Table of Contents

Program Version:EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:31

Tabular Output Report in Format: HTML

Building: US+MF+CZ7+oilfurnace+crawlspace+IECC_2021

Environment: ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470

Simulation Timestamp: 2024-06-27 18:32:20


Table of Contents

Report: Annual Building Utility Performance Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Values gathered over 8760.00 hours



Site and Source Energy

Total Energy [kBtu] Energy Per Total Building Area [kBtu/ft2] Energy Per Conditioned Building Area [kBtu/ft2]
Total Site Energy 974441.67 24.98 45.09
Net Site Energy 974441.67 24.98 45.09
Total Source Energy 2159323.25 55.36 99.92
Net Source Energy 2159323.25 55.36 99.92


Site to Source Energy Conversion Factors

Site=>Source Conversion Factor
Electricity 3.167
Natural Gas 1.084
District Cooling 1.056
District Heating 3.613
Steam 1.200
Gasoline 1.050
Diesel 1.050
Coal 1.050
Fuel Oil No 1 1.050
Fuel Oil No 2 1.050
Propane 1.050
Other Fuel 1 1.000
Other Fuel 2 1.000


Building Area

Area [ft2]
Total Building Area 39005.22
Net Conditioned Building Area 21609.96
Unconditioned Building Area 17395.26


End Uses

Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating 0.00 444903.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 27599.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 58472.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 82650.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 529538.39 444903.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Note: Natural gas appears to be the principal heating source based on energy usage.

End Uses By Subcategory

Subcategory Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 444903.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 27599.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 10546.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 41096.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 5385.56 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 42687.44 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 30929.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 160227.26 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 10631.34 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 18093.79 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 40378.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
  Water Heater 4468.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Other 78181.98 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


End Uses By Space Type

Space Type Electricity [kBtu] Natural Gas [kBtu] Gasoline [kBtu] Diesel [kBtu] Coal [kBtu] Fuel Oil No 1 [kBtu] Fuel Oil No 2 [kBtu] Propane [kBtu] Other Fuel 1 [kBtu] Other Fuel 2 [kBtu] District Cooling [kBtu] District Heating [kBtu] Water [gal]
Heating Unassigned 0.00 444903.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling Unassigned 27599.30 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting GENERAL 38708.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Unassigned 20603.65 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment GENERAL 301503.54 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans Unassigned 58472.72 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems Unassigned 82650.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 312247.30
Refrigeration Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators Unassigned 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Utility Use Per Conditioned Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 2.74 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 7.81 20.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45
Other 13.95 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 24.50 20.59 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 14.45


Utility Use Per Total Floor Area

Electricity Intensity [kBtu/ft2] Natural Gas Intensity [kBtu/ft2] Gasoline Intensity [kBtu/ft2] Diesel Intensity [kBtu/ft2] Coal Intensity [kBtu/ft2] Fuel Oil No 1 Intensity [kBtu/ft2] Fuel Oil No 2 Intensity [kBtu/ft2] Propane Intensity [kBtu/ft2] Other Fuel 1 Intensity [kBtu/ft2] Other Fuel 2 Intensity [kBtu/ft2] District Cooling Intensity [kBtu/ft2] District Heating Intensity [kBtu/ft2] Water Intensity [gal/ft2]
Lighting 1.52 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
HVAC 4.33 11.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01
Other 7.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total 13.58 11.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 8.01


Electric Loads Satisfied

Electricity [kBtu] Percent Electricity [%]
Fuel-Fired Power Generation 0.000 0.00
High Temperature Geothermal* 0.000 0.00
Photovoltaic Power 0.000 0.00
Wind Power 0.000 0.00
Power Conversion 0.000 0.00
Net Decrease in On-Site Storage 0.000 0.00
Total On-Site Electric Sources 0.000 0.00
     
Electricity Coming From Utility 529538.392 100.00
Surplus Electricity Going To Utility 0.000 0.00
Net Electricity From Utility 529538.392 100.00
     
Total On-Site and Utility Electric Sources 529538.392 100.00
Total Electricity End Uses 529538.392 100.00


On-Site Thermal Sources

Heat [kBtu] Percent Heat [%]
Water-Side Heat Recovery 0.00 0.00
Air to Air Heat Recovery for Cooling 1150.16 0.67
Air to Air Heat Recovery for Heating 169418.83 99.33
High-Temperature Geothermal* 0.00 0.00
Solar Water Thermal 0.00 0.00
Solar Air Thermal 0.00 0.00
Total On-Site Thermal Sources 170568.99 100.00


Water Source Summary

Water [gal] Percent Water [%]
Rainwater Collection 0.00 0.00
Condensate Collection 0.00 0.00
Groundwater Well 0.00 0.00
Total On Site Water Sources 0.00 0.00
- - -
Initial Storage 0.00 0.00
Final Storage 0.00 0.00
Change in Storage 0.00 0.00
- - -
Water Supplied by Utility 312247.30 100.00
- - -
Total On Site, Change in Storage, and Utility Water Sources 312247.30 100.00
Total Water End Uses 312247.30 100.00


Setpoint Not Met Criteria

Degrees [deltaF]
Tolerance for Zone Heating Setpoint Not Met Time 0.36
Tolerance for Zone Cooling Setpoint Not Met Time 0.36


Comfort and Setpoint Not Met Summary

Facility [Hours]
Time Setpoint Not Met During Occupied Heating 2174.67
Time Setpoint Not Met During Occupied Cooling 1.00
Time Not Comfortable Based on Simple ASHRAE 55-2004 2337.17


Note 1: An asterisk (*) indicates that the feature is not yet implemented.

Table of Contents

Top
Annual Building Utility Performance Summary
Input Verification and Results Summary
Demand End Use Components Summary
Source Energy End Use Components Summary
Component Sizing Summary
Surface Shadowing Summary
Adaptive Comfort Summary
Initialization Summary
Annual Heat Emissions Summary
Annual Thermal Resilience Summary
Climatic Data Summary
Envelope Summary
Shading Summary
Lighting Summary
Equipment Summary
HVAC Sizing Summary
Coil Sizing Details
System Summary
Outdoor Air Summary
Outdoor Air Details
Object Count Summary
Energy Meters
Sensible Heat Gain Summary
Standard 62.1 Summary
LEED Summary
Annual CO2 Resilience Summary
Annual Visual Resilience Summary

FANSPLIT

| CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR | CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR | CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR | CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR |

COILLOADS

| MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR | MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR | MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR | DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR | DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR | DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR | DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |

WATER HEATER: LOADS

| HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR | HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR |

HEATING AND COOLING LOADS

| CRAWLSPACE | BREEZEWAY | LIVING_UNIT1_FRONTROW_BOTTOMFLOOR | LIVING_UNIT2_FRONTROW_BOTTOMFLOOR | LIVING_UNIT3_FRONTROW_BOTTOMFLOOR | LIVING_UNIT1_BACKROW_BOTTOMFLOOR | LIVING_UNIT2_BACKROW_BOTTOMFLOOR | LIVING_UNIT3_BACKROW_BOTTOMFLOOR | LIVING_UNIT1_FRONTROW_MIDDLEFLOOR | LIVING_UNIT2_FRONTROW_MIDDLEFLOOR | LIVING_UNIT3_FRONTROW_MIDDLEFLOOR | LIVING_UNIT1_BACKROW_MIDDLEFLOOR | LIVING_UNIT2_BACKROW_MIDDLEFLOOR | LIVING_UNIT3_BACKROW_MIDDLEFLOOR | ATTIC | LIVING_UNIT3_BACKROW_TOPFLOOR | LIVING_UNIT3_FRONTROW_TOPFLOOR | LIVING_UNIT1_FRONTROW_TOPFLOOR | LIVING_UNIT2_BACKROW_TOPFLOOR | LIVING_UNIT2_FRONTROW_TOPFLOOR | LIVING_UNIT1_BACKROW_TOPFLOOR |

Table of Contents

Report: Input Verification and Results Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

General

Value
Program Version and Build EnergyPlus, Version 23.1.0-87ed9199d4, YMD=2024.06.27 18:31
RunPeriod ANNUAL
Weather File International Falls Intl Ap MN USA TMY3 WMO#=727470
Latitude [deg] 48.57
Longitude [deg] -93.4
Elevation [ft] 1177.88
Time Zone -6.0
North Axis Angle [deg] 0.00
Rotation for Appendix G [deg] 0.00
Hours Simulated [hrs] 8760.00


ENVELOPE

Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 17103.09 6415.36 2136.19 6415.36 2136.19
Above Ground Wall Area [ft2] 16363.00 6175.53 2005.97 6175.53 2005.97
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 12.43 8.29 24.89 8.29 24.89
Above Ground Window-Wall Ratio [%] 13.00 8.61 26.51 8.61 26.51


Conditioned Window-Wall Ratio

Total North (315 to 45 deg) East (45 to 135 deg) South (135 to 225 deg) West (225 to 315 deg)
Gross Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Above Ground Wall Area [ft2] 15296.60 6115.58 1532.73 6115.58 1532.73
Window Opening Area [ft2] 2126.74 531.68 531.68 531.68 531.68
Gross Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69
Above Ground Window-Wall Ratio [%] 13.90 8.69 34.69 8.69 34.69


Skylight-Roof Ratio

Total
Gross Roof Area [ft2] 8451.30
Skylight Area [ft2] 0.00
Skylight-Roof Ratio [%] 0.00


PERFORMANCE

Zone Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Volume [ft3] Multipliers Above Ground Gross Wall Area [ft2] Underground Gross Wall Area [ft2] Window Glass Area [ft2] Opening Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
CRAWLSPACE 7794.39 No Yes 19513.17 1.00 185.02 740.10 0.00 0.00 0.0000   0.0000
BREEZEWAY 1798.16 No Yes 30553.25 1.00 0.00 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 10207.81 1.00 934.97 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
ATTIC 7802.71 No Yes 52795.56 1.00 881.37 0.00 0.00 0.00 0.0000   0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 679.51 0.00 59.08 59.08 0.5831 600.28 2.9092
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 10207.71 1.00 934.96 0.00 147.69 147.69 0.5831 600.28 2.9092
Total 39005.22     286601.37   16363.00 740.10 2126.74 2126.74 0.3230 1083.48 1.6118
Conditioned Total 21609.96     183739.38   15296.60 0.00 2126.74 2126.74 0.5831 600.28 2.9092
Unconditioned Total 17395.26     102861.98   1066.39 740.10 0.00 0.00 0.0000   0.0000
Not Part of Total 0.00     0.00   0.00 0.00 0.00 0.00      


Space Summary

Area [ft2] Conditioned (Y/N) Part of Total Floor Area (Y/N) Multipliers Zone Name Space Type Radiant/Solar Enclosure Name Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2] Tags
CRAWLSPACE 7794.39 No Yes 1.00 CRAWLSPACE GENERAL CRAWLSPACE 0.0000 0.00 0.0000  
BREEZEWAY 1798.16 No Yes 1.00 BREEZEWAY GENERAL BREEZEWAY 0.0000 0.00 0.0000  
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.5831 600.28 2.9092  
ATTIC 7802.71 No Yes 1.00 ATTIC GENERAL ATTIC 0.0000 0.00 0.0000  
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL LIVING_UNIT3_BACKROW_TOPFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT3_FRONTROW_TOPFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT1_FRONTROW_TOPFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL LIVING_UNIT2_BACKROW_TOPFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL LIVING_UNIT2_FRONTROW_TOPFLOOR 0.5831 600.28 2.9092  
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 Yes Yes 1.00 LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL LIVING_UNIT1_BACKROW_TOPFLOOR 0.5831 600.28 2.9092  
Total 39005.22             0.3230 1083.48 1.6118  
Conditioned Total 21609.96             0.5831 600.28 2.9092  
Unconditioned Total 17395.26             0.0000 0.00 0.0000  
Not Part of Total 0.00             0.0000 0.00 0.0000  


Space Type Summary

Total Area [ft2] Conditioned Area [ft2] Unconditioned Area [ft2] Not Part of Total Area [ft2] Lighting [Btu/h-ft2] People [ft2 per person] Plug and Process [Btu/h-ft2]
GENERAL 39005.22 21609.96 17395.26 0.00 0.3230 1083.48 1.6118
Total 39005.22 21609.96 17395.26 0.00      



Table of Contents

Report: Demand End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

End Uses

Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Time of Peak 30-JUN-18:20 06-JAN-08:19 - - - - - - - - - - 25-FEB-08:30
Heating 0.00 276.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 32.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 11.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 51.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 9.93 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 14.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                           
Total End Uses 124.02 276.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13


End Uses By Subcategory

Subcategory Electricity [kBtuh] Natural Gas [kBtuh] Gasoline [kBtuh] Diesel [kBtuh] Coal [kBtuh] Fuel Oil No 1 [kBtuh] Fuel Oil No 2 [kBtuh] Propane [kBtuh] Other Fuel 1 [kBtuh] Other Fuel 2 [kBtuh] District Cooling [kBtuh] Steam [kBtuh] Water [gal/min]
Heating General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler 0.00 276.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling General 32.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting General 11.38 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting Exterior-Lights 4.70 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment dishwasher 2.46 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  refrigerator 5.60 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  clotheswasher 0.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_dryer 5.66 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_range 9.89 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  electric_mels 25.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  IECC_adj 1.68 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans General 5.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation 4.61 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 1.13
  Water Heater 0.51 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
  Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Source Energy End Use Components Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Values gathered over 8760.00 hours



Source Energy End Use Components Summary

Source Electricity [kBtu] Source Natural Gas [kBtu] Source Gasoline [kBtu] Source Diesel [kBtu] Source Coal [kBtu] Source Fuel Oil No 1 [kBtu] Source Fuel Oil No 2 [kBtu] Source Propane [kBtu] Source Other Fuel 1 [kBtu] Source Other Fuel 2 [kBtu] Source District Cooling [kBtu] Source District Heating [kBtu]
Heating 0.00 482275.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 87406.97 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 122590.15 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 65251.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 954861.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 185183.10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 261754.41 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 1677048.09 482275.16 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Normalized Metrics

Source Energy End Use Components Per Conditioned Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 22.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 4.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 5.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 3.02 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 44.19 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 8.57 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 12.11 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 77.61 22.32 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Source Energy End Use Components Per Total Floor Area

Source Electricity [kBtu/ft2] Source Natural Gas [kBtu/ft2] Source Gasoline [kBtu/ft2] Source Diesel [kBtu/ft2] Source Coal [kBtu/ft2] Source Fuel Oil No 1 [kBtu/ft2] Source Fuel Oil No 2 [kBtu/ft2] Source Propane [kBtu/ft2] Source Other Fuel 1 [kBtu/ft2] Source Other Fuel 2 [kBtu/ft2] Source District Cooling [kBtu/ft2] Source District Heating [kBtu/ft2]
Heating 0.00 12.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling 2.24 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting 3.14 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting 1.67 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment 24.48 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans 4.75 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems 6.71 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
                         
Total Source Energy End Use Components 43.00 12.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00



Table of Contents

Report: Component Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

ZoneHVAC:EnergyRecoveryVentilator

User-Specified Supply Air Flow Rate [ft3/min] User-Specified Exhaust Air Flow Rate [ft3/min]
ERV_UNIT1_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_BOTTOMFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_MIDDLEFLOOR 44.99 44.99
ERV_UNIT3_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT3_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_BACKROW_TOPFLOOR 44.99 44.99
ERV_UNIT2_FRONTROW_TOPFLOOR 44.99 44.99
ERV_UNIT1_BACKROW_TOPFLOOR 44.99 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Fan:OnOff

User-Specified Maximum Flow Rate [ft3/min] Design Size Maximum Flow Rate [ft3/min]
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR 44.99  
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR 44.99  
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR 44.99  
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR   415.08
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR   187.42
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR   313.55
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR   390.79
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR   168.05
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR   286.20
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR   413.34
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR   189.22
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR   319.51
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR   389.33
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR   171.61
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR   290.38
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR   421.42
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR   196.56
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR   314.70
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR   411.94
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR   197.11
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR   286.79
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR   160.01
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR   160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

HeatExchanger:AirToAir:SensibleAndLatent

User-Specified Nominal Supply Air Flow Rate [ft3/min]
OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR 44.99
OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR 44.99
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirTerminal:SingleDuct:ConstantVolume:NoReheat

Design Size Maximum Air Flow Rate [ft3/min]
ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR 415.08
ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR 187.42
ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR 313.55
ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR 390.79
ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR 168.05
ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR 286.20
ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR 413.34
ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR 189.22
ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR 319.51
ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR 389.33
ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR 171.61
ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR 290.38
ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR 286.79
ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR 314.70
ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR 421.42
ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR 197.11
ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR 196.56
ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR 411.94
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC

Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] Sum of Air Terminal Maximum Flow Rates [ft3/min] Adjusted Heating Design Air Flow Rate [ft3/min] Adjusted Cooling Design Air Flow Rate [ft3/min] Adjusted Main Design Air Flow Rate [ft3/min] User Heating Air Flow Ratio [] Calculated Heating Air Flow Ratio [] Design Supply Air Flow Rate [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.08 415.08 415.08 415.08 415.08 415.08 1.00 1.00 415.08
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.42 187.42 187.42 187.42 187.42 187.42 1.00 1.00 187.42
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.55 313.55 313.55 313.55 313.55 313.55 1.00 1.00 313.55
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.79 390.79 390.79 390.79 390.79 390.79 1.00 1.00 390.79
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.05 168.05 168.05 168.05 168.05 168.05 1.00 1.00 168.05
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.20 286.20 286.20 286.20 286.20 286.20 1.00 1.00 286.20
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.34 413.34 413.34 413.34 413.34 413.34 1.00 1.00 413.34
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.22 189.22 189.22 189.22 189.22 189.22 1.00 1.00 189.22
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.51 319.51 319.51 319.51 319.51 319.51 1.00 1.00 319.51
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.33 389.33 389.33 389.33 389.33 389.33 1.00 1.00 389.33
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.61 171.61 171.61 171.61 171.61 171.61 1.00 1.00 171.61
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.38 290.38 290.38 290.38 290.38 290.38 1.00 1.00 290.38
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.42 421.42 421.42 421.42 421.42 421.42 1.00 1.00 421.42
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.56 196.56 196.56 196.56 196.56 196.56 1.00 1.00 196.56
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.70 314.70 314.70 314.70 314.70 314.70 1.00 1.00 314.70
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.94 411.94 411.94 411.94 411.94 411.94 1.00 1.00 411.94
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.11 197.11 197.11 197.11 197.11 197.11 1.00 1.00 197.11
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.79 286.79 286.79 286.79 286.79 286.79 1.00 1.00 286.79
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Cooling:DX:SingleSpeed

Design Size Rated Air Flow Rate [ft3/min] Design Size Gross Rated Total Cooling Capacity [ton] Design Size Gross Rated Sensible Heat Ratio
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 415.08 1.26 0.732019
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 187.42 0.624618 0.701083
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 313.55 0.966734 0.725914
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 390.79 1.18 0.731631
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 168.05 0.560049 0.701083
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 286.20 0.867768 0.731382
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 413.34 1.23 0.738884
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 189.22 0.630593 0.701083
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 319.51 0.970699 0.730849
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 389.33 1.16 0.737471
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 171.61 0.571920 0.701083
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 290.38 0.868328 0.736137
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 421.42 1.27 0.734748
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 196.56 0.655071 0.701083
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 314.70 0.974858 0.724665
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 411.94 1.23 0.735793
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 197.11 0.653459 0.703375
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 286.79 0.874779 0.729774
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

AirLoopHVAC:UnitaryHeatCool

Supply Air Flow Rate [ft3/min] Supply Air Flow Rate During Heating Operation [ft3/min] Supply Air Flow Rate During Cooling Operation [ft3/min] Nominal Cooling Capacity [ton] Fraction of Supply Air Flow That Goes Through the Controlling Zone
ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR 415.08 415.08 415.08 1.26 1.00
ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR 187.42 187.42 187.42 0.624618 1.00
ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR 313.55 313.55 313.55 0.966734 1.00
ACANDF_UNIT1_BACKROW_BOTTOMFLOOR 390.79 390.79 390.79 1.18 1.00
ACANDF_UNIT2_BACKROW_BOTTOMFLOOR 168.05 168.05 168.05 0.560049 1.00
ACANDF_UNIT3_BACKROW_BOTTOMFLOOR 286.20 286.20 286.20 0.867768 1.00
ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR 413.34 413.34 413.34 1.23 1.00
ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR 189.22 189.22 189.22 0.630593 1.00
ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR 319.51 319.51 319.51 0.970699 1.00
ACANDF_UNIT1_BACKROW_MIDDLEFLOOR 389.33 389.33 389.33 1.16 1.00
ACANDF_UNIT2_BACKROW_MIDDLEFLOOR 171.61 171.61 171.61 0.571920 1.00
ACANDF_UNIT3_BACKROW_MIDDLEFLOOR 290.38 290.38 290.38 0.868328 1.00
ACANDF_UNIT1_FRONTROW_TOPFLOOR 421.42 421.42 421.42 1.27 1.00
ACANDF_UNIT2_FRONTROW_TOPFLOOR 196.56 196.56 196.56 0.655071 1.00
ACANDF_UNIT3_FRONTROW_TOPFLOOR 314.70 314.70 314.70 0.974858 1.00
ACANDF_UNIT1_BACKROW_TOPFLOOR 411.94 411.94 411.94 1.23 1.00
ACANDF_UNIT2_BACKROW_TOPFLOOR 197.11 197.11 197.11 0.653459 1.00
ACANDF_UNIT3_BACKROW_TOPFLOOR 286.79 286.79 286.79 0.874779 1.00
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Coil:Heating:Water

Design Size Rated Capacity [Btu/h] Design Size Maximum Water Flow Rate [gal/min] Design Size U-Factor Times Area Value [Btu/h-F]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 30070.42 3.09 439.65
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 16488.20 1.69 228.25
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 24013.16 2.46 345.68
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 28621.40 2.94 417.21
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 15332.33 1.57 210.03
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 22381.33 2.30 320.31
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 29964.44 3.08 437.80
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 16594.45 1.70 229.76
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 24367.53 2.50 351.02
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 28532.29 2.93 415.63
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 15544.19 1.60 213.22
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 22629.35 2.32 324.01
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 30448.73 3.13 445.50
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 17033.36 1.75 236.81
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 24081.40 2.47 346.74
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 29883.14 3.07 436.74
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 17066.14 1.75 237.32
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 22416.53 2.30 320.86
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:HeatPump:WrappedCondenser

Evaporator air flow rate [ft3/min]
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 160.01
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 160.01
WATER HEATER_UNIT1_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT2_BACKROW_TOPFLOOR 160.01
WATER HEATER_UNIT3_BACKROW_TOPFLOOR 160.01
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

PlantLoop

Maximum Loop Flow Rate [ft3/min] Plant Loop Volume [ft3]
BOILER LOOP 5.70 11.40
DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR 1.04 2.09
DHW LOOP_UNIT1_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_FRONTROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT1_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT2_BACKROW_TOPFLOOR 1.04 2.09
DHW LOOP_UNIT3_BACKROW_TOPFLOOR 1.04 2.09
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Pump:VariableSpeed

Design Flow Rate [ft3/min]
BOILER CIRC PUMP 5.70
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR 1.04
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR 1.04
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

Boiler:HotWater

Design Size Nominal Capacity [Btu/h] Design Size Design Water Flow Rate [gal/min]
CENTRAL BOILER 415468.38 42.65
User-Specified values were used. Design Size values were used if no User-Specified values were provided.

WaterHeater:Stratified

Use Side Design Flow Rate [ft3/min]
WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR 1.04
WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR 1.04
WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR 1.04
WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR 1.04
WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR 1.04
WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR 1.04
WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR 1.04
User-Specified values were used. Design Size values were used if no User-Specified values were provided.


Table of Contents

Report: Surface Shadowing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Surfaces (Walls, Roofs, etc) that may be Shadowed by Other Surfaces

Possible Shadow Receivers
OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR | ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR | ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR ROOF_LEFT | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
Mir-OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR ROOF_RIGHT | WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR | WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR ROOF_LEFT | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR |
OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
Mir-OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDF OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
BGWALL_UPPER_SDR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_LDB OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
BGWALL_UPPER_SDL OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
BREEZEWAY_MIDDLEFLOOR WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR |
BREEZEWAY_TOPFLOOR WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDF_UNIT1_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_MIDDLEFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_SDR_UNIT3_FRONTROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR OVERHANG_LDB_UNIT1_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT2_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT3_BACKROW_BOTTOMFLOOR | OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR | WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDF_UNIT1_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | BREEZEWAY_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR | WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_SDR_UNIT3_FRONTROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR OVERHANG_LDB_UNIT1_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT2_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT3_BACKROW_MIDDLEFLOOR | OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_SDR_UNIT3_BACKROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR | WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDB_UNIT1_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT2_BACKROW_TOPFLOOR | OVERHANG_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR OVERHANG_LDF_UNIT1_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT2_FRONTROW_TOPFLOOR | OVERHANG_SDR_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_SDL_UNIT3_FRONTROW_TOPFLOOR | OVERHANG_LDF_UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR | WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR |


Subsurfaces (Windows and Doors) that may be Shadowed by Surfaces

Possible Shadow Receivers
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR |
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR |
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR |
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR |
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR DOOR_LDF_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR |
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR |
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR |
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR DOOR_LDF_UNIT2_BACKROW_TOPFLOOR |
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR |
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR |
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR |
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR DOOR_LDF_UNIT1_BACKROW_TOPFLOOR |



Table of Contents

Report: Adaptive Comfort Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Time Not Meeting the Adaptive Comfort Models during Occupied Hours

ASHRAE55 90% Acceptability Limits [Hours] ASHRAE55 80% Acceptability Limits [Hours] CEN15251 Category I Acceptability Limits [Hours] CEN15251 Category II Acceptability Limits [Hours] CEN15251 Category III Acceptability Limits [Hours]



Table of Contents

Report: Initialization Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Version

Version ID
1 23.1


Timesteps per Hour

#TimeSteps Minutes per TimeStep {minutes}
1 6 10


System Convergence Limits

Minimum System TimeStep {minutes} Max HVAC Iterations Minimum Plant Iterations Maximum Plant Iterations
1 1 20 2 8


Simulation Control

Do Zone Sizing Do System Sizing Do Plant Sizing Do Design Days Do Weather Simulation Do HVAC Sizing Simulation
1 Yes Yes No Yes Yes No


Performance Precision Tradeoffs

Use Coil Direct Simulation Zone Radiant Exchange Algorithm Override Mode Number of Timestep In Hour Force Euler Method Minimum Number of Warmup Days Force Suppress All Begin Environment Resets Minimum System Timestep MaxZoneTempDiff MaxAllowedDelTemp
1 No ScriptF Normal 6 No 1 No 1.0 0.300 2.0000E-003


Output Reporting Tolerances

Tolerance for Time Heating Setpoint Not Met Tolerance for Zone Cooling Setpoint Not Met Time
1 0.200 0.200


Site:GroundTemperature:BuildingSurface

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40 64.40


Site:GroundTemperature:FCfactorMethod

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 10.90 8.24 12.97 20.35 39.67 54.57 64.62 67.68 62.46 50.90 35.44 21.07


Site:GroundTemperature:Shallow

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40 55.40


Site:GroundTemperature:Deep

Jan{F} Feb{F} Mar{F} Apr{F} May{F} Jun{F} Jul{F} Aug{F} Sep{F} Oct{F} Nov{F} Dec{F}
1 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80 60.80


Site:GroundReflectance

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:SnowModifier

Normal Daylighting {dimensionless}
1 1.000 1.000


Site:GroundReflectance:Snow

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Site:GroundReflectance:Snow:Daylighting

Jan{dimensionless} Feb{dimensionless} Mar{dimensionless} Apr{dimensionless} May{dimensionless} Jun{dimensionless} Jul{dimensionless} Aug{dimensionless} Sep{dimensionless} Oct{dimensionless} Nov{dimensionless} Dec{dimensionless}
1 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20 0.20


Environment:Weather Station

Wind Sensor Height Above Ground {ft} Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Sensor Height Above Ground {ft} Wind Speed Modifier Coefficient-Internal Temperature Modifier Coefficient-Internal
1 32.810 0.140 885.870 4.921 1.586 9.750E-003


Site:Location

Location Name Latitude {N+/S- Deg} Longitude {E+/W- Deg} Time Zone Number {GMT+/-} Elevation {ft} Standard Pressure at Elevation {psi} Standard RhoAir at Elevation
1 International Falls Intl Ap MN USA TMY3 WMO#=727470 48.57 -93.40 -6.00 1177.88 14. 1.1539


Site Water Mains Temperature Information

Calculation Method{} Water Mains Temperature Schedule Name{} Annual Average Outdoor Air Temperature{F} Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaF} Fixed Default Water Mains Temperature{F}
1 Correlation NA 37.92 65.88 NA


Building Information

Building Name North Axis {deg} Terrain Loads Convergence Tolerance Value Temperature Convergence Tolerance Value Solar Distribution Maximum Number of Warmup Days Minimum Number of Warmup Days
1 US+MF+CZ7+oilfurnace+crawlspace+IECC_2021 0.000 Suburbs 4.00000E-002 0.40000 FullExterior 25 6


Inside Convection Algorithm

Algorithm {Simple
TARP
CeilingDiffuser
AdaptiveConvectionAlgorithm}
1 TARP


Outside Convection Algorithm

Algorithm {SimpleCombined
TARP
MoWitt
DOE-2
AdaptiveConvectionAlgorithm}
1 DOE-2


Sky Radiance Distribution

Value {Anisotropic}
1 Anisotropic


Zone Air Solution Algorithm

Algorithm {ThirdOrderBackwardDifference
AnalyticalSolution
EulerMethod}
Space Heat Balance Sizing

Space Heat Balance Simulation

1 ThirdOrderBackwardDifference No No


Zone Air Carbon Dioxide Balance Simulation

Simulation {Yes/No} Carbon Dioxide Concentration
1 No N/A


Zone Air Generic Contaminant Balance Simulation

Simulation {Yes/No} Generic Contaminant Concentration
1 No N/A


Zone Air Mass Flow Balance Simulation

Enforce Mass Balance



Adjust Zone Mixing and Return {AdjustMixingOnly
AdjustReturnOnly
AdjustMixingThenReturn
AdjustReturnThenMixing
None}
Adjust Zone Infiltration {AddInfiltration
AdjustInfiltration
None}

Infiltration Zones {MixingSourceZonesOnly
AllZones}


1 No N/A N/A N/A


HVACSystemRootFindingAlgorithm

Value {RegulaFalsi
Bisection
BisectionThenRegulaFalsi
RegulaFalsiThenBisection}
1 RegulaFalsi


Environment:Site Atmospheric Variation

Wind Speed Profile Exponent {} Wind Speed Profile Boundary Layer Thickness {ft} Air Temperature Gradient Coefficient {F/ft}
1 0.220 1213.970 0.003566


Material Details

Material Name ThermalResistance {m2-K/w} Roughness Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} Absorptance:Thermal Absorptance:Solar Absorptance:Visible
1 SHEATHING_CONSOL_LAYER 0.8807 Rough 0.1021 3.533E-002 1.255 0.350 0.9000 0.7000 0.7000
2 CEIL_CONSOL_LAYER 9.1788 Rough 1.8587 6.172E-002 2.618 0.185 0.9000 0.7000 0.7000
3 FLOOR_CONSOL_LAYER 5.7198 Rough 0.9377 4.996E-002 3.438 0.219 0.9000 0.7000 0.7000
4 BSMTWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
5 CRAWLWALL_CONSOL_LAYER 2.3423E-005 Rough 0.0008 10.844 7.541 0.248 0.9000 0.7000 0.7000
6 WALL_CONSOL_LAYER 2.4438 Rough 0.4584 5.717E-002 7.541 0.248 0.9000 0.7000 0.7000
7 VERY HIGH REFLECTIVITY SURFACE 2.1097E-006 Smooth 0.0016 237.000 168.680 0.216 0.9000 5.0000E-002 5.0000E-002
8 GYPSUMBOARD-5/16IN 5.0054E-002 Rough 0.0260 0.159 39.954 0.270 0.9000 0.4000 0.1000
9 COPPERPIPE 4.7506E-005 MediumRough 0.0625 401.000 140.026 0.200 0.9000 0.6500 0.6500
10 F08 METAL SURFACE 1.7668E-005 Smooth 0.0026 45.280 488.437 0.119 0.9000 0.7000 0.7000
11 CONCRETE_4IN 7.7356E-002 Rough 0.3330 1.312 140.014 0.111 0.9000 0.7000 0.7000
12 ASPHALT_SHINGLE 7.7448E-002 MediumRough 0.0208 8.186E-002 70.000 0.300 0.9000 0.7500 0.7000
13 WOOD_SHINGLE 0.1115 MediumSmooth 0.0417 0.114 26.600 0.390 0.9000 0.7000 0.7000
14 SLATE_SHINGLE 8.8061E-003 MediumSmooth 0.0417 1.442 100.000 0.300 0.9000 0.7000 0.7000
15 CEMENT_STUCCO 2.6422E-002 MediumSmooth 0.0625 0.721 116.464 0.210 0.9000 0.7000 0.7000
16 SYN_STUCCO 3.5237E-002 MediumSmooth 0.0100 8.650E-002 24.971 0.210 0.7000 0.7000 0.7000
17 DRYWALL_1/2IN 7.9331E-002 MediumSmooth 0.0417 0.160 50.000 0.260 0.9000 0.7000 0.7000
18 OSB_5/8IN 0.1365 MediumSmooth 0.0521 0.116 34.000 0.290 0.9000 0.7000 0.7000
19 OSB_7/16IN 9.5550E-002 MediumSmooth 0.0365 0.116 34.000 0.290 0.9000 0.7000 0.7000
20 BLOWN_R30 5.1614 MediumRough 0.6975 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
21 BLOWN_R30_TOP 2.8489 MediumRough 0.3849 4.119E-002 0.600 0.200 0.9000 0.7000 0.7000
22 PLYWOOD_3/4IN 0.1650 Rough 0.0625 0.115 34.003 0.161 0.9000 0.7000 0.7000
23 BATT_R19 7.3089 MediumRough 0.0833 3.475E-003 0.600 0.200 0.9000 0.7000 0.7000
24 LUMBER_2X4 0.7709 Rough 0.2920 0.115 32.003 0.183 0.9000 0.7000 0.7000
25 CARPET_N_PAD 0.4224 MediumSmooth 0.0833 6.013E-002 2.000 0.200 0.9000 0.7000 0.7000
26 BATT_R13 2.2936 MediumRough 0.2917 3.876E-002 0.600 0.200 0.9000 0.7000 0.7000
27 OSB_1/2IN 0.1092 MediumSmooth 0.0417 0.116 34.000 0.290 0.9000 0.7000 0.7000
28 SOIL_12IN 0.1761 Rough 1.0000 1.731 115.011 0.056 0.9000 0.7000 0.7000
29 DOOR_CONST 0.5870 Smooth 0.1387 7.201E-002 32.003 0.183 0.9000 0.7000 0.7000
30 GYP_BOARD_1/2IN 8.0130E-002 Rough 0.0417 0.159 39.954 0.270 0.9000 0.4000 0.1000
31 STD WOOD 6INCH 1.2500 MediumSmooth 0.4921 0.120 33.711 0.289 0.9000 0.7000 0.7000
32 PIPE INSULATION 0.3830 VeryRough 0.0417 3.317E-002 5.681 0.200 0.9000 0.5000 0.5000
33 MANF_WALL_AIRGAP 0.1200 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
34 BLDG_PAPER_FELT 1.0567E-002 Smooth 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
35 R_HIGH 177.0000 MediumRough 0.0000 0.000 0.000 0.000 0.9000 0.7000 0.7000
36 CLEAR ACRYLIC PLASTIC 3.3333E-003 VerySmooth 0.0098 0.900 0.000 0.000 0.9000 0.0000 0.0000
37 DIFFUSING ACRYLIC PLASTIC 2.4444E-003 VerySmooth 0.0072 0.900 0.000 0.000 0.9000 0.0000 0.0000
38 INT_BLIND 0.0000 Rough 0.0000 0.000 0.000 0.000 0.0000 0.0000 0.0000
39 GLASS 0.4127 VerySmooth 0.1373 0.101 0.000 0.000 0.8400 0.0000 0.0000


