404 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
405 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
406 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
407 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
408 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
409 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
410 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
411 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
412 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
413 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
414 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
415 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
416 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
417 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
418 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
419 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
420 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
421 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
422 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
423 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
424 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
425 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
426 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
427 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
428 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
429 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
430 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
431 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
432 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
433 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
434 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
435 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
436 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
437 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
438 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
439 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
440 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
441 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
442 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
443 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
444 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
445 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
446 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
447 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
448 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
449 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
450 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
451 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
452 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
453 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
454 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
455 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
456 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
457 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
458 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
459 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
460 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
461 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
462 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
463 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
464 WaterHeater:Mixed WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
465 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
466 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
467 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
468 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
469 WaterHeater:Mixed WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
470 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
471 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
472 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
473 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
474 WaterHeater:Mixed WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
475 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
476 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
477 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
478 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
479 WaterHeater:Mixed WATER HEATER_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
480 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
481 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
482 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
483 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
484 WaterHeater:Mixed WATER HEATER_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
485 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
486 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
487 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
488 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Maximum Heater Capacity [Btu/h] 36002.05920
489 WaterHeater:Mixed WATER HEATER_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.5 3.36 11.48 12.16 11.69 11.80
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.4 3.24 11.05 11.69 11.56 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 1.3 3.41 11.62 12.32 11.85 12.04
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 1.3 3.29 11.21 11.87 11.74 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.5 3.38 11.53 12.22 11.75 11.89
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 1.5 3.26 11.11 11.76 11.62 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.4 3.35 11.44 12.12 11.65 11.74
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.4 3.22 11.00 11.64 11.51 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 1.1 3.31 11.31 11.97 11.51 11.53
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 1.1 3.18 10.85 11.47 11.34 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.4 3.36 11.47 12.15 11.68 11.79
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 1.4 3.23 11.04 11.68 11.55 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.2 3.36 11.47 12.16 11.68 11.79
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.2 3.24 11.04 11.68 11.55 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.9 3.40 11.60 12.30 11.82 12.00
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.9 3.28 11.19 11.85 11.71 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.1 3.38 11.54 12.23 11.76 11.90
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 1.1 3.26 11.12 11.77 11.63 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.35 11.44 12.12 11.65 11.74
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.22 11.00 11.64 11.51 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.8 3.32 11.31 11.98 11.52 11.54
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.8 3.18 10.86 11.48 11.35 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.1 3.36 11.48 12.16 11.69 11.80
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 1.1 3.24 11.05 11.69 11.56 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.6 3.36 11.46 12.15 11.68 11.78
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.6 3.23 11.03 11.67 11.54 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.4 3.40 11.60 12.30 11.82 12.00
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 1.4 3.28 11.19 11.84 11.71 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.7 3.40 11.59 12.29 11.82 11.99
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 1.7 3.28 11.18 11.84 11.70 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.6 3.35 11.44 12.12 11.65 11.74
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.5 3.22 11.00 11.64 11.51 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.3 3.33 11.35 12.02 11.55 11.59
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 1.3 3.19 10.90 11.53 11.40 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.6 3.37 11.50 12.19 11.72 11.84
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 1.6 3.25 11.08 11.72 11.59 -99999.
37 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT 0.8 3.38 11.54 12.23 11.76 11.90
38 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNITHEATEDBSMT 0.8 3.26 11.12 11.77 11.63 -99999.


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 6
2 6
3 6


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 -43.4 0.00 DefaultMultipliers Wetbulb -41.90 {C} 14. 20 59.1 0.00 No No
2 81.32 10.20 DefaultMultipliers Wetbulb 16.10 {C} 14. 180 610.3 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 HEATEDBSMT SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.029994242 0.051630280 Pass Pass
2 BREEZEWAY SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000001650 0.000000828 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003980750 0.005890761 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004594356 0.006745979 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003981722 0.005892234 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003980845 0.005890948 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004594809 0.006746688 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003982366 0.005893208 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005170647 0.007515920 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.006488924 0.009388200 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005173059 0.007519532 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005170906 0.007516346 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.006490133 0.009390037 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.005174403 0.007521547 Pass Pass
15 ATTIC SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000102780 0.000085989 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003572862 0.004891485 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003572184 0.004890504 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003570848 0.004888578 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004149175 0.005659145 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.004148536 0.005658194 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 0.000000000 0.000000000 Pass Pass 0.003571157 0.004889045 Pass Pass
22 HEATEDBSMT SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.019928356 0.026312636 Pass Pass 0.227702986 0.697670412 Pass Pass
23 BREEZEWAY SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.320538115 0.173086735 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001856597 0.007706760 Pass Pass 0.306764232 0.556516505 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000000969 0.000002118 Pass Pass 0.210741863 0.201621903 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.001272341 0.006123922 Pass Pass 0.262059872 0.660108860 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001298 0.000002691 Pass Pass 0.217918408 0.234324331 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000000893 0.000001751 Pass Pass 0.134219549 0.130513829 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000301184 0.001822619 Pass Pass 0.213688965 0.384283179 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000051520 0.000282432 Pass Pass 0.132876729 0.073111817 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000032760 0.000245841 Pass Pass 0.100480640 0.062900410 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000041612 0.000263416 Pass Pass 0.114589122 0.090513079 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000045804 0.000261878 Pass Pass 0.110501307 0.068134903 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000000828 0.000001756 Pass Pass 0.071076716 0.061144129 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001473 0.000002687 Pass Pass 0.105141338 0.092156476 Pass Pass
36 ATTIC SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.472986232 0.287374116 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001530 0.000002744 Pass Pass 0.114385009 0.110752354 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001687 0.000003079 Pass Pass 0.127652150 0.108820141 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001457 0.000003064 Pass Pass 0.155130107 0.092064399 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000000959 0.000002051 Pass Pass 0.086587890 0.067913924 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001008 0.000002330 Pass Pass 0.117411910 0.076468293 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 0.000001410 0.000002905 Pass Pass 0.125031805 0.077853839 Pass Pass
43 HEATEDBSMT RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.036481762 0.062003342 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.033452034 0.023361378 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015249944 0.013171092 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.016249920 0.015031130 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015515899 0.013464107 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015128343 0.013162563 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.016135175 0.015062461 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015290623 0.013258271 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013542786 0.015687988 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015361060 0.020655314 Pass Pass
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013937482 0.015982915 Pass Pass
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013302591 0.015597243 Pass Pass
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.015074569 0.020554739 Pass Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013620670 0.015618709 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.092945789 0.083488457 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013651238 0.011235321 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013721896 0.011273452 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013476343 0.011103343 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.014346518 0.012718696 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.014314533 0.012664079 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000000000 0.000000000 Pass Pass 0.013492973 0.011147565 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 1572015.06 1081332.07 546775.26 0.00 375899.86 3576024.36



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 8760.00 0.00 0.00 0.00 0.00
BREEZEWAY 8716.67 43.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8540.00 208.33 11.67 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 8540.00 0.00 0.00 0.00 0.00
Max 8760.00 208.33 11.67 0.00 0.00
Average 8747.46 11.98 0.56 0.00 0.00
Sum 183696.67 251.67 11.67 0.00 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 437.50 8322.50 0.00 0.00 0.00
BREEZEWAY 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8600.33 159.67 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 437.50 0.00 0.00 0.00 0.00
Max 8760.00 8322.50 0.00 0.00 0.00
Average 8356.09 403.91 0.00 0.00 0.00
Sum 175477.83 8482.17 0.00 0.00 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
HEATEDBSMT 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
HEATEDBSMT 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.03 0.04 0.03 0.01 0.02 0.01
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.04 0.04 0.04 0.01 0.02 0.01
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.03 0.04 0.03 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.03 0.04 0.03 0.02 0.03 0.02
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.06 0.08 0.06 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.04 0.06 0.04 0.01 0.02 0.01
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.05 0.05 0.05 0.01 0.01 0.01
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.04 0.06 0.04 0.01 0.01 0.01
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.03 0.05 0.03 0.02 0.02 0.02
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.04 0.04 0.04 0.01 0.02 0.01
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.04 0.04 0.04 0.02 0.03 0.02
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.04 0.04 0.04 0.01 0.02 0.01
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.04 0.04 0.04 0.02 0.02 0.02
LIVING_UNIT2_BACKROW_TOPFLOOR 0.03 0.05 0.03 0.02 0.02 0.02
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
LIVING_UNIT1_BACKROW_TOPFLOOR 0.04 0.05 0.04 0.02 0.02 0.02
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.06 0.08 0.06 0.02 0.03 0.02
Average 0.03 0.04 0.03 0.01 0.02 0.01
Sum 0.71 0.87 0.70 0.29 0.36 0.29


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB -43.4 0.00 -43.4 Wetbulb [F] 59.06 20.00
FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 81.32 18.36 60.98 Wetbulb [F] 610.27 180.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.00 0      
Apr 0.00 0      
May 0.00 0      
Jun 0.00 0      
Jul 0.00 0      
Aug 0.00 0      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 180.00 90.00 S
BGWALL_UPPER_SDR BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 90.00 90.00 E
BGWALL_UPPER_LDB BASEMENT WALL 0.30 0.063 0.066 59.96 59.96 0.00 90.00 N
BGWALL_UPPER_SDL BASEMENT WALL 0.30 0.063 0.066 32.56 32.56 270.00 90.00 W
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.226 0.300 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.060 0.063 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_LOWER_LDF BASEMENT WALL 0.30 0.064 0.066 839.40 839.40 180.00 90.00 S
BGWALL_LOWER_SDR BASEMENT WALL 0.30 0.064 0.066 455.77 455.77 90.00 90.00 E
BGWALL_LOWER_LDB BASEMENT WALL 0.30 0.064 0.066 839.40 839.40 0.00 90.00 N
BGWALL_LOWER_SDL BASEMENT WALL 0.30 0.064 0.066 455.77 455.77 270.00 90.00 W
BGFLOOR EXTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.022 0.022 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.205 0.300 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.022 0.022 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.022 0.022 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.022 0.022 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.350 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.350 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.350 0.335 0.883                      
North Total or Average             531.68 0.350 0.335 0.883                      
Non-North Total or Average             1595.05 0.350 0.335 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.270 0.350 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.99 0.00 0.99 0.98 0.00 0.00 1.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 1.00 1.00 1.00 0.98 0.99 0.99 0.00 1.00 0.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 0.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.5693 1200.55 683.53 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 615.01
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
BASEMENT HARDWIRED LIGHTING HEATEDBSMT HEATEDBSMT GENERAL 0.3766 7794.39 2935.48 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 2641.24
BASEMENT PLUG-IN LIGHTING HEATEDBSMT HEATEDBSMT GENERAL 0.1206 7794.39 939.71 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 845.52
Interior Lighting Total       0.3421 58808.69 20117.33               18100.85


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
None              


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   18205.70 14533.29 3672.42 0.80 4.09    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   16467.31 12668.59 3798.72 0.77 4.09    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   18672.95 14717.14 3955.81 0.79 4.09    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   17874.13 14303.60 3570.54 0.80 4.09    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14186.84 11355.06 2831.77 0.80 4.09    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   18126.32 14510.84 3615.48 0.80 4.09    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   15479.38 12384.87 3094.51 0.80 4.09    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11267.06 8714.30 2552.76 0.77 4.09    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14005.33 11007.87 2997.46 0.79 4.09    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13367.50 10694.26 2673.24 0.80 4.09    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   9839.19 7873.86 1965.33 0.80 4.09    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13602.35 10856.49 2745.86 0.80 4.09    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   19734.47 15789.21 3945.26 0.80 4.09    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   17864.12 13823.46 4040.66 0.77 4.09    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20988.65 16279.91 4708.74 0.78 4.09    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   19501.45 15619.07 3882.38 0.80 4.09    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15867.25 12707.53 3159.72 0.80 4.09    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   20080.51 15930.34 4150.17 0.79 4.09    
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed   9527.68 7487.12 2040.56 0.79 4.09    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.5 3.36 11.48 12.16 11.69 11.80
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   1.3 3.41 11.62 12.32 11.85 12.04
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   1.5 3.38 11.53 12.22 11.75 11.89
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.4 3.35 11.44 12.12 11.65 11.74
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   1.1 3.31 11.31 11.97 11.51 11.53
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   1.4 3.36 11.47 12.15 11.68 11.79
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.36 11.47 12.16 11.68 11.79
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.9 3.40 11.60 12.30 11.82 12.00
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   1.1 3.38 11.54 12.23 11.76 11.90
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.35 11.44 12.12 11.65 11.74
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.8 3.32 11.31 11.98 11.52 11.54
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   1.1 3.36 11.48 12.16 11.69 11.80
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.6 3.36 11.46 12.15 11.68 11.78
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   1.4 3.40 11.60 12.30 11.82 12.00
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   1.7 3.40 11.59 12.29 11.82 11.99
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.6 3.35 11.44 12.12 11.65 11.74
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   1.3 3.33 11.35 12.02 11.55 11.59
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   1.6 3.37 11.50 12.19 11.72 11.84
DX COOLING COIL_UNITHEATEDBSMT   0.8 3.38 11.54 12.23 11.76 11.90
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.24 11.05 11.69 11.56  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.29 11.21 11.87 11.74  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.5 3.26 11.11 11.76 11.62  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.22 11.00 11.64 11.51  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.18 10.85 11.47 11.34  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.23 11.04 11.68 11.55  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.24 11.04 11.68 11.55  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.28 11.19 11.85 11.71  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.26 11.12 11.77 11.63  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.22 11.00 11.64 11.51  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.18 10.86 11.48 11.35  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.24 11.05 11.69 11.56  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.6 3.23 11.03 11.67 11.54  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.4 3.28 11.19 11.84 11.71  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.7 3.28 11.18 11.84 11.70  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.5 3.22 11.00 11.64 11.51  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.3 3.19 10.90 11.53 11.40  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.6 3.25 11.08 11.72 11.59  
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed 0.8 3.26 11.12 11.77 11.63  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   45080.93 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   39322.36 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel   45070.44 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   45080.73 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   39319.05 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel   45063.99 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   35830.61 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   29799.34 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel   35816.70 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   35829.81 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   29795.28 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel   35809.36 0.80
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel   48376.03 0.80
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel   42328.22 0.80
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel   48359.77 0.80
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel   48373.01 0.80
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel   42322.81 0.80
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel   48351.96 0.80
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel   29415.78 0.80


Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
ZONE EXHAUST FAN_UNITHEATEDBSMT Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT3_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT2_FRONTROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
ZONE EXHAUST FAN_UNIT1_BACKROW_TOPFLOOR Fan:ZoneExhaust 0.60 0.13 59.99 42.86 0.71 1.00 8.10 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 596.78 225.10 0.38 1.00 1.99 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 502.89 189.69 0.38 1.00 2.13 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 596.60 225.03 0.38 1.00 1.99 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 596.77 225.10 0.38 1.00 1.99 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 502.83 189.67 0.38 1.00 2.13 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 596.50 225.00 0.38 1.00 1.99 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 508.68 191.87 0.38 1.00 2.12 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 347.66 131.13 0.38 1.00 2.55 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 445.79 168.15 0.38 1.00 2.26 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 446.01 168.23 0.38 1.00 2.25 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 347.59 131.11 0.38 1.00 2.55 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 445.67 168.10 0.38 1.00 2.26 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 650.51 245.37 0.38 1.00 1.92 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 551.91 208.18 0.38 1.00 2.05 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 650.25 245.27 0.38 1.00 1.92 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 650.46 245.35 0.38 1.00 1.92 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 551.82 208.14 0.38 1.00 2.05 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 650.12 245.22 0.38 1.00 1.92 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 0.50 0.06 303.12 114.34 0.38 1.00 2.75 General FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:Mixed 5.35 36002.06 0.80 0.82 0.57



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10645.90 10645.90 8.87 460.399 460.399 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00758 76.45 0.00700 59.993 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 6287.92 6287.92 5.24 271.928 271.928 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 75.00 75.00 0.00750 81.14 0.00701 59.993 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8047.29 8047.29 6.70 348.014 348.014 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 75.00 75.00 0.00751 78.32 0.00700 59.993 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 9363.73 9363.73 7.80 404.952 404.952 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00763 74.16 0.00700 59.993 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4248.05 4248.05 3.54 183.714 183.714 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 75.00 75.00 0.00772 71.59 0.00700 59.993 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6477.93 6477.93 5.40 280.146 280.146 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 75.00 75.00 0.00751 75.72 0.00700 59.993 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11762.27 11762.27 9.80 508.681 508.681 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00761 75.54 0.00700 59.993 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 6978.09 6978.09 5.81 301.777 301.777 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 75.00 75.00 0.00754 80.77 0.00701 59.993 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9110.11 9110.11 7.59 393.979 393.979 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 75.00 75.00 0.00753 78.93 0.00701 59.993 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10286.21 10286.21 8.57 444.848 444.848 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 75.00 75.00 0.00764 73.82 0.00700 59.993 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4926.27 4926.27 4.10 213.047 213.047 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 75.00 75.00 0.00774 71.04 0.00700 59.993 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 7496.00 7496.00 6.24 324.174 324.174 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 75.00 0.00753 76.18 0.00700 59.993 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 7403.11 7403.11 6.17 320.156 320.156 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 75.00 75.00 0.00751 77.10 0.00700 59.993 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 9082.85 9082.85 7.57 392.798 392.798 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 75.00 75.00 0.00750 81.32 0.00701 59.993 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12073.97 12073.97 10.06 522.159 522.159 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00759 75.54 0.00700 59.993 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 5751.49 5751.49 4.79 248.734 248.734 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 75.00 75.00 0.00768 71.86 0.00700 59.993 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 7233.99 7233.99 6.03 312.842 312.842 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 75.00 75.00 0.00751 80.77 0.00701 59.993 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11155.90 11155.90 9.29 482.458 482.458 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00761 74.16 0.00700 59.993 0.00
HEATEDBSMT 4487.46 4487.46 0.58 194.071 194.071 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 75.00 75.00 0.00942 71.04 0.00700 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 32293.57 32293.57 26.90 596.775 596.775 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 27211.97 27211.97 22.67 502.889 502.889 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00592 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 32284.31 32284.31 26.89 596.604 596.604 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 32293.39 32293.39 26.90 596.772 596.772 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 27209.05 27209.05 22.66 502.835 502.835 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00592 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 32278.61 32278.61 26.89 596.499 596.499 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 24130.18 24130.18 20.10 446.020 446.020 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00628 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 18807.91 18807.91 15.67 347.660 347.660 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00612 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 24117.90 24117.90 20.09 445.793 445.793 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00628 -43.4 0.00006 59.993 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 24129.47 24129.47 20.10 446.006 446.006 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00628 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 18804.34 18804.34 15.66 347.594 347.594 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00612 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 24111.43 24111.43 20.08 445.673 445.673 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 72.00 71.98 0.00628 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 35179.96 35179.96 29.30 650.121 650.121 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00618 -43.4 0.00006 59.993 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 35186.84 35186.84 29.31 650.248 650.248 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00618 -43.4 0.00006 59.993 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 35201.19 35201.19 29.32 650.513 650.513 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00618 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29859.58 29859.58 24.87 551.825 551.825 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29864.35 29864.35 24.88 551.913 551.913 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00606 -43.4 0.00006 59.993 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 35198.53 35198.53 29.32 650.464 650.464 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.97 0.00618 -43.4 0.00006 59.993 0.00
HEATEDBSMT 16391.50 16391.50 2.10 303.124 303.124 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 72.00 72.00 0.00837 -43.4 0.00006 59.993 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 460.40 460.40 596.78 596.78 596.7754 596.7754 596.7754 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 271.93 271.93 502.89 502.89 502.8888 502.8888 502.8888 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 348.01 348.01 596.60 596.60 596.6043 596.6043 596.6043 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 404.95 404.95 596.77 596.77 596.7721 596.7721 596.7721 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 183.71 183.71 502.83 502.83 502.8349 502.8349 502.8349 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 280.15 280.15 596.50 596.50 596.4991 596.4991 596.4991 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.68 508.68 446.02 446.02 508.6812 508.6812 508.6812 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 301.78 301.78 347.66 347.66 347.6602 347.6602 347.6602 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 393.98 393.98 445.79 445.79 445.7926 445.7926 445.7926 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 444.85 444.85 446.01 446.01 446.0064 446.0064 446.0064 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 213.05 213.05 347.59 347.59 347.5941 347.5941 347.5941 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 324.17 324.17 445.67 445.67 445.6730 445.6730 445.6730 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 522.16 522.16 650.51 650.51 650.5133 650.5133 650.5133 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 312.84 312.84 551.91 551.91 551.9130 551.9130 551.9130 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 392.80 392.80 650.25 650.25 650.2481 650.2481 650.2481 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 482.46 482.46 650.46 650.46 650.4641 650.4641 650.4641 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 248.73 248.73 551.82 551.82 551.8248 551.8248 551.8248 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 320.16 320.16 650.12 650.12 650.1208 650.1208 650.1208 1.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 194.07 194.07 303.12 303.12 303.1236 303.1236 303.1236 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 18205.701 14533.285 596.775377 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 18367.70 18362.99 596.775377 76.38 60.07 0.00750155 53.60 51.08 0.00750000 76.45 0.00700305 59.30 10.0529 75.00 0.00757170 40.4540 10637.06 0.00 18213.30 14403.86
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 45080.930 45080.930 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 45080.93 45080.93 -999. 60.37 50.12 0.00545445 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605685 35.9220 32293.57 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 16467.306 12668.590 502.888799 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 16261.25 16261.25 502.888799 77.55 60.32 0.00739428 53.60 50.88 0.00739428 81.14 0.00700699 61.00 11.9297 75.00 0.00750411 40.0968 6287.76 0.00 16474.18 12564.75
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 39322.358 39322.358 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 39322.36 39322.36 -999. 58.20 48.71 0.00522304 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00592181 35.1263 27211.97 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 18672.947 14717.139 596.604281 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 18663.00 18663.00 596.604281 76.76 60.08 0.00742061 53.60 50.93 0.00742061 78.32 0.00700461 59.99 10.0558 75.00 0.00750705 40.1124 8031.22 0.00 18680.74 14591.35
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 45070.438 45070.438 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 45070.44 45070.44 -999. 60.36 50.12 0.00545390 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605643 35.9195 32284.31 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 17874.134 14303.599 596.772095 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 18230.09 18128.76 596.772095 76.07 60.01 0.00753348 53.60 51.08 0.00750000 74.16 0.00700114 58.45 10.0530 75.00 0.00761823 40.6997 9331.79 0.00 17881.59 14178.41
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 45080.729 45080.729 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 45080.73 45080.73 -999. 60.37 50.12 0.00545444 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605684 35.9219 32293.39 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 14186.836 11355.065 502.834909 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 14585.98 14585.98 502.834909 75.08 59.57 0.00748297 53.60 51.05 0.00748297 71.59 0.00699901 57.48 11.9310 75.00 0.00771946 41.2338 4195.97 0.00 14192.76 11253.77
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 39319.053 39319.053 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 39319.05 39319.05 -999. 58.20 48.71 0.00522283 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00592164 35.1253 27209.05 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 18126.317 14510.837 596.499080 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 18322.10 18322.10 596.499080 76.35 59.90 0.00740036 53.60 50.90 0.00740036 75.72 0.00700244 59.03 10.0576 75.00 0.00750863 40.1207 6435.51 0.00 18133.88 14366.77
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 45063.987 45063.987 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 45063.99 45063.99 -999. 60.36 50.12 0.00545356 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605618 35.9180 32278.61 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 15479.382 12384.874 508.681190 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 15692.56 15585.59 508.681190 76.25 60.09 0.00754139 53.60 51.08 0.00750000 75.54 0.00700229 58.96 11.7939 75.00 0.00759025 40.5520 11730.96 0.00 15485.84 12259.89
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 35830.612 35830.612 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 35830.61 35830.61 -999. 58.37 49.42 0.00554874 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00628203 37.2298 24130.18 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 11267.060 8714.302 347.660196 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 11145.34 11145.34 347.660196 77.34 60.31 0.00743014 53.60 50.95 0.00743014 80.77 0.00700668 60.87 17.2563 75.00 0.00753420 40.2558 6976.37 0.00 11271.76 8641.79
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 29799.337 29799.337 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 29799.34 29799.34 -999. 52.07 45.56 0.00507305 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00611759 36.2618 18807.91 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 14005.327 11007.866 445.792643 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 13961.84 13961.84 445.792643 76.79 60.14 0.00744875 53.60 50.99 0.00744875 78.93 0.00700513 60.21 13.4577 75.00 0.00752360 40.1998 8983.80 0.00 14011.17 10912.91
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 35816.701 35816.701 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 35816.70 35816.70 -999. 56.45 48.36 0.00544471 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00628136 37.2259 24117.90 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 13367.502 10694.264 446.006409 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 13659.56 13537.25 446.006409 76.03 60.03 0.00755404 53.60 51.08 0.00750000 73.82 0.00700086 58.32 13.4512 75.00 0.00763976 40.8135 10280.54 0.00 13373.08 10600.48
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 35829.807 35829.807 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 35829.81 35829.81 -999. 56.45 48.36 0.00544566 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00628199 37.2296 24129.47 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 9839.192 7873.862 347.594087 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 10151.60 10094.14 347.594087 75.08 59.65 0.00753286 53.60 51.08 0.00750000 71.04 0.00699856 57.27 17.2596 75.00 0.00775243 41.4079 4753.28 0.00 9843.30 7803.45
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 29795.284 29795.284 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 29795.28 29795.28 -999. 52.06 45.56 0.00507263 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00611732 36.2602 18804.34 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 13602.345 10856.487 445.672993 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 13728.61 13728.61 445.672993 76.41 59.98 0.00743437 53.60 50.96 0.00743437 76.18 0.00700282 59.20 13.4613 75.00 0.00753217 40.2450 7466.88 0.00 13608.02 10761.86
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 35809.365 35809.365 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 35809.36 35809.36 -999. 56.44 48.35 0.00544418 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.98 0.00628100 37.2238 24111.43 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 19734.469 15789.208 650.513274 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 20000.48 19919.07 650.513274 76.25 60.06 0.00752465 53.60 51.08 0.00750000 75.54 0.00700229 58.96 9.2225 75.00 0.00756953 40.4426 12034.72 0.00 19742.70 15651.57
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 48376.030 48376.030 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 48376.03 48376.03 -999. 61.32 50.85 0.00561513 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00617905 36.6390 35201.19 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 17864.122 13823.458 551.913023 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 17662.52 17662.52 551.913023 77.30 60.26 0.00740973 53.60 50.91 0.00740973 80.77 0.00700668 60.87 10.8701 75.00 0.00750425 40.0976 7223.56 0.00 17871.58 13709.05
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 42328.219 42328.219 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 42328.22 42328.22 -999. 59.43 49.62 0.00540776 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605941 35.9338 29864.35 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 20988.654 16279.912 650.248089 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 20686.10 20686.10 650.248089 77.16 60.23 0.00742384 53.60 50.94 0.00742384 81.32 0.00700714 61.07 9.2262 75.00 0.00749895 40.0696 9082.85 0.00 20997.41 16144.99
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 48359.767 48359.767 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 48359.77 48359.77 -999. 61.32 50.84 0.00561439 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00617848 36.6357 35186.84 0.00 -999.0 -999.0
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 19501.453 15619.072 650.464051 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 19891.69 19777.98 650.464051 76.09 60.02 0.00753446 53.60 51.08 0.00750000 74.16 0.00700114 58.45 9.2232 75.00 0.00761019 40.6574 11155.90 0.00 19509.59 15481.91
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 48373.011 48373.011 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 48373.01 48373.01 -999. 61.32 50.85 0.00561500 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00617894 36.6384 35198.53 0.00 -999.0 -999.0
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 15867.249 12707.527 551.824822 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 16322.71 16282.25 551.824822 75.43 59.75 0.00751454 53.60 51.08 0.00750000 71.86 0.00699924 57.58 10.8718 75.00 0.00768405 41.0471 5711.47 0.00 15873.87 12596.41
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 42322.811 42322.811 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 42322.81 42322.81 -999. 59.42 49.61 0.00540745 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00605918 35.9325 29859.58 0.00 -999.0 -999.0
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 20080.509 15930.342 650.120848 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 20179.21 20179.21 650.120848 76.58 60.01 0.00741303 53.60 50.92 0.00741303 77.10 0.00700359 59.54 9.2280 75.00 0.00750727 40.1135 7388.97 0.00 20088.89 15794.79
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 48351.964 48351.964 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 48351.96 48351.96 -999. 61.32 50.84 0.00561403 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 71.97 0.00617821 36.6341 35179.96 0.00 -999.0 -999.0
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT 9527.677 7487.120 303.123625 -999. -999.00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 10029.92 8332.48 303.123625 74.96 61.39 0.00867069 53.60 51.08 0.00750000 71.04 0.00699856 57.27 19.7917 75.00 0.00954168 50.8208 4460.32 0.00 9531.65 7422.41
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT 29415.781 29415.781 -999. -999. -999.00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 29415.78 29415.78 -999. 49.16 47.61 0.00672978 122.00 74.82 0.00800000 -43.4 0.00006450 -43.4 -999.000 72.00 0.00837447 49.4257 16391.50 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18205.701 14533.285 596.775377 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 596.775377 0.73614280   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 18367.70 18362.99 1.0089 0.73614280 596.775377 76.38 60.07 0.00750155 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 768.039 17599.66 76.45 0.00700305 59.30 59.99331119 10.0529 75.00 0.00757625 75.00 0.00757170 40.4540 10637.06 0.00 18213.30 14403.86 0.70707073 80.00 67.00 0.01118466 13.2 56.84 56.81 0.00981979 9.2
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 45080.930 45080.930 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 596.775377 0.73614280   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 45080.93 45080.93 1.0000 -0.261081E+04 -999. 60.37 50.12 0.00545445 7.1 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 45080.93 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605685 71.97 0.00605685 35.9220 32293.57 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 16467.306 12668.590 502.888799 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 502.888799 0.62033050   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:10:00 Sensible 16261.25 16261.25 0.9875 0.62033050 502.888799 77.55 60.32 0.00739428 10.6 53.60 50.88 0.00739428 7.3 -999. -999.0 -999.0 -999.0 647.209 15614.04 81.14 0.00700699 61.00 59.99331119 11.9297 75.00 0.00750391 75.00 0.00750411 40.0968 6287.76 0.00 16474.18 12564.75 0.59583214 80.00 67.00 0.01118466 13.2 56.01 55.97 0.00952247 8.9
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 39322.358 39322.358 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 502.888799 0.62033050   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 39322.36 39322.36 1.0000 -0.261081E+04 -999. 58.20 48.71 0.00522304 6.6 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 39322.36 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00592181 71.97 0.00592181 35.1263 27211.97 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18672.947 14717.139 596.604281 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 596.604281 0.73593175   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:40:00 Sensible 18663.00 18663.00 0.9995 0.73593175 596.604281 76.76 60.08 0.00742061 10.5 53.60 50.93 0.00742061 7.4 -999. -999.0 -999.0 -999.0 767.819 17895.18 78.32 0.00700461 59.99 59.99331119 10.0558 75.00 0.00750725 75.00 0.00750705 40.1124 8031.22 0.00 18680.74 14591.35 0.70686801 80.00 67.00 0.01118466 13.2 56.53 56.51 0.00971907 9.1
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 45070.438 45070.438 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 596.604281 0.73593175   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 45070.44 45070.44 1.0000 -0.261081E+04 -999. 60.36 50.12 0.00545390 7.1 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 45070.44 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605643 71.97 0.00605643 35.9195 32284.31 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17874.134 14303.599 596.772095 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 596.772095 0.73613876   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:40:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 18230.09 18128.76 1.0199 0.73613876 596.772095 76.07 60.01 0.00753348 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 768.035 17462.06 74.16 0.00700114 58.45 59.99331119 10.0530 75.00 0.00762606 75.00 0.00761823 40.6997 9331.79 0.00 17881.59 14178.41 0.70706684 80.00 67.00 0.01118466 13.2 57.21 57.01 0.00985786 9.3
MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 45080.729 45080.729 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 596.772095 0.73613876   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 45080.73 45080.73 1.0000 -0.261081E+04 -999. 60.37 50.12 0.00545444 7.1 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 45080.73 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605684 71.97 0.00605684 35.9219 32293.39 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14186.836 11355.065 502.834909 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 502.834909 0.62026403   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:20:00 Sensible 14585.98 14585.98 1.0281 0.62026403 502.834909 75.08 59.57 0.00748297 10.3 53.60 51.05 0.00748297 7.4 -999. -999.0 -999.0 -999.0 647.139 13938.84 71.59 0.00699901 57.48 59.99331119 11.9310 75.00 0.00771765 75.00 0.00771946 41.2338 4195.97 0.00 14192.76 11253.77 0.59576829 80.00 67.00 0.01118466 13.2 58.53 57.65 0.00993494 9.5
MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 39319.053 39319.053 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 502.834909 0.62026403   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 39319.05 39319.05 1.0000 -0.261081E+04 -999. 58.20 48.71 0.00522283 6.6 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 39319.05 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00592164 71.97 0.00592164 35.1253 27209.05 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 18126.317 14510.837 596.499080 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 596.499080 0.73580198   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:30:00 Sensible 18322.10 18322.10 1.0108 0.73580198 596.499080 76.35 59.90 0.00740036 10.4 53.60 50.90 0.00740036 7.3 -999. -999.0 -999.0 -999.0 767.683 17554.42 75.72 0.00700244 59.03 59.99331119 10.0576 75.00 0.00750879 75.00 0.00750863 40.1207 6435.51 0.00 18133.88 14366.77 0.70674337 80.00 67.00 0.01118466 13.2 56.89 56.85 0.00983433 9.3
MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 45063.987 45063.987 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 596.499080 0.73580198   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 45063.99 45063.99 1.0000 -0.261081E+04 -999. 60.36 50.12 0.00545356 7.1 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 45063.99 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605618 71.97 0.00605618 35.9180 32278.61 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15479.382 12384.874 508.681190 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 508.681190 0.62747562   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 15692.56 15585.59 1.0138 0.62747562 508.681190 76.25 60.09 0.00754139 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 654.663 15037.90 75.54 0.00700229 58.96 59.99331119 11.7939 75.00 0.00761347 75.00 0.00759025 40.5520 11730.96 0.00 15485.84 12259.89 0.60269507 80.00 67.00 0.01118466 13.2 56.88 56.84 0.00982868 9.2
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 35830.612 35830.612 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 508.681190 0.62747562   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 35830.61 35830.61 1.0000 -0.261081E+04 -999. 58.37 49.42 0.00554874 6.9 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 35830.61 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00628203 71.98 0.00628203 37.2298 24130.18 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11267.060 8714.302 347.660196 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 347.660196 0.42885072   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 11145.34 11145.34 0.9892 0.42885072 347.660196 77.34 60.31 0.00743014 10.6 53.60 50.95 0.00743014 7.4 -999. -999.0 -999.0 -999.0 447.432 10697.90 80.77 0.00700668 60.87 59.99331119 17.2563 75.00 0.00753522 75.00 0.00753420 40.2558 6976.37 0.00 11271.76 8641.79 0.41191436 80.00 67.00 0.01118466 13.2 56.14 56.10 0.00956719 9.0
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 29799.337 29799.337 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 347.660196 0.42885072   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 29799.34 29799.34 1.0000 -0.261081E+04 -999. 52.07 45.56 0.00507305 5.7 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 29799.34 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00611759 71.98 0.00611759 36.2618 18807.91 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14005.327 11007.866 445.792643 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 445.792643 0.54990045   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 12:00:00 Sensible 13961.84 13961.84 0.9969 0.54990045 445.792643 76.79 60.14 0.00744875 10.5 53.60 50.99 0.00744875 7.4 -999. -999.0 -999.0 -999.0 573.727 13388.11 78.93 0.00700513 60.21 59.99331119 13.4577 75.00 0.00752844 75.00 0.00752360 40.1998 8983.80 0.00 14011.17 10912.91 0.52818354 80.00 67.00 0.01118466 13.2 56.51 56.47 0.00969863 9.1
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 35816.701 35816.701 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 445.792643 0.54990045   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 35816.70 35816.70 1.0000 -0.261081E+04 -999. 56.45 48.36 0.00544471 6.5 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 35816.70 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00628136 71.98 0.00628136 37.2259 24117.90 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13367.502 10694.264 446.006409 -999. -999.00 -999.0000 1.00000 1.00000 0.2434 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 446.006409 0.55016413   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 Sensible 13659.56 13537.25 1.0218 0.55016413 446.006409 76.03 60.03 0.00755404 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 574.002 13085.55 73.82 0.00700086 58.32 59.99331119 13.4512 75.00 0.00764028 75.00 0.00763976 40.8135 10280.54 0.00 13373.08 10600.48 0.52843681 80.00 67.00 0.01118466 13.2 57.20 57.01 0.00985547 9.3
MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 35829.807 35829.807 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 446.006409 0.55016413   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 35829.81 35829.81 1.0000 -0.261081E+04 -999. 56.45 48.36 0.00544566 6.5 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 35829.81 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00628199 71.98 0.00628199 37.2296 24129.47 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9839.192 7873.862 347.594087 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 347.594087 0.42876917   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 Sensible 10151.60 10094.14 1.0318 0.42876917 347.594087 75.08 59.65 0.00753286 10.3 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 447.347 9704.26 71.04 0.00699856 57.27 59.99331119 17.2596 75.00 0.00774229 75.00 0.00775243 41.4079 4753.28 0.00 9843.30 7803.45 0.41183603 80.00 67.00 0.01118466 13.2 58.46 57.62 0.00992989 9.5
MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 29795.284 29795.284 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 347.594087 0.42876917   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 29795.28 29795.28 1.0000 -0.261081E+04 -999. 52.06 45.56 0.00507263 5.7 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 29795.28 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00611732 71.98 0.00611732 36.2602 18804.34 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13602.345 10856.487 445.672993 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 445.672993 0.54975285   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 13728.61 13728.61 1.0093 0.54975285 445.672993 76.41 59.98 0.00743437 10.4 53.60 50.96 0.00743437 7.4 -999. -999.0 -999.0 -999.0 573.573 13155.04 76.18 0.00700282 59.20 59.99331119 13.4613 75.00 0.00753238 75.00 0.00753217 40.2450 7466.88 0.00 13608.02 10761.86 0.52804177 80.00 67.00 0.01118466 13.2 56.83 56.80 0.00981919 9.2
MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 35809.365 35809.365 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 445.672993 0.54975285   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 11:10:00 Sensible 35809.36 35809.36 1.0000 -0.261081E+04 -999. 56.44 48.35 0.00544418 6.5 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 35809.36 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.98 0.00628100 71.98 0.00628100 37.2238 24111.43 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 19734.469 15789.208 650.513274 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 650.513274 0.80243033   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 20000.48 19919.07 1.0135 0.80243033 650.513274 76.25 60.06 0.00752465 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 837.198 19163.28 75.54 0.00700229 58.96 59.99331119 9.2225 75.00 0.00759245 75.00 0.00756953 40.4426 12034.72 0.00 19742.70 15651.57 0.77074040 80.00 67.00 0.01118466 13.2 56.92 56.87 0.00983995 9.3
MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 48376.030 48376.030 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 650.513274 0.80243033   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 48376.03 48376.03 1.0000 -0.261081E+04 -999. 61.32 50.85 0.00561513 7.3 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 48376.03 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00617905 71.97 0.00617905 36.6390 35201.19 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 17864.122 13823.458 551.913023 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 551.913023 0.68080356   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:20:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 15:30:00 Sensible 17662.52 17662.52 0.9887 0.68080356 551.913023 77.30 60.26 0.00740973 10.5 53.60 50.91 0.00740973 7.3 -999. -999.0 -999.0 -999.0 710.302 16952.21 80.77 0.00700668 60.87 59.99331119 10.8701 75.00 0.00750536 75.00 0.00750425 40.0976 7223.56 0.00 17871.58 13709.05 0.65391696 80.00 67.00 0.01118466 13.2 56.16 56.12 0.00957206 9.0
MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 42328.219 42328.219 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 551.913023 0.68080356   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 42328.22 42328.22 1.0000 -0.261081E+04 -999. 59.43 49.62 0.00540776 6.9 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 42328.22 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605941 71.97 0.00605941 35.9338 29864.35 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 20988.654 16279.912 650.248089 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 650.248089 0.80210322   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 20686.10 20686.10 0.9856 0.80210322 650.248089 77.16 60.23 0.00742384 10.5 53.60 50.94 0.00742384 7.4 -999. -999.0 -999.0 -999.0 836.857 19849.24 81.32 0.00700714 61.07 59.99331119 9.2262 75.00 0.00749895 75.00 0.00749895 40.0696 9082.85 0.00 20997.41 16144.99 0.77042621 80.00 67.00 0.01118466 13.2 56.17 56.15 0.00958907 9.0
MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 48359.767 48359.767 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 650.248089 0.80210322   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 48359.77 48359.77 1.0000 -0.261081E+04 -999. 61.32 50.84 0.00561439 7.3 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 48359.77 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00617848 71.97 0.00617848 36.6357 35186.84 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 19501.453 15619.072 650.464051 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 650.464051 0.80236962   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 19891.69 19777.98 1.0200 0.80236962 650.464051 76.09 60.02 0.00753446 10.5 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 837.135 19054.55 74.16 0.00700114 58.45 59.99331119 9.2232 75.00 0.00761019 75.00 0.00761019 40.6574 11155.90 0.00 19509.59 15481.91 0.77068208 80.00 67.00 0.01118466 13.2 57.17 57.00 0.00986071 9.3
MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 48373.011 48373.011 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 650.464051 0.80236962   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 48373.01 48373.01 1.0000 -0.261081E+04 -999. 61.32 50.85 0.00561500 7.3 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 48373.01 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00617894 71.97 0.00617894 36.6384 35198.53 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15867.249 12707.527 551.824822 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 551.824822 0.68069476   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 Sensible 16322.71 16282.25 1.0287 0.68069476 551.824822 75.43 59.75 0.00751454 10.4 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 710.188 15612.53 71.86 0.00699924 57.58 59.99331119 10.8718 75.00 0.00767833 75.00 0.00768405 41.0471 5711.47 0.00 15873.87 12596.41 0.65381246 80.00 67.00 0.01118466 13.2 58.10 57.45 0.00991474 9.5
MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 42322.811 42322.811 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 551.824822 0.68069476   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 42322.81 42322.81 1.0000 -0.261081E+04 -999. 59.42 49.61 0.00540745 6.9 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 42322.81 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00605918 71.97 0.00605918 35.9325 29859.58 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 20080.509 15930.342 650.120848 -999. -999.00 -999.0000 1.00000 1.00000 0.2433 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 650.120848 0.80194626   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 Sensible 20179.21 20179.21 1.0049 0.80194626 650.120848 76.58 60.01 0.00741303 10.5 53.60 50.92 0.00741303 7.3 -999. -999.0 -999.0 -999.0 836.693 19342.52 77.10 0.00700359 59.54 59.99331119 9.2280 75.00 0.00750745 75.00 0.00750727 40.1135 7388.97 0.00 20088.89 15794.79 0.77027545 80.00 67.00 0.01118466 13.2 56.69 56.67 0.00977239 9.2
MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 48351.964 48351.964 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 650.120848 0.80194626   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 48351.96 48351.96 1.0000 -0.261081E+04 -999. 61.32 50.84 0.00561403 7.3 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 48351.96 -43.4 0.00006450 -43.4 59.99331119 -999.000 71.97 0.00617821 71.97 0.00617821 36.6341 35179.96 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
DX COOLING COIL_UNITHEATEDBSMT Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT HEATEDBSMT Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 9527.677 7487.120 303.123625 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0740 SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 303.123625 0.37391334   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:10:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:00:00 FAIRBANKS INTL ARPT ANN CLG .4% CONDNS DB=>MWB 7/21 20:40:00 Sensible 10029.92 8332.48 1.0527 0.37391334 303.123625 74.96 61.39 0.00867069 11.0 53.60 51.08 0.00750000 7.4 -999. -999.0 -999.0 -999.0 390.114 9639.80 71.04 0.00699856 57.27 59.99331119 19.7917 75.00 0.00941889 75.00 0.00954168 50.8208 4460.32 0.00 9531.65 7422.41 0.35914659 80.00 67.00 0.01118466 13.2 56.50 56.46 0.00969685 9.1
MAIN FUEL HEATING COIL_UNITHEATEDBSMT Coil:Heating:Fuel AirLoop AirLoopHVAC CENTRAL SYSTEM_UNITHEATEDBSMT HEATEDBSMT Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes No unknown No 29415.781 29415.781 -999. -999. -999.00 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0740 SUPPLY FAN_UNITHEATEDBSMT Fan:OnOff 303.123625 0.37391334   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 unknown unknown FAIRBANKS INTL ARPT ANN HTG 99.6% CONDNS DB 1/21 04:00:00 Sensible 29415.78 29415.78 1.0000 -0.261081E+04 -999. 49.16 47.61 0.00672978 6.3 122.00 74.82 0.00800000 17.0 -999. -999.0 -999.0 -999.0 0.000 29415.78 -43.4 0.00006450 -43.4 59.99331119 -999.000 72.00 0.00837447 72.00 0.00837447 49.4257 16391.50 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 3293.17 7329.83 2744.17
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1664.67 7402.00 1373.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 3269.83 7118.67 2666.17
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3404.33 7578.67 3054.67
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1815.17 7694.17 1694.17
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3337.33 7389.00 2944.83
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 3400.83 6926.00 2666.83
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1653.50 6828.83 1172.83
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 3429.00 6638.83 2588.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 3518.00 7179.83 3008.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1728.83 7170.33 1491.50
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 3551.67 6956.83 2896.00
LIVING_UNIT3_BACKROW_TOPFLOOR 4176.50 7130.33 3504.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 4013.33 6905.17 3225.17
LIVING_UNIT1_FRONTROW_TOPFLOOR 4023.00 7168.50 3326.67
LIVING_UNIT2_BACKROW_TOPFLOOR 3130.33 7368.83 2796.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 2929.50 7145.00 2434.00
LIVING_UNIT1_BACKROW_TOPFLOOR 4124.33 7359.17 3579.17
HEATEDBSMT 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 4703.17 7836.33 3627.83
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 0.00 0.00 0.00 0.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.436 0.000 0.385
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.384 0.000 0.385
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.436 0.000 0.385
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.435 0.000 0.385
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.384 0.000 0.385
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.436 0.000 0.385
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.191 0.000 0.386
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.386
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.192 0.000 0.386
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.191 0.000 0.386
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.139 0.000 0.386
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.191 0.000 0.386
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.436 0.000 0.385
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.437 0.000 0.385
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.436 0.000 0.385
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.384 0.000 0.385
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.384 0.000 0.385
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.436 0.000 0.385
HEATEDBSMT     58539.52        
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.000 0.001 0.000 0.010
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.000 0.000 0.000 0.010
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.000 0.001 0.000 0.010
HEATEDBSMT     58539.52        
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 58539.52 7794.39 0.0000 0.000
Total Facility   24.79 36.00 242278.90 29404.35 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 38484476.94 72490445.14 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 33904584.98 67910553.18 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 38523025.54 72528993.74 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 38457250.26 72463218.46 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 33871724.24 67877692.45 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 38492873.15 72498841.36 31713442.25 618.50 1141.50 7048.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 16893916.39 50902005.04 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 12299047.43 46307136.08 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 16911188.54 50919277.19 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 16881162.97 50889251.62 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 12284633.76 46292722.41 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 16897130.84 50905219.49 31713442.25 616.67 1140.17 7051.17 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 38541896.58 72552107.93 31713442.25 614.50 1139.00 7054.50 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 38568695.52 72578906.87 31713442.25 614.50 1139.00 7054.50 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 38529898.36 72540109.71 31713442.25 614.50 1139.00 7054.50 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 33917994.45 67928205.80 31713442.25 614.50 1139.00 7054.50 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 33947719.64 67957930.99 31713442.25 614.50 1139.00 7054.50 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 38506482.18 72516693.53 31713442.25 614.50 1139.00 7054.50 0.00
HEATEDBSMT 0.00 0.00 0.00 0.00 0.00 31713442.25 8808.00 0.00 0.00 0.00
Total Facility 0.00 0.612146E+09 0.612146E+09 0.535914E+09 0.114806E+10 0.602555E+09 8808.00 1145.50 7054.50 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 72.8023 137.1324 59.9933 618.50 1141.50 7048.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 64.1384 128.4685 59.9933 618.50 1141.50 7048.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 72.8752 137.2054 59.9933 618.50 1141.50 7048.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 72.7508 137.0809 59.9933 618.50 1141.50 7048.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 64.0762 128.4064 59.9933 618.50 1141.50 7048.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 72.8182 137.1483 59.9933 618.50 1141.50 7048.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 31.9588 96.2929 59.9933 616.67 1140.17 7051.17
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 23.2665 87.6007 59.9933 616.67 1140.17 7051.17
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 31.9914 96.3256 59.9933 616.67 1140.17 7051.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 31.9346 96.2688 59.9933 616.67 1140.17 7051.17
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 23.2392 87.5734 59.9933 616.67 1140.17 7051.17
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 31.9648 96.2990 59.9933 616.67 1140.17 7051.17
LIVING_UNIT3_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 72.9109 137.2491 59.9933 614.50 1139.00 7054.50
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 72.9616 137.2998 59.9933 614.50 1139.00 7054.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 72.8882 137.2264 59.9933 614.50 1139.00 7054.50
LIVING_UNIT2_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 64.1637 128.5019 59.9933 614.50 1139.00 7054.50
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 64.2200 128.5581 59.9933 614.50 1139.00 7054.50
LIVING_UNIT1_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 72.8439 137.1821 59.9933 614.50 1139.00 7054.50
Total Facility 0.0000 1158.0150 1158.0150 1013.8047 2171.8197 1079.8796 8808.00 1145.50 7054.50