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


Surface Geometry

Starting Corner Vertex Input Direction Coordinate System Daylight Reference Point Coordinate System Rectangular (Simple) Surface Coordinate System
1 LowerLeftCorner Counterclockwise RelativeCoordinateSystem RelativeCoordinateSystem RelativeToZoneOrigin


Other Side Coefficients

Name Combined convective/radiative film coefficient {Btu/h-ft2-F} User selected Constant Temperature {F} Coefficient modifying the constant temperature term Coefficient modifying the external dry bulb temperature term Coefficient modifying the ground temperature term Coefficient modifying the wind speed term {s/m} Coefficient modifying the zone air temperature term Constant Temperature Schedule Name Sinusoidal Variation Period of Sinusoidal Variation Previous Other Side Temperature Coefficient Minimum Other Side Temperature {F} Maximum Other Side Temperature {F}
1 SURFPROPOTHSDCOEFSLABAVERAGE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABAVERAGESURFACETEMP NO 24.000 0.000 N/A N/A
2 SURFPROPOTHSDCOEFSLABPERIMETER N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABPERIMETERTEMP NO 24.000 0.000 N/A N/A
3 SURFPROPOTHSDCOEFSLABCORE N/A N/A 1.000 0.000 0.000 0.000 0.000 SCHEDULEOSCSLABCORETEMP NO 24.000 0.000 N/A N/A


Surface Heat Transfer Algorithm

Value {CTF - ConductionTransferFunction
EMPD - MoisturePenetrationDepthConductionTransferFunction
CondFD - ConductionFiniteDifference
HAMT - CombinedHeatAndMoistureFiniteElement} - Description
Inside Surface Max Temperature Limit{F}


Surface Convection Coefficient Lower Limit {Btu/h-ft2-F}


Surface Convection Coefficient Upper Limit {Btu/h-ft2-F}


1 CTF - ConductionTransferFunction 392. 0.02 176.1


Shading Summary

Number of Fixed Detached Shades Number of Building Detached Shades Number of Attached Shades
1 0 0 60


Zone Summary

Number of Zones Number of Zone Surfaces Number of SubSurfaces
1 21 186 48


Zone Information

Zone Name North Axis {deg} Origin X-Coordinate {ft} Origin Y-Coordinate {ft} Origin Z-Coordinate {ft} Centroid X-Coordinate {ft} Centroid Y-Coordinate {ft} Centroid Z-Coordinate {ft} Type Zone Multiplier Zone List Multiplier Minimum X {ft} Maximum X {ft} Minimum Y {ft} Maximum Y {ft} Minimum Z {ft} Maximum Z {ft} Ceiling Height {ft} Volume {ft3} Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} Floor Area {ft2} Exterior Gross Wall Area {ft2} Exterior Net Wall Area {ft2} Exterior Window Area {ft2} Number of Surfaces Number of SubSurfaces Number of Shading SubSurfaces Part of Total Building Area
1 CRAWLSPACE 0.0 0.00 0.00 0.00 59.94 32.51 -0.8 1 1 1 0.00 119.89 0.00 65.10 -2.0 0.49 2.49 19513.15 TARP DOE-2 7794.37 185.05 185.05 0.00 15 0 0 Yes
2 BREEZEWAY 0.0 0.00 0.00 0.00 59.94 32.55 13.26 1 1 1 0.00 119.89 30.05 35.04 0.49 25.99 17.00 30553.07 TARP DOE-2 1798.18 0.00 0.00 0.00 4 0 0 Yes
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 4.76 1 1 1 0.00 39.96 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 4.76 1 1 1 39.96 79.93 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 4.76 1 1 1 79.93 119.89 0.00 30.05 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 4.76 1 1 1 0.00 39.96 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 4.76 1 1 1 39.96 79.93 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 4.76 1 1 1 79.93 119.89 35.04 65.10 0.49 8.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 13.26 1 1 1 0.00 39.96 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 13.26 1 1 1 39.96 79.93 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 13.26 1 1 1 79.93 119.89 0.00 30.05 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 13.26 1 1 1 0.00 39.96 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 13.26 1 1 1 39.96 79.93 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 13.26 1 1 1 79.93 119.89 35.04 65.10 8.99 17.49 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
15 ATTIC 0.0 -134.9 51.61 0.00 59.94 32.55 29.56 1 1 1 0.00 119.89 0.00 65.10 25.99 39.54 6.76 52795.39 TARP DOE-2 7802.66 881.33 881.33 0.00 11 0 0 Yes
16 LIVING_UNIT3_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 50.07 21.75 1 1 1 79.93 119.89 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 99.91 15.03 21.75 1 1 1 79.93 119.89 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 15.03 21.75 1 1 1 0.00 39.96 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes
19 LIVING_UNIT2_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 50.07 21.75 1 1 1 39.96 79.93 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 0.0 0.00 0.00 0.00 59.94 15.03 21.75 1 1 1 39.96 79.93 0.00 30.05 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 679.48 599.39 59.10 6 2 2 Yes
21 LIVING_UNIT1_BACKROW_TOPFLOOR 0.0 0.00 0.00 0.00 19.98 50.07 21.75 1 1 1 0.00 39.96 35.04 65.10 17.49 25.99 8.50 10207.79 TARP DOE-2 1200.51 934.94 766.25 147.70 6 3 4 Yes


Zone Internal Gains Nominal

Zone Name Floor Area {ft2} # Occupants Area per Occupant {ft2/person} Occupant per Area {person/ft2} Interior Lighting {Btu/h-ft2} Electric Load {Btu/h-ft2} Gas Load {Btu/h-ft2} Other Load {Btu/h-ft2} Hot Water Eq {Btu/h-ft2} Steam Equipment {Btu/h-ft2} Sum Loads per Area {Btu/h-ft2} Outdoor Controlled Baseboard Heat
1 CRAWLSPACE 7794.37 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
2 BREEZEWAY 1798.18 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
15 ATTIC 7802.66 0.0 N/A 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 No
16 LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
17 LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
18 LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
19 LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
20 LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No
21 LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 600.276 0.002 0.583 2.909 0.000 0.000 0.000 0.000 3.492 No


People Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Number of People {} People/Floor Area {person/ft2} Floor Area per person {ft2/person} Fraction Radiant Fraction Convected Sensible Fraction Calculation Activity level ASHRAE 55 Warnings Carbon Dioxide Generation Rate Nominal Minimum Number of People Nominal Maximum Number of People
1 PEOPLE_UNIT1_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
2 PEOPLE_UNIT2_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
3 PEOPLE_UNIT3_FRONTROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
4 PEOPLE_UNIT1_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
5 PEOPLE_UNIT2_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
6 PEOPLE_UNIT3_BACKROW_BOTTOMFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
7 PEOPLE_UNIT1_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
8 PEOPLE_UNIT2_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
9 PEOPLE_UNIT3_FRONTROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
10 PEOPLE_UNIT1_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
11 PEOPLE_UNIT2_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
12 PEOPLE_UNIT3_BACKROW_MIDDLEFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
13 PEOPLE_UNIT1_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
14 PEOPLE_UNIT2_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
15 PEOPLE_UNIT3_FRONTROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
16 PEOPLE_UNIT1_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
17 PEOPLE_UNIT2_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2
18 PEOPLE_UNIT3_BACKROW_TOPFLOOR OCCUPANCY LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 2.0 0.002 600.276 0.000 1.000 AutoCalculate ACTIVITY_SCH No 3.8200E-008 0 2


Lights Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Lighting Level {Btu/h} Lights/Floor Area {Btu/h-ft2} Lights per person {W/person} Fraction Return Air Fraction Radiant Fraction Short Wave Fraction Convected Fraction Replaceable End-Use Category Nominal Minimum Lighting Level {Btu/h} Nominal Maximum Lighting Level {Btu/h}
1 LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
2 LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
3 LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
4 LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
5 LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
6 LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
7 LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
8 LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
9 LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
10 LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
11 LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
12 LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
13 LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
14 LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
15 LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
16 LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
17 LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
18 LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
19 LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
20 LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
21 LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
22 LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
23 LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
24 LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
25 LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
26 LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
27 LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
28 LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
29 LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
30 LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
31 LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
32 LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
33 LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
34 LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812
35 LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 481.174 0.401 70.512 0.000 0.600 0.200 0.200 0.000 General 33.079 481.174
36 LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR INTERIORLIGHTINGHE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 218.812 0.182 32.065 0.000 0.600 0.200 0.200 0.000 General 15.044 218.812


ElectricEquipment Internal Gains Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Equipment Level {Btu/h} Equipment/Floor Area {Btu/h-ft2} Equipment per person {W/person} Fraction Latent Fraction Radiant Fraction Lost Fraction Convected End-Use SubCategory Nominal Minimum Equipment Level {Btu/h} Nominal Maximum Equipment Level {Btu/h}
1 DISHWASHER1_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
2 REFRIGERATOR1_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
3 CLOTHESWASHER1_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
4 ELECTRIC_DRYER1_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
5 ELECTRIC_RANGE1_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
6 TELEVISION1_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
7 ELECTRIC_MELS1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
8 IECC_ADJ1_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
9 DISHWASHER2_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
10 REFRIGERATOR2_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
11 CLOTHESWASHER2_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
12 ELECTRIC_DRYER2_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
13 ELECTRIC_RANGE2_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
14 TELEVISION2_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
15 ELECTRIC_MELS2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
16 IECC_ADJ2_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
17 DISHWASHER3_FRONTROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
18 REFRIGERATOR3_FRONTROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
19 CLOTHESWASHER3_FRONTROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
20 ELECTRIC_DRYER3_FRONTROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
21 ELECTRIC_RANGE3_FRONTROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
22 TELEVISION3_FRONTROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
23 ELECTRIC_MELS3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
24 IECC_ADJ3_FRONTROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
25 DISHWASHER1_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
26 REFRIGERATOR1_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
27 CLOTHESWASHER1_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
28 ELECTRIC_DRYER1_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
29 ELECTRIC_RANGE1_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
30 TELEVISION1_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
31 ELECTRIC_MELS1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
32 IECC_ADJ1_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
33 DISHWASHER2_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
34 REFRIGERATOR2_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
35 CLOTHESWASHER2_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
36 ELECTRIC_DRYER2_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
37 ELECTRIC_RANGE2_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
38 TELEVISION2_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
39 ELECTRIC_MELS2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
40 IECC_ADJ2_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
41 DISHWASHER3_BACKROW_BOTTOMFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
42 REFRIGERATOR3_BACKROW_BOTTOMFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
43 CLOTHESWASHER3_BACKROW_BOTTOMFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
44 ELECTRIC_DRYER3_BACKROW_BOTTOMFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
45 ELECTRIC_RANGE3_BACKROW_BOTTOMFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
46 TELEVISION3_BACKROW_BOTTOMFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
47 ELECTRIC_MELS3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
48 IECC_ADJ3_BACKROW_BOTTOMFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
49 DISHWASHER1_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
50 REFRIGERATOR1_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
51 CLOTHESWASHER1_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
52 ELECTRIC_DRYER1_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
53 ELECTRIC_RANGE1_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
54 TELEVISION1_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
55 ELECTRIC_MELS1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
56 IECC_ADJ1_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
57 DISHWASHER2_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
58 REFRIGERATOR2_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
59 CLOTHESWASHER2_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
60 ELECTRIC_DRYER2_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
61 ELECTRIC_RANGE2_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
62 TELEVISION2_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
63 ELECTRIC_MELS2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
64 IECC_ADJ2_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
65 DISHWASHER3_FRONTROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
66 REFRIGERATOR3_FRONTROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
67 CLOTHESWASHER3_FRONTROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
68 ELECTRIC_DRYER3_FRONTROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
69 ELECTRIC_RANGE3_FRONTROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
70 TELEVISION3_FRONTROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
71 ELECTRIC_MELS3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
72 IECC_ADJ3_FRONTROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
73 DISHWASHER1_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
74 REFRIGERATOR1_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
75 CLOTHESWASHER1_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
76 ELECTRIC_DRYER1_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
77 ELECTRIC_RANGE1_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
78 TELEVISION1_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
79 ELECTRIC_MELS1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
80 IECC_ADJ1_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
81 DISHWASHER2_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
82 REFRIGERATOR2_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
83 CLOTHESWASHER2_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
84 ELECTRIC_DRYER2_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
85 ELECTRIC_RANGE2_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
86 TELEVISION2_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
87 ELECTRIC_MELS2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
88 IECC_ADJ2_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
89 DISHWASHER3_BACKROW_MIDDLEFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
90 REFRIGERATOR3_BACKROW_MIDDLEFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
91 CLOTHESWASHER3_BACKROW_MIDDLEFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
92 ELECTRIC_DRYER3_BACKROW_MIDDLEFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
93 ELECTRIC_RANGE3_BACKROW_MIDDLEFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
94 TELEVISION3_BACKROW_MIDDLEFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
95 ELECTRIC_MELS3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
96 IECC_ADJ3_BACKROW_MIDDLEFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
97 DISHWASHER1_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
98 REFRIGERATOR1_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
99 CLOTHESWASHER1_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
100 ELECTRIC_DRYER1_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
101 ELECTRIC_RANGE1_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
102 TELEVISION1_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
103 ELECTRIC_MELS1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
104 IECC_ADJ1_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
105 DISHWASHER2_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
106 REFRIGERATOR2_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
107 CLOTHESWASHER2_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
108 ELECTRIC_DRYER2_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
109 ELECTRIC_RANGE2_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
110 TELEVISION2_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
111 ELECTRIC_MELS2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
112 IECC_ADJ2_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
113 DISHWASHER3_FRONTROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
114 REFRIGERATOR3_FRONTROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
115 CLOTHESWASHER3_FRONTROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
116 ELECTRIC_DRYER3_FRONTROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
117 ELECTRIC_RANGE3_FRONTROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
118 TELEVISION3_FRONTROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
119 ELECTRIC_MELS3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
120 IECC_ADJ3_FRONTROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
121 DISHWASHER1_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
122 REFRIGERATOR1_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
123 CLOTHESWASHER1_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
124 ELECTRIC_DRYER1_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
125 ELECTRIC_RANGE1_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
126 TELEVISION1_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
127 ELECTRIC_MELS1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
128 IECC_ADJ1_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
129 DISHWASHER2_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
130 REFRIGERATOR2_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
131 CLOTHESWASHER2_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
132 ELECTRIC_DRYER2_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
133 ELECTRIC_RANGE2_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
134 TELEVISION2_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
135 ELECTRIC_MELS2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
136 IECC_ADJ2_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736
137 DISHWASHER3_BACKROW_TOPFLOOR DISHWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 186.821 0.156 27.377 0.150 0.600 0.250 0.000 dishwasher 0.000 186.821
138 REFRIGERATOR3_BACKROW_TOPFLOOR REFRIGERATOR LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 310.690 0.259 45.529 0.000 1.000 0.000 0.000 refrigerator 227.232 310.690
139 CLOTHESWASHER3_BACKROW_TOPFLOOR CLOTHESWASHER_EQUIP_SCH LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 80.974 0.068 11.866 0.000 0.800 0.200 0.000 clotheswasher 0.000 80.974
140 ELECTRIC_DRYER3_BACKROW_TOPFLOOR CLOTHESDRYER LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 605.958 0.505 88.798 5.000E-002 0.150 0.800 0.000 electric_dryer 0.000 605.958
141 ELECTRIC_RANGE3_BACKROW_TOPFLOOR COOKINGRANGE LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 705.353 0.588 103.363 0.300 0.400 0.300 0.000 electric_range 16.610 705.353
142 TELEVISION3_BACKROW_TOPFLOOR INTERIORLIGHTING LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 1.000 0.000 0.000 television 0.000 0.000
143 ELECTRIC_MELS3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 1503.167 1.252 220.277 6.000E-002 0.690 0.250 0.000 electric_mels 777.172 1503.167
144 IECC_ADJ3_BACKROW_TOPFLOOR MISCPLUGLOAD LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 99.736 0.083 14.616 6.244E-002 0.412 0.251 0.275 IECC_adj 51.566 99.736


Construction CTF

Construction Name Index #Layers #CTFs Time Step {Hours} ThermalConductance {Btu/h-ft2-F} OuterThermalAbsorptance InnerThermalAbsorptance OuterSolarAbsorptance InnerSolarAbsorptance Roughness
1 EXTERIOR WALL 1 5 10 0.167 0.0498 0.700 0.900 0.700 0.700 MediumSmooth
2 CEILING-FLOOR-LAYER 3 1 5 0.167 0.228 0.900 0.900 0.700 0.700 Rough
3 EXTERIOR FLOOR 4 3 11 0.167 0.0279 0.900 0.900 0.700 0.700 Rough
4 INTERIOR FLOOR 5 2 4 0.167 0.300 0.900 0.900 0.700 0.700 Rough
5 INTERIOR CEILING 6 2 13 0.167 0.0190 0.900 0.900 0.700 0.700 Rough
6 ATTIC FLOOR 7 2 13 0.167 0.0190 0.900 0.900 0.700 0.700 MediumSmooth
7 INTERIORWALL 9 3 5 0.167 0.597 0.900 0.900 0.700 0.700 MediumSmooth
8 EXTERIOR ROOF 11 2 4 0.167 0.943 0.900 0.900 0.750 0.700 MediumRough
9 EXTERIOR DOOR 14 1 5 0.167 0.300 0.900 0.900 0.700 0.700 Smooth
10 GABLE_END 16 5 6 0.167 0.428 0.900 0.900 0.700 0.700 MediumSmooth
11 CRAWL WALL 24 1 5 0.167 2.28 0.900 0.900 0.700 0.700 Rough
12 iz-EXTERIOR FLOOR 25 3 11 0.167 0.0279 0.900 0.900 0.700 0.700 MediumSmooth


Material CTF Summary

Material Name Thickness {ft} Conductivity {w/m-K} Density {lb/ft3} Specific Heat {Btu/lbm-R} ThermalResistance {m2-K/w}
1 SYN_STUCCO 0.0098 0.086 24.971 0.210 0.3524E-01
2 SHEATHING_CONSOL_LAYER 0.1020 0.035 1.255 0.350 0.8807
3 OSB_7/16IN 0.0364 0.116 34.000 0.290 0.9555E-01
4 WALL_CONSOL_LAYER 0.4584 0.057 7.541 0.248 2.444
5 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
6 LUMBER_2X4 0.2920 0.115 32.003 0.183 0.7709
7 FLOOR_CONSOL_LAYER 0.9377 0.050 3.438 0.219 5.720
8 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
9 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
10 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
11 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
12 CEIL_CONSOL_LAYER 1.8587 0.062 2.618 0.185 9.179
13 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
14 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
15 CEIL_CONSOL_LAYER 1.8587 0.062 2.618 0.185 9.179
16 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
17 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
18 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
19 ASPHALT_SHINGLE 0.0207 0.082 70.000 0.300 0.7745E-01
20 OSB_1/2IN 0.0417 0.116 34.000 0.290 0.1092
21 DOOR_CONST 0.1388 0.072 32.003 0.183 0.5870
22 CEMENT_STUCCO 0.0627 0.721 116.464 0.210 0.2642E-01
23 BLDG_PAPER_FELT 0.0000 0.000 0.000 0.000 0.1057E-01
24 OSB_5/8IN 0.0522 0.116 34.000 0.290 0.1365
25 DRYWALL_1/2IN 0.0417 0.160 50.000 0.260 0.7933E-01
26 CONCRETE_4IN 0.3330 1.312 140.014 0.111 0.7736E-01
27 CARPET_N_PAD 0.0833 0.060 2.000 0.200 0.4224
28 PLYWOOD_3/4IN 0.0627 0.115 34.003 0.161 0.1650
29 FLOOR_CONSOL_LAYER 0.9377 0.050 3.438 0.219 5.720


Material:Air

Material Name ThermalResistance {m2-K/w}
1 AIR_4_IN_VERT 0.1585
2 3/4IN_AIR_SPACE 8.5130E-002
3 3/4IN_REFLECTIVE_AIR_SPACE 0.2466
4 AIR_4_IN_VERT 0.1585


CTF

Time Outside Cross Inside Flux (except final one)
1 10 0.51360630E-08 -0.22035233E-13 0.91774209E-08 -0.50676220E-13
2 9 -0.14060012E-04 0.39159197E-12 -0.22958088E-04 0.29728831E-08
3 8 0.28980689E-02 0.65531654E-09 0.46215968E-02 -0.71708779E-05
4 7 -0.65978682E-01 0.13350779E-06 -0.16306378 0.13238707E-02
5 6 0.64596177 0.50193482E-05 2.1320981 -0.28125917E-01
6 5 -3.4215999 0.48298777E-04 -13.652056 0.25148823
7 4 10.645660 0.13839053E-03 47.881148 -1.1749737
8 3 -19.924231 0.11919231E-03 -96.040791 3.0621859
9 2 21.976583 0.26462555E-04 109.48934 -4.4404618
10 1 -13.118296 0.91387708E-06 -65.855375 3.3273744
11 0 3.2593552 0.33613880E-09 16.204438  
12 5 -0.10726087E-01 0.44268190E-05 -0.10726087E-01 0.97389233E-03
13 4 0.31857203 0.80150166E-03 0.31857203 -0.30727185E-01
14 3 -2.8372473 0.12516450E-01 -2.8372473 0.30041224
15 2 9.6667056 0.33176537E-01 9.6667056 -1.1584571
16 1 -13.322214 0.15207483E-01 -13.322214 1.8397512
17 0 6.2472388 0.62260140E-03 6.2472388  
18 11 0.76541396E-16 -0.66093266E-16 -0.60929972E-11 -0.23847962E-16
19 10 0.39406090E-10 -0.28120572E-15 0.79946244E-05 -0.23561984E-10
20 9 -0.38001770E-04 0.83058929E-12 -0.94209313E-03 0.22722403E-04
21 8 0.34824356E-02 0.73535950E-09 0.22619169E-01 -0.20949597E-02
22 7 -0.63320596E-01 0.66026276E-07 -0.25112985 0.39001137E-01
23 6 0.51991450 0.13029552E-05 1.5768494 -0.32985332
24 5 -2.3541315 0.76249747E-05 -6.0660500 1.5461930
25 4 6.3451018 0.14779851E-04 14.743171 -4.3333891
26 3 -10.407307 0.93590033E-05 -22.616366 7.4172847
27 2 10.167838 0.16508793E-05 21.148526 -7.5827206
28 1 -5.4301916 0.50559118E-07 -10.971024 4.2453367
29 0 1.2186872 0.30513734E-10 2.4143736  
30 4 0.50405178E-13 0.16668152E-13 0.29402090E-13 -0.58636069E-16
31 3 -0.78967347E-05 0.18486376E-05 -0.51544008E-05 0.20741056E-12
32 2 0.37655193 0.34407043E-01 0.80677627E-01 -0.16328896E-04
33 1 -8.0349315 0.81344511 -1.1624309 0.21506451
34 0 8.9946927 0.48845120 2.4180636  
35 13 -0.95016766E-17 -0.11776553E-17 -0.33255767E-09 0.99855310E-17
36 12 0.61338794E-09 -0.58488406E-15 0.16056222E-03 -0.43490528E-09
37 11 -0.75116140E-04 -0.12733754E-14 -0.83172474E-02 0.53259175E-04
38 10 0.23489104E-02 0.19285539E-11 0.16199673 -0.16913697E-02
39 9 -0.32325933E-01 0.31831827E-09 -1.7014869 0.23684835E-01
40 8 0.25799047 0.11552332E-07 11.081256 -0.19274894
41 7 -1.3247958 0.13607244E-06 -47.903612 1.0115855
42 6 4.5908388 0.61202310E-06 142.28685 -3.5913725
43 5 -10.947340 0.11168173E-05 -294.46769 8.7955522
44 4 17.960252 0.81578039E-06 423.45640 -14.856181
45 3 -19.872933 0.21758675E-06 -414.30161 16.962607
46 2 14.135270 0.16726228E-07 262.68178 -12.475847
47 1 -5.8235685 0.25078833E-09 -97.209670 5.3243306
48 0 1.0543411 -0.72051379E-11 15.923944  
49 13 -0.33255767E-09 -0.11776553E-17 -0.95016766E-17 0.99855310E-17
50 12 0.16056222E-03 -0.58488406E-15 0.61338794E-09 -0.43490528E-09
51 11 -0.83172474E-02 -0.12733754E-14 -0.75116140E-04 0.53259175E-04
52 10 0.16199673 0.19285539E-11 0.23489104E-02 -0.16913697E-02
53 9 -1.7014869 0.31831827E-09 -0.32325933E-01 0.23684835E-01
54 8 11.081256 0.11552332E-07 0.25799047 -0.19274894
55 7 -47.903612 0.13607244E-06 -1.3247958 1.0115855
56 6 142.28685 0.61202310E-06 4.5908388 -3.5913725
57 5 -294.46769 0.11168173E-05 -10.947340 8.7955522
58 4 423.45640 0.81578039E-06 17.960252 -14.856181
59 3 -414.30161 0.21758675E-06 -19.872933 16.962607
60 2 262.68178 0.16726228E-07 14.135270 -12.475847
61 1 -97.209670 0.25078833E-09 -5.8235685 5.3243306
62 0 15.923944 -0.72051379E-11 1.0543411  
63 5 -0.27590492E-07 0.65241430E-08 -0.27590492E-07 0.17331255E-13
64 4 0.68608714E-03 0.11323974E-03 0.68608714E-03 -0.15705033E-07
65 3 -0.21538511 0.37821720E-01 -0.21538511 0.25667047E-03
66 2 5.0173519 0.62258424 5.0173519 -0.50236511E-01
67 1 -19.904252 0.86481321 -19.904252 0.58144210
68 0 16.688993 0.62060609E-01 16.688993  
69 4 0.75441920E-10 0.23883683E-10 0.47514224E-10 -0.69373194E-20
70 3 -0.33730907E-03 0.89366797E-04 -0.22574866E-03 0.77828620E-10
71 2 0.58624422 0.18542418 0.49024360 -0.17301269E-03
72 1 -11.299243 2.8799011 -8.6239668 0.15905732
73 0 15.219762 1.4410112 12.640375  
74 5 -0.32935335E-06 0.42931990E-07 -0.32935335E-06 0.47097488E-08
75 4 0.68052310E-03 0.12823787E-03 0.68052310E-03 -0.14200104E-04
76 3 -0.11535993 0.17375615E-01 -0.11535993 0.40770076E-02
77 2 2.1922172 0.21284128 2.1922172 -0.13171357
78 1 -7.8704965 0.30308566 -7.8704965 0.79499401
79 0 6.3596665 0.33276539E-01 6.3596665  
80 6 0.97988530E-11 0.43917118E-12 0.24496810E-11 -0.34892153E-15
81 5 -0.75005310E-05 0.16499726E-06 -0.28271466E-05 0.19166609E-11
82 4 0.32354224E-01 0.66949565E-03 0.10283773E-01 -0.11111676E-05
83 3 -1.8201547 0.67148336E-01 -0.62076152 0.38788549E-02
84 2 21.173821 0.53241617 7.5279938 -0.97325542E-01
85 1 -64.420211 0.46601667 -21.697519 0.64629334
86 0 46.121323 0.20873329E-01 15.867130  
87 5 -0.15664505E-06 0.43005807E-07 -0.15664505E-06 0.11899247E-09
88 4 0.10791049E-02 0.34140917E-03 0.10791049E-02 -0.15677434E-05
89 3 -0.39592122 0.90314630E-01 -0.39592122 0.13116776E-02
90 2 11.651569 1.6702487 11.651569 -0.78737360E-01
91 1 -51.506798 3.1050242 -51.506798 0.66829999
92 0 45.538973 0.42297268 45.538973  
93 11 -0.60929972E-11 -0.66093266E-16 0.76541396E-16 -0.23847962E-16
94 10 0.79946244E-05 -0.28120572E-15 0.39406090E-10 -0.23561984E-10
95 9 -0.94209313E-03 0.83058929E-12 -0.38001770E-04 0.22722403E-04
96 8 0.22619169E-01 0.73535950E-09 0.34824356E-02 -0.20949597E-02
97 7 -0.25112985 0.66026276E-07 -0.63320596E-01 0.39001137E-01
98 6 1.5768494 0.13029552E-05 0.51991450 -0.32985332
99 5 -6.0660500 0.76249747E-05 -2.3541315 1.5461930
100 4 14.743171 0.14779851E-04 6.3451018 -4.3333891
101 3 -22.616366 0.93590033E-05 -10.407307 7.4172847
102 2 21.148526 0.16508793E-05 10.167838 -7.5827206
103 1 -10.971024 0.50559118E-07 -5.4301916 4.2453367
104 0 2.4143736 0.30513734E-10 1.2186872  


WindowConstruction

Construction Name Index #Layers Roughness Conductance {Btu/h-ft2-F} Conductance (Before Adjusted) {Btu/h-ft2-F} Convection Coefficient Adjustment Ratio SHGC Solar Transmittance at Normal Incidence Visible Transmittance at Normal Incidence
1 EXTERIOR WINDOW 12 1 VerySmooth 0.300 0.300 1.000 0.335    
2 INTERIOR WINDOW 13 1 VerySmooth 0.300 0.300 1.000 0.335    
3 WINDOW_W_BLINDS 18 2 VerySmooth 0.300 0.300 1.000 0.309    
4 TDD DOME 22 1 VerySmooth 1.071 1.071 1.000 0.929    
5 TDD DIFFUSER 23 1 VerySmooth 1.077 1.077 1.000 0.906    


WindowMaterial:Glazing

Material Name Optical Data Type Spectral Data Set Name Thickness {ft} Solar Transmittance Front Solar Reflectance Back Solar Reflectance Visible Transmittance Front Visible Reflectance Back Visible Reflectance Infrared Transmittance Front Thermal Emissivity Back Thermal Emissivity Conductivity {W/m-K} Dirt Factor Solar Diffusing
1 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
2 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
3 GLASS SpectralAverage   0.13728 0.24698 0.55113 0.55113 0.88000 0.11900 0.11900 0.00000 0.84000 0.84000 0.10138 1.00000 No
4 CLEAR ACRYLIC PLASTIC SpectralAverage   0.00984 0.92000 5.00000E-002 5.00000E-002 0.92000 5.00000E-002 5.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No
5 DIFFUSING ACRYLIC PLASTIC SpectralAverage   0.00722 0.90000 8.00000E-002 8.00000E-002 0.90000 8.00000E-002 8.00000E-002 0.00000 0.90000 0.90000 0.90000 1.00000 No


WindowMaterial:Blind

Material Name Slat Width {ft} Slat Separation {ft} Slat Thickness {ft} Slat Angle {deg} Slat Beam Solar Transmittance Slat Beam Solar Front Reflectance Blind To Glass Distance {ft}
1 INT_BLIND 0.0820 0.0615 0.0033 45.000 0.000 0.500 0.164


Shadowing/Sun Position Calculations Annual Simulations

Shading Calculation Method Shading Calculation Update Frequency Method Shading Calculation Update Frequency {days} Maximum Figures in Shadow Overlap Calculations {} Polygon Clipping Algorithm Pixel Counting Resolution Sky Diffuse Modeling Algorithm Output External Shading Calculation Results Disable Self-Shading Within Shading Zone Groups Disable Self-Shading From Shading Zone Groups to Other Zones
1 PolygonClipping Periodic 20 15000. SutherlandHodgman 512 SimpleSkyDiffuseModeling No No No


Heat Pump Water Heater Information

Type Name Volume {ft3} Maximum Capacity {Btu/h} Standard Rated Recovery Efficiency Standard Rated Energy Factor "DX Coil Total Cooling Rate {W HPWH Only}"
1 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
2 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
3 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
4 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
5 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
6 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR 6.6825 4435.6 0.000 0.0000 736  
7 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
8 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
9 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
10 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
11 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
12 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR 6.6825 4435.6 0.000 0.0000 736  
13 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  
14 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  
15 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  
16 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  
17 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  
18 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR 6.6825 4435.6 0.000 0.0000 736  


Water Heater Stratified Node Information

Node Number Height {ft} Volume {ft3} Maximum Capacity {Btu/h} Off-Cycle UA {Btu/h-F} On-Cycle UA {Btu/h-F} Number Of Inlets Number Of Outlets
1 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
2 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
3 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
4 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
5 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
6 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
7 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
8 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
9 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
10 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
11 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
12 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
13 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
14 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
15 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
16 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
17 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1
18 1 5.2299 6.6825 0.000 2.8646 2.8646 1 1


ZoneInfiltration Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/Exterior Surface Area {ft3/min-ft2} ACH - Air Changes per Hour Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2}
1 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
2 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
3 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
4 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
5 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
6 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
7 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
8 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
9 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
10 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
11 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
12 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
13 LIVING_SHERMANGRIMSRUD_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
14 LIVING_SHERMANGRIMSRUD_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
15 LIVING_SHERMANGRIMSRUD_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
16 LIVING_SHERMANGRIMSRUD_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
17 LIVING_SHERMANGRIMSRUD_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
18 LIVING_SHERMANGRIMSRUD_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
19 ATTICVENT ALWAYS_AVAIL ATTIC 7802.66 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
20 CRAWLVENT ALWAYS_AVAIL CRAWLSPACE 7794.37 0.0 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000


ZoneVentilation Airflow Stats Nominal

Name Schedule Name Zone Name Zone Floor Area {ft2} # Zone Occupants Design Volume Flow Rate {ft3/min} Volume Flow Rate/Floor Area {ft3/min-ft2} Volume Flow Rate/person Area {ft3/min-person} ACH - Air Changes per Hour Fan Type {Exhaust;Intake;Natural} Fan Pressure Rise {psi} Fan Efficiency {} Equation A - Constant Term Coefficient {} Equation B - Temperature Term Coefficient {1/C} Equation C - Velocity Term Coefficient {s/m} Equation D - Velocity Squared Term Coefficient {s2/m2} Minimum Indoor Temperature{F}/Schedule Maximum Indoor Temperature{F}/Schedule Delta Temperature{F}/Schedule Minimum Outdoor Temperature{F}/Schedule Maximum Outdoor Temperature{F}/Schedule Maximum WindSpeed{ft/min}
1 VENTILATION_UNIT1_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
2 VENTILATION_UNIT2_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
3 VENTILATION_UNIT3_FRONTROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
4 VENTILATION_UNIT1_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
5 VENTILATION_UNIT2_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
6 VENTILATION_UNIT3_BACKROW_BOTTOMFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
7 VENTILATION_UNIT1_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
8 VENTILATION_UNIT2_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
9 VENTILATION_UNIT3_FRONTROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
10 VENTILATION_UNIT1_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
11 VENTILATION_UNIT2_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
12 VENTILATION_UNIT3_BACKROW_MIDDLEFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
13 VENTILATION_UNIT1_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
14 VENTILATION_UNIT2_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
15 VENTILATION_UNIT3_FRONTROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
16 VENTILATION_UNIT1_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT1_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
17 VENTILATION_UNIT2_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT2_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40
18 VENTILATION_UNIT3_BACKROW_TOPFLOOR ALWAYS_AVAIL LIVING_UNIT3_BACKROW_TOPFLOOR 1200.51 2.0 0.000 0.000 0.000 0.000 Exhaust 0.000 0.6 1.000 0.000 0.000 0.000 -148.0 212.00 -148.0 -148.0 212.00 7874.40