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 34005968.20 34005968.20 31713442.25 618.50 1141.50 7048.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 34008088.65 34008088.65 31713442.25 616.67 1140.17 7051.17 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 34010211.35 34010211.35 31713442.25 614.50 1139.00 7054.50 0.00
CENTRAL SYSTEM_UNITHEATEDBSMT 0.00 0.00 0.00 31713442.25 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 64.3302 64.3302 59.9933 618.50 1141.50 7048.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 64.3342 64.3342 59.9933 616.67 1140.17 7051.17
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 64.3382 64.3382 59.9933 614.50 1139.00 7054.50


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNITHEATEDBSMT 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Surfaces by Class

Total Outdoors
Wall 82 54
Floor 29 3
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 19
Conditioned Zones 19
Unconditioned Zones 2
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2003
Defaulted Fields 1803
Fields with Defaults 6671
Autosized Fields 357
Autosizable Fields 524
Autocalculated Fields 161
Autocalculatable Fields 349



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
Electricity:Building 116031.81 9049.20 02-JAN-03:10 22208.02 01-JAN-20:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
Electricity:SpaceType:GENERAL 116031.81 9049.20 02-JAN-03:10 22208.02 01-JAN-20:10
InteriorLights:Electricity 18100.85 405.35 01-JAN-00:10 5896.05 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 18100.85 405.35 01-JAN-00:10 5896.05 01-JAN-19:10
General:InteriorLights:Electricity 18100.85 405.35 01-JAN-00:10 5896.05 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 18100.85 405.35 01-JAN-00:10 5896.05 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5097.08 391.97 02-JAN-03:10 975.43 01-JAN-20:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 811.89 18.18 01-JAN-00:10 264.46 01-JAN-19:10
Electricity:Zone:HEATEDBSMT 24284.35 1963.49 01-JAN-09:10 4650.26 01-JAN-20:10
InteriorLights:Electricity:Zone:HEATEDBSMT 3486.76 78.08 01-JAN-00:10 1135.75 01-JAN-19:10
General:InteriorLights:Electricity:Zone:HEATEDBSMT 3486.76 78.08 01-JAN-00:10 1135.75 01-JAN-19:10
InteriorEquipment:Electricity 97930.96 8367.37 02-JAN-04:10 16311.97 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
InteriorEquipment:Electricity:SpaceType:GENERAL 97930.96 8367.37 02-JAN-04:10 16311.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity 1138.84 5.81 02-JAN-03:10 291.20 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 1138.84 5.81 02-JAN-03:10 291.20 01-JAN-11:10
gas_range:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_range:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity 44924.98 3925.09 01-JAN-09:10 7591.70 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
gas_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 44924.98 3925.09 01-JAN-09:10 7591.70 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 35164.90 3072.35 01-JAN-09:10 5942.38 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 35164.90 3072.35 01-JAN-09:10 5942.38 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4285.19 362.45 02-JAN-04:10 710.97 01-JAN-20:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
gas_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 63.27 0.32 02-JAN-03:10 16.18 01-JAN-11:10
gas_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
gas_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2495.83 218.06 01-JAN-09:10 421.76 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 798.18 69.74 01-JAN-09:10 134.88 01-JAN-20:10
InteriorEquipment:Electricity:Zone:HEATEDBSMT 20797.59 1817.08 01-JAN-09:10 3514.51 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:HEATEDBSMT 20797.59 1817.08 01-JAN-09:10 3514.51 01-JAN-20:10
Fans:Electricity 14316.56 814.29 23-MAY-00:40 3501.54 12-JAN-10:00
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:HEATEDBSMT 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
ElectricityPurchased:Plant 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
Cogeneration:ElectricityPurchased 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
General:Cogeneration:ElectricityPurchased 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
ElectricityNet:Plant 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
Cogeneration:ElectricityNet 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
General:Cogeneration:ElectricityNet 142209.27 10824.31 14-AUG-12:30 36622.87 29-JUL-19:10
Electricity:HVAC 20143.16 814.29 23-MAY-00:40 13932.27 29-JUL-17:10
Ventilation:Fans:Electricity 7133.15 814.29 01-JAN-00:10 814.29 01-JAN-00:10
General:Fans:Electricity 7183.41 0.00 23-MAY-00:40 2687.25 12-JAN-10:00
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:Electricity 5826.60 0.00 01-JAN-00:10 11031.64 29-JUL-17:10
General:Cooling:Electricity 5826.60 0.00 01-JAN-00:10 11031.64 29-JUL-17:10
Electricity:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 18874.08 2752.05 31-MAY-03:30 795963.37 12-JAN-09:50
NaturalGas:Building 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
NaturalGas:SpaceType:GENERAL 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
InteriorEquipment:NaturalGas 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:SpaceType:GENERAL 1651.42 2752.05 02-JAN-03:10 43905.48 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas 792.69 403.80 02-JAN-03:10 20254.25 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_dryer:InteriorEquipment:NaturalGas:SpaceType:GENERAL 792.69 403.80 02-JAN-03:10 20254.25 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas 674.43 651.88 01-JAN-02:10 27685.38 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_range:InteriorEquipment:NaturalGas:SpaceType:GENERAL 674.43 651.88 01-JAN-02:10 27685.38 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas 184.30 1609.08 01-JAN-09:10 3112.21 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
gas_mels:InteriorEquipment:NaturalGas:SpaceType:GENERAL 184.30 1609.08 01-JAN-09:10 3112.21 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 91.75 152.89 02-JAN-03:10 2439.19 01-JAN-17:10
gas_dryer:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 44.04 22.43 02-JAN-03:10 1125.24 01-JAN-11:10
gas_range:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 37.47 36.22 01-JAN-02:10 1538.08 01-JAN-17:10
gas_mels:InteriorEquipment:NaturalGas:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 10.24 89.39 01-JAN-09:10 172.90 01-JAN-20:10
NaturalGas:HVAC 13213.37 0.00 17-APR-19:10 596385.85 12-JAN-10:00
Heating:NaturalGas 13213.37 0.00 17-APR-19:10 596385.85 12-JAN-10:00
General:Heating:NaturalGas 13213.37 0.00 17-APR-19:10 596385.85 12-JAN-10:00
NaturalGas:Plant 4009.29 0.00 01-JAN-00:10 178233.21 11-MAR-09:00
WaterSystems:NaturalGas 4009.29 0.00 01-JAN-00:10 178233.21 11-MAR-09:00
Water Heater:WaterSystems:NaturalGas 4009.29 0.00 01-JAN-00:10 178233.21 11-MAR-09:00


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:Water 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Facility 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
MainsWater:Plant 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Domestic Hot Water:WaterSystems:MainsWater 49522.55 0.01 02-JAN-02:10 0.18 01-JAN-08:10
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 2492745.55 1573.61 23-AUG-03:00 1001789.40 12-JAN-10:00
EnergyTransfer:Building 1159204.15 0.00 23-MAY-00:40 486277.58 12-JAN-10:00
EnergyTransfer:Zone:HEATEDBSMT 46747.66 0.00 17-APR-19:10 15988.83 12-JAN-04:00
Heating:EnergyTransfer 1077367.30 0.00 17-APR-19:10 486277.58 12-JAN-10:00
Heating:EnergyTransfer:Zone:HEATEDBSMT 45314.70 0.00 17-APR-19:10 15988.83 12-JAN-04:00
General:Heating:EnergyTransfer 1077367.30 0.00 17-APR-19:10 486277.58 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:HEATEDBSMT 45314.70 0.00 17-APR-19:10 15988.83 12-JAN-04:00
Cooling:EnergyTransfer 81836.85 0.00 01-JAN-00:10 139429.95 11-JUL-18:10
Cooling:EnergyTransfer:Zone:HEATEDBSMT 1432.96 0.00 01-JAN-00:10 4296.45 06-JUL-20:10
General:Cooling:EnergyTransfer 81836.85 0.00 01-JAN-00:10 139429.95 11-JUL-18:10
General:Cooling:EnergyTransfer:Zone:HEATEDBSMT 1432.96 0.00 01-JAN-00:10 4296.45 06-JUL-20:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 69069.72 0.00 22-MAR-14:30 29354.89 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 64484.48 0.00 22-MAR-14:30 29354.89 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 64484.48 0.00 22-MAR-14:30 29354.89 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4585.24 0.00 01-JAN-00:10 10061.32 11-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4585.24 0.00 01-JAN-00:10 10061.32 11-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 55554.89 0.00 20-MAR-14:00 24652.48 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 52307.14 0.00 20-MAR-14:00 24652.48 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 52307.14 0.00 20-MAR-14:00 24652.48 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3247.75 0.00 01-JAN-00:10 6570.19 29-JUL-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 3247.75 0.00 01-JAN-00:10 6570.19 29-JUL-15:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 68256.07 0.00 20-MAR-13:40 29358.02 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 63462.82 0.00 20-MAR-13:40 29358.02 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 63462.82 0.00 20-MAR-13:40 29358.02 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4793.25 0.00 01-JAN-00:10 8691.63 22-JUL-11:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4793.25 0.00 01-JAN-00:10 8691.63 22-JUL-11:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 70014.49 0.00 11-APR-16:10 29360.33 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 66842.75 0.00 11-APR-16:10 29360.33 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 66842.75 0.00 11-APR-16:10 29360.33 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3171.74 0.00 01-JAN-00:10 9193.23 11-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3171.74 0.00 01-JAN-00:10 9193.23 11-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 56714.19 0.00 17-APR-16:10 24655.27 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 54732.59 0.00 17-APR-16:10 24655.27 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 54732.59 0.00 17-APR-16:10 24655.27 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1981.60 0.00 01-JAN-00:10 5050.02 29-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1981.60 0.00 01-JAN-00:10 5050.02 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 69137.08 0.00 17-APR-11:20 29357.67 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 65790.62 0.00 17-APR-11:20 29357.67 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 65790.62 0.00 17-APR-11:20 29357.67 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3346.46 0.00 01-JAN-00:10 7154.99 07-JUL-08:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 3346.46 0.00 01-JAN-00:10 7154.99 07-JUL-08:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 53108.40 0.00 20-MAR-13:30 21949.30 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 46665.07 0.00 20-MAR-13:30 21949.30 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 46665.07 0.00 20-MAR-13:30 21949.30 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6443.33 0.00 01-JAN-00:10 11030.43 06-JUL-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 6443.33 0.00 01-JAN-00:10 11030.43 06-JUL-18:30
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 39047.93 0.00 20-MAR-12:50 17023.70 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 34000.69 0.00 20-MAR-12:50 17023.70 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 34000.69 0.00 20-MAR-12:50 17023.70 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5047.24 0.00 01-JAN-00:10 7060.00 29-JUL-15:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5047.24 0.00 01-JAN-00:10 7060.00 29-JUL-15:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 52929.53 0.00 20-MAR-12:10 21952.62 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 45777.07 0.00 20-MAR-12:10 21952.62 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 45777.07 0.00 20-MAR-12:10 21952.62 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7152.46 0.00 01-JAN-00:10 9887.37 22-JUL-11:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7152.46 0.00 01-JAN-00:10 9887.37 22-JUL-11:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 53728.02 0.00 06-APR-17:50 21955.59 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 49165.58 0.00 06-APR-17:50 21955.59 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 49165.58 0.00 06-APR-17:50 21955.59 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4562.43 0.00 01-JAN-00:10 9894.16 11-JUL-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4562.43 0.00 01-JAN-00:10 9894.16 11-JUL-18:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 39777.10 0.00 06-APR-18:10 17027.39 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 36513.44 0.00 06-APR-18:10 17027.39 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 36513.44 0.00 06-APR-18:10 17027.39 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3263.66 0.00 01-JAN-00:10 5420.72 29-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3263.66 0.00 01-JAN-00:10 5420.72 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 53431.99 0.00 06-APR-12:40 21952.82 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 48225.99 0.00 06-APR-12:40 21952.82 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 48225.99 0.00 06-APR-12:40 21952.82 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5206.00 0.00 01-JAN-00:10 8195.36 11-JUL-09:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5206.00 0.00 01-JAN-00:10 8195.36 11-JUL-09:40
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 76879.58 0.00 17-APR-11:50 31976.51 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 72213.42 0.00 17-APR-11:50 31976.51 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 72213.42 0.00 17-APR-11:50 31976.51 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4666.16 0.00 01-JAN-00:10 7887.63 22-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4666.16 0.00 01-JAN-00:10 7887.63 22-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 75685.08 0.00 20-MAR-14:00 31975.75 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 69691.35 0.00 20-MAR-14:00 31975.75 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 69691.35 0.00 20-MAR-14:00 31975.75 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5993.73 0.00 01-JAN-00:10 9762.91 22-JUL-11:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5993.73 0.00 01-JAN-00:10 9762.91 22-JUL-11:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 76346.28 0.00 22-MAR-15:00 31973.30 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 70806.36 0.00 22-MAR-15:00 31973.30 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 70806.36 0.00 22-MAR-15:00 31973.30 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5539.93 0.00 01-JAN-00:10 11393.04 11-JUL-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5539.93 0.00 01-JAN-00:10 11393.04 11-JUL-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 63350.40 0.00 17-APR-15:40 27038.60 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 60356.37 0.00 17-APR-15:40 27038.60 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 60356.37 0.00 17-APR-15:40 27038.60 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2994.03 0.00 01-JAN-00:10 6381.94 29-JUL-20:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2994.03 0.00 01-JAN-00:10 6381.94 29-JUL-20:00
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 61818.23 0.00 06-APR-12:30 27035.10 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 57665.14 0.00 06-APR-12:30 27035.10 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 57665.14 0.00 06-APR-12:30 27035.10 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4153.09 0.00 01-JAN-00:10 7621.56 21-JUL-16:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4153.09 0.00 01-JAN-00:10 7621.56 21-JUL-16:00
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 77607.52 0.00 11-APR-16:10 31978.55 12-JAN-10:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 73351.73 0.00 11-APR-16:10 31978.55 12-JAN-10:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 73351.73 0.00 11-APR-16:10 31978.55 12-JAN-10:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4255.79 0.00 01-JAN-00:10 10754.79 11-JUL-18:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4255.79 0.00 01-JAN-00:10 10754.79 11-JUL-18:30
PlantLoopHeatingDemand:Facility 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
PlantLoopHeatingDemand:Plant 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
WaterSystems:PlantLoopHeatingDemand 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
General:WaterSystems:PlantLoopHeatingDemand 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
EnergyTransfer:HVAC 1148807.46 0.00 23-MAY-00:40 477108.68 12-JAN-10:00
HeatingCoils:EnergyTransfer 1057069.38 0.00 17-APR-19:10 477108.68 12-JAN-10:00
CoolingCoils:EnergyTransfer 91738.09 0.00 01-JAN-00:10 152420.32 29-JUL-19:10
EnergyTransfer:Plant 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
WaterSystems:EnergyTransfer 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 184733.94 1518.14 05-SEP-03:00 43205.13 13-MAY-09:00
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.000 0.000 64484.302 -381.85 0.000 0.000 3115.715 2772.145 14573.293 6792.089 0.000 32.840 0.000 0.000 -12875.41 0.000 -61064.88 -13244.85
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.000 0.000 52306.997 -270.47 0.000 0.000 3110.886 2772.145 14573.293 4050.663 0.000 31.131 0.000 0.000 -5116.34 0.000 -57036.28 -11444.73
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.000 0.000 63462.644 -399.17 0.000 0.000 3111.239 2772.145 14573.293 8244.291 0.000 32.840 0.000 0.000 -12572.53 0.000 -61157.02 -13673.66
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.000 0.000 66842.578 -264.14 0.000 0.000 3118.823 2772.145 14573.293 3843.686 0.000 32.840 0.000 0.000 -13630.96 0.000 -60975.05 -13405.60
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.000 0.000 54732.454 -165.02 0.000 0.000 3115.760 2772.145 14573.293 819.012 0.000 31.131 0.000 0.000 -5664.97 0.000 -56925.07 -11472.14
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.000 0.000 65790.446 -278.69 0.000 0.000 3115.147 2772.145 14573.293 5209.534 0.000 32.840 0.000 0.000 -13238.42 0.000 -61062.18 -13846.33
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.000 0.000 46664.933 -536.59 0.000 0.000 3094.016 2772.145 14573.293 6705.339 0.000 24.513 0.000 0.000 -13040.53 0.000 -42126.44 -12223.92
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.000 0.000 34000.591 -420.32 0.000 0.000 3083.364 2772.145 14573.293 4008.215 0.000 22.825 0.000 0.000 -5192.48 0.000 -38112.96 -10107.74
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.000 0.000 45776.937 -595.64 0.000 0.000 3089.202 2772.145 14573.293 8131.527 0.000 24.514 0.000 0.000 -12727.14 0.000 -42199.95 -12288.06
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.000 0.000 49165.457 -379.95 0.000 0.000 3097.881 2772.145 14573.293 3768.640 0.000 24.513 0.000 0.000 -13780.51 0.000 -42058.26 -13000.70
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.000 0.000 36513.352 -271.79 0.000 0.000 3090.981 2772.145 14573.293 790.123 0.000 22.825 0.000 0.000 -5735.59 0.000 -38018.17 -10745.28
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.000 0.000 48225.861 -433.54 0.000 0.000 3094.827 2772.145 14573.293 5115.516 0.000 24.514 0.000 0.000 -13383.84 0.000 -42125.07 -13091.24
LIVING_UNIT3_BACKROW_TOPFLOOR 0.000 0.000 72213.249 -388.59 0.000 0.000 3108.323 2772.145 14573.293 5133.114 0.000 32.121 0.000 0.000 -13296.81 0.000 -61230.49 -18638.78
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.000 0.000 69691.167 -499.14 0.000 0.000 3104.459 2772.145 14573.293 8161.597 0.000 32.121 0.000 0.000 -12630.30 0.000 -61314.87 -18395.88
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.000 0.000 70806.181 -461.35 0.000 0.000 3108.380 2772.145 14573.293 6728.881 0.000 32.121 0.000 0.000 -12938.68 0.000 -61219.93 -18322.45
LIVING_UNIT2_BACKROW_TOPFLOOR 0.000 0.000 60356.239 -249.34 0.000 0.000 3107.893 2772.145 14573.293 796.336 0.000 30.450 0.000 0.000 -5691.17 0.000 -57090.30 -15860.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.000 0.000 57665.001 -345.86 0.000 0.000 3102.676 2772.145 14573.293 4019.827 0.000 30.450 0.000 0.000 -5143.83 0.000 -57192.37 -15674.09
LIVING_UNIT1_BACKROW_TOPFLOOR 0.000 0.000 73351.558 -354.41 0.000 0.000 3111.397 2772.145 14573.293 3779.769 0.000 32.121 0.000 0.000 -13687.70 0.000 -61141.62 -18535.15
HEATEDBSMT 0.000 0.000 45314.702 -119.33 0.000 0.000 0.000 11905.243 48750.612 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 -104537.69
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 29519.426 72051.266 0.000 0.000 0.000 -101570.69 -0.31
Total Facility 0.000 0.000 1077364.651 -6815.19 0.000 0.000 55880.969 61803.859 311069.882 86098.159 0.000 30046.137 72051.266 0.000 -190347.21 0.000 -1063621.59 -358509.44


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11-JUL-18:10 0.00 0.00 0.00 -0.8 0.00 0.00 426.77 814.22 2673.33 6355.65 0.00 513.57 0.00 0.00 0.00 0.00 0.00 -722.5
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 29-JUL-15:30 0.00 0.00 0.00 -0.5 0.00 0.00 115.09 201.62 1710.26 2984.99 0.00 1188.56 369.87 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 22-JUL-11:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 116.32 1627.30 7388.15 0.00 287.36 0.00 0.00 0.00 0.00 0.00 -840.6
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11-JUL-18:10 0.00 0.00 0.00 -0.8 0.00 0.00 426.77 814.22 2673.33 6372.51 0.00 513.57 0.00 0.00 0.00 0.00 0.00 -1607.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUL-19:00 0.00 0.00 0.00 -0.4 0.00 0.00 426.77 902.34 2361.48 377.15 0.00 722.40 259.77 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 07-JUL-08:35 0.00 0.00 0.00 -0.6 0.00 0.00 194.42 170.60 1628.02 7839.31 0.00 0.00 0.00 0.00 0.00 0.00 -643.6 -2031.9
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-JUL-18:30 0.00 0.00 0.00 -0.9 0.00 0.00 426.72 814.22 2673.33 6566.06 0.00 71.08 479.22 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 29-JUL-15:30 0.00 0.00 0.00 -0.6 0.00 0.00 115.08 201.62 1710.26 2966.85 0.00 841.38 1224.98 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 22-JUL-11:35 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 116.32 1627.30 7340.40 0.00 227.96 462.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11-JUL-18:19 0.00 0.00 0.00 -0.8 0.00 0.00 426.73 814.22 2673.33 6132.36 0.00 348.34 0.00 0.00 0.00 0.00 0.00 -499.1
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 29-JUL-19:00 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 902.34 2361.48 370.70 0.00 461.01 898.33 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11-JUL-09:30 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 116.32 1565.39 6860.16 0.00 0.00 0.00 0.00 0.00 0.00 -313.2 -146.1
LIVING_UNIT3_BACKROW_TOPFLOOR 22-JUL-10:35 0.00 0.00 0.00 -0.7 0.00 0.00 115.09 116.32 1586.13 5675.29 0.00 0.00 502.11 0.00 0.00 0.00 -105.5 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 22-JUL-11:35 0.00 0.00 0.00 -0.8 0.00 0.00 115.09 116.32 1627.30 7330.83 0.00 281.33 294.03 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11-JUL-18:10 0.00 0.00 0.00 -0.9 0.00 0.00 426.77 814.22 2673.33 6301.72 0.00 505.35 671.36 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 29-JUL-19:00 0.00 0.00 0.00 -0.5 0.00 0.00 426.77 902.34 2361.48 362.91 0.00 713.69 1614.62 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 21-JUL-15:04 0.00 0.00 0.00 -0.6 0.00 0.00 115.09 201.62 1679.50 1362.76 0.00 1834.08 2429.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11-JUL-18:34 0.00 0.00 0.00 -0.9 0.00 0.00 426.77 814.22 2673.33 5915.03 0.00 490.46 436.43 0.00 0.00 0.00 0.00 0.00
HEATEDBSMT 06-JUL-20:10 0.00 0.00 0.00 -0.4 0.00 0.00 0.00 3875.19 8232.35 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -7809.1
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 11-JUL-18:10 0.00 0.00 0.00 -11.6 0.00 0.00 7681.70 18152.75 55830.48 46441.14 0.00 8058.46 46704.51 0.00 0.00 0.00 -43443.2 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 29354.49 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4457.9 0.00 -22690.6 -4015.0
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 24652.12 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1803.1 0.00 -21024.8 -3633.2
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 29357.61 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4457.9 0.00 -22690.6 -4018.2
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 29359.92 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4457.8 0.00 -22690.6 -4020.5
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 24654.90 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1803.1 0.00 -21024.8 -3636.0
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12-JAN-09:00 0.00 0.00 29357.26 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4457.9 0.00 -22690.6 -4017.8
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 21948.87 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4450.0 0.00 -14857.7 -4450.2
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 17023.33 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1801.8 0.00 -13191.1 -3839.4
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 21952.19 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4450.0 0.00 -14857.7 -4453.5
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 21955.15 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4449.9 0.00 -14857.7 -4456.6
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 17027.01 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1801.8 0.00 -13191.1 -3843.2
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12-JAN-09:00 0.00 0.00 21952.39 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4450.0 0.00 -14857.7 -4453.8
LIVING_UNIT3_BACKROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 31976.06 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4412.6 0.00 -22710.3 -6662.1
LIVING_UNIT3_FRONTROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 31975.30 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4412.6 0.00 -22710.3 -6661.4
LIVING_UNIT1_FRONTROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 31972.85 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4412.6 0.00 -22710.3 -6658.9
LIVING_UNIT2_BACKROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 27038.20 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1785.1 0.00 -21042.9 -6019.2
LIVING_UNIT2_FRONTROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 27034.70 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -1785.1 0.00 -21042.9 -6015.6
LIVING_UNIT1_BACKROW_TOPFLOOR 12-JAN-09:00 0.00 0.00 31978.11 0.00 0.00 0.00 127.29 116.32 1565.39 0.00 0.00 0.00 0.00 0.00 -4412.5 0.00 -22710.3 -6664.2
HEATEDBSMT 12-JAN-03:00 0.00 0.00 15988.83 0.00 0.00 0.00 0.00 266.42 4487.22 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 -20742.5
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 12-JAN-09:00 0.00 0.00 486270.23 0.00 0.00 0.00 2291.27 2593.25 32433.35 0.00 0.00 16002.55 0.00 0.00 -64061.6 0.00 -351552.0 -123977.0



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 596.7754 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.7754 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 502.8888 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 502.8888 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 596.6043 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.6043 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 596.7721 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.7721 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 502.8349 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 502.8349 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 596.4991 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.4991 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.6812 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 508.6812 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 347.6602 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 347.6602 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 445.7926 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 445.7926 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 446.0064 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 446.0064 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 347.5941 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 347.5941 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 445.6730 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 445.6730 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 650.5133 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.5133 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 551.9130 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 551.9130 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 650.2481 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.2481 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 650.4641 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.4641 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 551.8248 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 551.8248 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 650.1208 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.1208 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNITHEATEDBSMT 303.1236 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 303.1236 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 596.7754 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.7754 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 502.8888 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 502.8888 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 596.6043 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.6043 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 596.7721 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.7721 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 502.8349 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 502.8349 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 596.4991 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 596.4991 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.6812 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 508.6812 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 347.6602 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 347.6602 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 445.7926 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 445.7926 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 446.0064 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 446.0064 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 347.5941 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 347.5941 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 445.6730 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 445.6730 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 650.5133 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.5133 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 551.9130 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 551.9130 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 650.2481 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.2481 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 650.4641 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.4641 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 551.8248 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 551.8248 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 650.1208 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 650.1208 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNITHEATEDBSMT 303.1236 0.0000 0.0000 1.0000 Calculated from schedules 0.0000 303.1236 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT 0.000000 0.0000 0.000000 7794.39 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNITHEATEDBSMT   0.00 0.000000 7794.3864 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.7754 596.7754 596.7754 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 502.8888 502.8888 502.8888 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.6043 596.6043 596.6043 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.7721 596.7721 596.7721 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 502.8349 502.8349 502.8349 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.4991 596.4991 596.4991 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 508.6812 508.6812 508.6812 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.6602 347.6602 347.6602 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 445.7926 445.7926 445.7926 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 446.0064 446.0064 446.0064 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.5941 347.5941 347.5941 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 445.6730 445.6730 445.6730 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.1208 650.1208 650.1208 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.2481 650.2481 650.2481 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.5133 650.5133 650.5133 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 551.8248 551.8248 551.8248 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 551.9130 551.9130 551.9130 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.4641 650.4641 650.4641 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 303.1236 303.1236 303.1236 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 596.7754 596.7754 596.7754 596.7754 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 502.8888 502.8888 502.8888 502.8888 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 596.6043 596.6043 596.6043 596.6043 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 596.7721 596.7721 596.7721 596.7721 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 502.8349 502.8349 502.8349 502.8349 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 596.4991 596.4991 596.4991 596.4991 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.6812 508.6812 508.6812 508.6812 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 347.6602 347.6602 347.6602 347.6602 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 445.7926 445.7926 445.7926 445.7926 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 446.0064 446.0064 446.0064 446.0064 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 347.5941 347.5941 347.5941 347.5941 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 445.6730 445.6730 445.6730 445.6730 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 650.5133 650.5133 650.5133 650.5133 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 551.9130 551.9130 551.9130 551.9130 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 650.2481 650.2481 650.2481 650.2481 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 650.4641 650.4641 650.4641 650.4641 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 551.8248 551.8248 551.8248 551.8248 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 650.1208 650.1208 650.1208 650.1208 0.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 303.1236 303.1236 303.1236 303.1236 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.7754 596.7754 596.7754 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 502.8888 502.8888 502.8888 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.6043 596.6043 596.6043 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.7721 596.7721 596.7721 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 502.8349 502.8349 502.8349 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 596.4991 596.4991 596.4991 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 508.6812 508.6812 508.6812 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.6602 347.6602 347.6602 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 445.7926 445.7926 445.7926 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 446.0064 446.0064 446.0064 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 347.5941 347.5941 347.5941 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 445.6730 445.6730 445.6730 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.1208 650.1208 650.1208 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.2481 650.2481 650.2481 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.5133 650.5133 650.5133 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 551.8248 551.8248 551.8248 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 551.9130 551.9130 551.9130 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 650.4641 650.4641 650.4641 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
HEATEDBSMT CENTRAL SYSTEM_UNITHEATEDBSMT AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 303.1236 303.1236 303.1236 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 596.7754 596.7754 596.7754 596.7754 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 502.8888 502.8888 502.8888 502.8888 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 596.6043 596.6043 596.6043 596.6043 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 596.7721 596.7721 596.7721 596.7721 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 502.8349 502.8349 502.8349 502.8349 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 596.4991 596.4991 596.4991 596.4991 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 508.6812 508.6812 508.6812 508.6812 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 347.6602 347.6602 347.6602 347.6602 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 445.7926 445.7926 445.7926 445.7926 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 446.0064 446.0064 446.0064 446.0064 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 347.5941 347.5941 347.5941 347.5941 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 445.6730 445.6730 445.6730 445.6730 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 650.5133 650.5133 650.5133 650.5133 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 551.9130 551.9130 551.9130 551.9130 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 650.2481 650.2481 650.2481 650.2481 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 650.4641 650.4641 650.4641 650.4641 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 551.8248 551.8248 551.8248 551.8248 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 650.1208 650.1208 650.1208 650.1208 0.0000 1.0000
CENTRAL SYSTEM_UNITHEATEDBSMT 303.1236 303.1236 303.1236 303.1236 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Sec1.1A-General Information

Data
Weather File ANNUAL ** Fairbanks Intl Arpt AK USA TMY3 WMO#=702610
Total gross floor area [ft2] 39005.22
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
HEATEDBSMT 7794.39 7794.39 0.00 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 29404.35 9600.87  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 0.00
Number of hours cooling loads not met 0.00
Number of hours not met 0.00


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 13213.37 596385.85 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 5826.60 11031.64 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 18100.85 5896.05 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_dryer 1138.84 291.20 792.69 20254.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_range 0.00 0.00 674.43 27685.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- gas_mels 44924.98 7591.70 184.30 3112.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 35164.90 5942.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 7133.15 814.29 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 7183.41 2687.25 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 0.00 0.00 4009.29 178233.21 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 334377.15 485561.80
Natural Gas 165141.93 1887408.10
Additional 0.00 0.00
Total 499519.07 2372969.90