AirFlow Model

Simple
1 Simple


RoomAir Model

Zone Name Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined
1 CRAWLSPACE Mixing/Well-Stirred
2 BREEZEWAY Mixing/Well-Stirred
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Mixing/Well-Stirred
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Mixing/Well-Stirred
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Mixing/Well-Stirred
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Mixing/Well-Stirred
15 ATTIC Mixing/Well-Stirred
16 LIVING_UNIT3_BACKROW_TOPFLOOR Mixing/Well-Stirred
17 LIVING_UNIT3_FRONTROW_TOPFLOOR Mixing/Well-Stirred
18 LIVING_UNIT1_FRONTROW_TOPFLOOR Mixing/Well-Stirred
19 LIVING_UNIT2_BACKROW_TOPFLOOR Mixing/Well-Stirred
20 LIVING_UNIT2_FRONTROW_TOPFLOOR Mixing/Well-Stirred
21 LIVING_UNIT1_BACKROW_TOPFLOOR Mixing/Well-Stirred


AirflowNetwork Model:Control

No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation
1 NoMultizoneOrDistribution


Zone Volume Capacitance Multiplier

Sensible Heat Capacity Multiplier Moisture Capacity Multiplier Carbon Dioxide Capacity Multiplier Generic Contaminant Capacity Multiplier
1 1.000 1.000 1.000 1.000


Load Timesteps in Zone Design Calculation Averaging Window

Value
1 6


Heating Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Cooling Sizing Factor Information

Sizing Factor ID Value
1 Global 1.0000


Zone Sizing Information

Zone Name Load Type Calc Des Load {Btu/h} User Des Load {Btu/h} Calc Des Air Flow Rate {ft3/min} User Des Air Flow Rate {ft3/min} Design Day Name Date/Time of Peak Temperature at Peak {F} Humidity Ratio at Peak {lbWater/lbDryAir} Floor Area {ft2} # Occupants Calc Outdoor Air Flow Rate {ft3/min} Calc DOAS Heat Addition Rate {Btu/h}
1 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Cooling 9342.35697 9342.35697 415.08469 415.08469 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 80.82320 0.01272 1200.55323 2.00000 44.99491 0.00000
2 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Heating 11515.03491 11515.03491 218.72879 218.72879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
3 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Cooling 4218.31780 4218.31780 187.42455 187.42455 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Heating 8368.31535 8368.31535 158.95994 158.95994 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Cooling 7057.33457 7057.33457 313.55928 313.55928 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 79.93040 0.01272 1200.55323 2.00000 44.99491 0.00000
6 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Heating 11522.89510 11522.89510 218.87709 218.87709 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
7 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Cooling 8795.66248 8795.66248 390.78385 390.78385 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 79.70720 0.01272 1200.55323 2.00000 44.99491 0.00000
8 LIVING_UNIT1_BACKROW_BOTTOMFLOOR Heating 11518.44060 11518.44060 218.79235 218.79235 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
9 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Cooling 3782.30692 3782.30692 168.04977 168.04977 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 76.24760 0.01272 1200.55323 2.00000 44.99491 0.00000
10 LIVING_UNIT2_BACKROW_BOTTOMFLOOR Heating 8368.95643 8368.95643 158.97201 158.97201 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
11 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Cooling 6441.73163 6441.73163 286.20759 286.20759 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 76.43359 0.01272 1200.55323 2.00000 44.99491 0.00000
12 LIVING_UNIT3_BACKROW_BOTTOMFLOOR Heating 11520.85421 11520.85421 218.83472 218.83472 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
13 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Cooling 9303.19649 9303.19649 413.32622 413.32622 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 80.26520 0.01272 1200.55323 2.00000 44.99491 0.00000
14 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Heating 8114.64571 8114.64571 154.15104 154.15104 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
15 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Cooling 4258.80715 4258.80715 189.21735 189.21735 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 86.18000 0.01273 1200.55323 2.00000 44.99491 0.00000
16 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Heating 4988.47502 4988.47502 94.76609 94.76609 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
17 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Cooling 7191.63311 7191.63311 319.51267 319.51267 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 80.48840 0.01272 1200.55323 2.00000 44.99491 0.00000
18 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Heating 8115.61789 8115.61789 154.16968 154.16968 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
19 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Cooling 8762.81666 8762.81666 389.32198 389.32198 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 79.14920 0.01272 1200.55323 2.00000 44.99491 0.00000
20 LIVING_UNIT1_BACKROW_MIDDLEFLOOR Heating 8116.37658 8116.37658 154.18409 154.18409 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
21 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Cooling 3862.53809 3862.53809 171.61163 171.61163 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 76.24760 0.01272 1200.55323 2.00000 44.99491 0.00000
22 LIVING_UNIT2_BACKROW_MIDDLEFLOOR Heating 4987.67218 4987.67218 94.75084 94.75084 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
23 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Cooling 6535.83319 6535.83319 290.38132 290.38132 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 77.06601 0.01272 1200.55323 2.00000 44.99491 0.00000
24 LIVING_UNIT3_BACKROW_MIDDLEFLOOR Heating 8112.28600 8112.28600 154.10634 154.10634 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
25 LIVING_UNIT3_BACKROW_TOPFLOOR Cooling 6455.00902 6455.00902 286.80081 286.80081 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 77.06601 0.01272 1200.55323 2.00000 44.99491 0.00000
26 LIVING_UNIT3_BACKROW_TOPFLOOR Heating 11753.90050 11753.90050 223.26268 223.26268 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
27 LIVING_UNIT3_FRONTROW_TOPFLOOR Cooling 7083.06791 7083.06791 314.70335 314.70335 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 80.48840 0.01272 1200.55323 2.00000 44.99491 0.00000
28 LIVING_UNIT3_FRONTROW_TOPFLOOR Heating 11758.09593 11758.09593 223.34743 223.34743 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
29 LIVING_UNIT1_FRONTROW_TOPFLOOR Cooling 9485.05753 9485.05753 421.41944 421.41944 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 80.26520 0.01272 1200.55323 2.00000 44.99491 0.00000
30 LIVING_UNIT1_FRONTROW_TOPFLOOR Heating 11761.94825 11761.94825 223.41099 223.41099 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
31 LIVING_UNIT2_BACKROW_TOPFLOOR Cooling 4436.40963 4436.40963 197.11184 197.11184 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 76.24760 0.01272 1200.55323 2.00000 44.99491 0.00000
32 LIVING_UNIT2_BACKROW_TOPFLOOR Heating 8620.39579 8620.39579 163.74828 163.74828 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
33 LIVING_UNIT2_FRONTROW_TOPFLOOR Cooling 4424.06376 4424.06376 196.56226 196.56226 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 77.47520 0.01272 1200.55323 2.00000 44.99491 0.00000
34 LIVING_UNIT2_FRONTROW_TOPFLOOR Heating 8622.76150 8622.76150 163.79320 163.79320 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000
35 LIVING_UNIT1_BACKROW_TOPFLOOR Cooling 9271.65197 9271.65197 411.94910 411.94910 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 79.14920 0.01272 1200.55323 2.00000 44.99491 0.00000
36 LIVING_UNIT1_BACKROW_TOPFLOOR Heating 11761.39851 11761.39851 223.41099 223.41099 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 -26.8600 0.00018 1200.55323 2.00000 44.99491 0.00000


System Sizing Information

System Name Load Type Peak Load Kind User Design Capacity Calc Des Air Flow Rate [ft3/min] User Des Air Flow Rate [ft3/min] Design Day Name Date/Time of Peak
1 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Cooling Sensible 2780.35 415.08469 415.08469 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
2 CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Heating Sensible 4678.12 218.72879 218.72879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
3 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Cooling Sensible 1372.40 187.42455 187.42455 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
4 CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Heating Sensible 3769.31 158.95994 158.95994 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
5 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Cooling Sensible 2107.58 313.55928 313.55928 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
6 CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Heating Sensible 4680.39 218.87709 218.87709 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
7 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Cooling Sensible 2607.05 390.78385 390.78385 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
8 CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Heating Sensible 4679.10 218.79235 218.79235 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
9 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Cooling Sensible 1110.47 168.04977 168.04977 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
10 CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Heating Sensible 3769.50 158.97201 158.97201 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
11 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Cooling Sensible 1881.79 286.20759 286.20759 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
12 CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Heating Sensible 4679.80 218.83472 218.83472 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
13 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Cooling Sensible 2761.39 413.32622 413.32622 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
14 CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Heating Sensible 3696.09 154.15104 154.15104 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
15 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Cooling Sensible 1384.10 189.21735 189.21735 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
16 CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Heating Sensible 2793.22 94.76609 94.76609 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
17 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Cooling Sensible 2154.04 319.51267 319.51267 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
18 CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Heating Sensible 3696.37 154.16968 154.16968 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
19 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Cooling Sensible 2589.92 389.32198 389.32198 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
20 CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Heating Sensible 3696.59 154.18409 154.18409 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
21 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Cooling Sensible 1133.66 171.61163 171.61163 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
22 CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Heating Sensible 2792.99 94.75084 94.75084 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
23 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Cooling Sensible 1917.64 290.38132 290.38132 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
24 CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Heating Sensible 3695.41 154.10634 154.10634 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
25 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Cooling Sensible 2813.97 421.41944 421.41944 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
26 CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Heating Sensible 4749.43 223.41099 223.41099 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
27 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Cooling Sensible 1312.78 196.56226 196.56226 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
28 CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Heating Sensible 3842.80 163.79320 163.79320 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
29 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Cooling Sensible 2122.66 314.70335 314.70335 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
30 CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Heating Sensible 4748.32 223.34743 223.34743 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
31 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Cooling Sensible 2737.01 411.94910 411.94910 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
32 CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Heating Sensible 4749.27 223.41099 223.41099 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
33 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Cooling Sensible 1299.56 197.11184 197.11184 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
34 CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Heating Sensible 3842.12 163.74828 163.74828 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
35 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Cooling Sensible 1894.28 286.80081 286.80081 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 05:00:00
36 CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Heating Sensible 4747.11 223.26268 223.26268 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00


Component Sizing Information

Component Type Component Name Input Field Description Value
1 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
2 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
3 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
4 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
5 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
6 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 415.08469
7 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
8 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
9 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
10 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
11 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
12 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 187.42455
13 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
14 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
15 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
16 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
17 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
18 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 313.55928
19 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
20 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
21 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
22 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
23 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
24 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 390.78385
25 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
26 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
27 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
28 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
29 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
30 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 168.04977
31 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
32 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
33 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
34 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
35 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_BOTTOMFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
36 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Air Flow Rate [ft3/min] 286.20759
37 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
38 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
39 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
40 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
41 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
42 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 413.32622
43 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
44 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
45 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
46 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
47 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
48 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 189.21735
49 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
50 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
51 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
52 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
53 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
54 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 319.51267
55 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
56 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
57 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
58 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
59 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
60 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 389.32198
61 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
62 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
63 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
64 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
65 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
66 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 171.61163
67 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
68 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
69 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
70 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
71 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_MIDDLEFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
72 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Air Flow Rate [ft3/min] 290.38132
73 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
74 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
75 Fan:OnOff OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
76 Fan:OnOff OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
77 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
78 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 286.80081
79 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
80 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT3_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
81 Fan:OnOff OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
82 Fan:OnOff OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
83 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT3_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
84 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 314.70335
85 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
86 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
87 Fan:OnOff OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
88 Fan:OnOff OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
89 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
90 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 421.41944
91 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
92 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
93 Fan:OnOff OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
94 Fan:OnOff OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
95 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
96 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 197.11184
97 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
98 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT2_FRONTROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
99 Fan:OnOff OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
100 Fan:OnOff OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
101 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT2_FRONTROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
102 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 196.56226
103 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Supply Air Flow Rate [ft3/min] 44.99491
104 ZoneHVAC:EnergyRecoveryVentilator ERV_UNIT1_BACKROW_TOPFLOOR User-Specified Exhaust Air Flow Rate [ft3/min] 44.99491
105 Fan:OnOff OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
106 Fan:OnOff OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR User-Specified Maximum Flow Rate [ft3/min] 44.99491
107 HeatExchanger:AirToAir:SensibleAndLatent OA_HEAT_RECOVERY_UNIT1_BACKROW_TOPFLOOR User-Specified Nominal Supply Air Flow Rate [ft3/min] 44.99491
108 AirTerminal:SingleDuct:ConstantVolume:NoReheat ZONEDIRECTAIR_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Air Flow Rate [ft3/min] 411.94910
109 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 415.08469
110 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 415.08469
111 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 415.08469
112 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 415.08469
113 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 415.08469
114 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 415.08469
115 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
116 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
117 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 187.42455
118 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 187.42455
119 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 187.42455
120 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 187.42455
121 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 187.42455
122 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 187.42455
123 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
124 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
125 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 313.55928
126 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 313.55928
127 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 313.55928
128 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 313.55928
129 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 313.55928
130 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 313.55928
131 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
132 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
133 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 390.78385
134 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 390.78385
135 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 390.78385
136 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 390.78385
137 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 390.78385
138 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 390.78385
139 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
140 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
141 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 168.04977
142 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 168.04977
143 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 168.04977
144 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 168.04977
145 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 168.04977
146 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 168.04977
147 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
148 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
149 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 286.20759
150 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 286.20759
151 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 286.20759
152 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 286.20759
153 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 286.20759
154 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 286.20759
155 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR User Heating Air Flow Ratio [] 1.00000
156 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Calculated Heating Air Flow Ratio [] 1.00000
157 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 413.32622
158 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 413.32622
159 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 413.32622
160 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 413.32622
161 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 413.32622
162 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 413.32622
163 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
164 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
165 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 189.21735
166 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 189.21735
167 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 189.21735
168 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 189.21735
169 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 189.21735
170 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 189.21735
171 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
172 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
173 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 319.51267
174 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 319.51267
175 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 319.51267
176 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 319.51267
177 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 319.51267
178 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 319.51267
179 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
180 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
181 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 389.32198
182 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 389.32198
183 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 389.32198
184 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 389.32198
185 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 389.32198
186 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 389.32198
187 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
188 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
189 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 171.61163
190 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 171.61163
191 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 171.61163
192 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 171.61163
193 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 171.61163
194 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 171.61163
195 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
196 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
197 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 290.38132
198 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 290.38132
199 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 290.38132
200 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 290.38132
201 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 290.38132
202 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 290.38132
203 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR User Heating Air Flow Ratio [] 1.00000
204 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Calculated Heating Air Flow Ratio [] 1.00000
205 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 421.41944
206 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 421.41944
207 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 421.41944
208 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 421.41944
209 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 421.41944
210 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 421.41944
211 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
212 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
213 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 196.56226
214 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 196.56226
215 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 196.56226
216 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 196.56226
217 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 196.56226
218 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 196.56226
219 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
220 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
221 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 314.70335
222 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 314.70335
223 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 314.70335
224 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 314.70335
225 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 314.70335
226 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 314.70335
227 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
228 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
229 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 411.94910
230 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 411.94910
231 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 411.94910
232 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 411.94910
233 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 411.94910
234 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 411.94910
235 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
236 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
237 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 197.11184
238 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 197.11184
239 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 197.11184
240 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 197.11184
241 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 197.11184
242 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 197.11184
243 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
244 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
245 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Heating Flow Rates [ft3/min] 286.80081
246 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Minimum Heating Flow Rates [ft3/min] 286.80081
247 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Sum of Air Terminal Maximum Flow Rates [ft3/min] 286.80081
248 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Heating Design Air Flow Rate [ft3/min] 286.80081
249 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Cooling Design Air Flow Rate [ft3/min] 286.80081
250 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Adjusted Main Design Air Flow Rate [ft3/min] 286.80081
251 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR User Heating Air Flow Ratio [] 1.00000
252 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Calculated Heating Air Flow Ratio [] 1.00000
253 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 415.08469
254 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 187.42455
255 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 313.55928
256 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 390.78385
257 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 168.04977
258 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR Design Supply Air Flow Rate [ft3/min] 286.20759
259 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 413.32622
260 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 189.21735
261 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 319.51267
262 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 389.32198
263 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 171.61163
264 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR Design Supply Air Flow Rate [ft3/min] 290.38132
265 AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 421.41944
266 AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 196.56226
267 AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 314.70335
268 AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 411.94910
269 AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 197.11184
270 AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR Design Supply Air Flow Rate [ft3/min] 286.80081
271 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 415.08469
272 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.25557
273 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73202
274 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 415.08469
275 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 415.08469
276 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 415.08469
277 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.25557
278 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 30070.42068
279 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.08662
280 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 439.64926
281 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
282 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 415.08469
283 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 187.42455
284 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.62462
285 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
286 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 187.42455
287 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 187.42455
288 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 187.42455
289 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.62462
290 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 16488.20233
291 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.69245
292 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 228.25264
293 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
294 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 187.42455
295 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 313.55928
296 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.96673
297 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72591
298 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 313.55928
299 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 313.55928
300 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 313.55928
301 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.96673
302 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 24013.15921
303 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.46488
304 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 345.68311
305 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
306 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 313.55928
307 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 390.78385
308 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.18380
309 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73163
310 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 390.78385
311 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 390.78385
312 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 390.78385
313 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 1.18380
314 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 28621.39628
315 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.93790
316 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 417.20686
317 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
318 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 390.78385
319 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 168.04977
320 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.56005
321 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
322 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 168.04977
323 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 168.04977
324 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 168.04977
325 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.56005
326 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 15332.32783
327 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.57381
328 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 210.02555
329 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
330 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 168.04977
331 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Air Flow Rate [ft3/min] 286.20759
332 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.86777
333 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73138
334 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate [ft3/min] 286.20759
335 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 286.20759
336 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 286.20759
337 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Nominal Cooling Capacity [ton] 0.86777
338 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Rated Capacity [Btu/h] 22381.33353
339 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.29737
340 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 320.31473
341 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_BOTTOMFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
342 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 286.20759
343 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 413.32622
344 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.22816
345 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73888
346 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 413.32622
347 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 413.32622
348 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 413.32622
349 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.22816
350 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 29964.44195
351 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.07575
352 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 437.80031
353 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
354 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 413.32622
355 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 189.21735
356 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.63059
357 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
358 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 189.21735
359 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 189.21735
360 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 189.21735
361 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.63059
362 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 16594.44884
363 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.70336
364 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 229.75888
365 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
366 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 189.21735
367 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 319.51267
368 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.97070
369 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73085
370 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 319.51267
371 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 319.51267
372 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 319.51267
373 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.97070
374 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 24367.52646
375 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.50124
376 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 351.01778
377 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
378 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 319.51267
379 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 389.32198
380 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.15857
381 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73747
382 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 389.32198
383 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 389.32198
384 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 389.32198
385 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 1.15857
386 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 28532.28593
387 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.92875
388 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 415.62790
389 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
390 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 389.32198
391 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 171.61163
392 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.57192
393 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
394 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 171.61163
395 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 171.61163
396 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 171.61163
397 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.57192
398 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 15544.19338
399 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.59557
400 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 213.21547
401 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
402 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 171.61163
403 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Air Flow Rate [ft3/min] 290.38132
404 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.86833
405 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73614
406 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate [ft3/min] 290.38132
407 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 290.38132
408 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 290.38132
409 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Nominal Cooling Capacity [ton] 0.86833
410 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Rated Capacity [Btu/h] 22629.34567
411 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.32283
412 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 324.01460
413 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_MIDDLEFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
414 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 290.38132
415 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 421.41944
416 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.26664
417 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73475
418 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 421.41944
419 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 421.41944
420 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 421.41944
421 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.26664
422 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 30448.72959
423 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.12546
424 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 445.49882
425 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
426 Fan:OnOff SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 421.41944
427 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 196.56226
428 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.65507
429 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70108
430 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 196.56226
431 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 196.56226
432 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 196.56226
433 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.65507
434 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 17033.35695
435 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.74841
436 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 236.80774
437 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
438 Fan:OnOff SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 196.56226
439 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 314.70335
440 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.97486
441 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72466
442 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 314.70335
443 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 314.70335
444 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 314.70335
445 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.97486
446 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 24081.39621
447 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.47188
448 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 346.73742
449 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_FRONTROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
450 Fan:OnOff SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 314.70335
451 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 411.94910
452 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 1.23340
453 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.73579
454 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 411.94910
455 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 411.94910
456 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 411.94910
457 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 1.23340
458 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 29883.14388
459 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 3.06741
460 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 436.74197
461 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT1_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
462 Fan:OnOff SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 411.94910
463 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 197.11184
464 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.65346
465 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.70337
466 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 197.11184
467 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 197.11184
468 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 197.11184
469 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.65346
470 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 17066.14078
471 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 1.75179
472 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 237.32231
473 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT2_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
474 Fan:OnOff SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 197.11184
475 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Air Flow Rate [ft3/min] 286.80081
476 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Total Cooling Capacity [ton] 0.87478
477 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Gross Rated Sensible Heat Ratio 0.72977
478 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate [ft3/min] 286.80081
479 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Heating Operation [ft3/min] 286.80081
480 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Supply Air Flow Rate During Cooling Operation [ft3/min] 286.80081
481 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Nominal Cooling Capacity [ton] 0.87478
482 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Rated Capacity [Btu/h] 22416.52811
483 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Water Flow Rate [gal/min] 2.30098
484 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Design Size U-Factor Times Area Value [Btu/h-F] 320.85695
485 AirLoopHVAC:UnitaryHeatCool ACANDF_UNIT3_BACKROW_TOPFLOOR Fraction of Supply Air Flow That Goes Through the Controlling Zone 1.00000
486 Fan:OnOff SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 286.80081
487 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
488 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
489 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
490 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
491 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
492 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
493 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
494 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
495 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
496 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
497 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
498 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR Evaporator air flow rate [ft3/min] 160.01057
499 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
500 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
501 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
502 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
503 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
504 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
505 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
506 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
507 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
508 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
509 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
510 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR Evaporator air flow rate [ft3/min] 160.01057
511 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
512 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
513 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
514 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
515 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
516 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_FRONTROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
517 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
518 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT1_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
519 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
520 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT2_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
521 Fan:OnOff HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Design Size Maximum Flow Rate [ft3/min] 160.01057
522 WaterHeater:HeatPump:WrappedCondenser WATER HEATER_UNIT3_BACKROW_TOPFLOOR Evaporator air flow rate [ft3/min] 160.01057
523 PlantLoop BOILER LOOP Maximum Loop Flow Rate [ft3/min] 5.69977
524 PlantLoop BOILER LOOP Plant Loop Volume [ft3] 11.40230
525 Pump:VariableSpeed BOILER CIRC PUMP Design Flow Rate [ft3/min] 5.69977
526 Boiler:HotWater CENTRAL BOILER Design Size Nominal Capacity [Btu/h] 0.415468E+06
527 Boiler:HotWater CENTRAL BOILER Design Size Design Water Flow Rate [gal/min] 42.64648
528 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
529 PlantLoop DHW LOOP_UNIT1_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
530 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
531 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
532 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
533 PlantLoop DHW LOOP_UNIT2_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
534 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
535 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
536 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
537 PlantLoop DHW LOOP_UNIT3_FRONTROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
538 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
539 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
540 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
541 PlantLoop DHW LOOP_UNIT1_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
542 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
543 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
544 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
545 PlantLoop DHW LOOP_UNIT2_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
546 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
547 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
548 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
549 PlantLoop DHW LOOP_UNIT3_BACKROW_BOTTOMFLOOR Plant Loop Volume [ft3] 2.08975
550 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Design Flow Rate [ft3/min] 1.04461
551 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_BOTTOMFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
552 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
553 PlantLoop DHW LOOP_UNIT1_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
554 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
555 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
556 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
557 PlantLoop DHW LOOP_UNIT2_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
558 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
559 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
560 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
561 PlantLoop DHW LOOP_UNIT3_FRONTROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
562 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
563 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
564 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
565 PlantLoop DHW LOOP_UNIT1_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
566 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
567 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
568 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
569 PlantLoop DHW LOOP_UNIT2_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
570 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
571 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
572 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
573 PlantLoop DHW LOOP_UNIT3_BACKROW_MIDDLEFLOOR Plant Loop Volume [ft3] 2.08975
574 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Design Flow Rate [ft3/min] 1.04461
575 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_MIDDLEFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
576 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
577 PlantLoop DHW LOOP_UNIT1_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
578 Pump:VariableSpeed MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
579 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
580 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
581 PlantLoop DHW LOOP_UNIT2_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
582 Pump:VariableSpeed MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
583 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
584 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
585 PlantLoop DHW LOOP_UNIT3_FRONTROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
586 Pump:VariableSpeed MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
587 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_FRONTROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
588 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
589 PlantLoop DHW LOOP_UNIT1_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
590 Pump:VariableSpeed MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
591 WaterHeater:Stratified WATER HEATER_TANK_UNIT1_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
592 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
593 PlantLoop DHW LOOP_UNIT2_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
594 Pump:VariableSpeed MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
595 WaterHeater:Stratified WATER HEATER_TANK_UNIT2_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461
596 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Maximum Loop Flow Rate [ft3/min] 1.04461
597 PlantLoop DHW LOOP_UNIT3_BACKROW_TOPFLOOR Plant Loop Volume [ft3] 2.08975
598 Pump:VariableSpeed MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Design Flow Rate [ft3/min] 1.04461
599 WaterHeater:Stratified WATER HEATER_TANK_UNIT3_BACKROW_TOPFLOOR Use Side Design Flow Rate [ft3/min] 1.04461


DX Cooling Coil Standard Rating Information

Component Type Component Name Standard Rating (Net) Cooling Capacity {ton} Standard Rated Net COP {Btuh/Btuh} EER {Btu/W-h} SEER User {Btu/W-h} SEER Standard {Btu/W-h} IEER {Btu/W-h}
1 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.2 3.47 11.82 12.55 12.06 12.37
2 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 1.2 3.35 11.44 12.13 11.99 -99999.
3 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.52 12.00 12.74 12.25 12.67
4 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 0.6 3.41 11.65 12.35 12.21 -99999.
5 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.48 11.86 12.59 12.10 12.43
6 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 0.9 3.37 11.48 12.17 12.03 -99999.
7 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.47 11.83 12.55 12.06 12.38
8 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR 1.1 3.35 11.45 12.13 11.99 -99999.
9 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.52 12.00 12.74 12.25 12.67
10 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR 0.5 3.41 11.65 12.35 12.21 -99999.
11 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.47 11.83 12.55 12.06 12.38
12 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR 0.8 3.36 11.45 12.13 11.99 -99999.
13 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.2 3.46 11.79 12.51 12.02 12.32
14 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 1.2 3.34 11.40 12.08 11.95 -99999.
15 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.6 3.52 12.00 12.74 12.25 12.67
16 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 0.6 3.41 11.65 12.35 12.21 -99999.
17 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.9 3.47 11.83 12.55 12.07 12.39
18 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 0.9 3.36 11.45 12.14 12.00 -99999.
19 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.46 11.79 12.51 12.03 12.32
20 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR 1.1 3.34 11.41 12.09 11.95 -99999.
21 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.6 3.52 12.00 12.74 12.25 12.67
22 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR 0.6 3.41 11.65 12.35 12.21 -99999.
23 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.8 3.46 11.80 12.52 12.04 12.34
24 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR 0.8 3.35 11.42 12.10 11.96 -99999.
25 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.2 3.46 11.81 12.53 12.05 12.35
26 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR 1.2 3.35 11.43 12.11 11.97 -99999.
27 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.6 3.52 12.00 12.74 12.25 12.67
28 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR 0.6 3.41 11.65 12.35 12.21 -99999.
29 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.9 3.48 11.87 12.59 12.11 12.45
30 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR 0.9 3.37 11.49 12.18 12.04 -99999.
31 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.2 3.46 11.81 12.52 12.04 12.34
32 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR 1.2 3.35 11.42 12.10 11.96 -99999.
33 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.6 3.51 11.99 12.73 12.24 12.66
34 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR 0.6 3.41 11.63 12.34 12.20 -99999.
35 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.47 11.84 12.56 12.08 12.40
36 Coil:Cooling:DX:SingleSpeed DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR 0.8 3.36 11.46 12.15 12.01 -99999.


Water Heating Coil Capacity Information

Component Type Name Nominal Total Capacity {Btu/h}
1 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR 30050.27
2 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR 14852.20
3 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR 23315.01
4 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR 28442.81
5 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR 13530.35
6 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR 21492.56
7 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR 29925.59
8 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR 14968.07
9 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR 23704.53
10 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR 28337.10
11 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR 13768.51
12 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR 21764.67
13 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR 30469.36
14 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR 15472.09
15 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR 23390.93
16 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR 29842.31
17 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR 15509.35
18 Coil:Heating:Water MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR 21531.73


Environment

Environment Name Environment Type Start Date End Date Start DayOfWeek Duration {#days} Source:Start DayOfWeek Use Daylight Saving Use Holidays Apply Weekend Holiday Rule Use Rain Values Use Snow Values Sky Temperature Model
1 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB SizingPeriod:DesignDay 01/21 01/21 WinterDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
2 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB SizingPeriod:DesignDay 07/21 07/21 SummerDesignDay 1 N/A N/A N/A N/A N/A N/A Clark and Allen
3 ANNUAL WeatherFileRunPeriod 01/01/2017 12/31/2017 Sunday 365 Use RunPeriod Specified Day Yes Yes No Yes Yes Clark and Allen


Environment:Daylight Saving

Daylight Saving Indicator Source Start Date End Date
1 No SizingPeriod:DesignDay    
2 No SizingPeriod:DesignDay    
3 No      


Environment:WarmupDays

NumberofWarmupDays
1 9
2 25
3 25


Environment:Design Day Data

Max Dry-Bulb Temp {F} Temp Range {dC} Temp Range Ind Type Hum Ind Type Hum Ind Value at Max Temp Hum Ind Units Pressure {psi} Wind Direction {deg CW from N} Wind Speed {ft/min} Clearness Rain Snow
1 -26.9 0.00 DefaultMultipliers Wetbulb -32.70 {C} 14. 210 472.5 0.00 No No
2 86.18 12.40 DefaultMultipliers Wetbulb 21.10 {C} 14. 200 925.2 0.00 No No


Environment:Design Day Misc

DayOfYear ASHRAE A Coeff ASHRAE B Coeff ASHRAE C Coeff Solar Constant-Annual Variation Eq of Time {minutes} Solar Declination Angle {deg} Solar Model
1 21 1229.0 0.1415 5.7310E-002 1.0 -11.15 -20. ASHRAEClearSky
2 202 1084.4 0.2082 0.1365 1.0 -6.23 20.6 ASHRAETau


Tabular Report

Style Unit Conversion
1 Commaandhtml commaandhtml


Warmup Convergence Information

Zone Name Environment Type/Name Average Warmup Temperature Difference {deltaF} Std Dev Warmup Temperature Difference {deltaF} Max Temperature Pass/Fail Convergence Min Temperature Pass/Fail Convergence Average Warmup Load Difference {Btu/h} Std Dev Warmup Load Difference {Btu/h} Heating Load Pass/Fail Convergence Cooling Load Pass/Fail Convergence
1 CRAWLSPACE SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000080680 0.000060385 Pass Pass 0.000000000 0.000000000 Pass Pass
2 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.001253348 0.000310777 Pass Pass 0.000000000 0.000000000 Pass Pass
3 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000122250 0.000360785 Pass Pass 0.007924347 0.014320626 Pass Pass
4 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000225208 0.000552941 Pass Pass 0.011080185 0.019878424 Pass Pass
5 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.018147764 0.048742880 Pass Pass 0.020531315 0.041995401 Pass Pass
6 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000065202 0.000192136 Pass Pass 0.007945974 0.014367335 Pass Pass
7 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000889492 0.002984888 Pass Pass 0.011571127 0.019811993 Pass Pass
8 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.103941835 0.180268178 Pass Pass 0.051169093 0.135942592 Pass Pass
9 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000023213 0.000048126 Pass Pass 0.011106063 0.019643580 Pass Pass
10 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000153032 0.000329955 Pass Pass 0.018936468 0.033669167 Pass Pass
11 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000034365 0.000067162 Pass Pass 0.011103808 0.019618985 Pass Pass
12 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000029073 0.000063845 Pass Pass 0.011100726 0.019641033 Pass Pass
13 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000151482 0.000322172 Pass Pass 0.018928126 0.033632919 Pass Pass
14 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000033851 0.000064211 Pass Pass 0.011220051 0.019457087 Pass Pass
15 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000045125 0.000032415 Pass Pass 0.000000000 0.000000000 Pass Pass
16 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.015200815 0.040549831 Pass Pass 0.017892737 0.035477577 Pass Pass
17 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.006283156 0.020095133 Pass Pass 0.011303715 0.019346558 Pass Pass
18 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000119858 0.000353771 Pass Pass 0.007562368 0.012696843 Pass Pass
19 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000184145 0.000506592 Pass Pass 0.010505678 0.017449060 Pass Pass
20 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000181981 0.000498759 Pass Pass 0.010513951 0.017439017 Pass Pass
21 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 0.000021986 0.000050315 Pass Pass 0.007568062 0.012698549 Pass Pass
22 CRAWLSPACE SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.239213487 0.137741187 Pass Pass 0.000000000 0.000000000 Pass Pass
23 BREEZEWAY SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.040003646 0.022452827 Pass Pass 0.000000000 0.000000000 Pass Pass
24 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.015935336 0.084080101 Pass Pass 0.223502057 0.742369806 Pass Pass
25 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.018507156 0.088952584 Pass Pass 0.191880153 0.779934065 Pass Pass
26 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000285593 0.000961831 Pass Pass 0.094836671 0.092999407 Pass Pass
27 LIVING_UNIT1_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.017793850 0.073468564 Pass Pass 0.173288688 0.368605205 Pass Pass
28 LIVING_UNIT2_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.024627770 0.090288893 Pass Pass 0.244719634 0.948638647 Pass Pass
29 LIVING_UNIT3_BACKROW_BOTTOMFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000245440 0.000945598 Pass Fail 0.095075274 0.098936441 Pass Pass
30 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.012570799 0.066705155 Pass Pass 0.204917590 0.716866234 Pass Pass
31 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.014792096 0.071486006 Pass Pass 0.171776022 0.726482001 Pass Pass
32 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000292012 0.000953637 Pass Pass 0.082628405 0.075196079 Pass Pass
33 LIVING_UNIT1_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.012919027 0.054494188 Pass Pass 0.146733977 0.361679454 Pass Pass
34 LIVING_UNIT2_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.018413532 0.067107988 Pass Pass 0.211337075 0.849975123 Pass Pass
35 LIVING_UNIT3_BACKROW_MIDDLEFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000242767 0.000934133 Pass Pass 0.081871909 0.080465628 Pass Pass
36 ATTIC SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.511109430 0.349559276 Pass Pass 0.000000000 0.000000000 Pass Pass
37 LIVING_UNIT3_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000253806 0.000920898 Pass Fail 0.080840210 0.081108674 Pass Pass
38 LIVING_UNIT3_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.000287200 0.000937725 Pass Fail 0.082234028 0.076188118 Pass Pass
39 LIVING_UNIT1_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.012459910 0.065752121 Pass Pass 0.125888803 0.204711402 Pass Pass
40 LIVING_UNIT2_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.016329988 0.062510925 Pass Pass 0.167711302 0.539152097 Pass Pass
41 LIVING_UNIT2_FRONTROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.014086637 0.069178244 Pass Pass 0.177850372 0.759581378 Pass Pass
42 LIVING_UNIT1_BACKROW_TOPFLOOR SizingPeriod: INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 0.012019836 0.053962264 Pass Pass 0.110927289 0.103446960 Pass Pass
43 CRAWLSPACE RunPeriod: ANNUAL 0.268627409 0.208666995 Pass Pass 0.000000000 0.000000000 Pass Pass
44 BREEZEWAY RunPeriod: ANNUAL 0.016816569 0.010073858 Pass Pass 0.000000000 0.000000000 Pass Pass
45 LIVING_UNIT1_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000019716 0.000036948 Pass Pass 0.065931915 0.066517029 Pass Pass
46 LIVING_UNIT2_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000175820 0.000341583 Pass Pass 0.064550766 0.061515843 Pass Pass
47 LIVING_UNIT3_FRONTROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000075864 0.000173157 Pass Pass 0.054486496 0.065968650 Pass Pass
48 LIVING_UNIT1_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000056108 0.000149350 Pass Pass 0.031666042 0.036036223 Pass Pass
49 LIVING_UNIT2_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000215460 0.000489162 Pass Pass 0.024300107 0.031246063 Pass Pass
50 LIVING_UNIT3_BACKROW_BOTTOMFLOOR RunPeriod: ANNUAL 0.000034332 0.000065787 Pass Pass 0.026762292 0.037700285 Pass Pass
51 LIVING_UNIT1_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000020013 0.000043983 Pass Pass 0.161023518 0.228899855 Pass Pass
52 LIVING_UNIT2_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.022050291 0.059533695 Pass Pass 1.651786399 4.826808774 Fail Fail
53 LIVING_UNIT3_FRONTROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.060058135 0.165490311 Pass Fail 1.135559587 3.508348767 Fail Fail
54 LIVING_UNIT1_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.012964389 0.078240600 Pass Pass 0.135585390 0.563778306 Fail Fail
55 LIVING_UNIT2_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000192374 0.000408606 Pass Pass 0.033758986 0.050627126 Fail Pass
56 LIVING_UNIT3_BACKROW_MIDDLEFLOOR RunPeriod: ANNUAL 0.000037181 0.000082675 Pass Pass 0.032220541 0.046513327 Pass Pass
57 ATTIC RunPeriod: ANNUAL 0.322750644 0.277416990 Pass Pass 0.000000000 0.000000000 Pass Pass
58 LIVING_UNIT3_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000068468 0.000175772 Pass Pass 0.024838604 0.031554733 Pass Pass
59 LIVING_UNIT3_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000063136 0.000170332 Pass Pass 0.046654286 0.052498338 Pass Pass
60 LIVING_UNIT1_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000058435 0.000238621 Pass Pass 0.057307394 0.057177207 Pass Pass
61 LIVING_UNIT2_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000177448 0.000405059 Pass Pass 0.023619792 0.029566179 Pass Pass
62 LIVING_UNIT2_FRONTROW_TOPFLOOR RunPeriod: ANNUAL 0.000183669 0.000364189 Pass Pass 0.056418846 0.051066387 Pass Pass
63 LIVING_UNIT1_BACKROW_TOPFLOOR RunPeriod: ANNUAL 0.000026819 0.000051511 Pass Pass 0.028875443 0.030935606 Pass Pass



Table of Contents

Report: Annual Heat Emissions Report

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Annual Heat Emissions Summary

Envelope Convection Zone Exfiltration Zone Exhaust Air HVAC Relief Air HVAC Reject Heat Total
Heat Emissions [kBtu] 2172120.99 623854.65 0.00 0.00 244390.02 3040371.46



Table of Contents

Report: Annual Thermal Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Heat Index Hours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 8694.67 58.17 7.17 0.00 0.00
BREEZEWAY 8749.67 10.33 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8189.33 378.17 166.83 25.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 8189.33 0.00 0.00 0.00 0.00
Max 8760.00 378.17 166.83 25.67 0.00
Average 8729.22 21.27 8.29 1.22 0.00
Sum 183313.67 446.67 174.00 25.67 0.00


Heat Index OccupantHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 0.00 0.00 0.00 0.00
Average 10339.18 0.00 0.00 0.00 0.00
Sum 217122.86 0.00 0.00 0.00 0.00


Heat Index OccupiedHours

Safe (≤ 80.1°F) [hr] Caution (> 80.1°F, ≤ 90.0°F) [hr] Extreme Caution (> 90.0°F, ≤ 102.9°F) [hr] Danger (> 102.9, ≤ 125.1°F) [hr] Extreme Danger (> 125.1°F) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 0.00 0.00 0.00 0.00
Average 7508.57 0.00 0.00 0.00 0.00
Sum 157680.00 0.00 0.00 0.00 0.00


Humidex Hours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 8486.50 273.33 0.17 0.00 0.00
BREEZEWAY 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8756.00 4.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8759.17 0.83 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8754.17 5.83 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8755.50 4.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8755.50 4.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8752.17 7.83 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 8086.50 573.83 84.00 15.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8759.67 0.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8758.33 1.67 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 8086.50 0.00 0.00 0.00 0.00
Max 8760.00 573.83 84.00 15.67 0.00
Average 8713.50 41.75 4.01 0.75 0.00
Sum 182983.50 876.67 84.17 15.67 0.00


Humidex OccupantHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 12054.38 8.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 12060.71 1.67 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 12050.71 11.67 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12053.38 9.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12056.67 5.71 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 12046.71 15.67 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 12062.38 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 12062.22 0.16 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 12061.58 0.81 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 12062.38 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 12062.38 15.67 0.00 0.00 0.00
Average 10336.68 2.51 0.00 0.00 0.00
Sum 217070.18 52.68 0.00 0.00 0.00


Humidex OccupiedHours

Little to no Discomfort (≤ 29) [hr] Some Discomfort (> 29, ≤ 40) [hr] Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] Dangerous (> 45, ≤ 50) [hr] Heat Stroke Quite Possible (> 50) [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8756.00 4.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8759.17 0.83 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8754.17 5.83 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8755.50 4.50 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8755.50 4.50 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8752.17 7.83 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8759.67 0.33 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8758.33 1.67 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00 0.00
Max 8760.00 7.83 0.00 0.00 0.00
Average 7507.17 1.40 0.00 0.00 0.00
Sum 157650.50 29.50 0.00 0.00 0.00


Hours of Safety for Cold Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Hours of Safety for Heat Events

Hours of Safety [hr] End Time of the Safety Duration Safe Temperature Exceedance Hours [hr] Safe Temperature Exceedance OccupantHours [hr] Safe Temperature Exceedance OccupiedHours [hr]
CRAWLSPACE 0.00 - 0.00 0.00 0.00
BREEZEWAY 0.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8760.00 - 0.00 0.00 0.00
ATTIC 0.00 - 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 8760.00 - 0.00 0.00 0.00
Min 0.00 - 0.00 0.00 0.00
Max 8760.00 - 0.00 0.00 0.00
Average 7508.57 - 0.00 0.00 0.00
Sum 157680.00 - 0.00 0.00 0.00


Unmet Degree-Hours

Cooling Setpoint Unmet Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Cooling Setpoint Unmet Occupied Degree-Hours [°F·hr] Heating Setpoint Unmet Degree-Hours [°F·hr] Heating Setpoint Unmet Occupant-Weighted Degree-Hours [°F·hr] Heating Setpoint Unmet Occupied Degree-Hours [°C·hr]
CRAWLSPACE 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.23 0.26 0.23 226.32 263.18 226.32
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.92 0.63 0.92 292.34 316.14 292.34
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.25 0.26 0.25 590.79 917.09 590.79
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.20 0.24 0.20 787.76 633.59 787.76
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.87 1.41 0.87 393.83 434.17 393.83
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.19 0.22 0.19 431.89 706.55 431.89
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.23 0.25 0.23 182.52 197.63 182.52
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.28 0.31 0.28 294.56 337.42 294.56
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.25 0.24 0.25 913.29 1418.83 913.29
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.18 0.21 0.18 1002.83 879.46 1002.83
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.30 0.44 0.30 344.21 395.43 344.21
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.19 0.22 0.19 721.19 1161.05 721.19
ATTIC 0.00 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.22 0.23 0.22 359.44 581.13 359.44
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.25 0.25 0.25 516.50 803.16 516.50
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.24 0.27 0.24 390.84 431.28 390.84
LIVING_UNIT2_BACKROW_TOPFLOOR 0.35 0.54 0.35 316.84 344.35 316.84
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.74 0.59 0.74 258.96 285.97 258.96
LIVING_UNIT1_BACKROW_TOPFLOOR 0.21 0.25 0.21 689.51 554.81 689.51
Min 0.00 0.00 0.00 0.00 0.00 0.00
Max 0.92 1.41 0.92 1002.83 1418.83 1002.83
Average 0.29 0.32 0.29 414.93 507.68 414.93
Sum 6.11 6.81 6.11 8713.63 10661.25 8713.63


Discomfort-weighted Exceedance OccupantHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00


Discomfort-weighted Exceedance OccupiedHours

Very-cold Exceedance OccupantHours [hr] Cool Exceedance OccupantHours [hr] Warm Exceedance OccupantHours [hr] Very-hot Exceedance OccupantHours [hr]
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00
Min 0.00 0.00 0.00 0.00
Max 0.00 0.00 0.00 0.00
Average 0.00 0.00 0.00 0.00
Sum 0.00 0.00 0.00 0.00



Table of Contents

Report: Climatic Data Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

SizingPeriod:DesignDay

Maximum Dry Bulb [F] Daily Temperature Range [deltaF] Humidity Value Humidity Type Wind Speed [ft/min] Wind Direction
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB -26.9 0.00 -26.9 Wetbulb [F] 472.46 210.00
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 86.18 22.32 69.98 Wetbulb [F] 925.24 200.00


Monthly Precipitation Summary

Monthly Total Precipitation from .epw [in] Monthly Total Hours of Rain from .epw Monthly Total Precipitation in Site:Precipitation [in] Monthly Total Roof Irrigation Depth [in] Monthly Total Rain Collection Volume [ft3]
Jan 0.00 0      
Feb 0.00 0      
Mar 0.47 13      
Apr 0.63 23      
May 0.00 0      
Jun 7.48 53      
Jul 5.35 41      
Aug 3.43 42      
Sep 0.00 0      
Oct 0.00 0      
Nov 0.00 0      
Dec 0.00 0      


Weather Statistics File

Value
None  



Table of Contents

Report: Envelope Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Opaque Exterior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
BGWALL_UPPER_LDF CRAWL WALL 0.30 0.776 2.276 59.96 59.96 180.00 90.00 S
BGWALL_LOWER_LDF CRAWL WALL 0.30 0.893 2.276 239.83 239.83 180.00 90.00 S
BGWALL_UPPER_SDR CRAWL WALL 0.30 0.776 2.276 32.56 32.56 90.00 90.00 E
BGWALL_LOWER_SDR CRAWL WALL 0.30 0.893 2.276 130.22 130.22 90.00 90.00 E
BGWALL_UPPER_LDB CRAWL WALL 0.30 0.776 2.276 59.96 59.96 0.00 90.00 N
BGWALL_LOWER_LDB CRAWL WALL 0.30 0.893 2.276 239.83 239.83 0.00 90.00 N
BGWALL_UPPER_SDL CRAWL WALL 0.30 0.776 2.276 32.56 32.56 270.00 90.00 W
BGWALL_LOWER_SDL CRAWL WALL 0.30 0.893 2.276 130.22 130.22 270.00 90.00 W
BGFLOOR INTERIOR FLOOR 0.30 0.235 0.300 7794.39 7794.39 0.00 180.00  
BREEZEWAY_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
BREEZEWAY_MIDDLEFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
BREEZEWAY_TOPFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 599.39 599.39 0.00 180.00  
WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.46 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.76 280.68 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
ROOF_RIGHT GABLE_END 0.30 0.314 0.428 440.68 440.68 90.00 90.00 E
ROOF_LEFT GABLE_END 0.30 0.314 0.428 440.68 440.68 270.00 90.00 W
ROOF_BACK EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 0.00 22.59  
ROOF_FRONT EXTERIOR ROOF 0.25 0.543 0.943 4225.65 4225.65 180.00 22.59  
WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 90.00 90.00 E
WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S
WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 180.00 90.00 S
WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 0.00 90.00 N
WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 280.68 0.00 90.00 N
WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 255.45 166.84 270.00 90.00 W
WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR EXTERIOR WALL 0.30 0.048 0.050 339.75 318.74 180.00 90.00 S


Opaque Interior

Construction Reflectance U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Net Area [ft2] Azimuth [deg] Tilt [deg] Cardinal Direction
iz-FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT1_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT2_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
iz-FLOOR_UNIT3_BACKROW_BOTTOMFLOOR iz-EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 180.00 0.00  
BREEZEWAYROOF INTERIOR CEILING 0.30 0.018 0.019 599.39 599.39 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 90.00 90.00 E
FLOOR_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_BOTTOMFLOOR INTERIORWALL 0.30 0.329 0.597 255.46 255.46 270.00 90.00 W
FLOOR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR FLOOR 0.30 0.027 0.028 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_BOTTOMFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDR_1.UNIT2_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_BACKROW_MIDDLEFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_MIDDLEFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 180.00 0.00  
iz-BREEZEWAYROOF ATTIC FLOOR 0.30 0.018 0.019 599.39 599.39 0.00 180.00  
iz-CEILING_UNIT3_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT3_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT2_FRONTROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
iz-CEILING_UNIT1_BACKROW_TOPFLOOR ATTIC FLOOR 0.30 0.018 0.019 1200.55 1200.55 0.00 180.00  
WALL_SDL_1.UNIT3_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT3_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT3_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT3_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDL_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
WALL_SDR_1.UNIT2_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT2_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
WALL_SDL_1.UNIT2_FRONTROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 270.00 90.00 W
FLOOR_UNIT2_FRONTROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT2_FRONTROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  
WALL_SDR_1.UNIT1_BACKROW_TOPFLOOR INTERIORWALL 0.30 0.329 0.597 255.45 255.45 90.00 90.00 E
FLOOR_UNIT1_BACKROW_TOPFLOOR CEILING-FLOOR-LAYER 0.30 0.169 0.228 1200.55 1200.55 0.00 180.00  
CEILING_UNIT1_BACKROW_TOPFLOOR INTERIOR CEILING 0.30 0.018 0.019 1200.55 1200.55 180.00 0.00  


Exterior Fenestration

Construction Frame and Divider Glass Area [ft2] Frame Area [ft2] Divider Area [ft2] Area of One Opening [ft2] Area of Multiplied Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Frame Conductance [Btu/h-ft2-F] Divider Conductance [Btu/h-ft2-F] NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance Shade Control Parent Surface Azimuth [deg] Tilt [deg] Cardinal Direction
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_BOTTOMFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_BOTTOMFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_BOTTOMFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_BOTTOMFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_MIDDLEFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_MIDDLEFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_MIDDLEFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_MIDDLEFLOOR 0.00 90.00 N
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_BACKROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT3_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT3_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDR_1.UNIT3_FRONTROW_TOPFLOOR 90.00 90.00 E
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT1_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_FRONTROW_TOPFLOOR 270.00 90.00 W
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT2_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDF_1.UNIT2_FRONTROW_TOPFLOOR 180.00 90.00 S
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR EXTERIOR WINDOW   59.08 0.00 0.00 59.08 59.08 0.300 0.335 0.883             Yes WALL_LDB_1.UNIT1_BACKROW_TOPFLOOR 0.00 90.00 N
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR EXTERIOR WINDOW   88.61 0.00 0.00 88.61 88.61 0.300 0.335 0.883             Yes WALL_SDL_1.UNIT1_BACKROW_TOPFLOOR 270.00 90.00 W
Total or Average             2126.74 0.300 0.335 0.883                      
North Total or Average             531.68 0.300 0.335 0.883                      
Non-North Total or Average             1595.05 0.300 0.335 0.883                      


Exterior Fenestration Shaded State

Frame and Divider Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance NFRC Product Type Assembly U-Factor [Btu/h-ft2-F] Assembly SHGC Assembly Visible Transmittance
None                


Interior Fenestration

Construction Area of One Opening [ft2] Area of Openings [ft2] Glass U-Factor [Btu/h-ft2-F] Glass SHGC Glass Visible Transmittance Parent Surface
Total or Average     0.00 - - -  


Exterior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
DOOR_LDB_UNIT1_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT2_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_BOTTOMFLOOR
DOOR_LDB_UNIT3_FRONTROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_BOTTOMFLOOR
DOOR_LDF_UNIT1_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT2_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_BOTTOMFLOOR
DOOR_LDF_UNIT3_BACKROW_BOTTOMFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_BOTTOMFLOOR
DOOR_LDB_UNIT1_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT2_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_MIDDLEFLOOR
DOOR_LDB_UNIT3_FRONTROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_MIDDLEFLOOR
DOOR_LDF_UNIT1_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT2_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_MIDDLEFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_MIDDLEFLOOR
DOOR_LDF_UNIT3_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT3_BACKROW_TOPFLOOR
DOOR_LDB_UNIT3_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT3_FRONTROW_TOPFLOOR
DOOR_LDB_UNIT1_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT1_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT2_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT2_BACKROW_TOPFLOOR
DOOR_LDB_UNIT2_FRONTROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDB_1.UNIT2_FRONTROW_TOPFLOOR
DOOR_LDF_UNIT1_BACKROW_TOPFLOOR EXTERIOR DOOR 0.239 0.300 21.01 WALL_LDF_1.UNIT1_BACKROW_TOPFLOOR


Interior Door

Construction U-Factor with Film [Btu/h-ft2-F] U-Factor no Film [Btu/h-ft2-F] Gross Area [ft2] Parent Surface
None          



Table of Contents

Report: Shading Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Sunlit Fraction

March 21 9am March 21 noon March 21 3pm June 21 9am June 21 noon June 21 3pm December 21 9am December 21 noon December 21 3pm
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR 1.00 0.97 0.00 0.99 0.95 0.00 1.00 0.98 0.00
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR 0.99 0.99 0.99 0.96 0.98 0.98 1.00 1.00 1.00
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.99 0.00 0.00 0.99 0.00 0.00 1.00


Window Control

Name Type Shaded Construction Control Glare Control
WINDOW_LDF_UNIT1_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT1_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT2_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_BOTTOMFLOOR SHADES-LIVING_UNIT3_BACKROW_BOTTOMFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT1_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT2_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_MIDDLEFLOOR SHADES-LIVING_UNIT3_BACKROW_MIDDLEFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDR_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT1_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT1_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT3_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT2_BACKROW_TOPFLOOR SHADES-LIVING_UNIT2_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDF_UNIT2_FRONTROW_TOPFLOOR SHADES-LIVING_UNIT2_FRONTROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_LDB_UNIT1_BACKROW_TOPFLOOR SHADES-LIVING_UNIT1_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No
WINDOW_SDL_UNIT3_BACKROW_TOPFLOOR SHADES-LIVING_UNIT3_BACKROW_TOPFLOOR Interior Blind WINDOW_W_BLINDS AlwaysOff No



Table of Contents

Report: Lighting Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Interior Lighting

Zone Name Space Name Space Type Lighting Power Density [Btu/h-ft2] Space Area [ft2] Total Power [Btu/h] End Use Subcategory Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Return Air Fraction Conditioned (Y/N) Consumption [kWh]
LIVING HARDWIRED LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
LIVING HARDWIRED LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.4008 1200.55 481.17 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 432.94
LIVING PLUG-IN LIGHTING3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR GENERAL 0.1823 1200.55 218.81 General INTERIORLIGHTINGHE 58.88 168.00 58.88 0.0000 Y 196.88
Interior Lighting Total       0.2915 43219.92 12599.76               11336.81


Daylighting

Zone Control Name Daylighting Method Control Type Fraction Controlled Lighting Installed in Zone [Btu/h] Lighting Controlled [Btu/h]
None              


Exterior Lighting

Total Watts Astronomical Clock/Schedule Schedule Name Scheduled Hours/Week [hr] Hours/Week > 1% [hr] Full Load Hours/Week [hr] Consumption [kWh]
EXTERIOR-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_BOTTOMFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_MIDDLEFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_FRONTROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT1_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT1_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT2_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT2_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
EXTERIOR-LIGHTS_UNIT3_BACKROW_TOPFLOOR 76.54 Schedule EXTERIORLIGHTING 84.00 84.00 84.00 335.24
GARAGE-LIGHTS_UNIT3_BACKROW_TOPFLOOR 0.00 Schedule INTERIORLIGHTINGHE 58.88 0.00   0.00
Exterior Lighting Total 1377.69           6034.31



Table of Contents

Report: Equipment Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Central Plant

Type Reference Capacity [Btu/h] Reference Efficiency [Btuh/Btuh] Rated Capacity [Btu/h] Rated Efficiency [Btuh/Btuh] IPLV in SI Units [W/W] IPLV in IP Units [Btu/W-h]
CENTRAL BOILER Boiler:HotWater 415468.38 0.80        


Cooling Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Sensible Capacity [Btu/h] Nominal Latent Capacity [Btu/h] Nominal Sensible Heat Ratio Nominal Efficiency [Btuh/Btuh] Nominal Coil UA Value [Btu/h-F] Nominal Coil Surface Area [ft2]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   15066.87 11029.23 4037.64 0.73 4.09    
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   7495.42 5254.91 2240.51 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   11600.81 8421.19 3179.62 0.73 4.09    
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   14205.66 10393.30 3812.36 0.73 4.09    
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   6720.59 4711.69 2008.90 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed   10413.21 7616.04 2797.18 0.73 4.09    
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   14737.92 10889.62 3848.30 0.74 4.09    
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   7567.12 5305.18 2261.94 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   11648.39 8513.21 3135.18 0.73 4.09    
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   13902.82 10252.93 3649.89 0.74 4.09    
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   6863.04 4811.56 2051.48 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed   10419.94 7670.51 2749.43 0.74 4.09    
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   15199.69 11167.95 4031.74 0.73 4.09    
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7860.85 5511.11 2349.74 0.70 4.09    
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   11698.30 8477.35 3220.96 0.72 4.09    
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   14800.85 10890.36 3910.48 0.74 4.09    
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   7841.51 5515.52 2325.99 0.70 4.09    
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed   10497.35 7660.69 2836.66 0.73 4.09    
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

DX Cooling Coils

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP [Btuh/Btuh] EER [Btu/W-h] SEER User [Btu/W-h] SEER Standard [Btu/W-h] IEER [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR   1.2 3.47 11.82 12.55 12.06 12.37
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR   0.6 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR   0.9 3.48 11.86 12.59 12.10 12.43
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR   1.1 3.47 11.83 12.55 12.06 12.38
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR   0.5 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR   0.8 3.47 11.83 12.55 12.06 12.38
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR   1.2 3.46 11.79 12.51 12.02 12.32
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR   0.6 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR   0.9 3.47 11.83 12.55 12.07 12.39
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR   1.1 3.46 11.79 12.51 12.03 12.32
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR   0.6 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR   0.8 3.46 11.80 12.52 12.04 12.34
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR   1.2 3.46 11.81 12.53 12.05 12.35
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR   0.6 3.52 12.00 12.74 12.25 12.67
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR   0.9 3.48 11.87 12.59 12.11 12.45
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR   1.2 3.46 11.81 12.52 12.04 12.34
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR   0.6 3.51 11.99 12.73 12.24 12.66
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR   0.8 3.47 11.84 12.56 12.08 12.40
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER Standard is calculated using AHRI Std 210/240-2008 default PLF curve and cooling coefficient of degradation.

DX Cooling Coils [ SEER2 ]

DX Cooling Coil Type Standard Rated Net Cooling Capacity [ton] Standard Rated Net COP2 [Btuh/Btuh] EER2 [Btu/W-h] SEER2 User [Btu/W-h] SEER2 Standard [Btu/W-h] IEER2 [Btu/W-h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.35 11.44 12.13 11.99  
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.37 11.48 12.17 12.03  
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.35 11.45 12.13 11.99  
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.5 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.36 11.45 12.13 11.99  
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.34 11.40 12.08 11.95  
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.36 11.45 12.14 12.00  
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 1.1 3.34 11.41 12.09 11.95  
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.35 11.42 12.10 11.96  
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.35 11.43 12.11 11.97  
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.65 12.35 12.21  
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.9 3.37 11.49 12.18 12.04  
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 1.2 3.35 11.42 12.10 11.96  
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.6 3.41 11.63 12.34 12.20  
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed 0.8 3.36 11.46 12.15 12.01  
ANSI/AHRI ratings account for supply air fan heat and electric power. SEER2 User is calculated using user-input PLF curve and cooling coefficient of degradation whereas SEER2 Standard is calculated using AHRI Std 210/240-2023 default PLF curve and cooling coefficient of degradation. IEER Calculation was removed from the 2023 Version of the Standard.

DX Cooling Coil ASHRAE 127 Standard Ratings Report

DX Cooling Coil Type Rated Net Cooling Capacity Test A [ton] Rated Electric Power Test A [W] Rated Net Cooling Capacity Test B [ton] Rated Electric Power Test B [W] Rated Net Cooling Capacity Test C [ton] Rated Electric Power Test C [W] Rated Net Cooling Capacity Test D [ton] Rated Electric Power Test D [W]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed                


Water-to-Air Heat Pumps at Rated Temperatures Report

Coil Type Rated Total Capacity [Btu/h] Rated Sensible Capacity [Btu/h] Rated Power[Btu/h] Rated COP [Btuh/Btuh] Rated Air Dry-bulb Temperature [F] Rated Air Wet-bulb Temperature [F] Rated Water Temperature [F] Design Day used for Sizing
None                  


DX Heating Coils

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF [Btu/W-h] Region Number
None          


DX Heating Coils [ HSPF2 ]

DX Heating Coil Type High Temperature Heating (net) Rating Capacity [Btu/h] Low Temperature Heating (net) Rating Capacity [Btu/h] HSPF2 [Btu/W-h] Region Number
None          


Heating Coils

Type Design Coil Load [Btu/h] Nominal Total Capacity [Btu/h] Nominal Efficiency [Btuh/Btuh]
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 30070.42 30050.25 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 16488.20 14852.21 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water 24013.16 23315.03 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water 28621.40 28442.81 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water 15332.33 13530.37 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water 22381.33 21492.58 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 29964.44 29925.58 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 16594.45 14968.05 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water 24367.53 23704.52 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water 28532.29 28337.11 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water 15544.19 13768.52 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water 22629.35 21764.66 -
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water 30448.73 30469.36 -
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water 17033.36 15472.10 -
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water 24081.40 23390.93 -
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water 29883.14 29842.31 -
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water 17066.14 15509.35 -
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water 22416.53 21531.74 -
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped   3165.61 2.75
Nominal values are gross at rated conditions, i.e., the supply air fan heat and electric power NOT accounted for.

Fans

Type Total Efficiency [Btuh/Btuh] Delta Pressure [psi] Max Air Flow Rate [ft3/min] Rated Electricity Rate [W] Rated Power Per Max Air Flow Rate [W-min/ft3] Motor Heat In Air Fraction Fan Energy Index End Use Subcategory Design Day Name for Fan Sizing Peak Date/Time for Fan Sizing Peak
OASUPPLYFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OASUPPLYFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
OAEXHAUSTFAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.60 0.15 44.99 37.50 0.83 0.00 9.97 Ventilation    
SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 415.08 156.57 0.38 1.00 2.33 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 187.42 70.70 0.38 1.00 3.68 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 313.55 118.27 0.38 1.00 2.70 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 390.79 147.40 0.38 1.00 2.40 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 168.05 63.39 0.38 1.00 3.96 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.50 0.06 286.20 107.95 0.38 1.00 2.84 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 413.34 155.91 0.38 1.00 2.34 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 189.22 71.37 0.38 1.00 3.66 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 319.51 120.52 0.38 1.00 2.67 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 389.33 146.85 0.38 1.00 2.41 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 171.61 64.73 0.38 1.00 3.90 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.50 0.06 290.38 109.53 0.38 1.00 2.81 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 421.42 158.96 0.38 1.00 2.32 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 196.56 74.14 0.38 1.00 3.57 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.50 0.06 314.70 118.70 0.38 1.00 2.69 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 411.94 155.38 0.38 1.00 2.34 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 197.11 74.35 0.38 1.00 3.56 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.50 0.06 286.79 108.18 0.38 1.00 2.83 General INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    
HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 0.70 0.01 160.01 10.79 0.07 1.00 11.80 General    


Pumps

Type Control Head [psi] Water Flow [gal/min] Electricity Rate [W] Power Per Water Flow Rate [W-min/gal] Motor Efficiency [Btuh/Btuh] End Use Subcategory
BOILER CIRC PUMP Pump:VariableSpeed Intermittent 0.00 42.646461 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_BOTTOMFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_MIDDLEFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_FRONTROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT1_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT2_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General
MAINS PRESSURE_UNIT3_BACKROW_TOPFLOOR Pump:VariableSpeed Intermittent 0.00 7.815904 0.00 0.00 1.00 General


Service Water Heating

Type Storage Volume [ft3] Input [Btu/h] Thermal Efficiency [Btuh/Btuh] Recovery Efficiency [Btuh/Btuh] Energy Factor
WATER HEATER_UNIT1_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_BOTTOMFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_MIDDLEFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT1_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_FRONTROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT1_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT2_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00
WATER HEATER_UNIT3_BACKROW_TOPFLOOR WaterHeater:HeatPump:WrappedCondenser 6.69 4435.83 1.00 0.00 0.00



Table of Contents

Report: HVAC Sizing Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Zone Sensible Cooling

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 9342.36 9342.36 7.78 415.082 415.082 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 75.00 75.00 0.00794 80.82 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4218.32 4218.32 3.51 187.425 187.425 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 75.00 75.00 0.00817 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 7057.33 7057.33 5.88 313.553 313.553 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 75.00 75.00 0.00792 79.93 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8795.66 8795.66 7.33 390.794 390.794 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 75.00 75.00 0.00799 79.71 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 3782.31 3782.31 3.15 168.050 168.050 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 75.00 75.00 0.00858 76.25 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 6441.73 6441.73 5.37 286.200 286.200 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 75.00 75.00 0.00799 76.43 0.01272 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9303.20 9303.20 7.75 413.336 413.336 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00784 80.27 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4258.81 4258.81 3.55 189.217 189.217 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 75.00 75.00 0.00792 86.18 0.01273 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 7191.63 7191.63 5.99 319.515 319.515 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 75.00 75.00 0.00778 80.49 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8762.82 8762.82 7.30 389.329 389.329 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00789 79.15 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 3862.54 3862.54 3.22 171.612 171.612 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 75.00 75.00 0.00833 76.25 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 6535.83 6535.83 5.44 290.378 290.378 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 75.00 75.00 0.00783 77.07 0.01272 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 6455.01 6455.01 5.38 286.790 286.790 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 75.00 75.00 0.00799 77.07 0.01272 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 7083.07 7083.07 5.90 314.696 314.696 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 75.00 75.00 0.00792 80.49 0.01272 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 9485.06 9485.06 7.90 421.423 421.423 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 75.00 75.00 0.00794 80.27 0.01272 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 4436.41 4436.41 3.70 197.112 197.112 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 75.00 75.00 0.00842 76.25 0.01272 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 4424.06 4424.06 3.69 196.562 196.562 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 75.00 75.00 0.00841 77.48 0.01272 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 9271.65 9271.65 7.72 411.943 411.943 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 75.00 75.00 0.00797 79.15 0.01272 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

Zone Sensible Heating

Calculated Design Load [Btu/h] User Design Load [Btu/h] User Design Load per Area [Btu/h-ft2] Calculated Design Air Flow [ft3/min] User Design Air Flow [ft3/min] Design Day Name Date/Time Of Peak {TIMESTAMP} Thermostat Setpoint Temperature at Peak Load [F] Indoor Temperature at Peak Load [F] Indoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Outdoor Temperature at Peak Load [F] Outdoor Humidity Ratio at Peak Load [lbWater/lbDryAir] Minimum Outdoor Air Flow Rate [ft3/min] Heat Gain Rate from DOAS [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 11515.03 11515.03 9.59 218.729 218.729 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00706 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 8368.32 8368.32 6.97 158.960 158.960 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00693 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 11522.90 11522.90 9.60 218.879 218.879 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00707 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 11518.44 11518.44 9.59 218.794 218.794 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00706 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 8368.96 8368.96 6.97 158.972 158.972 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00693 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 11520.85 11520.85 9.60 218.840 218.840 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00707 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 8114.65 8114.65 6.76 154.151 154.151 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00754 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4988.48 4988.48 4.16 94.766 94.766 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00759 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 8115.62 8115.62 6.76 154.170 154.170 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00754 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 8116.38 8116.38 6.76 154.184 154.184 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00754 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4987.67 4987.67 4.15 94.751 94.751 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00759 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 8112.29 8112.29 6.76 154.106 154.106 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 72.00 0.00754 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 11753.90 11753.90 9.79 223.267 223.267 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00708 -26.9 0.00018 44.995 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 11758.10 11758.10 9.79 223.346 223.346 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00708 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 11761.95 11761.95 9.80 223.419 223.419 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00708 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 8620.40 8620.40 7.18 163.748 163.748 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00696 -26.9 0.00018 44.995 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 8622.76 8622.76 7.18 163.793 163.793 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00696 -26.9 0.00018 44.995 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 11761.40 11761.40 9.80 223.409 223.409 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 72.00 71.99 0.00708 -26.9 0.00018 44.995 0.00
The Design Load is the zone sensible load only. It does not include any system effects or ventilation loads.