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.46
Space Heating 0.00
Space Cooling 0.15
Fans (All) 0.37
Service Water Heating 0.00
Receptacle Equipment 2.51
Miscellaneous (All) 3.65
Subtotal 3.65


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 9.92
Service Water Heating 3.01
Miscellaneous (All) 14.17
Subtotal 14.17


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 2.60
Space Heating 55.68
Space Cooling 0.84
Fans (All) 2.06
Service Water Heating 16.90
Receptacle Equipment 21.05
Miscellaneous 0.87


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 3134. 8760.
CLOTHESWASHER_FLOW_SCH 3692. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:34:18

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 65.636 65.636
February 0.000 0.000 672.000 52.736 52.736
March 0.000 0.000 742.333 44.522 44.522
April 59.333 2.026 564.750 22.284 22.284
May 204.000 8.333 357.917 13.871 13.871
June 377.167 19.444 122.222 20.313 20.313
July 411.667 22.538 90.444 23.034 23.034
August 314.097 14.548 219.278 16.602 16.602
September 73.167 2.033 525.667 11.672 11.672
October 0.500 0.001 733.833 30.659 30.659
November 0.000 0.000 720.000 61.088 61.088
December 0.000 0.000 744.000 69.415 69.415
           
Annual Sum or Average 1439.931 68.922 6236.444 431.833 431.833
Minimum of Months 0.000 0.000 90.444 11.672 11.672
Maximum of Months 411.667 22.538 744.000 69.415 69.415



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 51.915 51.915
February 0.000 0.000 672.000 41.718 41.718
March 0.000 0.000 743.667 35.347 35.347
April 37.861 0.510 586.583 16.725 16.725
May 191.583 4.583 331.806 8.526 8.526
June 391.639 13.018 88.917 13.481 13.481
July 435.028 16.913 59.500 17.152 17.152
August 331.667 11.050 161.833 12.223 12.223
September 80.500 1.259 490.167 8.021 8.021
October 0.000 0.000 726.833 23.399 23.399
November 0.000 0.000 720.000 48.364 48.364
December 0.000 0.000 744.000 55.042 55.042
           
Annual Sum or Average 1468.278 47.333 6069.306 331.912 331.912
Minimum of Months 0.000 0.000 59.500 8.021 8.021
Maximum of Months 435.028 16.913 744.000 55.042 55.042



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 65.506 65.506
February 0.000 0.000 672.000 52.254 52.254
March 0.000 0.000 742.250 43.236 43.236
April 49.556 0.929 581.139 20.697 20.697
May 261.139 8.888 288.333 13.442 13.442
June 448.472 19.719 82.917 20.286 20.286
July 464.778 25.055 72.667 25.449 25.449
August 355.958 14.916 163.361 16.420 16.420
September 88.861 1.632 501.167 10.499 10.499
October 0.000 0.000 731.583 30.010 30.010
November 0.000 0.000 720.000 61.087 61.087
December 0.000 0.000 744.000 69.394 69.394
           
Annual Sum or Average 1668.764 71.138 6043.417 428.280 428.280
Minimum of Months 0.000 0.000 72.667 10.499 10.499
Maximum of Months 464.778 25.055 744.000 69.394 69.394



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 66.392 66.392
February 0.000 0.000 672.000 54.807 54.807
March 0.000 0.000 744.000 47.867 47.867
April 19.417 0.486 642.556 23.278 23.278
May 138.139 4.645 418.222 10.404 10.404
June 367.611 15.877 103.222 16.518 16.518
July 410.389 18.397 79.750 18.828 18.828
August 265.514 9.685 238.139 11.941 11.941
September 26.833 0.399 580.250 11.265 11.265
October 0.000 0.000 743.333 32.441 32.441
November 0.000 0.000 720.000 62.278 62.278
December 0.000 0.000 744.000 69.653 69.653
           
Annual Sum or Average 1227.903 49.490 6429.472 425.672 425.672
Minimum of Months 0.000 0.000 79.750 10.404 10.404
Maximum of Months 410.389 18.397 744.000 69.653 69.653



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 52.619 52.619
February 0.000 0.000 672.000 43.652 43.652
March 0.000 0.000 744.000 38.550 38.550
April 0.000 0.000 691.250 19.095 19.095
May 99.611 1.731 407.639 5.877 5.877
June 378.944 10.730 61.083 11.035 11.035
July 435.278 14.278 55.833 14.485 14.485
August 275.042 7.123 187.222 8.510 8.510
September 5.500 0.028 564.917 7.996 7.996
October 0.000 0.000 744.000 25.103 25.103
November 0.000 0.000 720.000 49.480 49.480
December 0.000 0.000 744.000 55.258 55.258
           
Annual Sum or Average 1194.375 33.891 6335.944 331.660 331.660
Minimum of Months 0.000 0.000 55.833 5.877 5.877
Maximum of Months 435.278 14.278 744.000 55.258 55.258



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 66.235 66.235
February 0.000 0.000 672.000 54.278 54.278
March 0.000 0.000 744.000 46.503 46.503
April 0.000 0.000 664.556 22.468 22.468
May 200.028 4.427 306.028 9.069 9.069
June 456.333 16.328 72.000 16.812 16.812
July 467.042 21.178 70.833 21.555 21.555
August 318.944 9.931 185.944 11.596 11.596
September 8.444 0.038 558.000 9.982 9.982
October 0.000 0.000 744.000 31.760 31.760
November 0.000 0.000 720.000 62.263 62.263
December 0.000 0.000 744.000 69.610 69.610
           
Annual Sum or Average 1450.792 51.902 6225.361 422.132 422.132
Minimum of Months 0.000 0.000 70.833 9.069 9.069
Maximum of Months 467.042 21.178 744.000 69.610 69.610



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 52.768 52.768
February 0.000 0.000 672.000 41.551 41.551
March 0.000 0.000 731.500 33.441 33.441
April 121.583 4.668 482.778 18.062 18.062
May 298.806 13.041 263.806 15.824 15.824
June 474.139 25.644 35.000 25.818 25.818
July 517.167 28.589 28.167 28.693 28.693
August 405.472 19.316 99.722 20.202 20.202
September 114.417 3.347 450.639 9.908 9.908
October 4.667 0.042 720.000 23.982 23.982
November 0.000 0.000 720.000 49.294 49.294
December 0.000 0.000 744.000 56.361 56.361
           
Annual Sum or Average 1936.250 94.645 5691.611 375.904 375.904
Minimum of Months 0.000 0.000 28.167 9.908 9.908
Maximum of Months 517.167 28.589 744.000 56.361 56.361



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 32.357 32.357
February 0.000 0.000 672.000 25.290 25.290
March 0.000 0.000 728.083 20.110 20.110
April 104.722 2.090 469.875 9.920 9.920
May 323.583 8.823 197.167 9.995 9.995
June 527.597 18.871 14.833 18.908 18.908
July 579.278 22.827 10.833 22.842 22.842
August 451.778 15.829 56.750 16.170 16.170
September 136.000 2.682 389.611 5.780 5.780
October 6.500 0.070 689.917 13.727 13.727
November 0.000 0.000 720.000 30.310 30.310
December 0.000 0.000 744.000 34.808 34.808
           
Annual Sum or Average 2129.458 71.191 5437.069 240.217 240.217
Minimum of Months 0.000 0.000 10.833 5.780 5.780
Maximum of Months 579.278 22.827 744.000 34.808 34.808



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 46.250 46.250
February 0.000 0.000 672.000 36.014 36.014
March 0.000 0.000 728.583 28.019 28.019
April 115.331 3.167 470.556 14.458 14.458
May 382.986 15.545 199.750 17.417 17.417
June 545.778 27.309 19.667 27.406 27.406
July 564.972 31.986 22.833 32.050 32.050
August 450.972 20.583 62.167 21.115 21.115
September 122.306 3.265 421.556 8.407 8.407
October 6.500 0.075 707.250 20.448 20.448
November 0.000 0.000 720.000 43.331 43.331
December 0.000 0.000 744.000 49.520 49.520
           
Annual Sum or Average 2188.844 101.931 5512.361 344.436 344.436
Minimum of Months 0.000 0.000 19.667 8.407 8.407
Maximum of Months 564.972 31.986 744.000 49.520 49.520



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 47.172 47.172
February 0.000 0.000 672.000 38.699 38.699
March 0.000 0.000 744.000 32.965 32.965
April 45.333 1.288 578.417 15.217 15.217
May 213.667 7.554 294.306 10.012 10.012
June 494.542 21.879 23.111 21.989 21.989
July 533.667 24.303 24.500 24.372 24.372
August 360.278 13.238 113.458 14.157 14.157
September 53.833 0.766 531.333 7.634 7.634
October 0.000 0.000 738.333 22.926 22.926
November 0.000 0.000 720.000 44.580 44.580
December 0.000 0.000 744.000 49.790 49.790
           
Annual Sum or Average 1701.319 69.028 5927.458 329.513 329.513
Minimum of Months 0.000 0.000 23.111 7.634 7.634
Maximum of Months 533.667 24.303 744.000 49.790 49.790



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 33.067 33.067
February 0.000 0.000 672.000 27.288 27.288
March 0.000 0.000 744.000 23.482 23.482
April 4.417 0.027 614.139 10.111 10.111
May 191.944 4.080 210.000 5.274 5.274
June 562.153 17.322 13.583 17.348 17.348
July 604.833 20.979 9.000 20.990 20.990
August 396.167 11.093 76.694 11.555 11.555
September 35.333 0.224 478.083 4.279 4.279
October 0.000 0.000 722.000 15.362 15.362
November 0.000 0.000 720.000 31.450 31.450
December 0.000 0.000 744.000 35.025 35.025
           
Annual Sum or Average 1794.847 53.724 5747.500 235.232 235.232
Minimum of Months 0.000 0.000 9.000 4.279 4.279
Maximum of Months 604.833 20.979 744.000 35.025 35.025



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 47.009 47.009
February 0.000 0.000 672.000 38.147 38.147
March 0.000 0.000 744.000 31.526 31.526
April 16.528 0.179 584.778 13.682 13.682
May 341.139 9.790 202.500 11.731 11.731
June 565.944 24.404 18.167 24.493 24.493
July 577.778 28.360 20.167 28.418 28.418
August 408.000 14.677 72.250 15.281 15.281
September 41.000 0.349 483.722 6.436 6.436
October 0.000 0.000 742.333 22.189 22.189
November 0.000 0.000 720.000 44.566 44.566
December 0.000 0.000 744.000 49.744 49.744
           
Annual Sum or Average 1950.389 77.759 5747.917 333.222 333.222
Minimum of Months 0.000 0.000 18.167 6.436 6.436
Maximum of Months 577.778 28.360 744.000 49.744 49.744



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 73.461 73.461
February 0.000 0.000 672.000 58.829 58.829
March 0.000 0.000 742.083 49.209 49.209
April 67.250 2.589 556.167 24.000 24.000
May 220.833 10.137 342.250 15.561 15.561
June 414.694 24.081 99.222 24.753 24.753
July 450.778 27.464 66.722 27.867 27.867
August 333.333 17.050 201.278 19.120 19.120
September 69.750 2.000 538.167 13.106 13.106
October 0.000 0.000 735.583 35.328 35.328
November 0.000 0.000 720.000 68.849 68.849
December 0.000 0.000 744.000 77.900 77.900
           
Annual Sum or Average 1556.639 83.321 6161.472 487.984 487.984
Minimum of Months 0.000 0.000 66.722 13.106 13.106
Maximum of Months 450.778 27.464 744.000 77.900 77.900



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 58.669 58.669
February 0.000 0.000 672.000 46.853 46.853
March 0.000 0.000 744.000 39.194 39.194
April 45.389 0.852 572.222 17.952 17.952
May 215.194 6.132 307.333 9.853 9.853
June 437.500 17.239 51.278 17.540 17.540
July 488.806 21.638 41.194 21.820 21.820
August 365.097 13.547 134.722 14.711 14.711
September 76.333 1.263 507.667 9.101 9.101
October 0.000 0.000 730.167 27.200 27.200
November 0.000 0.000 720.000 55.096 55.096
December 0.000 0.000 744.000 62.429 62.429
           
Annual Sum or Average 1628.319 60.671 5968.583 380.418 380.418
Minimum of Months 0.000 0.000 41.194 9.101 9.101
Maximum of Months 488.806 21.638 744.000 62.429 62.429



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 73.316 73.316
February 0.000 0.000 672.000 58.273 58.273
March 0.000 0.000 741.667 47.672 47.672
April 62.472 1.414 566.389 22.299 22.299
May 296.000 11.077 268.083 15.444 15.444
June 488.278 24.570 58.917 24.991 24.991
July 507.083 30.114 56.167 30.442 30.442
August 378.139 17.568 144.528 19.062 19.062
September 85.667 1.684 509.194 11.912 11.912
October 0.000 0.000 734.000 34.557 34.557
November 0.000 0.000 720.000 68.850 68.850
December 0.000 0.000 744.000 77.873 77.873
           
Annual Sum or Average 1817.639 86.427 5958.944 484.689 484.689
Minimum of Months 0.000 0.000 56.167 11.912 11.912
Maximum of Months 507.083 30.114 744.000 77.873 77.873



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 74.276 74.276
February 0.000 0.000 672.000 61.081 61.081
March 0.000 0.000 744.000 52.784 52.784
April 26.417 0.812 623.500 24.877 24.877
May 165.167 6.494 391.222 12.139 12.139
June 416.472 21.405 71.250 21.887 21.887
July 461.250 24.216 62.556 24.575 24.575
August 291.936 12.432 223.417 14.753 14.753
September 24.333 0.356 584.333 12.898 12.898
October 0.000 0.000 744.000 37.347 37.347
November 0.000 0.000 720.000 70.149 70.149
December 0.000 0.000 744.000 78.153 78.153
           
Annual Sum or Average 1385.575 65.715 6324.278 484.920 484.920
Minimum of Months 0.000 0.000 62.556 12.139 12.139
Maximum of Months 461.250 24.216 744.000 78.153 78.153



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 59.460 59.460
February 0.000 0.000 672.000 49.071 49.071
March 0.000 0.000 744.000 42.739 42.739
April 1.917 0.010 667.917 20.125 20.125
May 140.583 3.282 364.889 7.205 7.205
June 440.833 16.087 35.222 16.312 16.312
July 505.306 20.124 37.583 20.282 20.282
August 318.542 9.929 161.806 11.368 11.368
September 3.500 0.027 577.417 9.315 9.315
October 0.000 0.000 744.000 29.197 29.197
November 0.000 0.000 720.000 56.377 56.377
December 0.000 0.000 744.000 62.669 62.669
           
Annual Sum or Average 1410.681 49.460 6212.833 384.119 384.119
Minimum of Months 0.000 0.000 35.222 7.205 7.205
Maximum of Months 505.306 20.124 744.000 62.669 62.669



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 74.109 74.109
February 0.000 0.000 672.000 60.499 60.499
March 0.000 0.000 744.000 51.220 51.220
April 8.333 0.039 637.958 23.701 23.701
May 251.000 7.084 279.778 11.541 11.541
June 500.028 22.680 50.083 23.050 23.050
July 517.750 27.624 56.667 27.936 27.936
August 344.639 13.257 169.472 14.960 14.960
September 11.083 0.057 572.000 11.586 11.586
October 0.000 0.000 744.000 36.551 36.551
November 0.000 0.000 720.000 70.141 70.141
December 0.000 0.000 744.000 78.108 78.108
           
Annual Sum or Average 1632.833 70.742 6133.958 483.403 483.403
Minimum of Months 0.000 0.000 50.083 11.541 11.541
Maximum of Months 517.750 27.624 744.000 78.108 78.108



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNITHEATEDBSMT

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 43.468 43.468
February 0.000 0.000 672.000 36.569 36.569
March 0.000 0.000 744.000 34.985 34.985
April 0.000 0.000 700.917 23.315 23.315
May 49.861 1.311 222.639 2.940 2.940
June 169.167 8.280 1.833 8.284 8.284
July 213.306 10.210 0.000 10.210 10.210
August 192.167 9.119 5.167 9.130 9.130
September 62.333 2.522 82.750 2.781 2.781
October 0.000 0.000 464.167 3.898 3.898
November 0.000 0.000 720.000 30.319 30.319
December 0.000 0.000 744.000 41.966 41.966
           