System Design Air Flow Rates

Calculated cooling [ft3/min] User cooling [ft3/min] Calculated heating [ft3/min] User heating [ft3/min] Adjusted cooling [ft3/min] Adjusted heating [ft3/min] Adjusted main [ft3/min] Calculated Heating Air Flow Ratio [] User Heating Air Flow Ratio []
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.08 415.08 218.73 218.73 415.0821 415.0821 415.0821 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.42 187.42 158.96 158.96 187.4245 187.4245 187.4245 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.55 313.55 218.88 218.88 313.5526 313.5526 313.5526 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.79 390.79 218.79 218.79 390.7941 390.7941 390.7941 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.05 168.05 158.97 158.97 168.0498 168.0498 168.0498 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.20 286.20 218.84 218.84 286.2005 286.2005 286.2005 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.34 413.34 154.15 154.15 413.3358 413.3358 413.3358 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.22 189.22 94.77 94.77 189.2174 189.2174 189.2174 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.51 319.51 154.17 154.17 319.5147 319.5147 319.5147 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.33 389.33 154.18 154.18 389.3286 389.3286 389.3286 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.61 171.61 94.75 94.75 171.6117 171.6117 171.6117 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.38 290.38 154.11 154.11 290.3776 290.3776 290.3776 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.42 421.42 223.42 223.42 421.4232 421.4232 421.4232 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.56 196.56 163.79 163.79 196.5623 196.5623 196.5623 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.70 314.70 223.35 223.35 314.6963 314.6963 314.6963 1.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.94 411.94 223.41 223.41 411.9431 411.9431 411.9431 1.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.11 197.11 163.75 163.75 197.1119 197.1119 197.1119 1.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.79 286.79 223.27 223.27 286.7904 286.7904 286.7904 1.0000 1.0000


Plant Loop Coincident Design Fluid Flow Rate Adjustments

Previous Design Volume Flow Rate [ft3/min] Algorithm Volume Flow Rate [ft3/min] Coincident Design Volume Flow Rate [ft3/min] Coincident Size Adjusted Peak Sizing Period Name Peak Day into Period {TIMESTAMP}[day] Peak Hour Of Day {TIMESTAMP}[hr] Peak Step Start Minute {TIMESTAMP}[min]
None                


Coil Sizing Summary

Coil Type HVAC Type HVAC Name Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Flow Percentage at Ideal Loads Peak [%] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 15066.867 11029.231 415.082150 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 15053.38 13064.13 415.082150 76.85 61.24 0.00846262 53.60 50.67 0.00750000 80.82 0.01272064 68.46 10.8400 75.00 0.00793914 41.2670 9332.56 0.00 15073.15 10812.57
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 30070.421 30070.421 415.082150 0.41253273 439.649 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 30070.42 26534.69 415.082150 61.28 51.72 0.00631875 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.8400 71.99 0.00706469 40.6812 11515.03 0.00 30054.32 30054.32
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 7495.417 5254.911 187.424505 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 7445.90 5905.28 187.424505 78.90 63.13 0.00926670 53.60 50.67 0.00750000 86.18 0.01272586 70.04 24.0070 75.00 0.00817392 42.4721 4218.32 0.00 7498.54 5162.20
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 16488.202 16488.202 187.424505 0.22619980 228.253 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 16488.20 14549.49 187.424505 48.26 43.87 0.00531036 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 24.0070 71.99 0.00693003 39.9131 8368.32 0.00 14843.29 14843.29
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 11600.809 8421.191 313.552561 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 11679.86 9936.74 313.552561 76.93 61.49 0.00861193 53.60 50.67 0.00750000 79.93 0.01271977 68.19 14.3501 75.00 0.00792157 41.1763 7040.22 0.00 11605.65 8257.32
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 24013.159 24013.159 313.552561 0.32943384 345.683 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 24013.16 21189.65 313.552561 57.81 49.79 0.00607768 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 14.3501 71.99 0.00706523 40.6843 11522.90 0.00 23314.49 23314.49
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 14205.660 10393.300 390.794135 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 14289.48 12276.95 390.794135 76.76 61.31 0.00853310 53.60 50.67 0.00750000 79.71 0.01271956 68.12 11.5137 75.00 0.00797940 41.4738 8774.63 0.00 14211.59 10188.78
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 28621.396 28621.396 390.794135 0.39265373 417.207 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28621.40 25256.05 390.794135 60.61 51.36 0.00627260 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 11.5137 71.99 0.00706493 40.6826 11518.44 0.00 28445.83 28445.83
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 6720.592 4711.694 168.049821 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 7030.93 5209.67 168.049821 76.55 62.95 0.00968704 53.60 50.67 0.00750000 76.25 0.01271621 67.07 26.7748 75.00 0.00860988 44.7061 3759.11 0.00 6723.40 4628.57
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 15332.328 15332.328 168.049821 0.21034249 210.026 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 15332.33 13529.53 168.049821 45.53 42.13 0.00512367 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 26.7748 71.99 0.00693009 39.9135 8368.96 0.00 13520.10 13520.10
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 10413.213 7616.037 286.200499 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 10679.38 8918.98 286.200499 76.45 61.50 0.00873019 53.60 50.67 0.00750000 76.43 0.01271639 67.12 15.7215 75.00 0.00798258 41.4892 6426.28 0.00 10417.56 7466.00
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 22381.334 22381.334 286.200499 0.30704701 320.315 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 22381.33 19749.70 286.200499 56.45 49.02 0.00598318 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.7215 71.99 0.00706509 40.6835 11520.85 0.00 21490.67 21490.67
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 14737.921 10889.618 413.335819 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 14742.00 12948.28 413.335819 76.79 61.08 0.00837401 53.60 50.67 0.00750000 80.27 0.01272010 68.29 10.8858 75.00 0.00783698 40.7422 9293.46 0.00 14744.07 10673.47
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 29964.442 29964.442 413.335819 0.41107882 437.800 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 29964.44 26441.18 413.335819 61.24 52.47 0.00673912 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.8858 72.00 0.00753994 43.3791 8114.65 0.00 29937.84 29937.84
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 7567.120 5305.181 189.217442 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 7487.28 6080.83 189.217442 78.88 62.83 0.00906505 53.60 50.67 0.00750000 86.18 0.01272586 70.04 23.7795 75.00 0.00792294 41.1835 4258.81 0.00 7570.28 5211.58
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 16594.449 16594.449 189.217442 0.22765738 229.759 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 16594.45 14643.25 189.217442 48.49 45.08 0.00583060 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 23.7795 72.00 0.00759244 43.6761 4988.48 0.00 14964.91 14964.91
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 11648.394 8513.213 319.514728 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 11667.48 10117.57 319.514728 76.99 61.30 0.00847323 53.60 50.67 0.00750000 80.49 0.01272031 68.36 14.0823 75.00 0.00777511 40.4239 7172.96 0.00 11653.25 8347.45
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 24367.526 24367.526 319.514728 0.33429536 351.018 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 24367.53 21502.35 319.514728 58.08 50.71 0.00650401 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 14.0823 72.00 0.00753999 43.3794 8115.62 0.00 23710.82 23710.82
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 13902.822 10252.927 389.328589 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 14000.48 12171.95 389.328589 76.70 61.16 0.00844470 53.60 50.67 0.00750000 79.15 0.01271901 67.95 11.5571 75.00 0.00787652 40.9453 8737.62 0.00 13908.62 10049.25
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 28532.286 28532.286 389.328589 0.39143123 415.628 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 28532.29 25177.41 389.328589 60.57 52.11 0.00668982 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 11.5571 72.00 0.00754003 43.3796 8116.38 0.00 28347.89 28347.89
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 6863.036 4811.559 171.611668 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 7149.81 5432.18 171.611668 76.55 62.65 0.00947768 53.60 50.67 0.00750000 76.25 0.01271621 67.07 26.2191 75.00 0.00833928 43.3191 3848.00 0.00 6865.90 4726.67
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 15544.193 15544.193 171.611668 0.21324905 213.215 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 15544.19 13716.48 171.611668 46.08 43.54 0.00564981 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 26.2191 72.00 0.00759238 43.6758 4987.67 0.00 13763.67 13763.67
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 10419.938 7670.505 290.377605 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 10628.00 9052.56 290.377605 76.54 61.32 0.00858833 53.60 50.67 0.00750000 77.07 0.01271700 67.32 15.4953 75.00 0.00781975 40.6530 6516.14 0.00 10424.29 7517.22
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 22629.346 22629.346 290.377605 0.31044946 324.015 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 22629.35 19968.55 290.377605 56.68 49.92 0.00639992 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.4953 72.00 0.00753982 43.3785 8112.29 0.00 21768.97 21768.97
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 15199.691 11167.946 421.423236 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 15224.55 13223.39 421.423236 76.78 61.20 0.00845442 53.60 50.67 0.00750000 80.27 0.01272010 68.29 10.6769 75.00 0.00793948 41.2688 9469.09 0.00 15206.03 10949.71
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 30448.730 30448.730 421.423236 0.41772271 445.499 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 30448.73 26868.52 421.423236 61.44 51.84 0.00634463 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.6769 71.99 0.00708110 40.7746 11761.95 0.00 30473.99 30473.99
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 7860.855 5511.113 196.562343 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 8132.77 6250.18 196.562343 76.78 62.61 0.00939977 53.60 50.67 0.00750000 77.48 0.01271739 67.44 22.8909 75.00 0.00814037 42.3000 4387.13 0.00 7864.13 5413.88
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 17033.357 17033.357 196.562343 0.23367871 236.808 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 17033.36 15030.55 196.562343 49.37 44.60 0.00540554 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 22.8909 71.99 0.00695582 40.0600 8622.76 0.00 15464.00 15464.00
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 11698.302 8477.346 314.696334 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 11746.01 10003.09 314.696334 77.00 61.51 0.00860738 53.60 50.67 0.00750000 80.49 0.01272031 68.36 14.2979 75.00 0.00791957 41.1661 7068.25 0.00 11703.18 8315.94
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 24081.396 24081.396 314.696334 0.33036997 346.737 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 24081.40 21249.87 314.696334 57.86 49.85 0.00609465 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 14.2979 71.99 0.00708084 40.7732 11758.10 0.00 23390.66 23390.66
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 14800.848 10890.364 411.943096 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 14915.80 12880.87 411.943096 76.67 61.22 0.00849255 53.60 50.67 0.00750000 79.15 0.01271901 67.95 10.9226 75.00 0.00796624 41.4063 9248.75 0.00 14807.02 10675.51
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 29883.144 29883.144 411.943096 0.40996350 436.742 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 29883.14 26369.44 411.943096 61.20 51.71 0.00632765 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 10.9226 71.99 0.00708106 40.7744 11761.40 0.00 29846.53 29846.53
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 7841.514 5515.522 197.111863 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 8155.73 6250.28 197.111863 76.50 62.52 0.00940393 53.60 50.67 0.00750000 76.25 0.01271621 67.07 22.8271 75.00 0.00843918 43.8316 4423.19 0.00 7844.79 5417.22
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 17066.141 17066.141 197.111863 0.23412847 237.322 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 17066.14 15059.48 197.111863 49.43 44.64 0.00540968 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 22.8271 71.99 0.00695558 40.0587 8620.40 0.00 15501.28 15501.28
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 10497.349 7660.690 286.790427 -999. -999.00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 10734.33 8973.10 286.790427 76.54 61.53 0.00872760 53.60 50.67 0.00750000 77.07 0.01271700 67.32 15.6892 75.00 0.00796873 41.4184 6425.98 0.00 10501.73 7512.88
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 22416.528 22416.528 286.790427 0.30752984 320.857 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 22416.53 19780.76 286.790427 56.48 49.06 0.00599845 122.00 74.22 0.00800000 -26.9 0.00018338 -26.9 15.6892 71.99 0.00708056 40.7716 11753.90 0.00 21530.06 21530.06
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.318 3264.099 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3318.223 3255.177 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.200 3263.983 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.471 3264.249 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3318.211 3255.165 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3284.400 3221.996 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3379.263 3315.057 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3403.406 3338.742 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3379.009 3314.808 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3379.603 3315.390 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3403.396 3338.731 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3378.989 3314.788 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.321 3264.102 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3318.160 3255.115 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.200 3263.984 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.337 3264.118 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3318.160 3255.115 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown 3327.272 3264.054 400.423678 -999. -999.00 unknown unknown unknown unknown 3165.61 -999.0 -999. -999.0 -999.0 -999. -999.0 -999.0 -999. -999.0 -999. -999.0 -999.000 -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0



Table of Contents

Report: Coil Sizing Details

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Coils

Coil Type Coil Location HVAC Type HVAC Name Zone Name(s) System Sizing Method Concurrence System Sizing Method Capacity System Sizing Method Air Flow Autosized Coil Capacity? Autosized Coil Airflow? Autosized Coil Water Flow? OA Pretreated prior to coil inlet? Coil Final Gross Total Capacity [Btu/h] Coil Final Gross Sensible Capacity [Btu/h] Coil Final Reference Air Volume Flow Rate [ft3/min] Coil Final Reference Plant Fluid Volume Flow Rate [ft3/min] Coil U-value Times Area Value [Btu/h-F] Terminal Unit Reheat Coil Multiplier DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio Moist Air Heat Capacity [Btu/lbm-R] Dry Air Heat Capacity [Btu/lbm-R] Standard Air Density Adjusted for Elevation [lb/ft3] Supply Fan Name for Coil Supply Fan Type for Coil Supply Fan Maximum Air Volume Flow Rate [ft3/min] Supply Fan Maximum Air Mass Flow Rate [lb/s] Plant Name for Coil Plant Fluid Specific Heat Capacity [Btu/lbm-R] Plant Fluid Density [lb/ft3] Plant Maximum Fluid Mass Flow Rate [lb/s] Plant Design Fluid Return Temperature [F] Plant Design Fluid Supply Temperature [F] Plant Design Fluid Temperature Difference [deltaF] Plant Design Capacity [Btu/h] Coil Capacity Percentage of Plant Design Capacity [%] Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] Design Day Name at Sensible Ideal Loads Peak Date/Time at Sensible Ideal Loads Peak Design Day Name at Total Ideal Loads Peak Date/Time at Total Ideal Loads Peak Design Day Name at Air Flow Ideal Loads Peak Date/Time at Air Flow Ideal Loads Peak Peak Load Type to Size On Coil Total Capacity at Ideal Loads Peak [Btu/h] Coil Sensible Capacity at Ideal Loads Peak [Btu/h] Coil Off-Rating Capacity Modifier at Ideal Loads Peak [] Coil Air Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Coil Entering Air Drybulb at Ideal Loads Peak [F] Coil Entering Air Wetbulb at Ideal Loads Peak [F] Coil Entering Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Entering Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Leaving Air Drybulb at Ideal Loads Peak [F] Coil Leaving Air Wetbulb at Ideal Loads Peak [F] Coil Leaving Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Ideal Loads Peak [Btu/lbm-R] Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [lb/s] Coil Entering Plant Fluid Temperature at Ideal Loads Peak [F] Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [F] Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaF] Supply Fan Air Heat Gain at Ideal Loads Peak [Btu/h] Coil and Fan Net Total Capacity at Ideal Loads Peak [Btu/h] Outdoor Air Drybulb at Ideal Loads Peak [F] Outdoor Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Outdoor Air Wetbulb at Ideal Loads Peak [F] Outdoor Air Volume Flow Rate at Ideal Loads Peak [ft3/min] Outdoor Air Flow Percentage at Ideal Loads Peak [%] System Return Air Drybulb at Ideal Loads Peak [F] System Return Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Drybulb at Ideal Loads Peak [F] Zone Air Humidity Ratio at Ideal Loads Peak [lbWater/lbDryAir] Zone Air Relative Humidity at Ideal Loads Peak [%] Zone Sensible Heat Gain at Ideal Loads Peak [Btu/h] Zone Latent Heat Gain at Ideal Loads Peak [Btu/h] Coil Total Capacity at Rating Conditions [Btu/h] Coil Sensible Capacity at Rating Conditions [Btu/h] Coil Air Mass Flow Rate at Rating Conditions [lb/s] Coil Entering Air Drybulb at Rating Conditions [F] Coil Entering Air Wetbulb at Rating Conditions [F] Coil Entering Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Entering Air Enthalpy at Rating Conditions [Btu/lbm-R] Coil Leaving Air Drybulb at Rating Conditions [F] Coil Leaving Air Wetbulb at Rating Conditions [F] Coil Leaving Air Humidity Ratio at Rating Conditions [lbWater/lbDryAir] Coil Leaving Air Enthalpy at Rating Conditions [Btu/lbm-R]
DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15066.867 11029.231 415.082150 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 415.082150 0.49840621   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 17:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 Sensible 15053.38 13064.13 0.9991 0.49840621 415.082150 76.85 61.24 0.00846262 11.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 534.203 14519.18 80.82 0.01272064 68.46 44.99498340 10.8400 75.00 0.00794493 75.00 0.00793914 41.2670 9332.56 0.00 15073.15 10812.57 0.47872293 80.00 67.00 0.01118466 13.2 54.28 54.24 0.00893002 8.4
MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR LIVING_UNIT1_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 30070.421 30070.421 415.082150 0.41253273 439.649 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 415.082150 0.49840621   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 7.0949 7.237716 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 30070.42 26534.69 1.0000 0.49840621 415.082150 61.28 51.72 0.00631875 7.7 122.00 74.22 0.00800000 17.0 0.42922595 140.00 120.20 19.80 0.000 30070.42 -26.9 0.00018338 -26.9 44.99498340 10.8400 71.99 0.00706469 71.99 0.00706469 40.6812 11515.03 0.00 30054.32 30054.32 0.49840621 61.88 52.65 0.00631875 7.8 130.87 75.55 0.00631875 17.1
DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7495.417 5254.911 187.424505 -999. -999.00 -999.0000 1.00000 0.90849 0.2441 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 187.424505 0.22504831   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:30:00 Sensible 7445.90 5905.28 0.9934 0.22504831 187.424505 78.90 63.13 0.00926670 11.9 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 241.212 7204.69 86.18 0.01272586 70.04 44.99498340 24.0070 75.00 0.00817392 75.00 0.00817392 42.4721 4218.32 0.00 7498.54 5162.20 0.21616060 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR LIVING_UNIT2_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 16488.202 16488.202 187.424505 0.22619980 228.253 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 187.424505 0.22504831   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 3.8903 3.968582 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 16488.20 14549.49 1.0000 0.22504831 187.424505 48.26 43.87 0.00531036 5.4 122.00 74.22 0.00800000 17.0 0.23535302 140.00 120.20 19.80 0.000 16488.20 -26.9 0.00018338 -26.9 44.99498340 24.0070 71.99 0.00693003 71.99 0.00693003 39.9131 8368.32 0.00 14843.29 14843.29 0.22504831 61.88 50.75 0.00531036 7.2 137.48 76.11 0.00531036 17.4
DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11600.809 8421.191 313.552561 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 313.552561 0.37649545   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:40:00 Sensible 11679.86 9936.74 1.0068 0.37649545 313.552561 76.93 61.49 0.00861193 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 403.536 11276.33 79.93 0.01271977 68.19 44.99498340 14.3501 75.00 0.00792369 75.00 0.00792157 41.1763 7040.22 0.00 11605.65 8257.32 0.36162673 80.00 67.00 0.01118466 13.2 54.00 53.96 0.00883902 8.3
MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR LIVING_UNIT3_FRONTROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 24013.159 24013.159 313.552561 0.32943384 345.683 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 313.552561 0.37649545   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.6658 5.779780 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 24013.16 21189.65 1.0000 0.37649545 313.552561 57.81 49.79 0.00607768 7.1 122.00 74.22 0.00800000 17.0 0.34276444 140.00 120.20 19.80 0.000 24013.16 -26.9 0.00018338 -26.9 44.99498340 14.3501 71.99 0.00706523 71.99 0.00706523 40.6843 11522.90 0.00 23314.49 23314.49 0.37649545 61.88 52.20 0.00607768 7.7 132.76 75.77 0.00607768 17.2
DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14205.660 10393.300 390.794135 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 390.794135 0.46924259   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 Sensible 14289.48 12276.95 1.0059 0.46924259 390.794135 76.76 61.31 0.00853310 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 502.945 13786.53 79.71 0.01271956 68.12 44.99498340 11.5137 75.00 0.00798837 75.00 0.00797940 41.4738 8774.63 0.00 14211.59 10188.78 0.45071105 80.00 67.00 0.01118466 13.2 54.26 54.22 0.00892354 8.3
MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR LIVING_UNIT1_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 28621.396 28621.396 390.794135 0.39265373 417.207 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 390.794135 0.46924259   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 6.7530 6.888947 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28621.40 25256.05 1.0000 0.46924259 390.794135 60.61 51.36 0.00627260 7.6 122.00 74.22 0.00800000 17.0 0.40854254 140.00 120.20 19.80 0.000 28621.40 -26.9 0.00018338 -26.9 44.99498340 11.5137 71.99 0.00706493 71.99 0.00706493 40.6826 11518.44 0.00 28445.83 28445.83 0.46924259 61.88 52.57 0.00627260 7.8 131.24 75.60 0.00627260 17.1
DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 6720.592 4711.694 168.049821 -999. -999.00 -999.0000 1.00000 0.97038 0.2443 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 168.049821 0.20178433   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 7030.93 5209.67 1.0462 0.20178433 168.049821 76.55 62.95 0.00968704 11.8 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 216.277 6814.66 76.25 0.01271621 67.07 44.99498340 26.7748 75.00 0.00857943 75.00 0.00860988 44.7061 3759.11 0.00 6723.40 4628.57 0.19381538 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR LIVING_UNIT2_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 15332.328 15332.328 168.049821 0.21034249 210.026 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 168.049821 0.20178433   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 3.6176 3.690372 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 15332.33 13529.53 1.0000 0.20178433 168.049821 45.53 42.13 0.00512367 4.9 122.00 74.22 0.00800000 17.0 0.21885404 140.00 120.20 19.80 0.000 15332.33 -26.9 0.00018338 -26.9 44.99498340 26.7748 71.99 0.00693009 71.99 0.00693009 39.9135 8368.96 0.00 13520.10 13520.10 0.20178433 61.88 50.38 0.00512367 7.1 138.70 76.21 0.00512367 17.4
DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10413.213 7616.037 286.200499 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 286.200499 0.34365271   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:40:00 Sensible 10679.38 8918.98 1.0256 0.34365271 286.200499 76.45 61.50 0.00873019 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 368.335 10311.04 76.43 0.01271639 67.12 44.99498340 15.7215 75.00 0.00798659 75.00 0.00798258 41.4892 6426.28 0.00 10417.56 7466.00 0.33008103 80.00 67.00 0.01118466 13.2 54.25 54.20 0.00891937 8.3
MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR LIVING_UNIT3_BACKROW_BOTTOMFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 22381.334 22381.334 286.200499 0.30704701 320.315 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 286.200499 0.34365271   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.2807 5.387013 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 22381.33 19749.70 1.0000 0.34365271 286.200499 56.45 49.02 0.00598318 6.9 122.00 74.22 0.00800000 17.0 0.31947172 140.00 120.20 19.80 0.000 22381.33 -26.9 0.00018338 -26.9 44.99498340 15.7215 71.99 0.00706509 71.99 0.00706509 40.6835 11520.85 0.00 21490.67 21490.67 0.34365271 61.88 52.03 0.00598318 7.6 133.47 75.85 0.00598318 17.3
DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14737.921 10889.618 413.335819 -999. -999.00 -999.0000 1.00000 1.00000 0.2437 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 413.335819 0.49630932   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 14742.00 12948.28 1.0003 0.49630932 413.335819 76.79 61.08 0.00837401 11.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 531.956 14210.04 80.27 0.01272010 68.29 44.99498340 10.8858 75.00 0.00784311 75.00 0.00783698 40.7422 9293.46 0.00 14744.07 10673.47 0.47670885 80.00 67.00 0.01118466 13.2 54.51 54.49 0.00902145 8.4
MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR LIVING_UNIT1_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 29964.442 29964.442 413.335819 0.41107882 437.800 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 413.335819 0.49630932   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 7.0699 7.212208 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 29964.44 26441.18 1.0000 0.49630932 413.335819 61.24 52.47 0.00673912 8.0 122.00 74.22 0.00800000 17.0 0.42771320 140.00 120.20 19.80 0.000 29964.44 -26.9 0.00018338 -26.9 44.99498340 10.8858 72.00 0.00753994 72.00 0.00753994 43.3791 8114.65 0.00 29937.84 29937.84 0.49630932 61.88 53.42 0.00673912 8.1 130.84 76.03 0.00673912 17.4
DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7567.120 5305.181 189.217442 -999. -999.00 -999.0000 1.00000 0.93100 0.2440 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 189.217442 0.22720116   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 Sensible 7487.28 6080.83 0.9894 0.22720116 189.217442 78.88 62.83 0.00906505 11.8 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 243.519 7243.76 86.18 0.01272586 70.04 44.99498340 23.7795 75.00 0.00792294 75.00 0.00792294 41.1835 4258.81 0.00 7570.28 5211.58 0.21822844 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR LIVING_UNIT2_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 16594.449 16594.449 189.217442 0.22765738 229.759 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 189.217442 0.22720116   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 3.9154 3.994154 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 16594.45 14643.25 1.0000 0.22720116 189.217442 48.49 45.08 0.00583060 5.7 122.00 74.22 0.00800000 17.0 0.23686958 140.00 120.20 19.80 0.000 16594.45 -26.9 0.00018338 -26.9 44.99498340 23.7795 72.00 0.00759244 72.00 0.00759244 43.6761 4988.48 0.00 14964.91 14964.91 0.22720116 61.88 51.74 0.00583060 7.5 137.30 76.66 0.00583060 17.7
DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11648.394 8513.213 319.514728 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 319.514728 0.38365447   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 11667.48 10117.57 1.0016 0.38365447 319.514728 76.99 61.30 0.00847323 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 411.210 11256.27 80.49 0.01272031 68.36 44.99498340 14.0823 75.00 0.00777712 75.00 0.00777511 40.4239 7172.96 0.00 11653.25 8347.45 0.36850302 80.00 67.00 0.01118466 13.2 54.21 54.18 0.00891203 8.3
MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR LIVING_UNIT3_FRONTROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 24367.526 24367.526 319.514728 0.33429536 351.018 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 319.514728 0.38365447   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.7494 5.865074 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 24367.53 21502.35 1.0000 0.38365447 319.514728 58.08 50.71 0.00650401 7.4 122.00 74.22 0.00800000 17.0 0.34782269 140.00 120.20 19.80 0.000 24367.53 -26.9 0.00018338 -26.9 44.99498340 14.0823 72.00 0.00753999 72.00 0.00753999 43.3794 8115.62 0.00 23710.82 23710.82 0.38365447 61.88 52.99 0.00650401 7.9 132.56 76.21 0.00650401 17.5
DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 13902.822 10252.927 389.328589 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 389.328589 0.46748285   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 14000.48 12171.95 1.0070 0.46748285 389.328589 76.70 61.16 0.00844470 11.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 501.059 13499.42 79.15 0.01271901 67.95 44.99498340 11.5571 75.00 0.00788617 75.00 0.00787652 40.9453 8737.62 0.00 13908.62 10049.25 0.44902081 80.00 67.00 0.01118466 13.2 54.52 54.47 0.00900724 8.4
MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR LIVING_UNIT1_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 28532.286 28532.286 389.328589 0.39143123 415.628 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 389.328589 0.46748285   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 6.7320 6.867499 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 28532.29 25177.41 1.0000 0.46748285 389.328589 60.57 52.11 0.00668982 7.9 122.00 74.22 0.00800000 17.0 0.40727057 140.00 120.20 19.80 0.000 28532.29 -26.9 0.00018338 -26.9 44.99498340 11.5571 72.00 0.00754003 72.00 0.00754003 43.3796 8116.38 0.00 28347.89 28347.89 0.46748285 61.88 53.33 0.00668982 8.0 131.21 76.07 0.00668982 17.4
DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 6863.036 4811.559 171.611668 -999. -999.00 -999.0000 1.00000 0.99509 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 171.611668 0.20606119   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 7149.81 5432.18 1.0418 0.20606119 171.611668 76.55 62.65 0.00947768 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 220.861 6928.94 76.25 0.01271621 67.07 44.99498340 26.2191 75.00 0.00832682 75.00 0.00833928 43.3191 3848.00 0.00 6865.90 4726.67 0.19792333 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR LIVING_UNIT2_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 15544.193 15544.193 171.611668 0.21324905 213.215 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 171.611668 0.20606119   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 3.6676 3.741366 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 15544.19 13716.48 1.0000 0.20606119 171.611668 46.08 43.54 0.00564981 5.3 122.00 74.22 0.00800000 17.0 0.22187821 140.00 120.20 19.80 0.000 15544.19 -26.9 0.00018338 -26.9 44.99498340 26.2191 72.00 0.00759238 72.00 0.00759238 43.6758 4987.67 0.00 13763.67 13763.67 0.20606119 61.88 51.40 0.00564981 7.4 138.39 76.73 0.00564981 17.7
DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10419.938 7670.505 290.377605 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 290.377605 0.34866833   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 10628.00 9052.56 1.0200 0.34866833 290.377605 76.54 61.32 0.00858833 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 373.711 10254.29 77.07 0.01271700 67.32 44.99498340 15.4953 75.00 0.00783127 75.00 0.00781975 40.6530 6516.14 0.00 10424.29 7517.22 0.33489857 80.00 67.00 0.01118466 13.2 54.44 54.40 0.00898562 8.4
MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR LIVING_UNIT3_BACKROW_MIDDLEFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 22629.346 22629.346 290.377605 0.31044946 324.015 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 290.377605 0.34866833   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.3393 5.446707 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 22629.35 19968.55 1.0000 0.34866833 290.377605 56.68 49.92 0.00639992 7.2 122.00 74.22 0.00800000 17.0 0.32301185 140.00 120.20 19.80 0.000 22629.35 -26.9 0.00018338 -26.9 44.99498340 15.4953 72.00 0.00753982 72.00 0.00753982 43.3785 8112.29 0.00 21768.97 21768.97 0.34866833 61.88 52.80 0.00639992 7.9 133.30 76.28 0.00639992 17.5
DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 15199.691 11167.946 421.423236 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 421.423236 0.50602021   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:10:00 Sensible 15224.55 13223.39 1.0016 0.50602021 421.423236 76.78 61.20 0.00845442 11.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 542.364 14682.19 80.27 0.01272010 68.29 44.99498340 10.6769 75.00 0.00794453 75.00 0.00793948 41.2688 9469.09 0.00 15206.03 10949.71 0.48603624 80.00 67.00 0.01118466 13.2 54.35 54.33 0.00896616 8.4
MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR LIVING_UNIT1_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 30448.730 30448.730 421.423236 0.41772271 445.499 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 421.423236 0.50602021   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 7.1842 7.328772 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 30448.73 26868.52 1.0000 0.50602021 421.423236 61.44 51.84 0.00634463 7.8 122.00 74.22 0.00800000 17.0 0.43462594 140.00 120.20 19.80 0.000 30448.73 -26.9 0.00018338 -26.9 44.99498340 10.6769 71.99 0.00708110 71.99 0.00708110 40.7746 11761.95 0.00 30473.99 30473.99 0.50602021 61.88 52.70 0.00634463 7.8 130.78 75.56 0.00634463 17.1
DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7860.855 5511.113 196.562343 -999. -999.00 -999.0000 1.00000 0.99165 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 196.562343 0.23602049   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:50:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 14:40:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:00:00 Sensible 8132.77 6250.18 1.0346 0.23602049 196.562343 76.78 62.61 0.00939977 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 252.972 7879.79 77.48 0.01271739 67.44 44.99498340 22.8909 75.00 0.00841488 75.00 0.00814037 42.3000 4387.13 0.00 7864.13 5413.88 0.22669946 80.00 67.00 0.01118466 13.2 52.78 52.74 0.00844654 7.9
MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR LIVING_UNIT2_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 17033.357 17033.357 196.562343 0.23367871 236.808 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 196.562343 0.23602049   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 4.0189 4.099796 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 17033.36 15030.55 1.0000 0.23602049 196.562343 49.37 44.60 0.00540554 5.6 122.00 74.22 0.00800000 17.0 0.24313457 140.00 120.20 19.80 0.000 17033.36 -26.9 0.00018338 -26.9 44.99498340 22.8909 71.99 0.00695582 71.99 0.00695582 40.0600 8622.76 0.00 15464.00 15464.00 0.23602049 61.88 50.93 0.00540554 7.3 136.96 76.09 0.00540554 17.4
DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 11698.302 8477.346 314.696334 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 314.696334 0.37786883   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 11:00:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:50:00 Sensible 11746.01 10003.09 1.0041 0.37786883 314.696334 77.00 61.51 0.00860738 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 405.008 11341.00 80.49 0.01272031 68.36 44.99498340 14.2979 75.00 0.00792121 75.00 0.00791957 41.1661 7068.25 0.00 11703.18 8315.94 0.36294587 80.00 67.00 0.01118466 13.2 53.91 53.89 0.00882039 8.2
MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR LIVING_UNIT3_FRONTROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 24081.396 24081.396 314.696334 0.33036997 346.737 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 314.696334 0.37786883   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.6819 5.796204 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 24081.40 21249.87 1.0000 0.37786883 314.696334 57.86 49.85 0.00609465 7.1 122.00 74.22 0.00800000 17.0 0.34373846 140.00 120.20 19.80 0.000 24081.40 -26.9 0.00018338 -26.9 44.99498340 14.2979 71.99 0.00708084 71.99 0.00708084 40.7732 11758.10 0.00 23390.66 23390.66 0.37786883 61.88 52.23 0.00609465 7.7 132.73 75.78 0.00609465 17.2
DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 14800.848 10890.364 411.943096 -999. -999.00 -999.0000 1.00000 1.00000 0.2438 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 411.943096 0.49463702   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 18:30:00 Sensible 14915.80 12880.87 1.0078 0.49463702 411.943096 76.67 61.22 0.00849255 11.1 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 530.163 14385.64 79.15 0.01271901 67.95 44.99498340 10.9226 75.00 0.00797430 75.00 0.00796624 41.4063 9248.75 0.00 14807.02 10675.51 0.47510259 80.00 67.00 0.01118466 13.2 54.42 54.39 0.00898166 8.4
MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR LIVING_UNIT1_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 29883.144 29883.144 411.943096 0.40996350 436.742 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 411.943096 0.49463702   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 7.0507 7.192640 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 29883.14 26369.44 1.0000 0.49463702 411.943096 61.20 51.71 0.00632765 7.7 122.00 74.22 0.00800000 17.0 0.42655275 140.00 120.20 19.80 0.000 29883.14 -26.9 0.00018338 -26.9 44.99498340 10.9226 71.99 0.00708106 71.99 0.00708106 40.7744 11761.40 0.00 29846.53 29846.53 0.49463702 61.88 52.67 0.00632765 7.8 130.91 75.58 0.00632765 17.1
DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 7841.514 5515.522 197.111863 -999. -999.00 -999.0000 1.00000 1.00000 0.2442 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 197.111863 0.23668032   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 19:30:00 Sensible 8155.73 6250.28 1.0401 0.23668032 197.111863 76.50 62.52 0.00940393 11.7 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 253.679 7902.05 76.25 0.01271621 67.07 44.99498340 22.8271 75.00 0.00842419 75.00 0.00843918 43.8316 4423.19 0.00 7844.79 5417.22 0.22733324 80.00 67.00 0.01118466 13.2 52.85 52.83 0.00847945 7.9
MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR LIVING_UNIT2_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 17066.141 17066.141 197.111863 0.23412847 237.322 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 197.111863 0.23668032   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 4.0266 4.107687 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 17066.14 15059.48 1.0000 0.23668032 197.111863 49.43 44.64 0.00540968 5.6 122.00 74.22 0.00800000 17.0 0.24360253 140.00 120.20 19.80 0.000 17066.14 -26.9 0.00018338 -26.9 44.99498340 22.8271 71.99 0.00695558 71.99 0.00695558 40.0587 8620.40 0.00 15501.28 15501.28 0.23668032 61.88 50.94 0.00540968 7.3 136.93 76.09 0.00540968 17.4
DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Cooling:DX:SingleSpeed AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedCoolingCapacity N/A Yes Yes unknown No 10497.349 7660.690 286.790427 -999. -999.00 -999.0000 1.00000 1.00000 0.2439 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 286.790427 0.34436106   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:20:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 10:10:00 INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB 7/21 09:50:00 Sensible 10734.33 8973.10 1.0226 0.34436106 286.790427 76.54 61.53 0.00872760 11.2 53.60 50.67 0.00750000 7.4 -999. -999.0 -999.0 -999.0 369.094 10365.24 77.07 0.01271700 67.32 44.99498340 15.6892 75.00 0.00798523 75.00 0.00796873 41.4184 6425.98 0.00 10501.73 7512.88 0.33076140 80.00 67.00 0.01118466 13.2 54.14 54.12 0.00889547 8.3
MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR Coil:Heating:Water AirLoop AirLoopHVAC CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR LIVING_UNIT3_BACKROW_TOPFLOOR Non-Coincident FractionOfAutosizedHeatingCapacity N/A Yes Yes Yes No 22416.528 22416.528 286.790427 0.30752984 320.857 -999.0000 1.00000 1.00000 0.2436 0.2400 0.0720 SUPPLY FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 286.790427 0.34436106   1.0027 62.4216 5.93040614 159.80 179.60 19.80 423829.84 5.2890 5.395484 INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 unknown unknown INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB 1/21 15:00:00 Sensible 22416.53 19780.76 1.0000 0.34436106 286.790427 56.48 49.06 0.00599845 6.9 122.00 74.22 0.00800000 17.0 0.31997409 140.00 120.20 19.80 0.000 22416.53 -26.9 0.00018338 -26.9 44.99498340 15.6892 71.99 0.00708056 71.99 0.00708056 40.7716 11753.90 0.00 21530.06 21530.06 0.34436106 61.88 52.05 0.00599845 7.6 133.45 75.86 0.00599845 17.3
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.318 3264.099 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3318.223 3255.177 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.200 3263.983 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.471 3264.249 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3318.211 3255.165 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3284.400 3221.996 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_BOTTOMFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3379.263 3315.057 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3403.406 3338.742 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3379.009 3314.808 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3379.603 3315.390 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3403.396 3338.731 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3378.989 3314.788 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_MIDDLEFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.321 3264.102 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3318.160 3255.115 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.200 3263.984 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_FRONTROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.337 3264.118 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT1_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3318.160 3255.115 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT2_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.
HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR Coil:WaterHeating:AirToWaterHeatPump:Wrapped unknown unknown unknown N/A N/A N/A N/A No No unknown No 3327.272 3264.054 400.423678 -999. -999.00 -999.0000 1.00000 1.00000 0.2400 0.2400 0.0720 HEAT PUMP WATER HEATER FAN_UNIT3_BACKROW_TOPFLOOR Fan:OnOff 160.010573 0.19213128   -999.000 -999.000 -999. -999.0 -999.0 -999.0 -999.0 -999.000 -999. unknown unknown unknown unknown unknown unknown Sensible 3165.61 -999.0 1.0000 -999. -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999. -999. -999.0 -999.0 -999.0 0.000 3165.61 -999.0 -999. -999.0 -999. -999.000 -999.0 -999. -999.0 -999. -999.000 -999.0 0.00 -999.0 -999.0 -999. -999.0 -999.0 -999. -999. -999.0 -999.0 -999. -999.



Table of Contents

Report: System Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Economizer

High Limit Shutoff Control Minimum Outdoor Air [ft3/min] Maximum Outdoor Air [ft3/min] Return Air Temp Limit Return Air Enthalpy Limit Outdoor Air Temperature Limit [F] Outdoor Air Enthalpy Limit [F]
None              


Demand Controlled Ventilation using Controller:MechanicalVentilation

Controller:MechanicalVentilation Name Outdoor Air Per Person [ft3/min-person] Outdoor Air Per Area [ft3/min-ft2] Outdoor Air Per Zone [ft3/min] Outdoor Air ACH [ACH] Outdoor Air Method Outdoor Air Schedule Name Air Distribution Effectiveness in Cooling Mode Air Distribution Effectiveness in Heating Mode Air Distribution Effectiveness Schedule Name
None                    


Time Not Comfortable Based on Simple ASHRAE 55-2004

Winter Clothes [hr] Summer Clothes [hr] Summer or Winter Clothes [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2786.67 6478.83 1568.83
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1608.17 6599.00 798.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2804.00 6380.50 1533.83
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 3065.33 6744.00 2027.83
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2012.17 6935.00 1336.17
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2989.83 6659.00 1899.50
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2316.00 6249.00 1011.33
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1038.67 6381.17 205.67
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2384.17 6142.83 1012.17
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2662.83 6525.50 1543.50
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1158.33 6706.67 460.33
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2558.33 6429.50 1379.67
LIVING_UNIT3_BACKROW_TOPFLOOR 3081.83 6501.50 1843.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 2870.83 6299.83 1526.67
LIVING_UNIT1_FRONTROW_TOPFLOOR 2874.00 6399.00 1583.00
LIVING_UNIT2_BACKROW_TOPFLOOR 2068.17 6747.00 1256.83
LIVING_UNIT2_FRONTROW_TOPFLOOR 1670.33 6505.00 772.00
LIVING_UNIT1_BACKROW_TOPFLOOR 3107.17 6614.50 1950.17
CRAWLSPACE 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00
Facility 3975.33 7461.17 2337.17
Aggregated over the RunPeriods for Weather

Time Setpoint Not Met

During Heating [hr] During Cooling [hr] During Occupied Heating [hr] During Occupied Cooling [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 144.00 0.00 144.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 187.67 0.00 187.67 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 347.17 0.00 347.17 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 337.00 0.00 337.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 211.67 1.00 211.67 1.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 278.67 0.00 278.67 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 101.17 0.00 101.17 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 181.33 0.00 181.33 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 620.67 0.00 620.67 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 434.33 0.00 434.33 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 189.83 0.00 189.83 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 457.67 0.00 457.67 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 238.17 0.00 238.17 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 338.33 0.00 338.33 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 214.00 0.00 214.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 177.17 0.00 177.17 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 165.50 0.00 165.50 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 317.33 0.00 317.33 0.00
CRAWLSPACE 0.00 0.00 0.00 0.00
BREEZEWAY 0.00 0.00 0.00 0.00
ATTIC 0.00 0.00 0.00 0.00
Facility 2174.67 1.00 2174.67 1.00
Aggregated over the RunPeriods for Weather


Table of Contents

Report: Outdoor Air Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Average Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.140 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.123 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.269 0.140 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.139 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.123 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.268 0.139 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.061 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.045 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.061 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.061 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.044 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.269 0.061 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.140 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.140 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.140 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.123 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.269 0.123 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.268 0.140 0.000 0.000
Values shown for a single zone without multipliers

Minimum Outdoor Air During Occupied Hours

Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Mechanical Ventilation [ACH] Infiltration [ACH] AFN Infiltration [ACH] Simple Ventilation [ACH]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.258 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 0.260 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.257 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 0.260 0.000 0.000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 0.259 0.000 0.000 0.000
Values shown for a single zone without multipliers


Table of Contents

Report: Outdoor Air Details

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Mechanical Ventilation Parameters by Zone

AirLoop Name Average Number of Occupants Nominal Number of Occupants Zone Volume [ft3] Zone Area [ft2] Design Zone Outdoor Airflow - Voz [ft3/min] Minimum Dynamic Target Ventilation - Voz-dyn-min [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 1.38 2.00 10207.81 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 1.38 2.00 10207.71 1200.55 0.0000 0.000
Total Facility   24.79 36.00 183739.38 21609.96 0.0000 0.000


Total Outdoor Air by Zone

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Infiltration [ft3] Total Ventilation and Infiltration [ft3] Dynamic Target Ventilation - Voz-dyn [ft3] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr] Time Above Zero When Unoccupied [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 12386473.85 36171555.54 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10909455.40 34694537.09 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 12385480.95 36170562.64 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 12368713.68 36153795.37 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 10893885.74 34678967.43 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 23785081.69 0.00 23785081.69 12375625.29 36160706.98 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 5433899.24 29218980.93 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3953800.47 27738882.15 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 5431395.93 29216477.62 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 5423715.68 29208797.37 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 3947503.43 27732585.12 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 23785081.69 0.00 23785081.69 5426252.58 29211334.27 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 12389802.10 36174883.79 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 12397366.75 36182448.44 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 12395218.36 36180300.05 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 10907318.10 34692399.78 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 23785081.69 0.00 23785081.69 10919533.07 34704614.76 23785081.69 0.00 8808.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 23785081.69 0.00 23785081.69 12382274.94 36167356.62 23785081.69 0.00 8808.00 0.00 0.00
Total Facility 0.428131E+09 0.00 0.428131E+09 0.172328E+09 0.600459E+09 0.428131E+09 0.00 8808.00 0.00 0.00


Average Outdoor Air During Occupancy by Zone - Flow Rates

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Infiltration [ft3/min] Total Ventilation and Infiltration [ft3/min] Dynamic Target Ventilation - Voz-dyn [ft3/min] Time Below Voz-dyn [hr] Time At Voz-dyn [hr] Time Above Voz-dyn [hr]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 23.4319 68.4269 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 20.6378 65.6327 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 23.4300 68.4250 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 23.3983 68.3933 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 20.6083 65.6033 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 44.9950 0.0000 44.9950 23.4114 68.4063 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 10.2795 55.2745 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.4795 52.4745 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 10.2747 55.2697 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 10.2602 55.2552 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 7.4676 52.4626 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 44.9950 0.0000 44.9950 10.2650 55.2600 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 23.4382 68.4332 44.9950 0.00 8808.00 0.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 23.4525 68.4475 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 23.4484 68.4434 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 20.6337 65.6287 44.9950 0.00 8808.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 44.9950 0.0000 44.9950 20.6568 65.6518 44.9950 0.00 8808.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 44.9950 0.0000 44.9950 23.4239 68.4189 44.9950 0.00 8808.00 0.00
Total Facility 809.9097 0.0000 809.9097 325.9977 1135.9074 809.9097 0.00 8808.00 0.00


Total Outdoor Air by AirLoop

Mechanical Ventilation [ft3] Natural Ventilation [ft3] Total Ventilation [ft3] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr] Time Above Zero When Unoccupied [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 23785081.69 8808.00 0.00 0.00 0.00


Average Outdoor Air During Occupancy by AirLoop

Mechanical Ventilation [ft3/min] Natural Ventilation [ft3/min] Total Ventilation [ft3/min] Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [ft3/min] Time Below Voz-sum-dyn [hr] Time At Voz-sum-dyn [hr] Time Above Voz-sum-dyn [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 44.9950 8808.00 0.00 0.00


Outdoor Air Controller Limiting Factors by AirLoop

No Limiting Factor [hr] Limits and Scheduled Limits [hr] Economizer [hr] Exhaust Flow [hr] Mixed Air Flow [hr] High Humidity [hr] Demand Controlled Ventilation [hr] Night Ventilation [hr] Demand Limiting [hr] Energy Management System [hr]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


Average Outdoor Air for Limiting Factors During Occupancy

No Limiting Factor [ft3/min] Limits and Scheduled Limits [ft3/min] Economizer [ft3/min] Exhaust Flow [ft3/min] Mixed Air Flow [ft3/min] High Humidity [ft3/min] Demand Controlled Ventilation [ft3/min] Night Ventilation [ft3/min] Demand Limiting [ft3/min] Energy Management System [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000



Table of Contents

Report: Object Count Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Surfaces by Class

Total Outdoors
Wall 82 58
Floor 29 4
Roof 27 2
Internal Mass 0 0
Building Detached Shading 0 0
Fixed Detached Shading 0 0
Window 30 30
Door 18 18
Glass Door 0 0
Shading 60 60
Overhang 30 30
Fin 0 0
Tubular Daylighting Device Dome 0 0
Tubular Daylighting Device Diffuser 0 0


HVAC

Count
HVAC Air Loops 18
Conditioned Zones 18
Unconditioned Zones 3
Supply Plenums 0
Return Plenums 0


Input Fields

Count
IDF Objects 2091
Defaulted Fields 1871
Fields with Defaults 7584
Autosized Fields 400
Autosizable Fields 672
Autocalculated Fields 198
Autocalculatable Fields 422



Table of Contents

Report: Energy Meters

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Annual and Peak Values - Electricity

Electricity Annual Value [kWh] Electricity Minimum Value [W] Timestamp of Minimum {TIMESTAMP} Electricity Maximum Value [W] Timestamp of Maximum {TIMESTAMP}
Electricity:Facility 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
Electricity:Building 99639.89 6275.41 02-JAN-03:10 18829.48 01-JAN-18:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
Electricity:SpaceType:GENERAL 99639.89 6275.41 02-JAN-03:10 18829.48 01-JAN-18:10
InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
InteriorLights:Electricity:SpaceType:GENERAL 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
General:InteriorLights:Electricity 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:SpaceType:GENERAL 11336.81 253.88 01-JAN-00:10 3692.78 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 5535.55 348.63 02-JAN-03:10 1046.08 01-JAN-18:10
InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
General:InteriorLights:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 629.82 14.10 01-JAN-00:10 205.15 01-JAN-19:10
InteriorEquipment:Electricity 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
InteriorEquipment:Electricity:SpaceType:GENERAL 88303.07 5995.41 02-JAN-04:10 15497.32 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
dishwasher:InteriorEquipment:Electricity:SpaceType:GENERAL 3088.82 28.28 02-JAN-03:10 985.58 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
refrigerator:InteriorEquipment:Electricity:SpaceType:GENERAL 12036.11 1198.77 01-JAN-04:10 1639.04 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
clotheswasher:InteriorEquipment:Electricity:SpaceType:GENERAL 1577.30 15.15 02-JAN-02:10 427.18 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_dryer:InteriorEquipment:Electricity:SpaceType:GENERAL 12502.11 63.73 02-JAN-03:10 3196.73 01-JAN-11:10
electric_range:InteriorEquipment:Electricity 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
electric_range:InteriorEquipment:Electricity:SpaceType:GENERAL 9058.39 87.62 01-JAN-02:10 3721.08 01-JAN-17:10
television:InteriorEquipment:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
television:InteriorEquipment:Electricity:SpaceType:GENERAL 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
electric_mels:InteriorEquipment:Electricity:SpaceType:GENERAL 46926.68 4099.97 01-JAN-09:10 7929.96 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:SpaceType:GENERAL 3113.66 272.04 01-JAN-09:10 526.17 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 4905.73 333.08 02-JAN-04:10 860.96 01-JAN-18:10
dishwasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 171.60 1.57 02-JAN-03:10 54.75 01-JAN-19:10
refrigerator:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 668.67 66.60 01-JAN-04:10 91.06 01-JAN-18:10
clotheswasher:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 87.63 0.84 02-JAN-02:10 23.73 01-JAN-09:10
electric_dryer:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 694.56 3.54 02-JAN-03:10 177.60 01-JAN-11:10
electric_range:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 503.24 4.87 01-JAN-02:10 206.73 01-JAN-17:10
television:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
electric_mels:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 2607.04 227.78 01-JAN-09:10 440.55 01-JAN-20:10
IECC_adj:InteriorEquipment:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 172.98 15.11 01-JAN-09:10 29.23 01-JAN-20:10
Electricity:HVAC 25208.40 1350.00 18-APR-03:00 14927.64 29-JUN-18:10
Cooling:Electricity 8083.16 0.00 01-JAN-00:10 11790.28 29-JUN-18:10
General:Cooling:Electricity 8083.16 0.00 01-JAN-00:10 11790.28 29-JUN-18:10
Electricity:Plant 24206.35 149.40 01-JAN-00:10 9663.76 13-JUN-07:40
WaterSystems:Electricity 24206.35 149.40 01-JAN-00:10 9663.76 13-JUN-07:40
Fans:Electricity 17125.24 1350.00 18-APR-03:00 3137.37 29-JUN-18:10
General:Fans:Electricity 5299.23 0.00 18-APR-03:00 1787.37 29-JUN-18:10
Ventilation:Fans:Electricity 11826.01 1350.00 01-JAN-00:10 1350.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Ventilation (simple):Fans:Electricity:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityPurchased:Facility 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
ElectricityPurchased:Plant 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
Cogeneration:ElectricityPurchased 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
General:Cogeneration:ElectricityPurchased 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
ElectricitySurplusSold:Facility 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricitySurplusSold:Plant 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cogeneration:ElectricitySurplusSold 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ElectricityNet:Facility 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
ElectricityNet:Plant 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
Cogeneration:ElectricityNet 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
General:Cogeneration:ElectricityNet 155088.95 9152.51 05-MAY-03:40 36321.45 30-JUN-18:10
HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:HeatRecovery:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Exterior-Lights:ExteriorLights:Electricity 6034.31 0.00 01-JAN-06:10 1377.69 01-JAN-00:10
Garage-Lights:ExteriorLights:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Boiler Parasitic:Heating:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:Electricity 1308.75 149.40 20-MAR-09:40 149.40 01-JAN-00:30
Water Heater Parasitic:WaterSystems:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Pumps:Electricity 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Natural Gas

Natural Gas Annual Value [therm] Natural Gas Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Natural Gas Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
NaturalGas:Facility 4449.03 0.00 26-MAR-14:50 276491.03 06-JAN-08:10
NaturalGas:Plant 4449.03 0.00 26-MAR-14:50 276491.03 06-JAN-08:10
Heating:NaturalGas 4449.03 0.00 26-MAR-14:50 276491.03 06-JAN-08:10
Boiler:Heating:NaturalGas 4449.03 0.00 26-MAR-14:50 276491.03 06-JAN-08:10


Annual and Peak Values - Cooling

Cooling Annual Value [ton-hrs] Cooling Minimum Value [ton] Timestamp of Minimum {TIMESTAMP} Cooling Maximum Value [ton] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Water

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
Water:Facility 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Water:Plant 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Domestic Hot Water:WaterSystems:Water 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
MainsWater:Facility 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
MainsWater:Plant 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Domestic Hot Water:WaterSystems:MainsWater 41747.51 0.01 02-JAN-02:10 0.15 25-FEB-08:20
Water Heater:WaterSystems:Water 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Water Heater:WaterSystems:MainsWater 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10


Annual and Peak Values - Other by Weight/Mass

Annual Value [lb] Minimum Value [lb/s] Timestamp of Minimum {TIMESTAMP} Maximum Value [lb/s] Timestamp of Maximum {TIMESTAMP}
Carbon Equivalent:Facility 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10
CarbonEquivalentEmissions:Carbon Equivalent 0.00 0.000 01-JAN-00:10 0.000 01-JAN-00:10


Annual and Peak Values - Other Volumetric

Annual Value [ft3] Minimum Value [ft3/min] Timestamp of Minimum {TIMESTAMP} Maximum Value [ft3/min] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other Liquid/Gas

Annual Value [gal] Minimum Value [gal] Timestamp of Minimum {TIMESTAMP} Maximum Value [gal] Timestamp of Maximum {TIMESTAMP}
None          


Annual and Peak Values - Other

Annual Value [kBtu] Minimum Value [Btu/h] Timestamp of Minimum {TIMESTAMP} Maximum Value [Btu/h] Timestamp of Maximum {TIMESTAMP}
EnergyTransfer:Facility 1680586.50 13075.70 01-JUN-03:00 730286.14 06-JAN-08:10
EnergyTransfer:HVAC 787740.11 5042.74 01-NOV-12:30 321399.87 06-JAN-06:30
CoolingCoils:EnergyTransfer 261645.78 0.00 01-JAN-00:10 170329.25 29-JUN-18:10
EnergyTransfer:Building 405617.90 676.33 01-NOV-12:30 165179.66 06-JAN-05:00
EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer 240599.17 0.00 26-MAR-19:20 165179.66 06-JAN-05:00
Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer 240599.17 0.00 26-MAR-19:20 165179.66 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer 165018.72 0.00 01-JAN-00:10 122126.31 30-JUN-18:10
Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer 165018.72 0.00 01-JAN-00:10 122126.31 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:CRAWLSPACE 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:BREEZEWAY 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 26214.15 0.45 10-MAY-09:50 11347.32 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 16133.73 0.00 17-JAN-15:30 11347.32 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 16133.73 0.00 17-JAN-15:30 11347.32 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10080.41 0.00 01-JAN-00:10 10186.69 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 10080.41 0.00 01-JAN-00:10 10186.69 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 18198.60 1.80 18-NOV-12:50 8098.17 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10277.40 0.00 17-JAN-15:30 8098.17 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 10277.40 0.00 17-JAN-15:30 8098.17 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7921.20 0.00 01-JAN-00:10 5041.05 01-SEP-13:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 7921.20 0.00 01-JAN-00:10 5041.05 01-SEP-13:30
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 25994.94 0.57 31-MAR-23:00 11377.14 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15998.69 0.00 17-JAN-16:00 11377.14 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 15998.69 0.00 17-JAN-16:00 11377.14 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9996.25 0.00 01-JAN-00:10 7597.17 29-JUL-10:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 9996.25 0.00 01-JAN-00:10 7597.17 29-JUL-10:20
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 26954.78 0.13 07-SEP-04:40 12965.47 18-MAR-12:40
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18731.54 0.00 04-FEB-16:10 12965.47 18-MAR-12:40
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 18731.54 0.00 04-FEB-16:10 12965.47 18-MAR-12:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8223.24 0.00 01-JAN-00:10 9988.59 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_BOTTOMFLOOR 8223.24 0.00 01-JAN-00:10 9988.59 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 18837.05 0.11 22-OCT-14:50 8246.13 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12840.87 0.00 08-FEB-16:40 8246.13 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 12840.87 0.00 08-FEB-16:40 8246.13 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5996.18 0.00 01-JAN-00:10 4977.76 29-JUN-19:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_BOTTOMFLOOR 5996.18 0.00 01-JAN-00:10 4977.76 29-JUN-19:20
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 26396.92 0.11 21-OCT-13:10 11662.50 09-JAN-07:40
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18501.78 0.00 20-MAR-09:50 11662.50 09-JAN-07:40
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 18501.78 0.00 20-MAR-09:50 11662.50 09-JAN-07:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7895.14 0.00 01-JAN-00:10 6941.05 29-JUL-09:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_BOTTOMFLOOR 7895.14 0.00 01-JAN-00:10 6941.05 29-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 21205.21 0.28 28-OCT-16:20 10034.12 30-JUN-18:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9526.56 0.00 09-JAN-14:20 7718.59 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 9526.56 0.00 09-JAN-14:20 7718.59 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11678.65 0.00 01-JAN-00:10 10034.12 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 11678.65 0.00 01-JAN-00:10 10034.12 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 14537.54 0.09 02-JAN-13:20 5967.00 14-MAR-17:40
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4431.83 0.00 01-JAN-13:30 4544.33 14-MAR-17:40
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 4431.83 0.00 01-JAN-13:30 4544.33 14-MAR-17:40
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10105.71 0.00 01-JAN-00:10 5147.20 01-SEP-13:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 10105.71 0.00 01-JAN-00:10 5147.20 01-SEP-13:40
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 21610.92 0.01 14-OCT-00:40 7773.88 31-DEC-21:20
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9597.29 0.00 01-JAN-12:40 7738.87 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 9597.29 0.00 01-JAN-12:40 7738.87 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12013.63 0.00 01-JAN-00:10 7736.09 29-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 12013.63 0.00 01-JAN-00:10 7736.09 29-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 21360.34 0.60 13-SEP-11:50 10794.59 18-MAR-13:10
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11635.96 0.00 17-JAN-15:40 10491.27 18-MAR-13:10
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 11635.96 0.00 17-JAN-15:40 10491.27 18-MAR-13:10
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9724.37 0.00 01-JAN-00:10 9785.23 30-JUN-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_MIDDLEFLOOR 9724.37 0.00 01-JAN-00:10 9785.23 30-JUN-18:20
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 13868.76 0.09 12-APR-04:40 6228.87 01-FEB-18:20
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6195.97 0.00 16-JAN-20:50 5935.28 04-APR-18:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 6195.97 0.00 16-JAN-20:50 5935.28 04-APR-18:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7672.80 0.00 01-JAN-00:10 4533.66 30-JUN-19:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_MIDDLEFLOOR 7672.80 0.00 01-JAN-00:10 4533.66 30-JUN-19:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 21091.45 0.03 27-OCT-23:40 7853.20 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11509.49 0.00 16-JAN-18:30 7853.20 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 11509.49 0.00 16-JAN-18:30 7853.20 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9581.96 0.00 01-JAN-00:10 6958.83 29-JUL-09:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_MIDDLEFLOOR 9581.96 0.00 01-JAN-00:10 6958.83 29-JUL-09:00
EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Heating:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
General:Cooling:EnergyTransfer:Zone:ATTIC 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10
EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 27534.00 0.12 21-OCT-13:00 11608.61 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18810.88 0.00 28-FEB-22:50 11608.61 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 18810.88 0.00 28-FEB-22:50 11608.61 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8723.12 0.00 01-JAN-00:10 6910.37 29-JUL-09:00
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_BACKROW_TOPFLOOR 8723.12 0.00 01-JAN-00:10 6910.37 29-JUL-09:00
EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 27044.34 0.58 02-APR-11:40 11515.62 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 16633.95 0.00 04-FEB-12:50 11515.62 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 16633.95 0.00 04-FEB-12:50 11515.62 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10410.39 0.00 01-JAN-00:10 7614.61 29-JUL-10:30
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT3_FRONTROW_TOPFLOOR 10410.39 0.00 01-JAN-00:10 7614.61 29-JUL-10:30
EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 27399.06 0.84 10-MAY-09:40 11502.00 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 16802.06 0.00 04-FEB-13:30 11502.00 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 16802.06 0.00 04-FEB-13:30 11502.00 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10597.00 0.00 01-JAN-00:10 10421.39 30-JUN-18:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_FRONTROW_TOPFLOOR 10597.00 0.00 01-JAN-00:10 10421.39 30-JUN-18:10
EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 19991.77 0.01 15-SEP-15:10 8374.31 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 13089.82 0.00 20-FEB-16:10 8374.31 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 13089.82 0.00 20-FEB-16:10 8374.31 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6901.95 0.00 01-JAN-00:10 5155.47 30-JUN-19:10
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_BACKROW_TOPFLOOR 6901.95 0.00 01-JAN-00:10 5155.47 30-JUN-19:10
EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 19323.03 0.05 20-SEP-16:30 8262.95 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10847.12 0.00 04-FEB-12:50 8262.95 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 10847.12 0.00 04-FEB-12:50 8262.95 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 8475.92 0.00 01-JAN-00:10 5125.50 29-JUN-18:40
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT2_FRONTROW_TOPFLOOR 8475.92 0.00 01-JAN-00:10 5125.50 29-JUN-18:40
EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 28055.03 0.47 14-SEP-13:10 11600.22 06-JAN-05:00
Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 19034.22 0.00 08-FEB-12:00 11600.22 06-JAN-05:00
General:Heating:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 19034.22 0.00 08-FEB-12:00 11600.22 06-JAN-05:00
Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9020.81 0.00 01-JAN-00:10 10399.01 30-JUN-18:20
General:Cooling:EnergyTransfer:Zone:LIVING_UNIT1_BACKROW_TOPFLOOR 9020.81 0.00 01-JAN-00:10 10399.01 30-JUN-18:20
PlantLoopHeatingDemand:Facility 486831.20 935.92 18-AUG-03:00 253427.68 09-JAN-08:10
PlantLoopHeatingDemand:Plant 131305.87 932.99 21-SEP-03:00 34601.46 26-FEB-09:00
WaterSystems:PlantLoopHeatingDemand 131305.87 932.99 21-SEP-03:00 34601.46 26-FEB-09:00
General:WaterSystems:PlantLoopHeatingDemand 131305.87 932.99 21-SEP-03:00 34601.46 26-FEB-09:00
HeatRecoveryForHeating:EnergyTransfer 169418.83 0.00 23-APR-13:50 56817.83 06-JAN-09:00
HeatRecoveryForCooling:EnergyTransfer 1150.16 0.00 01-JAN-00:10 11126.90 29-JUN-16:00
HeatingCoils:EnergyTransfer 355525.33 0.00 26-MAR-14:50 222345.59 09-JAN-08:10
PlantLoopHeatingDemand:HVAC 355525.33 0.00 26-MAR-14:50 222345.59 09-JAN-08:10
HeatingCoils:PlantLoopHeatingDemand 355525.33 0.00 26-MAR-14:50 222345.59 09-JAN-08:10
EnergyTransfer:Plant 487228.49 935.92 18-AUG-03:00 251873.90 06-JAN-08:10
WaterSystems:EnergyTransfer 131305.87 932.99 21-SEP-03:00 34601.46 26-FEB-09:00
Domestic Hot Water:WaterSystems:EnergyTransfer 131305.87 932.99 21-SEP-03:00 34601.46 26-FEB-09:00
Boilers:EnergyTransfer 355922.63 0.00 26-MAR-14:50 221192.83 06-JAN-08:10
Water Heater:WaterSystems:PlantLoopHeatingDemand 0.00 0.00 01-JAN-00:10 0.00 01-JAN-00:10



Table of Contents

Report: Sensible Heat Gain Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Annual Building Sensible Heat Gain Components

HVAC Zone Eq & Other Sensible Air Heating [kBtu] HVAC Zone Eq & Other Sensible Air Cooling [ton-hrs] HVAC Terminal Unit Sensible Air Heating [kBtu] HVAC Terminal Unit Sensible Air Cooling [ton-hrs] HVAC Input Heated Surface Heating [kBtu] HVAC Input Cooled Surface Cooling [ton-hrs] People Sensible Heat Addition [kBtu] Lights Sensible Heat Addition [kBtu] Equipment Sensible Heat Addition [kBtu] Window Heat Addition [kBtu] Interzone Air Transfer Heat Addition [kBtu] Infiltration Heat Addition [kBtu] Opaque Surface Conduction and Other Heat Addition [kBtu] Equipment Sensible Heat Removal [kBtu] Window Heat Removal [kBtu] Interzone Air Transfer Heat Removal [kBtu] Infiltration Heat Removal [kBtu] Opaque Surface Conduction and Other Heat Removal [kBtu]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 95.035 -901.90 23403.624 -550.91 0.000 0.000 3072.667 2150.478 10464.601 8934.369 0.000 37.034 0.000 0.000 -8526.24 0.000 -8949.36 -13236.91
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 95.557 -900.87 17271.112 -349.17 0.000 0.000 3067.758 2150.478 10464.601 4469.644 0.000 32.728 0.000 0.000 -3395.75 0.000 -7883.49 -11262.19
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 94.727 -903.03 22973.461 -518.17 0.000 0.000 3078.622 2150.478 10464.601 8805.130 0.000 36.925 0.000 0.000 -8361.45 0.000 -8942.82 -13233.90
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 95.579 -897.69 26257.698 -421.83 0.000 0.000 3082.357 2150.478 10464.601 5753.815 0.000 37.320 0.000 0.000 -9141.97 0.000 -8906.92 -13948.03
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 95.994 -895.78 20407.966 -241.73 0.000 0.000 3079.556 2150.478 10464.601 1059.520 0.000 33.657 0.000 0.000 -3884.88 0.000 -7853.08 -11894.55
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 94.953 -900.08 26022.468 -391.62 0.000 0.000 3084.365 2150.478 10464.601 5561.987 0.000 37.058 0.000 0.000 -8938.17 0.000 -8922.91 -14044.03
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 94.931 -907.73 16244.102 -632.16 0.000 0.000 3055.824 2150.478 10464.601 8840.330 0.000 16.098 0.000 0.000 -8727.09 0.000 -3939.48 -9708.71
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 94.824 -908.69 10372.988 -435.56 0.000 0.000 3048.149 2150.478 10464.601 4422.952 0.000 11.751 0.000 0.000 -3475.97 0.000 -2868.91 -8079.19
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 94.540 -908.47 15691.448 -607.38 0.000 0.000 3067.507 2150.478 10464.601 8712.648 0.000 16.069 0.000 0.000 -8543.72 0.000 -3929.71 -9521.51
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 95.046 -902.57 18549.086 -490.87 0.000 0.000 3070.504 2150.478 10464.601 5690.825 0.000 16.188 0.000 0.000 -9348.20 0.000 -3912.69 -10043.34
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 95.447 -903.44 13007.673 -310.74 0.000 0.000 3062.461 2150.478 10464.601 1039.907 0.000 11.996 0.000 0.000 -3976.66 0.000 -2854.65 -8421.32
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 95.156 -905.06 18311.271 -467.26 0.000 0.000 3074.918 2150.478 10464.601 5498.962 0.000 16.107 0.000 0.000 -9133.83 0.000 -3919.22 -10079.53
LIVING_UNIT3_BACKROW_TOPFLOOR 95.094 -902.76 26287.833 -454.27 0.000 0.000 3077.946 2150.478 10464.601 5505.049 0.000 36.576 0.000 0.000 -9115.42 0.000 -8951.30 -13255.67
LIVING_UNIT3_FRONTROW_TOPFLOOR 94.780 -904.90 23625.750 -552.21 0.000 0.000 3073.775 2150.478 10464.601 8729.193 0.000 36.475 0.000 0.000 -8511.49 0.000 -8966.27 -13200.29
LIVING_UNIT1_FRONTROW_TOPFLOOR 95.121 -902.82 23916.564 -580.07 0.000 0.000 3069.974 2150.478 10464.601 8857.972 0.000 36.555 0.000 0.000 -8682.28 0.000 -8965.70 -13136.70
LIVING_UNIT2_BACKROW_TOPFLOOR 95.945 -899.27 20583.323 -307.54 0.000 0.000 3072.360 2150.478 10464.601 1043.040 0.000 32.924 0.000 0.000 -3962.49 0.000 -7880.80 -11108.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 95.326 -903.06 17823.943 -391.74 0.000 0.000 3063.424 2150.478 10464.601 4428.711 0.000 32.330 0.000 0.000 -3454.65 0.000 -7904.27 -11151.83
LIVING_UNIT1_BACKROW_TOPFLOOR 95.505 -899.84 26509.479 -481.87 0.000 0.000 3076.451 2150.478 10464.601 5693.034 0.000 36.806 0.000 0.000 -9328.13 0.000 -8936.53 -13170.16
CRAWLSPACE 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 12395.321 384430.552 0.000 0.000 0.000 -396825.87 0.000
BREEZEWAY 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000
ATTIC 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 0.000 19705.050 110768.953 0.000 0.000 0.000 -130474.00 -0.84
Total Facility 1713.562 -16247.94 367259.789 -8185.12 0.000 0.000 55278.619 38708.604 188362.826 103047.088 0.000 32614.968 495199.505 0.000 -128508.40 0.000 -651787.98 -208496.69


Peak Cooling Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 30-JUN-18:10 0.00 -0.2 0.00 -0.6 0.00 0.00 426.77 631.63 1724.99 6748.96 0.00 219.89 435.71 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 01-SEP-13:30 0.00 0.01 0.00 -0.4 0.00 0.00 115.09 90.23 1084.63 4112.80 0.00 23.55 0.00 0.00 0.00 0.00 0.00 -385.9
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 29-JUL-10:25 0.00 -0.2 0.00 -0.4 0.00 0.00 115.09 90.23 1121.12 7084.60 0.00 87.99 0.00 0.00 0.00 0.00 0.00 -901.3
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 30-JUN-18:10 0.00 -0.2 0.00 -0.6 0.00 0.00 426.77 631.63 1724.99 7317.80 0.00 219.89 0.00 0.00 0.00 0.00 0.00 -332.1
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 29-JUN-19:19 0.00 -0.2 0.00 -0.3 0.00 0.00 417.94 699.99 1664.78 393.90 0.00 223.65 3075.28 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 29-JUL-08:03 0.00 0.01 0.00 -0.6 0.00 0.00 194.42 132.34 1179.68 7066.21 0.00 36.94 0.00 0.00 0.00 0.00 0.00 -1667.1
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 30-JUN-18:15 0.00 0.03 0.00 -0.9 0.00 0.00 426.75 631.63 1724.99 6734.28 0.00 95.99 421.09 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 01-SEP-13:39 0.00 0.01 0.00 -0.4 0.00 0.00 115.09 90.23 1084.63 3918.20 0.00 10.41 0.00 0.00 0.00 0.00 0.00 -71.9
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 29-JUL-10:30 0.00 -0.2 0.00 -0.4 0.00 0.00 115.09 90.23 1121.12 6886.11 0.00 38.06 0.00 0.00 0.00 0.00 0.00 -511.6
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 30-JUN-18:24 0.00 0.02 0.00 -0.8 0.00 0.00 426.76 631.63 1724.99 7160.06 0.00 87.02 0.00 0.00 0.00 0.00 0.00 -244.0
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 30-JUN-19:15 0.00 0.02 0.00 -0.4 0.00 0.00 426.76 699.99 1664.78 1093.35 0.00 31.61 617.91 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 29-JUL-08:03 0.00 0.01 0.00 -0.6 0.00 0.00 194.42 132.34 1179.68 7052.38 0.00 16.01 0.00 0.00 0.00 0.00 0.00 -1614.6
LIVING_UNIT3_BACKROW_TOPFLOOR 29-JUL-08:03 0.00 0.01 0.00 -0.6 0.00 0.00 194.42 132.34 1179.68 7046.19 0.00 36.16 0.00 0.00 0.00 0.00 0.00 -1676.9
LIVING_UNIT3_FRONTROW_TOPFLOOR 29-JUL-10:35 0.00 0.02 0.00 -0.7 0.00 0.00 115.09 90.23 1121.12 6879.72 0.00 86.41 0.00 0.00 0.00 0.00 0.00 -676.6
LIVING_UNIT1_FRONTROW_TOPFLOOR 30-JUN-18:10 0.00 -0.2 0.00 -0.7 0.00 0.00 426.77 631.63 1724.99 6720.46 0.00 218.50 700.11 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_BACKROW_TOPFLOOR 30-JUN-19:15 0.00 0.02 0.00 -0.4 0.00 0.00 426.76 699.99 1664.78 1087.84 0.00 86.91 1190.14 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 29-JUN-18:45 0.00 -0.2 0.00 -0.2 0.00 0.00 425.36 631.63 1724.99 436.64 0.00 286.95 1823.67 0.00 0.00 0.00 0.00 0.00
LIVING_UNIT1_BACKROW_TOPFLOOR 30-JUN-18:24 0.00 0.02 0.00 -0.9 0.00 0.00 426.76 631.63 1724.99 7140.48 0.00 198.03 277.04 0.00 0.00 0.00 0.00 0.00
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 30-JUN-18:15 0.00 -0.6 0.00 -9.6 0.00 0.00 7681.74 11369.32 31049.73 54334.65 0.00 28436.52 25766.04 0.00 0.00 0.00 -36496.5 0.00