Annual Sum or Average 686.833 31.442 5101.472 247.865 247.865
Minimum of Months 0.000 0.000 0.000 2.781 2.781
Maximum of Months 213.306 10.210 744.000 43.468 43.468



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 15363.38 0.00 0.00
February 13666.66 0.00 0.00
March 10421.34 0.00 0.00
April 4899.93 0.00 0.00
May 1296.33 0.00 0.00
June 210.14 0.00 0.00
July 116.27 0.00 0.00
August 480.85 0.00 0.00
September 2331.46 0.00 0.00
October 7176.19 0.00 0.00
November 14775.66 0.00 0.00
December 16247.96 0.00 0.00
       
Annual Sum or Average 7214.67 0.00 0.00
Minimum of Months 116.27 0.00 0.00
Maximum of Months 16247.96 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 12578.30 0.00 0.00
February 11190.85 0.00 0.00
March 8564.13 0.00 0.00
April 4059.62 0.00 0.00
May 955.33 0.00 0.00
June 115.93 0.00 0.00
July 58.01 0.00 0.00
August 284.41 0.00 0.00
September 1692.75 0.00 0.00
October 5669.38 0.00 0.00
November 12108.59 0.00 0.00
December 13335.94 0.00 0.00
       
Annual Sum or Average 5856.06 0.00 0.00
Minimum of Months 58.01 0.00 0.00
Maximum of Months 13335.94 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 15333.92 0.00 0.00
February 13542.35 0.00 0.00
March 10120.82 0.00 0.00
April 4781.48 0.00 0.00
May 1066.02 0.00 0.00
June 137.30 0.00 0.00
July 92.42 0.00 0.00
August 352.00 0.00 0.00
September 2145.00 0.00 0.00
October 7024.85 0.00 0.00
November 14776.13 0.00 0.00
December 16243.93 0.00 0.00
       
Annual Sum or Average 7100.37 0.00 0.00
Minimum of Months 92.42 0.00 0.00
Maximum of Months 16243.93 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 15540.47 0.00 0.00
February 14203.15 0.00 0.00
March 11204.33 0.00 0.00
April 5512.92 0.00 0.00
May 1347.93 0.00 0.00
June 155.23 0.00 0.00
July 100.84 0.00 0.00
August 527.91 0.00 0.00
September 2628.20 0.00 0.00
October 7593.51 0.00 0.00
November 15063.33 0.00 0.00
December 16303.73 0.00 0.00
       
Annual Sum or Average 7478.52 0.00 0.00
Minimum of Months 100.84 0.00 0.00
Maximum of Months 16303.73 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 12749.30 0.00 0.00
February 11709.77 0.00 0.00
March 9340.44 0.00 0.00
April 4780.81 0.00 0.00
May 1004.56 0.00 0.00
June 76.21 0.00 0.00
July 50.08 0.00 0.00
August 336.08 0.00 0.00
September 1994.87 0.00 0.00
October 6082.37 0.00 0.00
November 12388.29 0.00 0.00
December 13388.66 0.00 0.00
       
Annual Sum or Average 6127.60 0.00 0.00
Minimum of Months 50.08 0.00 0.00
Maximum of Months 13388.66 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 15505.04 0.00 0.00
February 14067.39 0.00 0.00
March 10885.87 0.00 0.00
April 5434.99 0.00 0.00
May 1086.71 0.00 0.00
June 117.09 0.00 0.00
July 88.19 0.00 0.00
August 389.86 0.00 0.00
September 2405.41 0.00 0.00
October 7434.79 0.00 0.00
November 15061.07 0.00 0.00
December 16295.15 0.00 0.00
       
Annual Sum or Average 7360.82 0.00 0.00
Minimum of Months 88.19 0.00 0.00
Maximum of Months 16295.15 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 11517.24 0.00 0.00
February 10040.58 0.00 0.00
March 7298.74 0.00 0.00
April 3020.87 0.00 0.00
May 607.33 0.00 0.00
June 39.33 0.00 0.00
July 22.77 0.00 0.00
August 193.26 0.00 0.00
September 1479.91 0.00 0.00
October 5225.25 0.00 0.00
November 11117.63 0.00 0.00
December 12301.41 0.00 0.00
       
Annual Sum or Average 5213.74 0.00 0.00
Minimum of Months 22.77 0.00 0.00
Maximum of Months 12301.41 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8593.88 0.00 0.00
February 7436.44 0.00 0.00
March 5341.10 0.00 0.00
April 2149.14 0.00 0.00
May 311.49 0.00 0.00
June 10.25 0.00 0.00
July 4.01 0.00 0.00
August 90.63 0.00 0.00
September 850.18 0.00 0.00
October 3627.20 0.00 0.00
November 8318.36 0.00 0.00
December 9244.68 0.00 0.00
       
Annual Sum or Average 3812.77 0.00 0.00
Minimum of Months 4.01 0.00 0.00
Maximum of Months 9244.68 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 11514.18 0.00 0.00
February 9926.41 0.00 0.00
March 6975.48 0.00 0.00
April 2904.44 0.00 0.00
May 466.01 0.00 0.00
June 24.94 0.00 0.00
July 15.83 0.00 0.00
August 132.56 0.00 0.00
September 1322.90 0.00 0.00
October 5071.97 0.00 0.00
November 11147.09 0.00 0.00
December 12328.13 0.00 0.00
       
Annual Sum or Average 5127.53 0.00 0.00
Minimum of Months 15.83 0.00 0.00
Maximum of Months 12328.13 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 11742.21 0.00 0.00
February 10665.31 0.00 0.00
March 8205.88 0.00 0.00
April 3582.93 0.00 0.00
May 611.94 0.00 0.00
June 28.27 0.00 0.00
July 17.14 0.00 0.00
August 228.83 0.00 0.00
September 1766.47 0.00 0.00
October 5706.89 0.00 0.00
November 11467.04 0.00 0.00
December 12393.92 0.00 0.00
       
Annual Sum or Average 5507.07 0.00 0.00
Minimum of Months 17.14 0.00 0.00
Maximum of Months 12393.92 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8782.78 0.00 0.00
February 8024.60 0.00 0.00
March 6237.03 0.00 0.00
April 2767.71 0.00 0.00
May 317.28 0.00 0.00
June 7.13 0.00 0.00
July 3.06 0.00 0.00
August 122.70 0.00 0.00
September 1112.99 0.00 0.00
October 4080.35 0.00 0.00
November 8631.91 0.00 0.00
December 9302.91 0.00 0.00
       
Annual Sum or Average 4094.55 0.00 0.00
Minimum of Months 3.06 0.00 0.00
Maximum of Months 9302.91 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 11703.88 0.00 0.00
February 10514.97 0.00 0.00
March 7849.10 0.00 0.00
April 3474.03 0.00 0.00
May 483.26 0.00 0.00
June 22.87 0.00 0.00
July 14.45 0.00 0.00
August 150.19 0.00 0.00
September 1565.91 0.00 0.00
October 5524.26 0.00 0.00
November 11465.51 0.00 0.00
December 12384.69 0.00 0.00
       
Annual Sum or Average 5401.84 0.00 0.00
Minimum of Months 14.45 0.00 0.00
Maximum of Months 12384.69 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 16927.67 0.00 0.00
February 15008.53 0.00 0.00
March 11339.14 0.00 0.00
April 5098.18 0.00 0.00
May 1249.93 0.00 0.00
June 159.97 0.00 0.00
July 92.97 0.00 0.00
August 477.00 0.00 0.00
September 2644.57 0.00 0.00
October 8140.55 0.00 0.00
November 16393.71 0.00 0.00
December 17950.54 0.00 0.00
       
Annual Sum or Average 7919.57 0.00 0.00
Minimum of Months 92.97 0.00 0.00
Maximum of Months 17950.54 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 13942.25 0.00 0.00
February 12327.16 0.00 0.00
March 9314.22 0.00 0.00
April 4199.03 0.00 0.00
May 884.36 0.00 0.00
June 73.99 0.00 0.00
July 43.09 0.00 0.00
August 276.67 0.00 0.00
September 1924.77 0.00 0.00
October 6463.77 0.00 0.00
November 13529.73 0.00 0.00
December 14835.88 0.00 0.00
       
Annual Sum or Average 6453.57 0.00 0.00
Minimum of Months 43.09 0.00 0.00
Maximum of Months 14835.88 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 16895.35 0.00 0.00
February 14867.51 0.00 0.00
March 10985.93 0.00 0.00
April 4973.34 0.00 0.00
May 1006.42 0.00 0.00
June 100.17 0.00 0.00
July 75.41 0.00 0.00
August 344.43 0.00 0.00
September 2435.58 0.00 0.00
October 7963.53 0.00 0.00
November 16395.03 0.00 0.00
December 17945.50 0.00 0.00
       
Annual Sum or Average 7794.87 0.00 0.00
Minimum of Months 75.41 0.00 0.00
Maximum of Months 17945.50 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 17115.63 0.00 0.00
February 15583.25 0.00 0.00
March 12163.14 0.00 0.00
April 5730.20 0.00 0.00
May 1300.66 0.00 0.00
June 114.76 0.00 0.00
July 82.77 0.00 0.00
August 534.89 0.00 0.00
September 2986.64 0.00 0.00
October 8605.89 0.00 0.00
November 16703.58 0.00 0.00
December 18009.01 0.00 0.00
       
Annual Sum or Average 8204.27 0.00 0.00
Minimum of Months 82.77 0.00 0.00
Maximum of Months 18009.01 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 14130.65 0.00 0.00
February 12911.12 0.00 0.00
March 10156.90 0.00 0.00
April 4939.58 0.00 0.00
May 932.33 0.00 0.00
June 55.23 0.00 0.00
July 37.56 0.00 0.00
August 341.88 0.00 0.00
September 2280.86 0.00 0.00
October 6938.61 0.00 0.00
November 13844.66 0.00 0.00
December 14893.27 0.00 0.00
       
Annual Sum or Average 6754.76 0.00 0.00
Minimum of Months 37.56 0.00 0.00
Maximum of Months 14893.27 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 17078.77 0.00 0.00
February 15436.05 0.00 0.00
March 11803.83 0.00 0.00
April 5634.87 0.00 0.00
May 1027.06 0.00 0.00
June 88.09 0.00 0.00
July 71.96 0.00 0.00
August 392.46 0.00 0.00
September 2745.47 0.00 0.00
October 8423.37 0.00 0.00
November 16703.18 0.00 0.00
December 18000.43 0.00 0.00
       
Annual Sum or Average 8076.97 0.00 0.00
Minimum of Months 71.96 0.00 0.00
Maximum of Months 18000.43 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN FUEL HEATING COIL_UNITHEATEDBSMT

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 12024.86 0.00 0.00
February 11200.37 0.00 0.00
March 9678.35 0.00 0.00
April 6664.94 0.00 0.00
May 450.58 0.00 0.00
June 1.22 0.00 0.00
July 0.00 0.00 0.00
August 3.02 0.00 0.00
September 74.06 0.00 0.00
October 1078.31 0.00 0.00
November 8666.95 0.00 0.00
December 11609.41 0.00 0.00
       
Annual Sum or Average 5084.95 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 12024.86 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.07
June 0.00 0.00 0.16
July 0.00 0.00 0.18
August 0.00 0.00 0.12
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.18



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.11
July 0.00 0.00 0.15
August 0.00 0.00 0.10
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.17
July 0.00 0.00 0.21
August 0.00 0.00 0.12
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.21



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.04
June 0.00 0.00 0.13
July 0.00 0.00 0.15
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.08
July 0.00 0.00 0.11
August 0.00 0.00 0.05
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.02
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.11



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.13
July 0.00 0.00 0.17
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.17



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.11
June 0.00 0.00 0.22
July 0.00 0.00 0.24
August 0.00 0.00 0.16
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.08
June 0.00 0.00 0.17
July 0.00 0.00 0.20
August 0.00 0.00 0.14
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.13
June 0.00 0.00 0.24
July 0.00 0.00 0.28
August 0.00 0.00 0.18
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.28



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.06
June 0.00 0.00 0.18
July 0.00 0.00 0.20
August 0.00 0.00 0.11
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.03
June 0.00 0.00 0.14
July 0.00 0.00 0.16
August 0.00 0.00 0.09
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.08
June 0.00 0.00 0.21
July 0.00 0.00 0.24
August 0.00 0.00 0.12
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.08
June 0.00 0.00 0.20
July 0.00 0.00 0.22
August 0.00 0.00 0.14
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.05
June 0.00 0.00 0.15
July 0.00 0.00 0.19
August 0.00 0.00 0.12
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.22
July 0.00 0.00 0.26
August 0.00 0.00 0.15
September 0.00 0.00 0.01
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.05
June 0.00 0.00 0.18
July 0.00 0.00 0.19
August 0.00 0.00 0.10
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.02
June 0.00 0.00 0.13
July 0.00 0.00 0.15
August 0.00 0.00 0.08
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.15



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.06
June 0.00 0.00 0.19
July 0.00 0.00 0.23
August 0.00 0.00 0.11
September 0.00 0.00 0.00
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.23



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNITHEATEDBSMT

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.01
June 0.00 0.00 0.09
July 0.00 0.00 0.10
August 0.00 0.00 0.09
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.03
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.10



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2127.95 1533.21
May 0.00 0.00 2096.52 1560.92
June 0.00 0.00 2013.95 1451.07
July 0.00 0.00 1941.45 1445.47
August 0.00 0.00 1894.01 1410.14
September 0.00 0.00 1902.77 1370.97
October 0.00 0.00 1944.47 1447.72
November 0.00 0.00 2009.76 1448.05
December 0.00 0.00 2097.82 1561.89
         
Annual Sum or Average 0.00 0.00 2033.59 17826.89
Minimum of Months 0.00 0.00 1894.01 1370.97
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2128.06 1533.29
May 0.00 0.00 2098.59 1562.46
June 0.00 0.00 2011.77 1449.50
July 0.00 0.00 1938.21 1443.05
August 0.00 0.00 1893.72 1409.92
September 0.00 0.00 1901.44 1370.01
October 0.00 0.00 1944.71 1447.89
November 0.00 0.00 2011.20 1449.09
December 0.00 0.00 2096.25 1560.72
         
Annual Sum or Average 0.00 0.00 2033.19 17823.39
Minimum of Months 0.00 0.00 1893.72 1370.01
Maximum of Months 0.00 0.00 2128.06 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2128.14 1533.35
May 0.00 0.00 2094.75 1559.60
June 0.00 0.00 2010.03 1448.25
July 0.00 0.00 1939.71 1444.17
August 0.00 0.00 1891.99 1408.64
September 0.00 0.00 1901.32 1369.92
October 0.00 0.00 1944.82 1447.97
November 0.00 0.00 2011.48 1449.29
December 0.00 0.00 2096.33 1560.78
         
Annual Sum or Average 0.00 0.00 2032.74 17819.42
Minimum of Months 0.00 0.00 1891.99 1369.92
Maximum of Months 0.00 0.00 2128.14 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2129.81 1534.55
May 0.00 0.00 2102.05 1565.04
June 0.00 0.00 2012.17 1449.79
July 0.00 0.00 1939.72 1444.17
August 0.00 0.00 1895.79 1411.47
September 0.00 0.00 1904.94 1372.53
October 0.00 0.00 1944.89 1448.02
November 0.00 0.00 2011.45 1449.27
December 0.00 0.00 2096.52 1560.92
         
Annual Sum or Average 0.00 0.00 2034.31 17833.21
Minimum of Months 0.00 0.00 1895.79 1372.53
Maximum of Months 0.00 0.00 2129.81 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2131.93 1536.08
May 0.00 0.00 2102.26 1565.19
June 0.00 0.00 2010.11 1448.31
July 0.00 0.00 1939.77 1444.21
August 0.00 0.00 1893.91 1410.07
September 0.00 0.00 1904.93 1372.52
October 0.00 0.00 1944.89 1448.03
November 0.00 0.00 2011.44 1449.26
December 0.00 0.00 2096.53 1560.93
         
Annual Sum or Average 0.00 0.00 2034.18 17832.05
Minimum of Months 0.00 0.00 1893.91 1372.52
Maximum of Months 0.00 0.00 2131.93 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2130.21 1534.84
May 0.00 0.00 2098.32 1562.26
June 0.00 0.00 2009.71 1448.02
July 0.00 0.00 1938.04 1442.92
August 0.00 0.00 1893.93 1410.08
September 0.00 0.00 1905.07 1372.62
October 0.00 0.00 1944.96 1448.08
November 0.00 0.00 2011.47 1449.29
December 0.00 0.00 2096.35 1560.79
         