Peak Heating Sensible Heat Gain Components

Time of Peak {TIMESTAMP} HVAC Zone Eq & Other Sensible Air Heating [Btu/h] HVAC Zone Eq & Other Sensible Air Cooling [ton] HVAC Terminal Unit Sensible Air Heating [Btu/h] HVAC Terminal Unit Sensible Air Cooling [ton] HVAC Input Heated Surface Heating [Btu/h] HVAC Input Cooled Surface Cooling [ton] People Sensible Heat Addition [Btu/h] Lights Sensible Heat Addition [Btu/h] Equipment Sensible Heat Addition [Btu/h] Window Heat Addition [Btu/h] Interzone Air Transfer Heat Addition [Btu/h] Infiltration Heat Addition [Btu/h] Opaque Surface Conduction and Other Heat Addition [Btu/h] Equipment Sensible Heat Removal [Btu/h] Window Heat Removal [Btu/h] Interzone Air Transfer Heat Removal [Btu/h] Infiltration Heat Removal [Btu/h] Opaque Surface Conduction and Other Heat Removal [Btu/h]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 19-APR-08:50 -454.2 0.00 15551.81 0.00 0.00 0.00 233.11 132.34 1155.86 1267.04 0.00 0.00 0.00 0.00 0.00 0.00 -1509.3 -16376.6
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 15-MAR-17:40 -944.3 0.00 12821.50 0.00 0.00 0.00 314.45 469.21 1664.02 0.00 0.00 0.00 0.00 0.00 -562.6 0.00 -1734.6 -12027.7
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 13-APR-03:20 -604.4 0.00 12363.97 0.00 0.00 0.00 582.25 48.12 847.43 0.00 0.00 0.00 0.00 0.00 -1780.6 0.00 -926.3 -10530.4
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 12-MAR-13:06 -882.7 0.00 20260.97 0.00 0.00 0.00 135.62 90.23 1109.73 2230.13 0.00 0.00 0.00 0.00 0.00 0.00 -1452.1 -21491.9
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 06-MAR-15:46 -846.0 0.00 10478.14 0.00 0.00 0.00 127.29 156.40 1147.45 0.00 0.00 0.00 0.00 0.00 -584.7 0.00 -1747.6 -8731.0
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 04-JAN-08:39 -1399.9 0.00 13122.52 0.00 0.00 0.00 219.65 132.34 1155.86 0.00 0.00 0.00 0.00 0.00 -1970.8 0.00 -3953.4 -7306.3
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 06-APR-08:52 -3506.8 0.00 16540.86 0.00 0.00 0.00 232.47 132.34 1155.86 1436.22 0.00 0.00 0.00 0.00 0.00 0.00 -447.4 -15543.5
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 17-JAN-16:53 -710.5 0.00 11708.90 0.00 0.00 0.00 166.36 336.87 1350.56 0.00 0.00 0.00 0.00 0.00 -797.7 0.00 -383.3 -11671.1
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 27-FEB-21:10 -935.5 0.00 14397.75 0.00 0.00 0.00 560.35 529.36 1555.17 0.00 0.00 0.00 0.00 0.00 -2487.2 0.00 -805.8 -12814.1
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 12-MAR-11:50 -859.2 0.00 21785.45 0.00 0.00 0.00 149.01 90.23 1122.49 0.00 0.00 0.00 0.00 0.00 -449.5 0.00 -609.5 -21229.0
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 10-DEC-14:36 -1211.3 0.00 11588.32 0.00 0.00 0.00 127.38 90.23 1113.97 0.00 0.00 0.00 0.00 0.00 -1088.5 0.00 -967.1 -9653.1
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 05-OCT-23:27 -642.5 0.00 11355.40 0.00 0.00 0.00 565.46 120.31 1150.48 0.00 0.00 0.00 0.00 0.00 -1771.6 0.00 -443.7 -10333.9
LIVING_UNIT3_BACKROW_TOPFLOOR 06-JAN-04:00 -1557.8 0.00 13166.57 0.00 0.00 0.00 526.24 144.37 831.88 0.00 0.00 0.00 0.00 0.00 -3990.6 0.00 -4192.7 -4928.0
LIVING_UNIT3_FRONTROW_TOPFLOOR 22-APR-02:49 -643.2 0.00 12443.81 0.00 0.00 0.00 556.38 48.12 868.18 0.00 0.00 0.00 0.00 0.00 -1745.1 0.00 -955.7 -10572.6
LIVING_UNIT1_FRONTROW_TOPFLOOR 23-MAR-08:08 -834.8 0.00 19820.42 0.00 0.00 0.00 217.01 132.34 1155.86 995.98 0.00 0.00 0.00 0.00 0.00 0.00 -1465.1 -20021.8
LIVING_UNIT2_BACKROW_TOPFLOOR 23-MAR-18:53 -560.0 0.00 11383.44 0.00 0.00 0.00 511.30 631.63 1724.99 0.00 0.00 0.00 0.00 0.00 -683.8 0.00 -909.8 -12097.7
LIVING_UNIT2_FRONTROW_TOPFLOOR 06-MAR-17:49 -903.1 0.00 13451.33 0.00 0.00 0.00 309.50 469.21 1664.02 0.00 0.00 0.00 0.00 0.00 -801.8 0.00 -1676.0 -12513.2
LIVING_UNIT1_BACKROW_TOPFLOOR 17-MAR-12:15 -800.0 0.00 19593.97 0.00 0.00 0.00 150.63 90.23 1090.63 0.00 0.00 0.00 0.00 0.00 -19.1 0.00 -1133.9 -18972.5
CRAWLSPACE - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
BREEZEWAY - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
ATTIC - 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Total Facility 06-JAN-04:00 -28047.2 0.00 193231.54 0.00 0.00 0.00 9472.26 2598.70 14973.78 0.00 0.00 11881.67 91241.26 0.00 -57472.4 0.00 -237879.6 0.00



Table of Contents

Report: Standard 62.1 Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

System Ventilation Requirements for Cooling

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow - Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.0821 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 415.0821 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.4245 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 187.4245 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.5526 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 313.5526 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.7941 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 390.7941 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.0498 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 168.0498 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.2005 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.2005 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.3358 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 413.3358 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.2174 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 189.2174 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.5147 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 319.5147 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.3286 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 389.3286 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.6117 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 171.6117 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.3776 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 290.3776 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.4232 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 421.4232 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.5623 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 196.5623 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.6963 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 314.6963 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.9431 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 411.9431 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.1119 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 197.1119 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.7904 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.7904 0.0000 1.0000 Not calculated 0.0000 0.0000    


System Ventilation Requirements for Heating

Sum of Zone Primary Air Flow - Vpz-sum [ft3/min] System Population - Ps Sum of Zone Population - Pz-sum Occupant Diversity - D Origin of D Uncorrected Outdoor Air Intake Airflow - Vou [ft3/min] System Primary Airflow - Vps [ft3/min] Average Outdoor Air Fraction - Xs System Ventilation Efficiency - Ev Calculation Method for Ev Outdoor Air Intake Flow Vot [ft3/min] Percent Outdoor Air - %OA Environment Name of Peak System Population - Ps Date and Time of Last Peak System Population - Ps
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.0821 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 415.0821 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.4245 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 187.4245 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.5526 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 313.5526 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.7941 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 390.7941 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.0498 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 168.0498 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.2005 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.2005 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.3358 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 413.3358 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.2174 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 189.2174 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.5147 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 319.5147 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.3286 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 389.3286 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.6117 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 171.6117 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.3776 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 290.3776 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.4232 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 421.4232 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.5623 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 196.5623 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.6963 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 314.6963 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.9431 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 411.9431 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.1119 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 197.1119 0.0000 1.0000 Not calculated 0.0000 0.0000    
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.7904 0.0000 2.0000 1.0000 Calculated from schedules 0.0000 286.7904 0.0000 1.0000 Not calculated 0.0000 0.0000    


Zone Ventilation Parameters

AirLoop Name People Outdoor Air Rate - Rp [ft3/min-person] Zone Population - Pz Area Outdoor Air Rate - Ra [ft3/min-ft2] Zone Floor Area - Az [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Air Distribution Effectiveness - Ez-clg Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Air Distribution Effectiveness - Ez-htg Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.0000 0.000000 1200.55 0.0000 1.0000 0.0000 1.000 0.0000


System Ventilation Parameters

People Outdoor Air Rate - Rp [ft3/min-person] Sum of Zone Population - Pz-sum Area Outdoor Air Rate - Ra [ft3/min-ft2] Sum of Zone Floor Area - Az-sum [ft2] Breathing Zone Outdoor Airflow - Vbz [ft3/min] Cooling Zone Outdoor Airflow - Voz-clg [ft3/min] Heating Zone Outdoor Airflow - Voz-htg [ft3/min]
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 0.000000 2.00 0.000000 1200.5533 0.0000 0.0000 0.0000


Zone Ventilation Calculations for Cooling Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 415.0821 415.0821 415.0821 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 187.4245 187.4245 187.4245 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.5526 313.5526 313.5526 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 390.7941 390.7941 390.7941 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 168.0498 168.0498 168.0498 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.2005 286.2005 286.2005 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 413.3358 413.3358 413.3358 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 189.2174 189.2174 189.2174 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 319.5147 319.5147 319.5147 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 389.3286 389.3286 389.3286 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 171.6117 171.6117 171.6117 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 290.3776 290.3776 290.3776 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.7904 286.7904 286.7904 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 314.6963 314.6963 314.6963 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.4232 421.4232 421.4232 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 197.1119 197.1119 197.1119 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 196.5623 196.5623 196.5623 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 411.9431 411.9431 411.9431 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Cooling Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Cooling - Voz-clg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.0821 415.0821 415.0821 415.0821 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.4245 187.4245 187.4245 187.4245 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.5526 313.5526 313.5526 313.5526 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.7941 390.7941 390.7941 390.7941 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.0498 168.0498 168.0498 168.0498 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.2005 286.2005 286.2005 286.2005 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.3358 413.3358 413.3358 413.3358 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.2174 189.2174 189.2174 189.2174 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.5147 319.5147 319.5147 319.5147 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.3286 389.3286 389.3286 389.3286 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.6117 171.6117 171.6117 171.6117 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.3776 290.3776 290.3776 290.3776 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.4232 421.4232 421.4232 421.4232 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.5623 196.5623 196.5623 196.5623 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.6963 314.6963 314.6963 314.6963 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.9431 411.9431 411.9431 411.9431 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.1119 197.1119 197.1119 197.1119 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.7904 286.7904 286.7904 286.7904 0.0000 1.0000


Zone Ventilation Calculations for Heating Design

AirLoop Name Box Type Zone Primary Airflow - Vpz [ft3/min] Zone Discharge Airflow - Vdz [ft3/min] Minimum Zone Primary Airflow - Vpz-min [ft3/min] Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Primary Outdoor Air Fraction - Zpz Primary Air Fraction - Ep Secondary Recirculation Fraction- Er Supply Air Fraction- Fa Mixed Air Fraction - Fb Outdoor Air Fraction - Fc Zone Ventilation Efficiency - Evz
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 415.0821 415.0821 415.0821 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 187.4245 187.4245 187.4245 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 313.5526 313.5526 313.5526 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 390.7941 390.7941 390.7941 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 168.0498 168.0498 168.0498 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_BOTTOMFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.2005 286.2005 286.2005 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 413.3358 413.3358 413.3358 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 189.2174 189.2174 189.2174 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 319.5147 319.5147 319.5147 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 389.3286 389.3286 389.3286 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 171.6117 171.6117 171.6117 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_MIDDLEFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 290.3776 290.3776 290.3776 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 286.7904 286.7904 286.7904 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT3_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 314.6963 314.6963 314.6963 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 421.4232 421.4232 421.4232 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 197.1119 197.1119 197.1119 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT2_FRONTROW_TOPFLOOR CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 196.5623 196.5623 196.5623 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000
LIVING_UNIT1_BACKROW_TOPFLOOR CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT 411.9431 411.9431 411.9431 No 0.0000 0.0000 1.0000 0.0000 0.0000 0.0000 0.0000 1.0000


System Ventilation Calculations for Heating Design

Sum of Zone Primary Airflow - Vpz-sum [ft3/min] System Primary Airflow - Vps [ft3/min] Sum of Zone Discharge Airflow - Vdz-sum [ft3/min] Sum of Min Zone Primary Airflow - Vpz-min [ft3/min] Zone Outdoor Airflow Heating - Voz-htg [ft3/min] Zone Ventilation Efficiency - Evz-min
CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR 415.0821 415.0821 415.0821 415.0821 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR 187.4245 187.4245 187.4245 187.4245 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR 313.5526 313.5526 313.5526 313.5526 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR 390.7941 390.7941 390.7941 390.7941 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR 168.0498 168.0498 168.0498 168.0498 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR 286.2005 286.2005 286.2005 286.2005 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR 413.3358 413.3358 413.3358 413.3358 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR 189.2174 189.2174 189.2174 189.2174 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR 319.5147 319.5147 319.5147 319.5147 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR 389.3286 389.3286 389.3286 389.3286 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR 171.6117 171.6117 171.6117 171.6117 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR 290.3776 290.3776 290.3776 290.3776 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR 421.4232 421.4232 421.4232 421.4232 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR 196.5623 196.5623 196.5623 196.5623 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR 314.6963 314.6963 314.6963 314.6963 0.0000 1.0000
CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR 411.9431 411.9431 411.9431 411.9431 0.0000 1.0000
CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR 197.1119 197.1119 197.1119 197.1119 0.0000 1.0000
CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR 286.7904 286.7904 286.7904 286.7904 0.0000 1.0000



Table of Contents

Report: LEED Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Sec1.1A-General Information

Data
Weather File ANNUAL ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Total gross floor area [ft2] 39005.22
Principal Heating Source Natural Gas


EAp2-1. Space Usage Type

Space Area [ft2] Regularly Occupied Area [ft2] Unconditioned Area [ft2] Typical Hours/Week in Operation [hr/wk]
LIVING_UNIT1_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_BOTTOMFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_MIDDLEFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT3_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT2_FRONTROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
LIVING_UNIT1_BACKROW_TOPFLOOR 1200.55 1200.55 0.00 168.00
CRAWLSPACE 7794.39 0.00 7794.39 0.00
BREEZEWAY 1798.16 0.00 1798.16 0.00
ATTIC 7802.71 0.00 7802.71 0.00
Totals 39005.22 21609.96 17395.26  


EAp2-2. Advisory Messages

Data
Number of hours heating loads not met 2174.67
Number of hours cooling loads not met 1.00
Number of hours not met 2175.67


EAp2-3. Energy Type Summary

Utility Rate Virtual Rate [$/unit energy] Units of Energy Units of Demand
None        


EAp2-4/5. Performance Rating Method Compliance

Electricity Energy Use [kWh] Electricity Demand [W] Natural Gas Energy Use [therm] Natural Gas Demand [Btu/h] Gasoline Use [therm] Gasoline Demand [Btu/h] Diesel Use [kBtu] Diesel Demand [Btu/h] Coal Use [kBtu] Coal Demand [Btu/h] Fuel Oil No 1 Use [kBtu] Fuel Oil No 1 Demand [Btu/h] Fuel Oil No 2 Use [kBtu] Fuel Oil No 2 Demand [Btu/h] Propane Use [kBtu] Propane Demand [Btu/h] Other Fuel 1 Use [kBtu] Other Fuel 1 Demand [Btu/h] Other Fuel 2 Use [kBtu] Other Fuel 2 Demand [Btu/h] District Cooling Use [ton-hrs] District Cooling Demand [ton] District Heating Use [kBtu] District Heating Demand [Btu/h]
Heating -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler 0.00 0.00 4449.03 276491.03 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heating -- Boiler Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Cooling -- General 8083.16 11790.28 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Lighting -- General 11336.81 3692.78 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Exterior-Lights 6034.31 1377.69 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Lighting -- Garage-Lights 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- dishwasher 3088.82 985.58 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- refrigerator 12036.11 1639.04 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- clotheswasher 1577.30 427.18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_dryer 12502.11 3196.73 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_range 9058.39 3721.08 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- television 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- electric_mels 46926.68 7929.96 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Interior Equipment -- IECC_adj 3113.66 526.17 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Exterior Equipment -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- General 5299.23 1787.37 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation 11826.01 1350.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Fans -- Ventilation (simple) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Pumps -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Rejection -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Humidification -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Heat Recovery -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Domestic Hot Water 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater 1308.75 149.40 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Water Heater Parasitic 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Water Systems -- Other 0.00 9514.36 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Refrigeration -- Not Subdivided 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Generators -- General 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00


EAp2-6. Energy Use Summary

Process Subtotal [kBtu] Total Energy Use [kBtu]
Electricity 301503.54 529538.39
Natural Gas 0.00 444903.28
Additional 0.00 0.00
Total 301503.54 974441.67


EAp2-7. Energy Cost Summary

Process Subtotal [$] Total Energy Cost [$]
Electricity 0.00  
Natural Gas 0.00  
Additional 0.00  
Total 0.00  
Process energy cost based on ratio of process to total energy.

L-1. Renewable Energy Source Summary

Rated Capacity [kW] Annual Energy Generated [kBtu]
Photovoltaic 0.00 0.00
Wind 0.00 0.00


EAp2-17a. Energy Use Intensity - Electricity

Electricty [kWh/ft2]
Interior Lighting (All) 0.29
Space Heating 0.00
Space Cooling 0.21
Fans (All) 0.44
Service Water Heating 0.62
Receptacle Equipment 2.26
Miscellaneous (All) 3.98
Subtotal 3.98


EAp2-17b. Energy Use Intensity - Natural Gas

Natural Gas [kWh/ft2]
Space Heating 3.34
Service Water Heating 0.00
Miscellaneous (All) 3.34
Subtotal 3.34


EAp2-17c. Energy Use Intensity - Additional

Additional [kBtu/ft2]
Subtotal 0.00
Miscellaneous 0.00


EAp2-18. End Use Percentage

Percent [%]
Interior Lighting (All) 3.97
Space Heating 45.66
Space Cooling 2.83
Fans (All) 6.00
Service Water Heating 8.48
Receptacle Equipment 30.94
Miscellaneous 2.11


Schedules-Equivalent Full Load Hours (Schedule Type=Fraction)

Equivalent Full Load Hours of Operation Per Year [hr] Hours > 1% [hr]
OCCUPANCY 6031. 8760.
INTERIORLIGHTING 2852. 8760.
INTERIORLIGHTINGHE 3070. 8760.
INTERIORLIGHTINGHE_OS 2910. 8760.
INTERIORLIGHTINGHE_VS 2149. 8760.
EXTERIORLIGHTING 4380. 4380.
REFRIGERATOR 7343. 8760.
MISCPLUGLOAD 5918. 8760.
COOKINGRANGE 2434. 8760.
DISHWASHER_FLOW_SCH 2642. 8760.
CLOTHESWASHER_FLOW_SCH 3113. 8760.
DISHWASHER_EQUIP_SCH 3134. 8760.
CLOTHESWASHER_EQUIP_SCH 3692. 8760.
CLOTHESDRYER 3911. 8760.
SHADING_2012IECC 0. 0.
SHADING_2012IECC_HERS 7007. 8760.
SINKSENSSCHEDULE 6025. 8760.
SINKLATSCHEDULE 2735. 8760.
SHOWERSENSSCHEDULE 4492. 8760.
SHOWERLATSCHEDULE 4268. 8760.
BATHSENSSCHEDULE 8760. 8760.
BATHLATSCHEDULE 0. 0.


Schedules-SetPoints (Schedule Type=Temperature)

First Object Used Month Assumed 11am First Wednesday [F] Days with Same 11am Value 11pm First Wednesday [F] Days with Same 11pm Value
HEATING_SCH THERMOSTAT_LIVING DUAL SP CONTROL January 72.00 365 72.00 365
COOLING_SCH THERMOSTAT_LIVING DUAL SP CONTROL July 75.00 365 75.00 365



Table of Contents

Report: Annual CO2 Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

CO2 Level Hours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupantHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      


CO2 Level OccupiedHours

Safe (<= 1000 ppm) [hr] Caution (> 1000, <= 5000 ppm) [hr] Hazard (> 5000 ppm) [hr]
None      



Table of Contents

Report: Annual Visual Resilience Summary

For: Entire Facility

Timestamp: 2024-06-27 18:32:20

Illuminance Level Hours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupantHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        


Illuminance Level OccupiedHours

A Bit Dark (<= 100 lux) [hr] Dim (> 100, <= 300 lux) [hr] Adequate (> 300, <= 500 lux) [hr] Bright (>500 lux) [hr]
None        



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 741.806 42.589 42.589
February 9.500 0.156 614.858 30.160 30.239
March 24.911 0.633 618.995 25.273 26.454
April 102.083 3.516 388.974 15.862 23.881
May 335.306 12.004 73.742 14.580 23.280
June 459.158 19.594 8.006 19.922 22.185
July 587.747 26.799 0.875 26.847 27.583
August 534.917 20.553 3.872 20.662 22.370
September 261.036 8.202 104.025 10.800 14.708
October 76.025 2.394 464.050 14.502 16.123
November 4.711 0.029 654.619 23.104 23.364
December 0.000 0.000 744.000 40.893 40.893
           
Annual Sum or Average 2395.394 93.879 4417.821 285.195 313.669
Minimum of Months 0.000 0.000 0.875 10.800 14.708
Maximum of Months 587.747 26.799 744.000 42.589 42.589



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 741.806 18.538 18.642
February 2.250 0.006 600.875 12.817 13.654
March 7.413 0.039 605.120 10.307 12.795
April 74.153 1.154 367.562 6.126 9.741
May 296.742 6.094 50.706 7.094 9.772
June 459.019 11.896 4.567 12.030 12.386
July 578.533 16.861 0.325 16.872 17.133
August 546.014 13.584 0.861 13.619 14.098
September 277.161 5.268 50.180 6.268 7.096
October 77.614 1.516 380.621 5.939 8.075
November 3.554 0.019 619.680 8.913 9.678
December 0.000 0.000 741.556 17.441 17.441
           
Annual Sum or Average 2322.453 56.437 4163.857 135.964 150.512
Minimum of Months 0.000 0.000 0.325 5.939 7.096
Maximum of Months 578.533 16.861 741.806 18.538 18.642



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.056 46.220 46.315
February 0.770 0.002 604.406 32.221 36.049
March 9.292 0.087 600.710 26.047 31.007
April 103.021 2.475 345.264 14.428 21.142
May 351.367 10.199 44.272 11.836 19.347
June 521.913 19.643 1.528 19.699 21.081
July 620.617 26.113 0.278 26.128 26.792
August 556.806 19.274 0.708 19.298 20.647
September 264.050 7.383 42.491 8.863 22.606
October 74.922 1.941 383.507 13.628 30.849
November 2.233 0.012 618.095 24.798 29.881
December 0.000 0.000 741.556 44.321 44.524
           
Annual Sum or Average 2504.991 87.131 4125.869 287.486 350.242
Minimum of Months 0.000 0.000 0.278 8.863 19.347
Maximum of Months 620.617 26.113 743.056 46.220 46.315



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.861 42.164 42.184
February 0.000 0.000 633.471 31.009 35.711
March 4.589 0.060 634.473 25.597 35.315
April 55.950 1.541 409.927 14.700 30.252
May 298.403 9.507 88.050 12.352 19.323
June 453.356 17.717 8.149 18.031 19.748
July 582.650 23.899 1.575 23.967 24.318
August 510.111 16.547 4.156 16.699 18.338
September 190.931 4.419 131.186 7.447 13.777
October 27.778 0.410 508.415 13.105 21.279
November 0.000 0.000 659.584 23.282 29.215
December 0.000 0.000 743.278 39.699 39.785
           
Annual Sum or Average 2123.767 74.099 4566.124 268.052 329.243
Minimum of Months 0.000 0.000 1.575 7.447 13.777
Maximum of Months 582.650 23.899 743.861 42.164 42.184



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 21.813 21.813
February 0.000 0.000 663.536 16.095 16.471
March 0.000 0.000 697.202 13.129 15.176
April 13.556 0.176 464.197 6.831 10.561
May 242.656 4.241 69.867 5.591 8.417
June 448.717 10.292 4.364 10.440 10.710
July 562.461 14.273 0.556 14.289 14.335
August 501.828 9.913 0.514 9.939 10.515
September 185.550 2.021 70.306 3.288 5.683
October 8.722 0.036 476.202 5.695 8.716
November 0.056 0.000 682.949 10.811 11.310
December 0.000 0.000 743.861 19.930 19.939
           
Annual Sum or Average 1963.544 40.952 4617.553 137.851 153.646
Minimum of Months 0.000 0.000 0.514 3.288 5.683
Maximum of Months 562.461 14.273 744.000 21.813 21.813



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 51.200 51.200
February 0.000 0.000 668.500 38.089 38.302
March 0.000 0.000 710.077 31.435 32.624
April 41.158 0.581 418.333 15.055 20.946
May 307.897 7.744 51.736 9.754 16.515
June 508.278 17.965 1.700 18.059 19.173
July 615.219 23.510 0.833 23.571 23.839
August 528.514 15.487 0.889 15.534 16.812
September 204.436 3.524 62.037 5.731 18.669
October 19.361 0.101 481.959 14.729 27.380
November 0.000 0.000 685.731 28.551 30.621
December 0.000 0.000 744.000 48.194 48.194
           
Annual Sum or Average 2224.864 68.912 4569.796 299.901 344.276
Minimum of Months 0.000 0.000 0.833 5.731 16.515
Maximum of Months 615.219 23.510 744.000 51.200 51.200



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 725.914 30.232 30.232
February 15.687 0.324 567.911 21.068 21.120
March 39.793 0.969 554.072 17.886 18.955
April 135.472 4.396 315.150 12.625 18.057
May 393.017 14.052 38.131 15.904 19.978
June 525.894 21.912 2.761 22.084 22.827
July 628.025 29.420 0.200 29.429 29.537
August 594.539 23.320 0.597 23.378 23.885
September 329.306 10.061 42.252 11.544 13.635
October 96.736 2.978 354.229 10.836 13.054
November 9.035 0.097 598.554 16.065 16.273
December 0.000 0.000 736.611 29.273 29.273
           
Annual Sum or Average 2767.503 107.529 3936.381 240.323 256.826
Minimum of Months 0.000 0.000 0.200 10.836 13.054
Maximum of Months 628.025 29.420 736.611 30.232 30.232



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 691.392 10.793 11.158
February 12.451 0.094 514.778 7.423 8.228
March 20.523 0.190 474.752 6.096 8.213
April 122.133 1.869 201.694 4.633 7.630
May 381.003 7.825 15.208 8.337 9.641
June 537.325 14.053 1.222 14.096 14.181
July 621.747 19.006 0.000 19.006 19.036
August 591.375 16.018 0.056 16.022 16.194
September 357.444 7.254 8.478 7.579 9.606
October 116.583 2.182 184.167 4.793 6.359
November 14.083 0.093 452.744 5.348 6.001
December 0.000 0.000 714.431 10.277 10.411
           
Annual Sum or Average 2774.669 68.584 3258.921 114.403 126.658
Minimum of Months 0.000 0.000 0.000 4.633 6.001
Maximum of Months 621.747 19.006 714.431 19.006 19.036



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 692.908 32.858 37.605
February 6.566 0.058 513.283 22.154 30.881
March 26.986 0.350 461.049 17.649 30.092
April 141.182 3.600 182.125 9.988 27.542
May 405.264 12.516 12.172 13.169 19.076
June 572.836 22.206 0.819 22.245 22.597
July 655.883 28.736 0.278 28.749 28.866
August 607.125 22.155 0.917 22.192 22.446
September 330.681 9.276 8.894 9.578 20.111
October 94.665 2.591 177.221 9.288 36.688
November 8.884 0.057 449.372 16.395 35.674
December 0.000 0.000 712.201 31.848 34.596
           
Annual Sum or Average 2850.072 101.544 3211.241 236.112 346.175
Minimum of Months 0.000 0.000 0.278 9.288 19.076
Maximum of Months 655.883 28.736 712.201 32.858 37.605



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 730.394 30.259 31.667
February 0.000 0.000 582.391 21.398 31.360
March 8.178 0.115 557.387 17.233 33.239
April 77.756 1.966 327.718 10.454 26.519
May 358.539 11.440 44.603 13.171 16.625
June 518.681 20.082 2.222 20.221 21.077
July 625.119 26.600 0.417 26.613 26.678
August 568.019 19.318 1.222 19.384 19.862
September 271.639 5.937 51.175 7.338 13.752
October 37.458 0.567 364.976 8.343 23.516
November 0.500 0.002 603.367 15.986 27.121
December 0.000 0.000 733.743 28.580 29.819
           
Annual Sum or Average 2465.889 86.027 3999.616 218.980 301.237
Minimum of Months 0.000 0.000 0.417 7.338 13.752
Maximum of Months 625.119 26.600 733.743 30.259 33.239



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 736.247 13.254 13.430
February 0.000 0.000 623.068 9.777 10.713
March 0.000 0.000 616.887 8.112 10.939
April 42.833 0.341 294.128 4.298 7.802
May 317.850 5.667 22.403 6.406 8.596
June 522.152 12.468 1.125 12.504 12.581
July 598.783 16.514 0.000 16.514 16.519
August 553.889 12.412 0.361 12.433 12.617
September 276.264 3.493 20.897 4.223 5.225
October 28.333 0.144 252.028 3.659 5.815
November 2.167 0.008 582.026 6.684 7.530
December 0.000 0.000 736.542 12.159 12.254
           
Annual Sum or Average 2342.272 51.048 3885.712 110.024 124.020
Minimum of Months 0.000 0.000 0.000 3.659 5.225
Maximum of Months 598.783 16.514 736.542 16.514 16.519



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 737.850 37.341 37.774
February 0.000 0.000 633.543 27.068 29.948
March 0.000 0.000 609.391 21.572 28.030
April 68.136 1.044 245.855 9.042 24.604
May 370.183 9.785 12.947 10.471 16.193
June 572.516 20.623 1.208 20.681 20.826
July 654.058 26.178 0.083 26.184 26.299
August 590.125 18.370 0.986 18.419 18.680
September 275.514 5.118 11.708 5.511 16.876
October 34.481 0.275 240.079 8.712 34.391
November 0.000 0.000 585.722 19.871 29.833
December 0.000 0.000 737.028 35.172 35.777
           
Annual Sum or Average 2565.013 81.392 3816.402 240.043 319.234
Minimum of Months 0.000 0.000 0.083 5.511 16.193
Maximum of Months 654.058 26.178 737.850 37.341 37.774



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 741.167 43.962 44.293
February 4.806 0.055 614.689 31.070 31.959
March 18.967 0.446 597.480 25.666 30.532
April 99.417 3.168 342.743 15.447 30.764
May 352.728 12.758 56.200 15.027 25.234
June 491.633 21.311 4.649 21.567 23.250
July 608.519 29.146 0.639 29.178 29.584
August 556.208 22.108 2.033 22.240 23.637
September 269.889 8.238 82.703 10.601 16.847
October 73.181 2.098 412.724 14.152 23.434
November 0.833 0.005 638.930 23.881 27.335
December 0.000 0.000 742.500 42.136 42.304
           
Annual Sum or Average 2476.181 99.333 4236.457 294.927 349.174
Minimum of Months 0.000 0.000 0.639 10.601 16.847
Maximum of Months 608.519 29.146 742.500 43.962 44.293



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.139 19.212 19.255
February 0.000 0.000 607.786 13.267 14.451
March 2.750 0.018 602.987 10.670 13.346
April 77.850 1.111 356.706 6.206 9.254
May 318.456 6.973 47.269 7.929 9.843
June 495.694 13.576 3.619 13.701 13.768
July 605.075 19.062 0.111 19.066 19.262
August 564.722 15.169 1.111 15.205 15.465
September 288.847 5.565 41.594 6.259 9.023
October 76.933 1.404 372.655 6.039 7.888
November 1.028 0.003 628.823 9.355 10.062
December 0.000 0.000 741.972 18.052 18.066
           
Annual Sum or Average 2431.356 62.880 4147.774 144.962 159.684
Minimum of Months 0.000 0.000 0.111 6.039 7.888
Maximum of Months 605.075 19.062 743.139 19.212 19.262



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.667 46.083 46.116
February 0.000 0.000 615.211 32.352 35.411
March 5.993 0.033 604.862 26.019 31.078
April 98.876 2.238 331.572 13.651 22.598
May 365.797 10.909 34.406 12.173 19.998
June 545.819 21.155 1.306 21.238 21.989
July 641.483 28.142 0.194 28.152 28.578
August 580.989 20.671 0.903 20.701 21.643
September 271.956 7.425 47.636 8.926 20.384
October 69.737 1.747 374.879 14.017 28.491
November 0.000 0.000 628.142 24.783 30.922
December 0.000 0.000 742.167 44.110 44.304
           
Annual Sum or Average 2580.651 92.319 4124.944 292.205 351.513
Minimum of Months 0.000 0.000 0.194 8.926 19.998
Maximum of Months 641.483 28.142 743.667 46.083 46.116



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.889 44.438 44.447
February 0.000 0.000 637.572 32.653 37.174
March 2.089 0.026 633.945 26.615 36.564
April 59.917 1.613 400.116 15.054 29.071
May 326.139 11.011 75.275 13.683 19.812
June 488.339 20.151 6.058 20.389 21.899
July 606.811 27.293 1.083 27.341 27.465
August 539.639 19.096 4.428 19.272 20.335
September 216.933 5.087 116.100 7.990 14.482
October 26.389 0.363 487.207 13.428 26.174
November 0.000 0.000 676.322 24.819 29.350
December 0.000 0.000 743.806 41.901 41.923
           
Annual Sum or Average 2266.256 84.639 4525.800 287.584 348.694
Minimum of Months 0.000 0.000 1.083 7.990 14.482
Maximum of Months 606.811 27.293 743.889 44.438 44.447



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 743.944 21.870 21.875
February 0.000 0.000 665.300 16.100 16.420
March 0.000 0.000 688.605 13.008 15.616
April 21.250 0.261 445.161 6.732 10.208
May 275.639 5.584 56.603 6.714 9.639
June 493.074 12.632 1.000 12.670 13.337
July 595.403 17.483 0.528 17.497 17.526
August 537.972 12.486 2.000 12.550 12.682
September 212.778 2.769 60.606 3.876 6.155
October 14.972 0.060 470.202 5.706 9.146
November 0.000 0.000 686.449 11.060 11.378
December 0.000 0.000 743.944 20.074 20.078
           
Annual Sum or Average 2151.088 51.275 4564.343 147.856 164.060
Minimum of Months 0.000 0.000 0.528 3.876 6.155
Maximum of Months 595.403 17.483 743.944 21.870 21.875