Annual Sum or Average 0.00 0.00 2033.53 17826.35
Minimum of Months 0.00 0.00 1893.93 1372.62
Maximum of Months 0.00 0.00 2130.21 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.35 1583.12
April 0.00 0.00 2124.36 1530.63
May 0.00 0.00 2093.18 1558.43
June 0.00 0.00 2008.27 1446.98
July 0.00 0.00 1936.22 1441.57
August 0.00 0.00 1890.48 1407.52
September 0.00 0.00 1900.92 1369.63
October 0.00 0.00 1943.12 1446.71
November 0.00 0.00 2010.94 1448.91
December 0.00 0.00 2097.11 1561.36
         
Annual Sum or Average 0.00 0.00 2031.58 17809.23
Minimum of Months 0.00 0.00 1890.48 1369.63
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.31 1583.10
April 0.00 0.00 2123.90 1530.29
May 0.00 0.00 2091.93 1557.50
June 0.00 0.00 2005.90 1445.27
July 0.00 0.00 1934.72 1440.46
August 0.00 0.00 1886.80 1404.78
September 0.00 0.00 1899.14 1368.35
October 0.00 0.00 1943.10 1446.69
November 0.00 0.00 2011.48 1449.29
December 0.00 0.00 2096.33 1560.78
         
Annual Sum or Average 0.00 0.00 2030.62 17800.88
Minimum of Months 0.00 0.00 1886.80 1368.35
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.30 1583.09
April 0.00 0.00 2122.82 1529.52
May 0.00 0.00 2091.06 1556.85
June 0.00 0.00 2005.80 1445.20
July 0.00 0.00 1936.13 1441.50
August 0.00 0.00 1886.67 1404.68
September 0.00 0.00 1900.60 1369.40
October 0.00 0.00 1943.13 1446.72
November 0.00 0.00 2011.48 1449.29
December 0.00 0.00 2096.33 1560.78
         
Annual Sum or Average 0.00 0.00 2030.68 17801.40
Minimum of Months 0.00 0.00 1886.67 1369.40
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2127.88 1533.16
May 0.00 0.00 2096.67 1561.03
June 0.00 0.00 2007.90 1446.72
July 0.00 0.00 1934.60 1440.37
August 0.00 0.00 1892.13 1408.74
September 0.00 0.00 1902.93 1371.08
October 0.00 0.00 1944.88 1448.02
November 0.00 0.00 2011.27 1449.14
December 0.00 0.00 2096.28 1560.74
         
Annual Sum or Average 0.00 0.00 2032.40 17816.45
Minimum of Months 0.00 0.00 1892.13 1371.08
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2129.90 1534.62
May 0.00 0.00 2094.97 1559.76
June 0.00 0.00 2006.18 1445.48
July 0.00 0.00 1934.43 1440.24
August 0.00 0.00 1887.10 1405.00
September 0.00 0.00 1903.21 1371.28
October 0.00 0.00 1944.82 1447.97
November 0.00 0.00 2011.38 1449.22
December 0.00 0.00 2096.31 1560.76
         
Annual Sum or Average 0.00 0.00 2031.87 17811.78
Minimum of Months 0.00 0.00 1887.10 1371.28
Maximum of Months 0.00 0.00 2129.90 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2128.07 1533.30
May 0.00 0.00 2091.18 1556.94
June 0.00 0.00 2005.89 1445.26
July 0.00 0.00 1936.10 1441.48
August 0.00 0.00 1888.54 1406.07
September 0.00 0.00 1902.73 1370.94
October 0.00 0.00 1944.76 1447.93
November 0.00 0.00 2010.53 1448.61
December 0.00 0.00 2096.91 1561.21
         
Annual Sum or Average 0.00 0.00 2031.57 17809.19
Minimum of Months 0.00 0.00 1888.54 1370.94
Maximum of Months 0.00 0.00 2128.07 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2126.17 1531.93
May 0.00 0.00 2097.74 1561.82
June 0.00 0.00 2011.17 1449.07
July 0.00 0.00 1939.99 1444.37
August 0.00 0.00 1892.26 1408.84
September 0.00 0.00 1903.04 1371.16
October 0.00 0.00 1944.95 1448.07
November 0.00 0.00 2011.47 1449.29
December 0.00 0.00 2096.35 1560.79
         
Annual Sum or Average 0.00 0.00 2033.12 17822.80
Minimum of Months 0.00 0.00 1892.26 1371.16
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2128.00 1533.25
May 0.00 0.00 2096.83 1561.15
June 0.00 0.00 2009.97 1448.20
July 0.00 0.00 1936.32 1441.64
August 0.00 0.00 1892.25 1408.84
September 0.00 0.00 1901.39 1369.97
October 0.00 0.00 1944.84 1447.99
November 0.00 0.00 2011.48 1449.29
December 0.00 0.00 2096.33 1560.78
         
Annual Sum or Average 0.00 0.00 2032.64 17818.56
Minimum of Months 0.00 0.00 1892.25 1369.97
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2126.36 1532.07
May 0.00 0.00 2094.50 1559.41
June 0.00 0.00 2009.56 1447.91
July 0.00 0.00 1936.28 1441.61
August 0.00 0.00 1892.01 1408.65
September 0.00 0.00 1902.60 1370.85
October 0.00 0.00 1942.89 1446.53
November 0.00 0.00 2011.16 1449.06
December 0.00 0.00 2097.83 1561.89
         
Annual Sum or Average 0.00 0.00 2032.29 17815.45
Minimum of Months 0.00 0.00 1892.01 1370.85
Maximum of Months 0.00 0.00 2128.05 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2129.99 1534.68
May 0.00 0.00 2098.60 1562.47
June 0.00 0.00 2012.02 1449.68
July 0.00 0.00 1938.55 1443.30
August 0.00 0.00 1894.13 1410.23
September 0.00 0.00 1905.10 1372.65
October 0.00 0.00 1944.79 1447.95
November 0.00 0.00 2011.48 1449.29
December 0.00 0.00 2096.33 1560.77
         
Annual Sum or Average 0.00 0.00 2033.77 17828.48
Minimum of Months 0.00 0.00 1894.13 1372.65
Maximum of Months 0.00 0.00 2129.99 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2130.18 1534.82
May 0.00 0.00 2100.43 1563.83
June 0.00 0.00 2009.87 1448.13
July 0.00 0.00 1936.51 1441.78
August 0.00 0.00 1892.58 1409.08
September 0.00 0.00 1906.32 1373.52
October 0.00 0.00 1944.82 1447.97
November 0.00 0.00 2011.35 1449.20
December 0.00 0.00 2096.31 1560.76
         
Annual Sum or Average 0.00 0.00 2033.55 17826.55
Minimum of Months 0.00 0.00 1892.58 1373.52
Maximum of Months 0.00 0.00 2130.18 1584.39



Table of Contents

Report: WATER HEATER: LOADS

For: WATER HEATER_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] WATER HEATER HEATING RATE [Btu/h] WATER HEATER HEATING ENERGY [kBtu]
January 0.00 0.00 2128.05 1584.39
February 0.00 0.00 2126.45 1429.99
March 0.00 0.00 2126.28 1583.08
April 0.00 0.00 2129.92 1534.63
May 0.00 0.00 2094.86 1559.68
June 0.00 0.00 2009.78 1448.06
July 0.00 0.00 1936.38 1441.69
August 0.00 0.00 1892.07 1408.70
September 0.00 0.00 1906.39 1373.57
October 0.00 0.00 1944.72 1447.90
November 0.00 0.00 2011.30 1449.17
December 0.00 0.00 2096.15 1560.64
         
Annual Sum or Average 0.00 0.00 2032.98 17821.49
Minimum of Months 0.00 0.00 1892.07 1373.57
Maximum of Months 0.00 0.00 2129.92 1584.39



Table of Contents

Report: HEATING AND COOLING LOADS

For: HEATEDBSMT

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 9101.26
February 0.00 7656.85
March 0.00 7325.26
April 0.00 4881.77
May 3.58 341.03
June 30.14 0.89
July 41.03 0.00
August 36.51 2.29
September 8.07 54.25
October 0.00 816.15
November 0.00 6348.15
December 0.00 8786.82
     
Annual Sum or Average 119.33 45314.70
Minimum of Months 0.00 0.00
Maximum of Months 41.03 9101.26



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11662.57
February 0.00 9370.57
March 0.00 7910.99
April 11.76 3599.63
May 47.44 984.07
June 108.71 154.38
July 122.03 88.26
August 80.24 365.02
September 11.66 1712.76
October 0.01 5447.56
November 0.00 10854.61
December 0.00 12334.07
     
Annual Sum or Average 381.85 64484.48
Minimum of Months 0.00 88.26
Maximum of Months 122.03 12334.07



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 9542.15
February 0.00 7668.03
March 0.00 6496.92
April 3.06 2980.37
May 27.34 724.73
June 75.54 85.11
July 94.20 44.01
August 62.72 215.76
September 7.59 1242.73
October 0.00 4300.91
November 0.00 8889.50
December 0.00 10116.91
     
Annual Sum or Average 270.47 52307.14
Minimum of Months 0.00 44.01
Maximum of Months 94.20 10116.91



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11640.19
February 0.00 9285.33
March 0.00 7682.86
April 5.37 3512.60
May 51.43 809.23
June 111.76 100.87
July 138.02 70.16
August 83.17 267.21
September 9.42 1575.78
October 0.00 5332.66
November 0.00 10854.94
December 0.00 12330.99
     
Annual Sum or Average 399.17 63462.82
Minimum of Months 0.00 70.16
Maximum of Months 138.02 12330.99



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11797.00
February 0.00 9738.42
March 0.00 8505.38
April 2.72 4049.94
May 25.63 1023.24
June 86.13 114.03
July 96.17 76.55
August 51.28 400.75
September 2.20 1930.75
October 0.00 5764.35
November 0.00 11065.94
December 0.00 12376.40
     
Annual Sum or Average 264.14 66842.75
Minimum of Months 0.00 76.55
Maximum of Months 96.17 12376.40



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 9671.87
February 0.00 8023.59
March 0.00 7085.84
April 0.00 3509.82
May 8.76 762.08
June 53.36 55.95
July 68.31 37.99
August 34.45 254.96
September 0.15 1464.53
October 0.00 4614.21
November 0.00 9094.84
December 0.00 10156.90
     
Annual Sum or Average 165.02 54732.59
Minimum of Months 0.00 37.99
Maximum of Months 68.31 10156.90



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 11770.09
February 0.00 9645.32
March 0.00 8263.61
April 0.00 3992.69
May 24.49 824.93
June 89.16 86.02
July 112.24 66.95
August 52.59 295.95
September 0.21 1767.08
October 0.00 5643.85
November 0.00 11064.26
December 0.00 12369.87
     
Annual Sum or Average 278.69 65790.62
Minimum of Months 0.00 66.95
Maximum of Months 112.24 12369.87



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8755.08
February 0.00 6893.93
March 0.00 5548.30
April 27.97 2222.31
May 76.16 461.68
June 146.76 28.93
July 157.72 17.31
August 108.23 146.91
September 19.50 1088.69
October 0.24 3972.09
November 0.00 8178.68
December 0.00 9351.18
     
Annual Sum or Average 536.59 46665.07
Minimum of Months 0.00 17.31
Maximum of Months 157.72 9351.18



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6508.86
February 0.00 5087.18
March 0.00 4045.26
April 13.00 1575.22
May 54.36 235.92
June 112.85 7.51
July 130.89 3.04
August 92.29 68.64
September 16.51 623.14
October 0.42 2747.18
November 0.00 6096.96
December 0.00 7001.77
     
Annual Sum or Average 420.32 34000.69
Minimum of Months 0.00 3.04
Maximum of Months 130.89 7001.77



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8730.55
February 0.00 6798.24
March 0.00 5289.11
April 19.07 2131.23
May 93.82 353.35
June 161.08 18.30
July 182.99 12.01
August 118.77 100.51
September 19.47 970.72
October 0.44 3845.78
November 0.00 8179.55
December 0.00 9347.71
     
Annual Sum or Average 595.64 45777.07
Minimum of Months 0.00 12.01
Maximum of Months 182.99 9347.71



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8903.47
February 0.00 7304.31
March 0.00 6222.06
April 7.48 2629.10
May 43.12 464.00
June 122.79 20.74
July 130.65 13.00
August 71.61 173.51
September 4.30 1296.21
October 0.00 4327.22
November 0.00 8414.34
December 0.00 9397.62
     
Annual Sum or Average 379.95 49165.58
Minimum of Months 0.00 13.00
Maximum of Months 130.65 9397.62



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 6651.93
February 0.00 5489.53
March 0.00 4723.82
April 0.14 2028.60
May 21.49 240.30
June 89.78 5.23
July 103.99 2.32
August 55.22 92.93
September 1.17 815.77
October 0.00 3090.39
November 0.00 6326.77
December 0.00 7045.87
     
Annual Sum or Average 271.79 36513.44
Minimum of Months 0.00 2.32
Maximum of Months 103.99 7045.87



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 8874.37
February 0.00 7201.32
March 0.00 5951.52
April 1.00 2549.18
May 56.16 366.43
June 138.60 16.78
July 155.73 10.95
August 80.11 113.88
September 1.95 1149.04
October 0.00 4188.72
November 0.00 8413.19
December 0.00 9390.59
     
Annual Sum or Average 433.54 48225.99
Minimum of Months 0.00 10.95
Maximum of Months 155.73 9390.59



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 12968.66
February 0.00 10586.96
March 0.00 8963.17
April 0.22 4140.78
May 40.02 779.89
June 126.82 64.73
July 149.52 54.64
August 71.70 298.01
September 0.32 2017.51
October 0.00 6396.23
November 0.00 12274.31
December 0.00 13668.52
     
Annual Sum or Average 388.59 72213.42
Minimum of Months 0.00 54.64
Maximum of Months 149.52 13668.52



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 12829.39
February 0.00 10197.02
March 0.00 8342.11
April 8.47 3654.66
May 66.28 764.22
June 143.69 73.61
July 170.36 57.26
August 100.34 261.54
September 10.00 1789.78
October 0.00 6047.06
November 0.00 12047.88
December 0.00 13626.81
     
Annual Sum or Average 499.14 69691.35
Minimum of Months 0.00 57.26
Maximum of Months 170.36 13626.81



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 12853.95
February 0.00 10293.75
March 0.00 8610.32
April 15.06 3746.40
May 57.69 949.13
June 134.72 117.55
July 148.77 70.60
August 93.72 362.21
September 11.39 1943.36
October 0.00 6181.49
November 0.00 12046.92
December 0.00 13630.66
     
Annual Sum or Average 461.35 70806.36
Minimum of Months 0.00 70.60
Maximum of Months 148.77 13630.66



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10723.68
February 0.00 8849.98
March 0.00 7708.03
April 0.05 3627.70
May 17.16 707.54
June 82.81 40.56
July 99.64 28.50
August 49.54 259.45
September 0.14 1675.10
October 0.00 5265.68
November 0.00 10167.72
December 0.00 11302.43
     
Annual Sum or Average 249.34 60356.37
Minimum of Months 0.00 28.50
Maximum of Months 99.64 11302.43



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 10580.71
February 0.00 8449.70
March 0.00 7068.52
April 5.11 3083.83
May 36.46 671.14
June 99.87 54.34
July 120.37 32.70
August 76.51 209.96
September 7.54 1413.58
October 0.00 4905.33
November 0.00 9936.44
December 0.00 11258.88
     
Annual Sum or Average 345.86 57665.14
Minimum of Months 0.00 32.70
Maximum of Months 120.37 11258.88



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:34:18

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 12996.67
February 0.00 10687.93
March 0.00 9236.02
April 4.60 4210.84
May 36.17 987.65
June 117.36 84.33
July 128.00 62.85
August 66.31 406.17
September 1.97 2194.74
October 0.00 6534.84
November 0.00 12274.63
December 0.00 13675.05
     
Annual Sum or Average 354.41 73351.73
Minimum of Months 0.00 62.85
Maximum of Months 128.00 13675.05