Table of Contents

Report: FANSPLIT

For: CENTRAL SYSTEM_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY {HOURS NON-ZERO} [HOURS] AIR SYSTEM FAN ELECTRICITY ENERGY {FOR HOURS SHOWN} [kWh] AIR SYSTEM FAN ELECTRICITY ENERGY [kWh]
January 0.000 0.000 744.000 46.383 46.383
February 0.000 0.000 668.931 34.455 34.634
March 0.000 0.000 702.119 28.141 29.674
April 48.183 0.710 402.566 13.356 19.211
May 329.600 9.106 40.814 10.499 17.345
June 545.094 20.032 0.450 20.052 21.031
July 641.489 26.421 0.361 26.447 26.688
August 565.350 17.847 1.333 17.922 18.622
September 225.992 4.166 55.745 6.057 17.935
October 20.444 0.119 479.757 13.554 25.646
November 0.000 0.000 687.294 26.121 27.825
December 0.000 0.000 744.000 43.690 43.690
           
Annual Sum or Average 2376.153 78.401 4527.371 286.677 328.682
Minimum of Months 0.000 0.000 0.361 6.057 17.345
Maximum of Months 641.489 26.421 744.000 46.383 46.383



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7260.85 0.00 0.00
February 5580.75 0.00 0.00
March 3928.99 0.00 0.00
April 1732.60 0.00 0.00
May 260.53 0.00 0.00
June 29.39 0.00 0.00
July 4.72 0.00 0.00
August 9.44 0.00 0.00
September 290.54 0.00 0.00
October 1571.76 0.00 0.00
November 3571.41 0.00 0.00
December 6911.94 0.00 0.00
       
Annual Sum or Average 2584.59 0.00 0.00
Minimum of Months 4.72 0.00 0.00
Maximum of Months 7260.85 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5514.25 0.00 0.00
February 4244.57 0.00 0.00
March 3001.50 0.00 0.00
April 1293.23 0.00 0.00
May 183.23 0.00 0.00
June 24.30 0.00 0.00
July 1.73 0.00 0.00
August 5.84 0.00 0.00
September 194.84 0.00 0.00
October 1066.37 0.00 0.00
November 2574.61 0.00 0.00
December 5205.99 0.00 0.00
       
Annual Sum or Average 1933.71 0.00 0.00
Minimum of Months 1.73 0.00 0.00
Maximum of Months 5514.25 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7241.41 0.00 0.00
February 5511.88 0.00 0.00
March 3818.45 0.00 0.00
April 1589.81 0.00 0.00
May 182.38 0.00 0.00
June 4.88 0.00 0.00
July 1.33 0.00 0.00
August 2.21 0.00 0.00
September 161.38 0.00 0.00
October 1417.42 0.00 0.00
November 3536.96 0.00 0.00
December 6886.59 0.00 0.00
       
Annual Sum or Average 2518.27 0.00 0.00
Minimum of Months 1.33 0.00 0.00
Maximum of Months 7241.41 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8033.95 0.00 0.00
February 6401.43 0.00 0.00
March 4507.41 0.00 0.00
April 1948.02 0.00 0.00
May 309.80 0.00 0.00
June 30.97 0.00 0.00
July 7.61 0.00 0.00
August 14.05 0.00 0.00
September 360.60 0.00 0.00
October 1795.76 0.00 0.00
November 4001.73 0.00 0.00
December 7502.18 0.00 0.00
       
Annual Sum or Average 2895.27 0.00 0.00
Minimum of Months 7.61 0.00 0.00
Maximum of Months 8033.95 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6282.98 0.00 0.00
February 5143.94 0.00 0.00
March 3733.48 0.00 0.00
April 1695.13 0.00 0.00
May 248.78 0.00 0.00
June 25.24 0.00 0.00
July 2.85 0.00 0.00
August 2.40 0.00 0.00
September 242.63 0.00 0.00
October 1333.30 0.00 0.00
November 3056.72 0.00 0.00
December 5786.98 0.00 0.00
       
Annual Sum or Average 2284.21 0.00 0.00
Minimum of Months 2.40 0.00 0.00
Maximum of Months 6282.98 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7982.18 0.00 0.00
February 6404.26 0.00 0.00
March 4539.68 0.00 0.00
April 1892.63 0.00 0.00
May 222.83 0.00 0.00
June 8.77 0.00 0.00
July 5.51 0.00 0.00
August 3.74 0.00 0.00
September 241.77 0.00 0.00
October 1735.31 0.00 0.00
November 4016.38 0.00 0.00
December 7453.69 0.00 0.00
       
Annual Sum or Average 2861.20 0.00 0.00
Minimum of Months 3.74 0.00 0.00
Maximum of Months 7982.18 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5164.29 0.00 0.00
February 3876.61 0.00 0.00
March 2704.15 0.00 0.00
April 1117.10 0.00 0.00
May 147.11 0.00 0.00
June 14.28 0.00 0.00
July 0.84 0.00 0.00
August 2.51 0.00 0.00
September 158.08 0.00 0.00
October 1012.70 0.00 0.00
November 2485.22 0.00 0.00
December 4956.51 0.00 0.00
       
Annual Sum or Average 1795.66 0.00 0.00
Minimum of Months 0.84 0.00 0.00
Maximum of Months 5164.29 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 3415.80 0.00 0.00
February 2557.79 0.00 0.00
March 1777.91 0.00 0.00
April 696.54 0.00 0.00
May 88.42 0.00 0.00
June 7.75 0.00 0.00
July 0.00 0.00 0.00
August 0.10 0.00 0.00
September 51.68 0.00 0.00
October 605.81 0.00 0.00
November 1541.48 0.00 0.00
December 3253.42 0.00 0.00
       
Annual Sum or Average 1161.44 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 3415.80 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5106.49 0.00 0.00
February 3762.22 0.00 0.00
March 2538.39 0.00 0.00
April 849.51 0.00 0.00
May 62.78 0.00 0.00
June 3.34 0.00 0.00
July 1.23 0.00 0.00
August 2.96 0.00 0.00
September 30.72 0.00 0.00
October 813.48 0.00 0.00
November 2338.54 0.00 0.00
December 4906.92 0.00 0.00
       
Annual Sum or Average 1694.26 0.00 0.00
Minimum of Months 1.23 0.00 0.00
Maximum of Months 5106.49 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5861.13 0.00 0.00
February 4509.93 0.00 0.00
March 3083.36 0.00 0.00
April 1258.40 0.00 0.00
May 186.77 0.00 0.00
June 11.62 0.00 0.00
July 1.50 0.00 0.00
August 7.57 0.00 0.00
September 157.27 0.00 0.00
October 1112.09 0.00 0.00
November 2802.18 0.00 0.00
December 5490.29 0.00 0.00
       
Annual Sum or Average 2030.64 0.00 0.00
Minimum of Months 1.50 0.00 0.00
Maximum of Months 5861.13 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 4118.52 0.00 0.00
February 3313.63 0.00 0.00
March 2381.35 0.00 0.00
April 974.96 0.00 0.00
May 114.28 0.00 0.00
June 6.69 0.00 0.00
July 0.00 0.00 0.00
August 0.89 0.00 0.00
September 136.74 0.00 0.00
October 791.86 0.00 0.00
November 1933.17 0.00 0.00
December 3786.91 0.00 0.00
       
Annual Sum or Average 1455.72 0.00 0.00
Minimum of Months 0.00 0.00 0.00
Maximum of Months 4118.52 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5842.55 0.00 0.00
February 4580.83 0.00 0.00
March 3153.24 0.00 0.00
April 1069.60 0.00 0.00
May 70.71 0.00 0.00
June 4.30 0.00 0.00
July 0.53 0.00 0.00
August 4.92 0.00 0.00
September 39.30 0.00 0.00
October 1017.55 0.00 0.00
November 2823.10 0.00 0.00
December 5460.50 0.00 0.00
       
Annual Sum or Average 1995.62 0.00 0.00
Minimum of Months 0.53 0.00 0.00
Maximum of Months 5842.55 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7470.02 0.00 0.00
February 5746.23 0.00 0.00
March 4008.48 0.00 0.00
April 1651.17 0.00 0.00
May 200.71 0.00 0.00
June 25.07 0.00 0.00
July 3.19 0.00 0.00
August 8.31 0.00 0.00
September 259.21 0.00 0.00
October 1556.71 0.00 0.00
November 3681.50 0.00 0.00
December 7099.02 0.00 0.00
       
Annual Sum or Average 2630.53 0.00 0.00
Minimum of Months 3.19 0.00 0.00
Maximum of Months 7470.02 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 5709.23 0.00 0.00
February 4395.33 0.00 0.00
March 3100.59 0.00 0.00
April 1325.25 0.00 0.00
May 177.82 0.00 0.00
June 20.94 0.00 0.00
July 0.66 0.00 0.00
August 5.60 0.00 0.00
September 131.05 0.00 0.00
October 1110.68 0.00 0.00
November 2697.91 0.00 0.00
December 5382.47 0.00 0.00
       
Annual Sum or Average 1995.68 0.00 0.00
Minimum of Months 0.66 0.00 0.00
Maximum of Months 5709.23 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 7457.56 0.00 0.00
February 5707.88 0.00 0.00
March 3945.75 0.00 0.00
April 1566.94 0.00 0.00
May 144.29 0.00 0.00
June 8.80 0.00 0.00
July 0.97 0.00 0.00
August 2.96 0.00 0.00
September 171.64 0.00 0.00
October 1530.03 0.00 0.00
November 3650.91 0.00 0.00
December 7079.72 0.00 0.00
       
Annual Sum or Average 2593.89 0.00 0.00
Minimum of Months 0.97 0.00 0.00
Maximum of Months 7457.56 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8144.38 0.00 0.00
February 6481.08 0.00 0.00
March 4521.61 0.00 0.00
April 1946.86 0.00 0.00
May 277.45 0.00 0.00
June 19.77 0.00 0.00
July 5.18 0.00 0.00
August 13.55 0.00 0.00
September 323.88 0.00 0.00
October 1766.02 0.00 0.00
November 4102.36 0.00 0.00
December 7616.66 0.00 0.00
       
Annual Sum or Average 2920.40 0.00 0.00
Minimum of Months 5.18 0.00 0.00
Maximum of Months 8144.38 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 6385.43 0.00 0.00
February 5204.94 0.00 0.00
March 3726.51 0.00 0.00
April 1650.86 0.00 0.00
May 200.52 0.00 0.00
June 6.03 0.00 0.00
July 2.56 0.00 0.00
August 11.21 0.00 0.00
September 214.81 0.00 0.00
October 1351.85 0.00 0.00
November 3141.67 0.00 0.00
December 5898.46 0.00 0.00
       
Annual Sum or Average 2304.14 0.00 0.00
Minimum of Months 2.56 0.00 0.00
Maximum of Months 6385.43 0.00 0.00



Table of Contents

Report: COILLOADS

For: MAIN WATER HEATING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [Btu/h] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE []
January 8129.61 0.00 0.00
February 6510.01 0.00 0.00
March 4571.88 0.00 0.00
April 1865.39 0.00 0.00
May 171.68 0.00 0.00
June 1.80 0.00 0.00
July 2.73 0.00 0.00
August 8.24 0.00 0.00
September 227.29 0.00 0.00
October 1780.42 0.00 0.00
November 4122.51 0.00 0.00
December 7597.09 0.00 0.00
       
Annual Sum or Average 2901.10 0.00 0.00
Minimum of Months 1.80 0.00 0.00
Maximum of Months 8129.61 0.00 0.00



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.12
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.21
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.07
June 0.00 0.00 0.14
July 0.00 0.00 0.19
August 0.00 0.00 0.16
September 0.00 0.00 0.06
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.10
June 0.00 0.00 0.21
July 0.00 0.00 0.27
August 0.00 0.00 0.20
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.09
June 0.00 0.00 0.18
July 0.00 0.00 0.24
August 0.00 0.00 0.17
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.05
June 0.00 0.00 0.12
July 0.00 0.00 0.16
August 0.00 0.00 0.11
September 0.00 0.00 0.02
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.04
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.16



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.19
July 0.00 0.00 0.24
August 0.00 0.00 0.16
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.24



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.01
April 0.00 0.00 0.04
May 0.00 0.00 0.13
June 0.00 0.00 0.22
July 0.00 0.00 0.29
August 0.00 0.00 0.23
September 0.00 0.00 0.10
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.09
June 0.00 0.00 0.16
July 0.00 0.00 0.22
August 0.00 0.00 0.18
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.04
May 0.00 0.00 0.12
June 0.00 0.00 0.23
July 0.00 0.00 0.29
August 0.00 0.00 0.23
September 0.00 0.00 0.10
October 0.00 0.00 0.03
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.09
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.11
June 0.00 0.00 0.20
July 0.00 0.00 0.26
August 0.00 0.00 0.19
September 0.00 0.00 0.06
October 0.00 0.00 0.01
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.19
August 0.00 0.00 0.14
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.19



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.21
July 0.00 0.00 0.26
August 0.00 0.00 0.18
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.26



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.03
May 0.00 0.00 0.12
June 0.00 0.00 0.22
July 0.00 0.00 0.29
August 0.00 0.00 0.22
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.08
June 0.00 0.00 0.16
July 0.00 0.00 0.22
August 0.00 0.00 0.17
September 0.00 0.00 0.06
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.06
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.22



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.11
June 0.00 0.00 0.22
July 0.00 0.00 0.29
August 0.00 0.00 0.21
September 0.00 0.00 0.08
October 0.00 0.00 0.02
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.08
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.29



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.02
May 0.00 0.00 0.11
June 0.00 0.00 0.20
July 0.00 0.00 0.27
August 0.00 0.00 0.19
September 0.00 0.00 0.05
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.00
May 0.00 0.00 0.06
June 0.00 0.00 0.15
July 0.00 0.00 0.20
August 0.00 0.00 0.14
September 0.00 0.00 0.03
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.05
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.20



Table of Contents

Report: COILLOADS

For: DX COOLING COIL_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.00
February 0.00 0.00 0.00
March 0.00 0.00 0.00
April 0.00 0.00 0.01
May 0.00 0.00 0.09
June 0.00 0.00 0.21
July 0.00 0.00 0.27
August 0.00 0.00 0.18
September 0.00 0.00 0.04
October 0.00 0.00 0.00
November 0.00 0.00 0.00
December 0.00 0.00 0.00
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.00
Maximum of Months 0.00 0.00 0.27



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: COILLOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

HEATING COIL HEATING RATE [] HEATING COIL AIR HEATING RATE [] COOLING COIL TOTAL COOLING RATE [ton]
January 0.00 0.00 0.07
February 0.00 0.00 0.08
March 0.00 0.00 0.08
April 0.00 0.00 0.08
May 0.00 0.00 0.07
June 0.00 0.00 0.07
July 0.00 0.00 0.07
August 0.00 0.00 0.06
September 0.00 0.00 0.06
October 0.00 0.00 0.07
November 0.00 0.00 0.07
December 0.00 0.00 0.07
       
Annual Sum or Average 0.00 0.00 0.07
Minimum of Months 0.00 0.00 0.06
Maximum of Months 0.00 0.00 0.08



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 179.71 85.67
March 0.00 0.00 174.34 94.12
April 0.00 0.00 162.75 88.01
May 0.00 0.00 142.99 85.40
June 0.00 0.00 124.71 76.65
July 0.00 0.00 115.19 74.78
August 0.00 0.00 110.77 71.57
September 0.00 0.00 117.27 70.31
October 0.00 0.00 129.96 76.09
November 0.00 0.00 147.67 78.70
December 0.00 0.00 166.09 87.47
         
Annual Sum or Average 0.00 0.00 145.46 980.91
Minimum of Months 0.00 0.00 110.77 70.31
Maximum of Months 0.00 0.00 179.71 94.12



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.52 92.34
February 0.00 0.00 178.98 85.41
March 0.00 0.00 174.78 94.36
April 0.00 0.00 162.80 88.04
May 0.00 0.00 142.80 85.26
June 0.00 0.00 124.88 76.85
July 0.00 0.00 114.44 74.48
August 0.00 0.00 110.86 71.71
September 0.00 0.00 117.00 70.15
October 0.00 0.00 129.62 75.89
November 0.00 0.00 147.82 78.90
December 0.00 0.00 165.90 87.50
         
Annual Sum or Average 0.00 0.00 145.34 980.89
Minimum of Months 0.00 0.00 110.86 70.15
Maximum of Months 0.00 0.00 178.98 94.36



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 180.02 85.70
March 0.00 0.00 174.50 94.07
April 0.00 0.00 163.11 88.31
May 0.00 0.00 142.19 85.06
June 0.00 0.00 124.91 76.71
July 0.00 0.00 115.11 74.53
August 0.00 0.00 111.18 71.80
September 0.00 0.00 117.34 70.19
October 0.00 0.00 130.88 76.32
November 0.00 0.00 147.75 78.71
December 0.00 0.00 166.10 87.47
         
Annual Sum or Average 0.00 0.00 145.60 981.02
Minimum of Months 0.00 0.00 111.18 70.19
Maximum of Months 0.00 0.00 180.02 94.07



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 179.99 85.70
March 0.00 0.00 174.92 94.17
April 0.00 0.00 163.91 88.19
May 0.00 0.00 142.98 85.34
June 0.00 0.00 124.65 76.65
July 0.00 0.00 114.89 74.71
August 0.00 0.00 110.49 71.60
September 0.00 0.00 117.37 70.34
October 0.00 0.00 130.37 76.21
November 0.00 0.00 147.85 78.71
December 0.00 0.00 166.09 87.47
         
Annual Sum or Average 0.00 0.00 145.63 981.24
Minimum of Months 0.00 0.00 110.49 70.34
Maximum of Months 0.00 0.00 179.99 94.17



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.52 92.34
February 0.00 0.00 179.01 85.43
March 0.00 0.00 174.76 94.31
April 0.00 0.00 163.55 88.23
May 0.00 0.00 142.88 85.20
June 0.00 0.00 124.43 76.64
July 0.00 0.00 114.36 74.63
August 0.00 0.00 110.52 71.73
September 0.00 0.00 117.29 70.31
October 0.00 0.00 130.06 76.06
November 0.00 0.00 147.63 78.81
December 0.00 0.00 165.90 87.50
         
Annual Sum or Average 0.00 0.00 145.38 981.18
Minimum of Months 0.00 0.00 110.52 70.31
Maximum of Months 0.00 0.00 179.01 94.31



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.66 92.18
February 0.00 0.00 179.87 85.69
March 0.00 0.00 174.40 94.05
April 0.00 0.00 163.06 88.07
May 0.00 0.00 143.06 85.49
June 0.00 0.00 124.49 76.59
July 0.00 0.00 115.16 74.75
August 0.00 0.00 110.45 71.61
September 0.00 0.00 117.32 70.27
October 0.00 0.00 130.28 76.02
November 0.00 0.00 148.19 78.96
December 0.00 0.00 166.12 87.47
         
Annual Sum or Average 0.00 0.00 145.56 981.15
Minimum of Months 0.00 0.00 110.45 70.27
Maximum of Months 0.00 0.00 179.87 94.05



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 174.95 92.27
February 0.00 0.00 177.44 85.41
March 0.00 0.00 172.71 94.12
April 0.00 0.00 161.50 88.10
May 0.00 0.00 141.99 85.24
June 0.00 0.00 125.12 76.88
July 0.00 0.00 115.13 74.52
August 0.00 0.00 111.06 71.56
September 0.00 0.00 116.51 70.04
October 0.00 0.00 129.17 76.08
November 0.00 0.00 146.40 78.69
December 0.00 0.00 164.58 87.52
         
Annual Sum or Average 0.00 0.00 144.52 980.42
Minimum of Months 0.00 0.00 111.06 70.04
Maximum of Months 0.00 0.00 177.44 94.12



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 174.58 92.29
February 0.00 0.00 177.06 85.41
March 0.00 0.00 172.89 94.28
April 0.00 0.00 161.30 88.10
May 0.00 0.00 141.74 85.08
June 0.00 0.00 124.76 76.59
July 0.00 0.00 115.48 74.76
August 0.00 0.00 111.39 71.72
September 0.00 0.00 116.52 69.87
October 0.00 0.00 129.01 76.04
November 0.00 0.00 146.37 78.84
December 0.00 0.00 163.85 87.36
         
Annual Sum or Average 0.00 0.00 144.39 980.35
Minimum of Months 0.00 0.00 111.39 69.87
Maximum of Months 0.00 0.00 177.06 94.28



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 175.05 92.28
February 0.00 0.00 177.61 85.36
March 0.00 0.00 173.21 94.21
April 0.00 0.00 161.88 88.25
May 0.00 0.00 141.68 85.12
June 0.00 0.00 125.21 76.85
July 0.00 0.00 115.47 74.51
August 0.00 0.00 111.11 71.54
September 0.00 0.00 117.12 70.23
October 0.00 0.00 129.43 75.98
November 0.00 0.00 147.09 78.88
December 0.00 0.00 164.44 87.39
         
Annual Sum or Average 0.00 0.00 144.75 980.61
Minimum of Months 0.00 0.00 111.11 70.23
Maximum of Months 0.00 0.00 177.61 94.21



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 174.99 92.27
February 0.00 0.00 178.47 85.61
March 0.00 0.00 173.89 94.24
April 0.00 0.00 162.29 88.08
May 0.00 0.00 142.00 85.22
June 0.00 0.00 124.95 76.80
July 0.00 0.00 115.13 74.61
August 0.00 0.00 111.05 71.72
September 0.00 0.00 116.97 70.20
October 0.00 0.00 129.22 75.86
November 0.00 0.00 147.06 78.81
December 0.00 0.00 164.60 87.52
         
Annual Sum or Average 0.00 0.00 144.86 980.95
Minimum of Months 0.00 0.00 111.05 70.20
Maximum of Months 0.00 0.00 178.47 94.24



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 174.54 92.29
February 0.00 0.00 177.17 85.39
March 0.00 0.00 173.24 94.36
April 0.00 0.00 161.68 88.00
May 0.00 0.00 142.35 85.32
June 0.00 0.00 124.81 76.70
July 0.00 0.00 114.89 74.57
August 0.00 0.00 111.09 71.79
September 0.00 0.00 116.85 70.22
October 0.00 0.00 128.65 75.78
November 0.00 0.00 146.38 78.80
December 0.00 0.00 164.41 87.68
         
Annual Sum or Average 0.00 0.00 144.48 980.90
Minimum of Months 0.00 0.00 111.09 70.22
Maximum of Months 0.00 0.00 177.17 94.36



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 174.93 92.25
February 0.00 0.00 177.86 85.49
March 0.00 0.00 173.47 94.24
April 0.00 0.00 162.09 88.08
May 0.00 0.00 141.92 85.23
June 0.00 0.00 124.89 76.73
July 0.00 0.00 115.47 74.69
August 0.00 0.00 110.72 71.57
September 0.00 0.00 117.06 70.23
October 0.00 0.00 129.88 76.22
November 0.00 0.00 146.29 78.55
December 0.00 0.00 164.59 87.52
         
Annual Sum or Average 0.00 0.00 144.74 980.80
Minimum of Months 0.00 0.00 110.72 70.23
Maximum of Months 0.00 0.00 177.86 94.24



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 179.76 85.66
March 0.00 0.00 174.57 94.20
April 0.00 0.00 163.03 88.00
May 0.00 0.00 143.10 85.39
June 0.00 0.00 124.75 76.63
July 0.00 0.00 115.09 74.62
August 0.00 0.00 110.96 71.66
September 0.00 0.00 117.30 70.29
October 0.00 0.00 129.76 75.94
November 0.00 0.00 148.09 78.93
December 0.00 0.00 166.09 87.47
         
Annual Sum or Average 0.00 0.00 145.55 980.93
Minimum of Months 0.00 0.00 110.96 70.29
Maximum of Months 0.00 0.00 179.76 94.20



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.52 92.34
February 0.00 0.00 179.04 85.43
March 0.00 0.00 174.48 94.18
April 0.00 0.00 163.10 88.25
May 0.00 0.00 142.53 85.15
June 0.00 0.00 125.03 76.85
July 0.00 0.00 114.70 74.47
August 0.00 0.00 111.03 71.70
September 0.00 0.00 117.17 70.19
October 0.00 0.00 129.70 75.95
November 0.00 0.00 147.62 78.81
December 0.00 0.00 165.90 87.50
         
Annual Sum or Average 0.00 0.00 145.37 980.80
Minimum of Months 0.00 0.00 111.03 70.19
Maximum of Months 0.00 0.00 179.04 94.18



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 179.96 85.69
March 0.00 0.00 174.48 94.05
April 0.00 0.00 162.90 88.11
May 0.00 0.00 142.81 85.36
June 0.00 0.00 124.77 76.60
July 0.00 0.00 115.41 74.60
August 0.00 0.00 111.18 71.73
September 0.00 0.00 117.38 70.25
October 0.00 0.00 129.91 75.94
November 0.00 0.00 148.09 78.84
December 0.00 0.00 166.28 87.56
         
Annual Sum or Average 0.00 0.00 145.61 980.89
Minimum of Months 0.00 0.00 111.18 70.25
Maximum of Months 0.00 0.00 179.96 94.05



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.48 92.15
February 0.00 0.00 180.04 85.72
March 0.00 0.00 174.75 94.05
April 0.00 0.00 163.60 88.21
May 0.00 0.00 143.02 85.39
June 0.00 0.00 124.73 76.64
July 0.00 0.00 114.96 74.63
August 0.00 0.00 110.83 71.72
September 0.00 0.00 117.41 70.36
October 0.00 0.00 130.32 76.09
November 0.00 0.00 148.00 78.78
December 0.00 0.00 166.09 87.47
         
Annual Sum or Average 0.00 0.00 145.65 981.20
Minimum of Months 0.00 0.00 110.83 70.36
Maximum of Months 0.00 0.00 180.04 94.05



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.52 92.34
February 0.00 0.00 179.02 85.43
March 0.00 0.00 174.55 94.20
April 0.00 0.00 163.54 88.33
May 0.00 0.00 142.59 85.07
June 0.00 0.00 124.82 76.74
July 0.00 0.00 114.72 74.63
August 0.00 0.00 110.67 71.69
September 0.00 0.00 117.24 70.24
October 0.00 0.00 129.85 75.97
November 0.00 0.00 147.87 78.93
December 0.00 0.00 165.90 87.50
         
Annual Sum or Average 0.00 0.00 145.41 981.07
Minimum of Months 0.00 0.00 110.67 70.24
Maximum of Months 0.00 0.00 179.02 94.20



Table of Contents

Report: WATER HEATER: LOADS

For: HEAT PUMP WATER HEATER EVAPORATOR_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

WATER HEATER TOTAL DEMAND RATE [] WATER HEATER TOTAL DEMAND ENERGY [] COOLING COIL WATER HEATING ELECTRICITY RATE [W] COOLING COIL TOTAL WATER HEATING ENERGY [ton-hrs]
January 0.00 0.00 176.49 92.15
February 0.00 0.00 179.86 85.69
March 0.00 0.00 174.33 93.99
April 0.00 0.00 163.13 88.12
May 0.00 0.00 143.03 85.46
June 0.00 0.00 124.71 76.62
July 0.00 0.00 115.41 74.73
August 0.00 0.00 110.62 71.59
September 0.00 0.00 117.25 70.29
October 0.00 0.00 130.51 76.20
November 0.00 0.00 147.72 78.71
December 0.00 0.00 166.09 87.47
         
Annual Sum or Average 0.00 0.00 145.56 981.03
Minimum of Months 0.00 0.00 110.62 70.29
Maximum of Months 0.00 0.00 179.86 93.99



Table of Contents

Report: HEATING AND COOLING LOADS

For: CRAWLSPACE

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: BREEZEWAY

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.19 4141.56
February 7.56 2740.41
March 18.79 1975.76
April 55.83 751.89
May 126.47 100.56
June 153.76 8.03
July 186.48 1.34
August 155.02 3.17
September 91.38 92.56
October 38.26 639.47
November 5.74 1726.86
December 0.00 3952.12
     
Annual Sum or Average 839.47 16133.73
Minimum of Months 0.00 1.34
Maximum of Months 186.48 4141.56



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.28 2758.29
February 8.18 1808.01
March 15.84 1256.81
April 41.82 415.46
May 93.99 55.57
June 114.15 6.07
July 136.63 0.86
August 121.05 2.12
September 78.90 53.39
October 39.63 317.22
November 8.86 998.65
December 0.33 2604.95
     
Annual Sum or Average 659.66 10277.40
Minimum of Months 0.28 0.86
Maximum of Months 136.63 2758.29



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.03 4137.95
February 7.22 2725.86
March 16.86 1938.70
April 53.01 690.24
May 118.52 71.51
June 159.24 1.87
July 187.10 0.26
August 150.91 0.91
September 90.43 76.11
October 41.20 655.48
November 7.70 1750.94
December 0.26 3948.85
     
Annual Sum or Average 832.46 15998.69
Minimum of Months 0.03 0.26
Maximum of Months 187.10 4137.95



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 4713.52
February 3.19 3275.31
March 10.15 2390.92
April 38.41 902.17
May 107.98 115.53
June 141.93 8.54
July 168.00 1.68
August 128.99 4.81
September 62.71 116.24
October 18.84 764.99
November 4.46 2048.28
December 0.14 4389.55
     
Annual Sum or Average 684.81 18731.54
Minimum of Months 0.00 1.68
Maximum of Months 168.00 4713.52



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 3338.05
February 1.05 2337.78
March 4.88 1684.14
April 23.72 585.22
May 77.34 73.30
June 102.91 6.87
July 118.79 0.98
August 95.18 1.36
September 52.42 63.57
October 20.27 426.01
November 2.75 1281.11
December 0.03 3042.49
     
Annual Sum or Average 499.35 12840.87
Minimum of Months 0.00 0.98
Maximum of Months 118.79 3338.05



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_BOTTOMFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 4706.36
February 0.73 3254.74
March 4.04 2334.49
April 31.38 820.66
May 100.01 89.60
June 146.73 3.50
July 168.30 1.91
August 124.10 0.93
September 60.95 103.38
October 19.10 774.32
November 2.15 2031.37
December 0.00 4380.53
     
Annual Sum or Average 657.49 18501.78
Minimum of Months 0.00 0.93
Maximum of Months 168.30 4706.36



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.19 2556.40
February 14.76 1631.68
March 29.41 1129.85
April 69.15 367.62
May 143.30 43.97
June 169.13 4.02
July 202.65 0.23
August 172.26 0.81
September 106.96 39.71
October 50.32 309.49
November 11.44 979.27
December 1.00 2463.51
     
Annual Sum or Average 972.57 9526.56
Minimum of Months 1.00 0.23
Maximum of Months 202.65 2556.40



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 6.69 1242.30
February 18.65 766.58
March 32.00 502.99
April 64.10 167.54
May 111.18 25.98
June 130.97 1.94
July 153.62 0.13
August 139.50 0.05
September 98.17 15.55
October 59.14 134.81
November 23.90 410.97
December 3.66 1162.99
     
Annual Sum or Average 841.58 4431.83
Minimum of Months 3.66 0.05
Maximum of Months 153.62 1242.30



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 5.42 2580.23
February 16.11 1633.47
March 32.16 1138.60
April 75.81 355.18
May 137.80 19.55
June 176.16 0.54
July 204.11 0.16
August 168.98 0.15
September 106.63 15.56
October 55.08 338.40
November 19.06 1042.09
December 3.14 2473.36
     
Annual Sum or Average 1000.47 9597.29
Minimum of Months 3.14 0.15
Maximum of Months 204.11 2580.23



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 2.04 3079.91
February 8.45 2052.68
March 19.76 1435.46
April 48.34 470.34
May 124.27 55.49
June 157.49 3.57
July 184.67 0.30
August 146.16 2.34
September 78.44 48.35
October 31.43 407.13
November 7.87 1217.54
December 0.92 2862.85
     
Annual Sum or Average 809.82 11635.96
Minimum of Months 0.92 0.30
Maximum of Months 184.67 3079.91



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 1.05 1705.53
February 5.71 1139.37
March 13.90 766.10
April 40.91 243.39
May 93.66 33.31
June 119.87 1.85
July 135.94 0.25
August 113.34 0.39
September 67.09 35.40
October 36.19 192.75
November 10.73 550.41
December 0.58 1527.22
     
Annual Sum or Average 638.97 6195.97
Minimum of Months 0.58 0.25
Maximum of Months 135.94 1705.53



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_MIDDLEFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.99 3073.36
February 3.84 2035.69
March 14.18 1405.72
April 50.44 431.94
May 118.23 28.29
June 164.27 0.64
July 185.64 0.17
August 142.20 1.06
September 76.64 18.09
October 33.10 418.55
November 7.81 1239.26
December 0.62 2856.73
     
Annual Sum or Average 797.96 11509.49
Minimum of Months 0.62 0.17
Maximum of Months 185.64 3073.36



Table of Contents

Report: HEATING AND COOLING LOADS

For: ATTIC

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 0.00
February 0.00 0.00
March 0.00 0.00
April 0.00 0.00
May 0.00 0.00
June 0.00 0.00
July 0.00 0.00
August 0.00 0.00
September 0.00 0.00
October 0.00 0.00
November 0.00 0.00
December 0.00 0.00
     
Annual Sum or Average 0.00 0.00
Minimum of Months 0.00 0.00
Maximum of Months 0.00 0.00



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 4799.07
February 0.65 3312.23
March 4.58 2355.63
April 33.12 804.02
May 111.56 73.76
June 161.34 0.47
July 188.33 1.07
August 139.82 2.42
September 65.70 91.52
October 19.29 800.32
November 2.05 2098.56
December 0.00 4471.80
     
Annual Sum or Average 726.44 18810.88
Minimum of Months 0.00 0.47
Maximum of Months 188.33 4799.07



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT3_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.05 4298.38
February 5.98 2840.99
March 15.57 2023.40
April 52.62 698.62
May 125.02 59.11
June 169.70 2.62
July 201.16 0.22
August 160.28 0.80
September 90.87 76.69
October 38.15 708.42
November 7.45 1835.23
December 0.11 4089.47
     
Annual Sum or Average 866.95 16633.95
Minimum of Months 0.05 0.22
Maximum of Months 201.16 4298.38



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.26 4304.18
February 6.64 2856.45
March 19.41 2075.06
April 56.23 758.46
May 132.60 81.08
June 164.50 7.20
July 200.43 0.70
August 164.24 3.60
September 91.95 87.21
October 39.52 698.90
November 6.45 1829.99
December 0.24 4099.27
     
Annual Sum or Average 882.49 16802.06
Minimum of Months 0.24 0.70
Maximum of Months 200.43 4304.18



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.00 3414.57
February 0.81 2375.57
March 6.45 1699.64
April 26.16 570.79
May 88.92 61.41
June 119.15 2.37
July 139.84 0.73
August 111.84 2.89
September 58.75 57.59
October 20.31 439.69
November 2.54 1338.84
December 0.01 3125.73
     
Annual Sum or Average 574.78 13089.82
Minimum of Months 0.00 0.73
Maximum of Months 139.84 3414.57



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT2_FRONTROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.05 2902.82
February 6.92 1898.10
March 15.99 1337.92
April 42.63 448.02
May 100.50 48.53
June 126.17 4.74
July 152.02 0.46
August 131.94 1.26
September 82.03 30.15
October 39.91 363.53
November 7.48 1074.44
December 0.21 2737.14
     
Annual Sum or Average 705.85 10847.12
Minimum of Months 0.05 0.46
Maximum of Months 152.02 2902.82



Table of Contents

Report: HEATING AND COOLING LOADS

For: LIVING_UNIT1_BACKROW_TOPFLOOR

Timestamp: 2024-06-27 18:32:20

Custom Monthly Report

ZONE AIR SYSTEM SENSIBLE COOLING ENERGY [ton-hrs] ZONE AIR SYSTEM SENSIBLE HEATING ENERGY [kBtu]
January 0.03 4803.76
February 2.63 3326.58
March 10.15 2409.92
April 39.05 896.47
May 118.57 101.78
June 156.77 6.00
July 187.80 0.98
August 144.04 3.72
September 68.31 110.02
October 20.82 790.89
November 3.04 2103.25
December 0.04 4480.83
     
Annual Sum or Average 751.23 19034.22